DH300 - Dehumidifier TAURUS - Free user manual and instructions

Find the device manual for free DH300 TAURUS in PDF.

📄 156 pages English EN 💬 AI Question
Notice TAURUS DH300 - page 15
Manual assistant
Powered by ChatGPT
Waiting for your message
Product information

Brand : TAURUS

Model : DH300

Category : Dehumidifier

Download the instructions for your Dehumidifier in PDF format for free! Find your manual DH300 - TAURUS and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. DH300 by TAURUS.

USER MANUAL DH300 TAURUS

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST [EN | (Original instructions) DEHUMIDIFIER

Please do not install or use your mobile dehumidifier before you have carefully read this manual. Please keep this _ instructions manual for an eventual product warranty and for future reference. DESCRIPTION

17. Water pump on/off

Ifthe model of your appliance does not have the accessories described above, they can also be bought separately from the Technical Assistance Service. USE AND CARE: Before each use, completely unplug the power cable from the power supply. Do not use the appliance if its start / stop device does not work. Do not remove the castors from the appliance. Do not move the appliance while it is in use. Use the handles to take or transport the appliance. Do not turn the appliance over while it is in use or connected to the mains. Unplug the power supply from the mains when not in use and before performing any cleaning operations. Keep this appliance out of the reach of children and / or persons with reduced physical, sensory or mental abilties or who are unfamiliar with its use. Do not expose the appliance to extreme temperatures. Keep the device in a dry, dust-free place protected from directsunlight. Never leave the appliance unattended. It will also save energy and prolong the life of the device.

INSTRUCTIONS FOR USE

BEFORE USE: Make sure that all products’ packaging has been removed. Some parts of the appliance have been lightly greased. Consequentiy, the first time the appliance is used a light smoke may be detected. After a short time, this smoke will disappear. To eliminate the smell given off by the appliance when used for the first time, it is recommended to have it on at full power for 2 hours in a well-ventilated room. Prepare the appliance according to the function you wish to use.

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST Display will show the ambient and selected humidity. When the ambient humidity is lower than 20% or higher than 80%, it will show. USE: Extend the power cord completely before plugging in. Plug the appliance into the mains. Turn the appliance on, by using the power button (10) The pilot light comes on. (19) Select the desired fan speed (13) To avoid a fierce start-up of the fan, itis advisable to start off from the lowest speed position and, once the fan has been switched on, progressively increase the speed to the desired position. Press the humidity setting buttons (18) to select the desired humidity. The display indicator above will start flashing. FAN MODE: Select the desired fan speed (high, medium or low) by pressing the fan speed button. The pilot light will indicate selected speed. HUMIDITY SETTING FUNCTION: Press the humidity setting buttons (18) to select the desired humidity. The display indicator above will start flashing. The humidiy range is 35% to 80%. And the default level is 50%. Press the arrows (18) to adjust the desired humidity level. For every press the humidity % will be adjusted by 5%. Once you have reached the desired humidity %. Stop pressing the buttons for 3 seconds. The light indicator above will stop flashing and the display (14) will show the ambient humidity again. TIMER FUNCTION: The appliance’s operating time can be controlled. When the dehumidifier is off, it can be pro- grammed to automatically turn on after the set time. When the dehumidifier is on, the running time of the compressor can be programmed. In standby mode, press the timer button (16) to iniciate this function. The display screen (14) will show the time that is selected. Adjust the desired time by pressing the arrows (18) as many times as hours needed (0,5-10h). Every press adjusts half an hour until to 10h. From 10h to 24h every press adjusts an hour. The time programmed or remaining time will appear on the display (14). Once you reach the desired time, stop pressing the button. After 3 seconds, the set time is confirmed. The light indicator above will turn on. DRAINAGE (WATER TANK): (Fig 1) When the water tank is full, the full tank light indicator (20) will turn on. The appliance also emits a buzzing sound to alert the user. When the water tank is full, the operation will stop. Proceed to remove the water tank. Place one hand on each side of the depression areas to gently remove the water tank. Pour the water out. Proceed to place the tank back into the appliance to restart the dehumidifier (be careful with the water pump filter, put it correctly) DRAINAGE (CONTINUOUS DRAINAGE): (Fig 2.1) If you do not want to empty the water tank everytime it gets full, you can connect the drainage pipe provided to the drainage outlet to drain the water continuousiy. (6) The low end of the water pipe must be more than 10cm lower than the height of the water outlet. The end of the pipe cannot remain in water. It is highly recommended to install it on a place that allows the water to drain constantiy. The water pipe must be kept smooth,

