DL 750 - Lighting STEINEL - Free user manual and instructions

Find the device manual for free DL 750 STEINEL in PDF.

📄 33 pages English EN 💬 AI Question
Notice STEINEL DL 750 - page 7

Download the instructions for your Lighting in PDF format for free! Find your manual DL 750 - STEINEL and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. DL 750 by STEINEL.

USER MANUAL DL 750 STEINEL

1110For exposed wiring 2: drill the hole for insertion of the cable and deburr with a round file.

4. Screw on housing a, align

at a right angle if required by means of the elongated holes.

5. Connection of the mains

lead (see diagram). The mains lead consists of a 3 phase cable (dia. 10 mm max.). L = phase conductor (usually black or brown) N = neutral conductor (usually blue) PE = protective-earth conductor (green/yellow) Principle The CeilingSensorLight is equipped with three 120° pyro sensors which detect the invisible heat emitted by mov- ing objects (pedestrians, ani- mals etc.). The heat detected is converted electronically into a signal that switches the light on automatically. No heat radiation is detected through obstacles, such as walls or glass and no switching therefore occurs. Pyro sensors have a detec- tion angle of 360° with an opening angle of 180°. Safety instructions

Disconnect the power supply before any work on the CeilingSensorLight!

During installation, the electric power cable to be connected must be voltage-free. Therefore, switch off the power first and check freedom from voltage with a voltage tester.

Installation of the CeilingSensorLight involves work on the Installation The installation site should be at least 50 cm from another light, since the latter's heat radiation could result in false triggering of the sensor. Furthermore, the Ceiling- SensorLight must be position- ed completely on the attach- ment surface. Installation procedure:

1. Hold housing a against

the wall and mark drill holes at the markings.

2. Drill the holes and insert

wall plugs (6 mm dia.).

3. Strip the insulation of the

mains lead, leaving 10 mm of insulation and push the enclosed heat-resistant silicone tubes on to the insulated conductors. Insert the sealing plug into the housing, pierce and pass the cable through. If in doubt, the cable must be identified with a voltage test- er. Switch off the current again. The phase (L) and neutral conductors (N) are connected to the terminal block. Connect the protect- ive-earth conductor to the corresponding terminal. Note: A mains switch for ON and OFF switching can of course be installed in the mains lead. This is a pre- requisite for permanent light function (refer to permanent light function section, page 15).

6. Apply the lampshade i

and secure by rotating.

7. Perform time, f light

threshold e and bright- ness control g adjustment (refer to functions section, page 14). Important: the safest motion detection is obtained when the device is mounted lateral- ly to the walking direction and no obstacles (such as trees and walls, for example) obstruct the view 1 . mains power supply; this work must therefore be carried out professionally in accordance with regulations. Dimensions (HxWxD): 315 x 315 x 135 mm Output: ceiling mounting: 100 W max. / E 27 wall mounting: 60 W max. / E 27 Connection: 230 – 240 V, 50 Hz Angle of coverage: 360° with 180° angle of aperture Pivoting range: Fine adjustment ± 60° Reach: max. 12 m (electronically stabilised) Twilight setting: 2 – 2000 lux Time setting: 5 sec. – 15 min. Brightness control: 0 – 50 % (Watt-o-matic) Permanent light: switchable (4 h max.) Prerequisite: connected switch in supply lead Enclosure: IP 44 Temperature range: -20 °C to +50 °C Installation instructions Dear customer, Congratulations on purchasing your new STEINEL Ceiling- SensorLight and thank you for the confidence you have shown in us. You have chosen a high- quality product that has been manufactured, tested and packed with the greatest care. Please familiarise yourself with these instructions before attempting to install the CeilingSensorLight as prolonged reliable and trouble- free operation will only be ensured if it is fitted correctly. System components a. Housing b Sensor c Lamp holder / E 27 d Decorative ring, removable e Twilight setting f Time setting g Brightness control (dimming) h Connection i Glass with bayonet Technical specifications

We hope your new Ceiling- SensorLight will give you lasting satisfaction.

1312Permanent light function If a power switch is installedin the supply lead, thefollowing functions arepossible in addition to simplyswitching ON and OFF:Sensor operation1) Switch on the light:Switch 1 x OFF and ONThe light remains on for theset time.2) Switch off light:Switch 1 x OFF and ONThe light goes out ortransfers to sensor operation.Permanent light operation1) Switch on the light:Switch 2 x OFF and ONThe light is set to permanentillumination for 4 hours (thered LED illuminates behindthe lens).It subsequently changesautomatically to sensor oper-ation (red LED goes out).2) Switch off light:Switch 1 x OFF and ONThe light goes out or changesto sensor operation. Reach setting/adjustment Assuming an installationheight of 2.5 m, the maximumreach of the sensor is 12 m.Optimum adjustment of thedetection zone is possibleaccording to needs. Theshrouds provided serve tocover any desired number oflens segments and individu-ally reduce the reach. Falseswitching by cars andImportant:The switch should beoperated repeatedly in shortsuccession (in the range of0.5 – 1 sec.)pedestrians, etc. is thereforeruled out, or risk areasdeliberately monitored.Theshrouds can be dividedvertically or horizontally alongthe grooved divisions, or cut with scissors 3. After removing the decorative ring4, the shrouds are to besuspended on the upper partof the sensor lens.The decorative ring issubsequently to be reappliedand the shrouds are fixedfirmly in place.Fine adjustment is alsopossible by turning the sensor housing by ± 60° 5. 5 sec. - 15 min. max. 4 hours 1 x OFF/ON 2 x OFF/ON Functions Once you have installed thehousing and connected theCeilingSensorLight, it can beTwilight setting(threshold)

