Sanicubic 2 Pro Expertline - Sanitary Sanibroyeur - Free user manual and instructions

Find the device manual for free Sanicubic 2 Pro Expertline Sanibroyeur in PDF.

📄 48 pages English EN 💬 AI Question
Notice Sanibroyeur Sanicubic 2 Pro Expertline - page 7

Download the instructions for your Sanitary in PDF format for free! Find your manual Sanicubic 2 Pro Expertline - Sanibroyeur and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Sanicubic 2 Pro Expertline by Sanibroyeur.

USER MANUAL Sanicubic 2 Pro Expertline Sanibroyeur

2 Pro is a lifting station designed to evacuate effluent from small private or commercial units. Please comply with all the installation and maintenance specifications set out in these instructions, and especially the information marked with the following signs:

» Failure to comply with this information could entail safety hazards for personnel,

» Information warning of the pre- sence of an electrical hazard,

» Instructions only for qualified professional specialists,

WARNING» Failure to comply with this information could affect the normal operation of the equipment. Please contact our Customer service for further information.

2 Pro contains 2 separate pumps. Each of the pumps is fitted with a high-performance maceration system. The 2 pumps operate alternately. In the event of inflow overload, both motors run at the same time (or if one of the pumps is faulty, the other one takes over). The SANICUBIC

2 Pro tank is fitted with 2 dip tubes; one tube controls motor operation, and the other one controls the alarm system. - Long pickup tube (normal operation): as soon as the waste water level in the tank reaches the triggering point in the long tube, the pumping system starts up. - Short pickup tube (inflow overload operation): if the waste water level in the tank reaches the upper point, a contact is closed, and the auxiliary pumping system is triggered. The contact also sets off an audible and visual alarm. The general alarm LED on the SANICUBIC

2 Pro is fitted with a remote alarm module that transmits a visible and audible alarm (HF link).

Hot water drain cycles from dishwashers or washing machines

FIELD OF APPLICATION

Household waste water (the combined inputs must not exceed 80% of those shown in the graph

2 Pro must be installed in compliance with standard EN12056. The equipment must be commissioned and maintained by a qualified professio- nal specialist. Please refer to installation standard EN 12056.

1- Attention: the space in which the

2 Pro is to be installed must be large enough to leave at least 600 mm of working room around and above the unit to facilitate such maintenance work as may be required. There must be sufficient lighting, and it must be sufficiently well ventilated and protected from freezing.

2- Isolating valves (not supplied) must

be fitted on waste inlets (especially the 110mm inlets) and on the dis- charge to ensure that any service/maintenance may be carried out safely).

3- The discharge pipe must be fitted

so as to avoid all back flow from the drainage system (see the examples in drawing

). Back flow can be avoided by installing an anti-back flow riser reaching a high point above the maximum back flow level. Comment: In the absence of local information to the contrary, the maximum back flow level corresponds to street level (roadway, pavements, etc.). Continue the discharge pipework after the anti-backflow riser, using a larger diameter pipe.

4- If the SANICUBIC is installed in a

space such as a pit for example, we would recommend the fitting of a bilge pump in case of flooding.

5- The lifting station must be vented with

an outlet at roof level.

6- The lifting station must be fixed to the

floor (see paragraph

PIPE Remove the end cover or covers from the back of the unit (cf.

As each pump is fitted with a macerator system, an ND50 mm discharge pipe can be used. The discharge bend is at the centre of the unit, at the back (cf.

to connect it to the riser pipe and fix it in place with the collars. Each pump in the SANICUBIC

2 Pro unit is fitted with check valves. See paragraph

regarding control valves and back flow.

INLETS If you want to install a shower or a bath at the same level as the SANICUBIC

2 Pro, you must make sure that the upper parts of the plugholes on the sanitary equipment are at least 250 mm above the lower inlets.

CONNECTING THE INLETS ND

40/50 Lower inlets (cf.

  • Cut off the end of the ND 50 inlet with a saw

to suit the pipe diameter: ND 40 or ND 50 (cf.

on the inlet and on the pipe, using the collars.

INLET Lower inlets (cf.

1- Remove the plug from the side inlet.

in place using the collar

the other end of the sleeve and fix it in place using the other collar

1- Cut off the upper end of the ND 100

in place using the collar

the other end of the sleeve and fix it in place using the other collar

2 Pro must be vented with an outlet at roof level. Fix the sleeve

in place using the collar

Fully insert the ND 50 tube in the other end of the sleeve and fix it in place using the other collar

WARNING: Do NOT fit air admittance

valve on the top of the air vent pipe. The vent must be an open vent or the unit will not operate.

PERFORMANCE CURVE Example: Pump P1 is operating nor- mally. It discharges 160 l/min at a pum- ping height of 5 m. If pump P1 shows any signs of weakness or if the waste water inflow is too great, pump P2 starts up. The output is then increased to about 275 l/min, until the situation returns to normal. The numbers refer to the explanatory diagrams.