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST otherwise the water may not be drained property. WATER PUMP FUNCTION: (Fig 2.2) If you do not want to empty the water tank every time it gets full, you can connect the drainage pipe provided to the drainage outlet to drain the water. The water pump drains to an overhead room located at a maximum 3 meters up. When the deshumidifier is on, press the water pump button (17) to iniciate this function. The pilot light comes on (21). When the tank water is to be filed, the pump water function is activated. The water pump cycles for 2 minutes with period of 1 minute between each cycle. The water pipe must be kept smooth, otherwise the water may not be drained property. The end of the pipe cannot remain in water. It is highly recommended to install it on a place that allows the water to drain constantly. ONCE THE APPLIANCE HAS BEEN USED: Stop the appliance using the Power button. Unplug the appliance from the mains. Put the power cord back in the power cord housing. Clean the appliance. CABLE COMPARTMENT: This appliance has a power cord housing situated on its posterior. CARRY HANDLE/S AND CASTORS: This appliance has two handles on the side of the body, which faciltates comfortable transport. There are also four castors to facilitate the transportation of the appliance and avoid injuries. SAFETY THERMAL PROTECTOR: The appliance has a safety device, which protects the appliance from overheating. Ifthe appliance turns itself off and does not switch itself on again, disconnect it from the mains supply, and wait for approximately 15 minutes before reconnecting. If the machine does not start again seek authorised technical assistance. CLEANING Disconnect the dehumidifier from the mains and allow it to cool before undertaking any cleaning task. Clean the electrical equipment and the mains connection with a damp cloth and dry. DO NOT IMMERSE IN WATER OR ANY OTHER LIQUID. Clean the equipment with a damp cloth with a few drops of washing-up liquid and then dry. Do not use solvents, or products with an acid or base pH such as bleach, or abrasive products, for cleaning the appliance. Do not let water or any other liquid get into the air vents to avoid damage to the inner parts of the appliance. Never submerge the appliance in water or any other liquid or place it under running water. Ifthe appliance is not in good condition of cleanliness, its surface may degrade and inexorably affect the duration of the appliance’s useful life and could become unsafe to use. Then dry all parts before its assembly and storage. CLEANING THE AIR FILTER (FIG 3) Clean the air filters every 2 weeks. If the air filter is blocked with dust, its effectiveness will be reduced. Open the inlet grill and washing the air filters by submerging them carefully in warm water with a neutral detergent, rinse them off and let them dry completely in a shady place.

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST Install the fiers carefully after having them cleaned.

ANOMALIES AND REPAIR

Tlf any anomaly is detected, check the following table: Anomalies | Cause Solution E2 Coil Check coil temperature | temperature sensor sensor and abnormal | related circuit EH Humidity Check sensor humidity. anomaly sensor and related circuit ES Water pump _ | Check water failure pump motor and related circuit

The appliance contains flammable refrigerant

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST INSTRUCTIONS FOR REPAIRING APPLIANCES CONTAINING R290 GENERAL INSTRUCTIONS

Prior to beginning work on systems containing flammable refrigerants, safety checks are nec- essary to ensure that the risk of ignition is mi- nimised. For repair to the refrigerating system, the following precautions shall be complied with prior to con-ducting work on the system. WORK PROCEDURE Work shall be undertaken under a controlled procedure so as to minimise the risk of a flam- mable gas or vapour being present while the work is being performed.

