TW 2 - Thermostat BOSCH - Free user manual and instructions
Find the device manual for free TW 2 BOSCH in PDF.
| Brand | Bosch |
| Model | TW 2 |
| Product type | Remote control for flow temperature regulator |
| Category | Room thermostat |
| Dimensions (H x W x D) | 82 x 82 x 42 mm |
| Rated voltage | 24 V DC |
| Rated current | 0.01 A |
| Adjustment range (with room temperature measurement) | Heating: 18.5 to 21.5 °C; Economy: 15.5 to 18.5 °C |
| Adjustment range (without room temperature measurement) | Flow temperature modification: -12 K to +12 K (heating); -37 K to -13 K (economy) |
| Permissible ambient temperature | 0 to +40 °C |
| Protection class | III |
| Protection type | IP 20 |
| Operating modes | Frost protection, Heating, Economy, Alternating |
| Main functions | Adjustment of room temperature or modification of the heating curve, with or without room temperature measurement |
| Mounting | On flush-mounted box Ø 55 mm or directly on the wall |
| Electrical connection | Two 24 V conductors, cross-section 1.5 mm² |
| Care and cleaning | Clean with a soft, dry cloth. Do not use abrasive products. |
| Safety | Do not connect to 230 V; disconnect power before mounting |
| Spare parts and repairability | Not specified in the manual |
| General information | 104-page user manual available in several languages |
Frequently Asked Questions - TW 2 BOSCH
User questions about TW 2 BOSCH
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Thermostat in PDF format for free! Find your manual TW 2 - BOSCH and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. TW 2 by BOSCH.
USER MANUAL TW 2 BOSCH
| 1 Safety Notes 7 | |
| 2 Details of Unit 7 | |
| 3 | Mounting |
| 4 Electrical Connection 8 | |
| 5 | Operation |
| 6 Important Notes 10 | |
| 7 Error Localisation 11 | |
1 Safety Notes
Correct functioning is ensured only when these instructions are observed. We request that this booklet be given to the customer.
Do not connect the remote control to the 230-V power mains.
This remote control is to be used only with the central heating appliances listed.
The remote control is to be connected to the respective heating equipment only in accordance with the circuit diagram.
Before the mounting of the remote control, the power supply (230 V, 50 Hz) to the heating equipment must be interrupted.
2 Details of Unit
2.1 Application
The TW2 remote control unit is only suitable for use with outside-temperature controlled central heating programmers with built-in timer.
It can be combined with the following central heating appliances:
| TYPE |
| ZR/ZWR/ZSR...-3/-4 |
| ZR/ZWR/ZSR/ZE/ZWE... |
| ZV/ZWV 20 A |
| Heating equipment with Bosch Heatronic |
| K/KN..-8 E/EC/P/KP |
| Mixer control + TA 130 A |
The TW2 can be used as a remote control with or without room thermostat function (see Section 5.3, "Room Thermostat Switch (h)").
Note: For use as a remote control without room temperature sensing, any mounting location can be selected. For use as a remote control with room temperature sensing, the unit must be mounted according to Fig. 2
2.2 Technical Data
| Height 82 mm | |
| Width 82 mm | |
| Depth 42 mm | |
| Rated Voltage 24 V DC | |
| Rated current regulator (clock) 0.01 A | |
| Regulation range with room temperature sensingCentral Heating ModeEconomy Mode | Switch (h)in position ●18.5...21.5 °C15.5...18.5 °C |
| Change in the feed temperature without room temperature sensingCentral Heating ModeEconomy Mode | Switch (h)in position ○-12 K...+12 K-37 K...-13 K |
| Minimum temperature changing speed 0.05 K/min | |
| Allowable environmental temperature 0 ... +40 °C | |
| Protection class | III |
| Protection type IP 20 | |
| CE |
3 Mounting

Before starting to work, the power supply (230 V, 50 Hz) to the heating equipment must be interrupted.
3.1 Choose a suitable installation site (if room thermostat function is to be used).
Important for the regulating quality of the remote control is the selection of a suitable mounting location.
Anforderungen
- The room in which it is mounted must be suitable for controlling the temperature of the complete heating system.
- The radiators installed in the room should not be equipped with thermostatic valves.