Continuously adjustablesensor response thresholdfrom 2 – 2000 lux.Adjustment control set to 1= daylight operation, approx.2000 lux. (factory setting)Adjustment control set to 6= night-time operationapprox. 2 lux.The adjustment control mustbe set to 1 (daylightoperation) when setting thedetection zone in daylight.Switch-off delay(time setting)

Continuously adjustable lightduration of 5 sec. to 15 min.Adjustment control set to 1= shortest time(5 sec., factory setting)Adjustment control set to 6= longest time (15 min.)When setting the detectionzone, it is recommended toselect the shortest time(setting 1).Brightness control(Watt-o-matic)

Continuously adjustable con-stant light from 0 – 50 %.When movement is detected,the light switches from, say,20 watts maintained lightoutput to maximum output(100 watts).Adjustment control set to 1= no dimming (factory setting)Adjustment control set to 6= greatest dimmingIf this control is rotated, thered LED (behind the lens)flashes and the light illumin-ates with the set brightness.After release, the dimminglevel can be further adjustedfor approx. 3 sec. (LED con-tinues to flash). Soft light illumination The CeilingSensorLight has asoft light illumination function.This means that the lightdoes not switch directly to fullput into operation. After remo-ving the decorative ring d,the adjusting screws fortwilight, time and brightnesscontrol are visible.output when switched on, butthe brightness is slowly incre-ased to 100% within twoseconds. The electronicsoperate equally gently whenswitching off.

GBOperation/Maintenance This product complies with the European Directive on Low-Voltage Appliances, Functional Warranty Declaration of conformity 06/95/EC and the EMC Directive 04/108/EC. This Steinel product has been manufactured with utmost care, tested for proper operation and safety and then subjected to random sample inspection. STEINEL guarantees that it is in perfect condition and proper working order. The warranty period is 36 months and starts on the date of sale to the consumer. We will remedy defects caused by material flaws or manufacturing faults. The warranty will be met by repair or replacement at our own discretion. The warranty does not cover damage to wear parts or damage and defects caused by improper treatment, maintenance or the use of non-genuine parts. Further consequential damage to other objects is excluded. Claims under the warranty will only be accepted if the unit is sent fully assembled and well packed with a brief description of the fault, a receipt or invoice (date of purchase and dealer’s stamp) to the appropriate Service Centre. Repair Service: Our Customer Service Department will repair faults not covered by warranty or after the warranty period. Please send the product well packed to your nearest Service Centre. The CeilingSensorLight is suitable for switching on a light automatically. Weather can affect operation of the sensor. Strong gusts of wind, snow, rain and hail can cause switching errors, since the sudden temperature changes cannot be distinguished from heat sources. The detection lens can be cleaned with a damp cloth (without detergents) if dirty. Troubleshooting Malfunction Cause Remedy CeilingSensorLight without power CeilingSensorLight does not switch on CeilingSensorLight does not switch off CeilingSensorLight switches on when it should not CeilingSensorLight reach modification Red LED is constantly illuminated, even without no permanent light setting

Fuse has blown; not switched ON; break in wiring

Replace fuse, switch on mains switch, check wiring with voltage tester

Twilight setting in nighttime mode during daytime operation

Product’s internal electrical fuse has been activated (LED illuminates permanently)

Switch off, eliminate short circuit if appropriate and switch on again

Continued movement within the detection zone

Wind is moving trees and bushes in the detection zone

Cars in the street are detected

Sunlight shining on the lens

Sudden temperature changes due to weather (wind, rain, snow) or exhaust air from fans or open windows

Mount sensor in a protected place or change detection zone

Adjust detection zone or install in a different place

Use shrouds to define detection zone precisely

Product’s internal electrical fuse has been activated

Bulb with more than 100 W connected

Switch off, eliminate short circuit if appropriate and switch on again

Switch off SensorLight, insert a bulb with max. 100 W and switch on again

Check detection zone and readjust if necessary

ny innstilling (regulator e)

Manual assistant
Powered by ChatGPT
Waiting for your message
Product information

Brand : STEINEL

Model : DL 750

Category : Lighting