All maintenance staff and others working in the local area shall be instructed on the nature of work being carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off. Ensure that the conditions within the area have been made safe by control of flammable material.

CHECKING FOR PRESENCE OF

REFRIGERANT The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure the technician is aware of potentially flammable atmospheres. Ensure that the leak tection equipment being used is suitable for use with flammable refrigerants, i.e. nonsparking, adequately sealed or intrinsically safe.

PRESENCE OF FIRE EXTINGUISHER

If any hot work is to be conducted on the refrigeration equipment or any associated parts, propriate fire extinguishing equipment shall be available to hand. Have a dry powder or CO 2 fire extinguisher adjacent to the charging area.

- No person carrying out work in relation to a refrigeration system which involves exposing any pipe work that contains or has contained flammable refrigerant shall use any sources of ignition in such a manner that it may lead to the risk of fire or explosion. AIl possible ignition sources, including igarette smoking, should be kept sufficiently far away from the site of installation, repairing, removing and disposal, during which flammable refrigerant can possibly be released to the surrounding space. Prior to work taking place, the area around the equip- ment is to be surveyed to make sure that there are no flammable hazards or ignition risks. “No Smoking’ signs shall be displayed. VENTILATED AREA - Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work. À degree of ventilation shall continue during the period that the work is carried out. The ventilation should safely disperse any released refrigerant and preferably expel it external into the atmo- sphere.

CHECKS TO THE REFRIGERATION

EQUIPMENT - Where electrical components are being changed, they shall be fit for the purpose and to the correct specification. At all times the manufacturer's maintenance and service guidelines shall be followed. If in doubt consult the manufacturer's technical department for as- sistance.The following checks shall be applied to installations using flammable refrigerants: the charge size is in accordance with the room size within which the refrigerant containing parts are installed: the ventilation machinery and outlets are operating adequately and are not obstruct- ed; if an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant; marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected; refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance which may corrode refrigerant containing components, unless the components are constructed of materials which are inherently resistant to being corroded or are suitably protected against being so corroded.

CHECKS TO ELECTRICAL DEVICES

- Repair and maintenance to electrical compo-

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST nents shall include initial safety checks and component inspection procedures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adequate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised. Initial safety checks shall include: that capac- itors are discharged: this shall be done in a safe manner to avoid possibility of sparking: that there no live electrical components and wiring are exposed while charging, recovering or purging the system; that there is continuity of earth bonding.

REPAIRS TO SEALED COMPONENTS

- During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. Ifit is absolute- ly necessary to have an electrical supply to equipment during servicing, then a permanentiy operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation. Particular attention shall be paid to the following to ensure that by working on electrical compo- nents, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incor- rect fitting of glands, etc. Ensure that appara- tus is mounted securely. Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of prevent- ing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's specifications. - NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.

REPAIR TO INTRINSICALLY SAFE

COMPONENTS = Do not apply any permanent inductive or ca- pacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak. CABLING - Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans.

DETECTION OF FLAMMABLE

REFRIGERANTS - Under no circumstances shall potential sources ofignition be used in the searching for or detection of refrigerant leaks. À halide torch (or any other detector using a naked flame) shall not be used.

LEAK DETECTION METHODS

-_ The following leak detection methods are deemed acceptable for systems contain- ing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need recalibration. (Detection equipment shall be calibrated in a refriger- ant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrig- erant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents contain- ing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process.