Note: It is more effective to install hand valves that can be preset so that the output of the radiator in the room where the TW 2 is mounted can be set as low as possible.
There must be sufficient space below the control unit to allow air to circulate unrestricted through the ventilation slots (shaded area in Figure 2)
Note: observe the recommended clearances as shown in Figure 2
3.2 Fitting the Remote Control
- For mounting, pull the upper part of the remote control (a) from the base (b).
- The base (b) of the TW 2 can be mounted either with two screws (d) on a standard flush connection box (c) of 55mm dia. (Fig. 4)
or
- with plugs (6 mm) and screws (3.5 mm dia., oval head), screwed directly onto the wall (Fig. 5, drilling template enclosed).
4 Electrical Connection
The TW2 remote control unit is connected to the outside-temperature controlled programmer by means of two cores in the connecting lead (24 V).
- Observe the applicable regulations.
- Use electrical cable conforming at least to H05VV-... with a cross-sectional area of 1.5 ~mm^2 .
- Connect the remote control unit to the central heating appliance according to the wiring diagram (see Figs. 6p)10
Avoiding Interference
- Route the connecting leads separately from wires carrying 230 V/400 V (minimum separation 100 mm).
- If there are external sources of inductive interference (e.g. high power cables, overhead tram cables, transformer substations, radio and television sets, amateur radio equipment, microwave appliances, etc.) the wires carrying the control signals should be shielded.
4.1 Commissioning
- After connecting the electrical wiring, press outer cover (a) onto base (b).
- Switch on the central heating appliance.
5 Operation
The TW2 is not an independent regulator but rather a remote control with or without room temperature sensing. It shifts the heating curve of the outside-temperature controlled programmer as required. It is therefore important that the settings on the regulator (e.g., heating curve) are correct.
Note: The mode switch on the outside-temperature controlled programmer must be set to position ⓂThe text display must be set to Automatic.
The TW 2 remote control has the following control elements (Fig. 1)
e Operational mode switch
f Adjustment knob
g Brief operating instructions: In the compartment on the right side of the base, a small instruction manual can be found. It contains all essentials for operation in brief form.
h Switch (Fig.) 3
5.1 Operating Mode Switch (e)
With this switch, selection can be made between the following four different operating modes:
Frost Protection Operation:
- At outside temperatures above + 4 °C, the central heating appliance is switched off (burner and pump). If a mixer valve is fitted, it closes and the circulation pump for that circuit is switched off.
- At outside temperatures below +3 °C, the central heating appliance is adjusted to the minimum temperature set on the outside-temperature controlled programmer. In case a heating mixer is present, it regulates to a feed temperature for +10 °C and the circulation pump for this heating circuit runs.
Central Heating Mode:
Continuous regulation of the temperature to the value set on the knob (f). See "Temperature Range" for the temperature range.
Economy Mode: Continuous reduction of the temperature
- Room thermostat function off: If the control knob (f) is in the centre position, the central heating flow temperature is reduced by approx. 25 K compared with the set heating characteristic.
- Room thermostat function on: If the control knob (f) is in the centre position, the central heating flow temperature is reduced by approx. 3 K compared with the set heating characteristic.
The reduced temperature setting on the outside-temperature controlled programmer has no effect. The circulation pump is switched on.
Alternating mode:
Temperature control alternates automatically between central heating and economy modes or between central heating and anti-freeze modes.
Alternation takes place according to the mode selected (or Automatic) on the outside-temperature controlled programmer or the timer program setting.
5.2 Knob (f)
The control knob shifts the heating characteristic set on the outside-temperature controlled programmer up or down.
- Set the central heating flow temperature on the control knob.
A division corresponds to a change of the feed temperature of 4 K and therefore a room temperature change of approx. 0.5 K (see "Temperature Range").
5.3 Switch (h)
- After removing the top part of the remote control (a) from the base (b), the switch (h) is accessible on the back side of the top part.
- With this switch, the room temperature sensing is switched on or off.
- Position O = Operation without room temperature sensing (delivered condition)
- Position = Operation with room temperature sensing.