FOR DISCHARGE Fully illustrated step by step instructions are downloadable on www.saniflo.co.ukREMOTE ALARM MODULE The remote alarm module is connected to the SANICUBIC

Pro via an HF link. It receives the various types of alarm information from the unit. If other HF appliances interfere with the system, a switching system is fitted for the HF code lin- king the base board with the remote alarm module. The code can be changed using the switches located on the 2 boards. In the event of interference with other HF equipment or other SANICUBIC

2 Pro units installed nearby, unplug the unit and the remote module, flip one of the 4 switches (or several swithces) on the unit board, and do the same on the remote unit board.

WARNING: You should have the same

code on the unit board and on the remote alarm board. To install the module on a wall, see illustration: The alarm module has 5 LEDS and a buzzer. The LEDs only come on if a fault has been detected. 1/ The red Led “general alarm” LED mirror operation of the corresponding LED on the base board. 2/ The yellow “HF reception” LED mirrors operation of the yellow mains power supply LED on the base board: - On steadily = transmission OK, base board powered by the mains supply - Flashing = transmission OK, but mains power supply fault on the base board (which is thus operating on its battery power supply) - Off = no HF reception from the base board = loss of HF signal, or base board battery flat, or base board failure.

ALARM OPERATION 1/ General alarms: High level alarm: If the water level in the unit is abnormally high: the buzzer is triggered and the red LED comes on; the other motor starts up 3 seconds later (see the illustration showing the control keyboard). Temporary alarm: If one of the 2 motors runs for more than 1 minute: the buzzer is triggered and the red alarm LED comes on; the other motor starts up 3 seconds later. Mains power supply alarm: In the event of a mains power failure (or if the unit is unplugged): the buzzer is triggered and the red alarm LED comes on; the yellow mains power LED also flashes. 2/ Resetting the general alarms: If the problem that has triggered one of the alarms referred to above ceases, the buzzer stops, but the red alarm LED stays on to memorize the fact that the system has met with a problem. One of two keys on the keyboard is used to switch the buzzer off in all cases, but it only switches the red LED off if the pro- blem that triggered the alarm has been dealt with. The alarm lights on the remote control box also stay on until the problem has been dealt with. This avoids the risk of having a system “abandoned” in fault status. UNIT ALARM

2 Pro unit is equipped with fittings to hold it on the floor and prevent it from turning or moving.

1- Place the unit on the desired spot.

2- Locate the 2 holes for attachment to the floor.

on the floor then replace the appliance.

4- Fix the unit in place with the screws

1- The electrical installation work must be carried out by a

qualified electrician. The electrical installation must comply with the standards in force in the country concerned

The power supply must be of the class 1 type. The unit must be connected via an earthed connection box. The electric power circuit must be protected by a high-sensitivity 30 mA differential circuit breaker set at 20 A. The connection must be used solely to power the SANICUBIC

2 Pro. If the power lead on the unit is damaged, it must be replaced by the manufactu- rer or its after-sales service to avoid all danger. red general alarm LED yellow transmission alarm LED green mains alarm LED motor 1 "override" “GeneralAlarm” LED “Mains” LED motor 2 "override"10

CONFORMITY WITH STANDARDS

2 Pro complies with standard EN 12050-1 (lift station for household waste containing faeces) and with the European directives covering construction products, electri- cal safety and electromagnetic compatibility This unit must be installed and used in compliance with European installation standard EN12056 and with local requirements. 3/ The green “mains” LED shows the status of the power supply for the remote alarm module: - On steadily = module powered by the mains supply - Flashing = mains supply fault for the module (which is thus operating on its battery power supply) - Off = module failure or module battery flat 4/ The buzzer stays on continuously during an alarm. It stops if the alarms are no longer present or if you press the button «Reset» General Alarm.

2 Pro unit is guaranteed for two years (parts and labour) provided that it has been installed and used in compliance with the present instructions.

MAINTENANCE A visual check of the lift station must be made once a month to make sure it is operating correctly, and the installation must be inspected regularly (once a year) by a qualified per- son. Meanwhile if encounter technical problems, please ask our after-sales service for advice. If the power supply cable of the unit is damaged, it must be replaced by the manufac- turer or its after-sales service to avoid all danger.

1- Once the plumbing and electrical connections have

been made, check that the connections are watertight by letting water flow successively through each inlet used. Make sure that the unit is operating correctly by carrying out at least two start cycles with water to test the system.

WARNING! Do not operate the motors in override status (by pressing the pushbuttons on the control box) until the pumps have been filled with water. Operation without water damages the maceration system.

2 Pro unit is designed to drain off household waste water. Any other use will invalidate the guarantee. Do not dispose of sanitary towels, condoms, hygiene articles, oils, solvents, acids, or any other poten- tially corrosive or explosive liquids etc., via the unit.

WARNING: In the event of a power failure, stop

draining any water from the equipment connected to the SANICUBIC

3- Do not install or use the unit in a zone where there is a

ALARM VAN HET APPARAAT

WERKING VAN HET ALARM

TILSLUTNING AF AFLØBSRØRET

Manual assistant
Powered by ChatGPT
Waiting for your message
Product information

Brand : Sanibroyeur

Model : Sanicubic 2 Pro Expertline

Category : Sanitary