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

REMOVAL AND EVACUATION

- When breaking into the refrigerant circuit to make repairs — or for any other purpose — con- ventional procedures shall be used. However, it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to: remove refriger- ant purge the circuit with inert gas: evacuate; purge again with inert gas: open the circuit by cutting or brazing. The refrigerant charge shall be recovered into the correct recovery cylin- ders. The system shall be “flushed” with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for this task. Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fil until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipework are to take place. Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available. CHARGING PROCEDURES - In addition to conventional charging proce- dures, the following requirements shall be followed. - Ensure that contamination of different refrig- erants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them. - Cylinders shall be kept upright. - Ensure that the refrigeration system is earthed prior to charging the system with refrigerant. - Label the system when charging is complete (if not already). - Extreme care shall be taken not to overfil the refrigeration system. = Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. À follow up leak test shall be carried out prior to leaving the site. DECOMMISSIONING - Before carrying out this procedure, it is essen- tial that the technician is completely familiar with the equipment and al its detail. It is rec- ommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced. a) Become familiar with the equipment and its operation. b) Isolate system electrically. c) Before attempting the procedure ensure that: mechanical handling equipment is available, if required, for handling refrigerant cylinders; all personal protective equipment is available and being used correctiy: the recovery process is supervised at all times by a competent person: recovery equipment and cylinders conform to the appropriate standards. d) Pump down refrigerant system, if possible. e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from vari- ous parts of the system. f) Make sure that cylinder is situated on the scales before recovery takes place.

9) Start the recovery machine and operate in

accordance with manufacturer's instructions. h) Do not overfill cylinders. (No more than 80 % volume liquid charge).

i) Do not exceed the maximum working pressure

of the cylinder, even temporarily. j) When the cylnders have been filled correctiy and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off. k) Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked. LABELLING - Equipment shall be labelled stating that it has been de-commissioned and emptied of refriger- ant. The label shall be dated and signed. - Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST RECOVERY - When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. When transferring refriger- ant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrig- erant (Le. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order. Empty recovery. cylinders are evacuated and, if possible, cooled before recovery occurs. The recovery equipment shall be in good work- ing order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery of flammable refriger- ants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good condition. Be- fore using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult man- ufacturer if in doubt. The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery. cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylnders. If compres- sors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out pri- or to returning the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.

COMPETENCE OF SERVICE

PERSONNEL GENERAL - Special training additional to usual refrigerat- ing equipment repair procedures is required when equipment with flammable refrigerants is affected. In many countries, this training is carried out by national training organisations that are accred- ited to teach the relevant national competency standards that may be set in legislation. The achieved competence should be docu- mented by a certificate. TRAINING The training should include the substance of the following: Information about the explosion potential of flammable refrigerants to show that flammables may be dangerous when handled without care. Information about potential ignition sources, especially those that are not obvious, such as lighters, light switches, vacuum cleaners, electric heaters. Information about the different safety concepts: Unventilated — (see Clause GG.2) Safety of the appliance does not depend on ventilation of the housing. Switching off the appliance or opening of the housing has no significant effect on the safety. Nevertheless, it is possible that leaking refrigerant may accumulate inside the enclosure and flammable atmosphere will be released when the enclosure is opened. - Ventilated enclosure — (see Clause GG.4) Safe- ty of the appliance depends on ventilation of the housing. Switching off the appliance or opening of the enclosure has a significant effect on the safety. Care should be taken to ensure a suficient ventilation before. - Ventilated room — (see Clause GG.5) Safety of the appliance depends on the ventilation of the room. Switching off the appliance or open- ing of the housing has no significant effect on the safety. The ventilation of the room shall not be switched off during repair procedures. - Information about the concept of sealed compo- nents and sealed enclosures according to IEC: 60079-15:2010. - Information about the correct working proce- dures: COMMISSIONING - Ensure that the floor area is sufficient for the refrigerant charge or that the ventilation duct is assembled in a correct manner. - Connect the pipes and carry out a leak test before charging with refrigerant.