Temperature Range
| Switch (h) in Position ○ without room temperature sensing | Switch (h) in Position ● with room temperature sensing | |||||||
| Knob (f) in nomy Position | Operational Mode Switch (e) in Position | Operational Mode Switch (e) in Position | ||||||
| ☀ | ☐ | ☐ | ☀ | ☐ | ☐ | |||
| Normal Mode | Re-duced Mode | Economy Mode | Normal Mode | Re-duced Mode | Economy Mode | |||
| Feed Temperature Change Approx. Room Temperature *) | ||||||||
| Left stop -12 K | -12 K | -37 K | ** | -37 K | 8.5 °C | 18.5 °C | 15.5 °C | ** |
| Middle position 0 | K 0 K | -25 K | ** | -25 K | 20 °C | 20 °C | 17 °C | ** |
| Right stop | +12 K | +12 K | -13 K | -13 K | 1.5 °C | 21.5 °C | 18 °C | ** |
*) The prerequisite is that the heating characteristic has been correctly set on the outside-temperature controlled programmer so that a room temperature of approx. 20 °C is obtained with the room thermostat function switched off.
**) Provided a temperature reduction of -25 K has been set on the outside-temperature controlled programmer.
6 Important Notes
6.1 Saving Energy
- The reducing of the room temperature over the day or night saves considerable energy. With the reduction of the room temperature by 1 K (°C), up to 5% less energy is used.
Note: It does not make sense to reduce the room temperature under +15 °C, however, since intense reheating consumes more energy than the uniform supplying of warmth.
- For buildings with good heat insulation, the reduced temperature setting may possibly not be reached. Energy is saved in spite of this, however, since the heating unit remains switched off.
In this case, the switching time for reduced operation can also be set for an earlier time.
- For ventilating, do not leave the windows in the tilted position. In this manner, heat escapes continuously from the room without the air in the room being significantly improved. Therefore, avoid continuous ventilating!
It is better to ventilate briefly but intensively (window completely open).
During ventilating, set the temperature regulator to a lower value.
6.2 Information for Operation with Room Temperature Sensing:
- The room (main room) in which the remote control is installed determines the temperature for the other rooms.
This means that the room temperature in the main room acts as a parameter for the complete heating network.
- For this reason, thermostatically regulated heating radiators that are mounted in the main room must always be completely open.
Otherwise the thermostatic valve restricts the heat supply although the regulator continuously demands more heat.
If a lower temperature is desired in adjacent rooms or if the radiators should be shut off completely, the radiator valves (thermostats) are to be set accordingly.
In this case, it is recommended to forego the room temperature sensing.
- Since the room in which the remote control is mounted acts as the main room, heat from exterior sources (e. g. sun radiation, fireplace, etc.) can lead to inadequate heating in the other rooms (Heating unit remains cold).
| Malfunction Cause Correction | ||
| Room temperature setting is not reached | Thermostat valve(s) installed in the room where the remote control (with room temperature sensing) is located | Have the thermostatic valve(s) removed or Open the thermostatic valve completely or switch off the room temperature sensing |
| Boiler thermostat on the heating equipment is set too low | Increase the setting of the feed temperature selector on the heating equipment | |
| The room temperature setting is exceeded | Mounting location of the remote control (with room temperature sensing) is unsuitable, e.g. on an outer wall, near a window, in a draft, etc. | Select a more suitable mounting location (see chapter on mounting) or switch off room temperature sensing |
| Room temperature variations too large | Temporary influence of external heat source on the remote control (with room temperature sensing), e. g. sun radiation, room lighting, TV, fireplace, etc. | Select a more suitable mounting location (see chapter on mounting) or switch off room temperature sensing |
| Temperature increases instead of decreasing | Time of day set incorrectly on the timer | Check setting on the timer for the outside-temperature controlled programmer |
| Switching riders incorrectly inserted | Check setting on the timer for the outside-temperature controlled programmer | |
| Room temperature too high in reduced operation | High heat storage capacity of the building | Select an earlier time for reduction |
| Minimum feed temperature set too high | Check settings against operating instructions for the outside-temperature controlled programmer and central heating appliance and correct as necessary. | |
| Improper or no regulation | Outside-temperature controlled programmer or remote control unit incorrectly wired | Check the wiring in accordance with the associated mounting instructions and correct if necessary. |