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST - Check safety equipment before putting into service. MAINTENANCE - Portable equipment shall be repaired outside or in a workshop specially equipped for servicing units with flammable refrigerants. Ensure sufficient ventilation at the repair place. Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrig- erant leak is possible. Discharge capacitors in a way that won't cause any spark. The standard procedure to short circuit the capacitor terminals usually creates sparks. Reassemble sealed enclosures accurately. If seals are worn, replace them. Check safety equipment before putting into service. REPAIR - Portable equipment shall be repaired outside or in a workshop specially equipped for servicing units with flammable refrigerants. - Ensure sufficient ventilation at the repair place. Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrig- erant leak is possible. - Discharge capacitors in a way that won't cause any spark. When brazing is required, the following proce- dures shall be carried out in the right order: - Remove the refrigerant. If the recovery is not required by national regulations, drain the refrigerant to the outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet. Take special care that drained refrigerant will not float back into the building. - Evacuate the refrigerant circuit. Purge the refrigerant circuit with nitrogen for 5 min. - Evacuate again. Remove parts to be replaced by cutting, not by flame. - Purge the braze point with nitrogen during the brazing procedure. Carry out a leak test before charging with refrigerant. - Reassemble sealed enclosures accurately. If seals are worn, replace them. - Check safety equipment before putting into service. DECOMMISSIONING - Ifthe safety is affected when the equipment is putted out of service, the refrigerant charge shall be removed before decommissioning. Ensure sufficient ventilation at the equipment location. Be aware that malfunction of the equipment may be caused by refrigerant loss and a refrig- erant leak is possible. Discharge capacitors in a way that won't cause any spark. Remove the refrigerant. If the recovery is not required by national regulations, drain the refrigerant to the outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet. Take special care that drained refrigerant will not float back into the building. Evacuate the refrigerant circuit. Purge the refrigerant circuit with nitrogen for 5 min. Evacuate again. Fill with nitrogen up to atmospheric pressure. Put a label on the equipment that the refrigerant is removed. DISPOSAL Ensure sufficient ventilation at the working place. Remove the refrigerant. If the recovery is not required by national regulations, drain the refrigerant to the outside. Take care that the drained refrigerant will not cause any danger. In doubt, one person should guard the outlet. Take special care that drained refrigerant will not float back into the building. Evacuate the refrigerant circuit. Purge the refrigerant circuit with nitrogen for 5 min. Evacuate again. Cut out the compressor and drain the oil.

TRANSPORTATION, MARKING AND

FLAMMABLE REFRIGERANTS - Attention is drawn to the fact that additional

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST transportation regulations may exist with re- spect to equipment containing flammable gas. The maximum number of pieces of equipment or the configuration of the equipment, permitted to be transported together will be determined by the applicable transport regulations.

MARKING OF EQUIPMENT USING SIGNS

= Signs for similar appliances used in a work area generally are addressed by local regulations and give the minimum requirements for the provision of safety and/or health signs for a work location. All required signs are to be maintained and em- ployers should ensure that employees receive suitable and sufficient instruction and training on the meaning of appropriate safety signs and the actions that need to be taken in connection with these signs. - The effectiveness of signs should not be dimin- ished by too many signs being placed together. Any pictograms used should be as simple as possible and contain only essential details.

- The storage of equipment should be in accor- dance with the manufacturer's instructions. Storage of packed (unsold) equipment Storage package protection should be con- structed such that mechanical damage to the equipment inside the package will not cause a leak of the refrigerant charge. The maximum number of pieces of equipment permitted to be stored together will be deter- mined by local regulations.

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST INSTRUCTIES VOOR

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

CBETNUHHAAT MHAMKATOP, KASBALU TOBA

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

M3BPLIBA OT AEPXABHA KBANADAKALMOHHU

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

This product enjoys the recognition and protection of the legal guarantee in accordance with current legislation. To enforce your rights or interests you must go to any of our official technical assistance services. You can find the closest one by accessing the following web link: http://taurus-home.com/ You can also request related information by. contacting us. You can download this instruction manual and its updates at http/taurus-home.com/ Français

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST

COUNTRY ADDRESS PHONE

Downloaded by: pd-oliana on 11-08-2022 08:24 CEST