MSP 1512 - Air-conditioner DOMETIC - Free user manual and instructions

Find the device manual for free MSP 1512 DOMETIC in PDF.

📄 240 pages English EN 💬 AI Question
Notice DOMETIC MSP 1512 - page 35

Download the instructions for your Air-conditioner in PDF format for free! Find your manual MSP 1512 - DOMETIC and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MSP 1512 by DOMETIC.

USER MANUAL MSP 1512 DOMETIC

We will be happy to provide you with further information about Domatic WAECO products. Please order our free catalogue with no obligation to buy on our homepage: www.domatic-waeco.com

DOMETIC MSP 1512 - 1

Please read this instruction manual carefully before installing and starting up the device, and store it in a safe place. If the device is passed on to another person, this manual must also be handed over with it.

Contents

1 Notes on using the manual 35
2 Safety instructions 35
3 Scope of delivery 38
4 Accessories 38
5 Target group for this manual 39
6 Intended use 39
7 Technical description 39
8 Fastening the inverter 43
9 Connecting the inverter to the exhaust system 45
10 Connecting the inverter 45
11 Using the inverter. 50
12 Cleaning and caring for the inverter. 52
13 Troubleshooting 52
14 Guarantee 53
15 Disposal 53
16 Technical data 53

1 Notes on using the manual

DOMETIC MSP 1512 - Notes on using the manual - 1

Caution

Safety instruction: Failure to observe this instruction can cause material damage and impair the function of the device.

DOMETIC MSP 1512 - Caution - 1

Caution

Safety instruction relating to a danger from an electrical current or voltage. Failure to observe this instruction can cause material damage and personal injury and impair the function of the device.

DOMETIC MSP 1512 - Caution - 1

Note

Supplementary information on operating the device.

Action: This symbol indicates that action is required on your part. The required action is described step-by-step.
This symbol describes the result of an action.

Please observe the following safety instructions.

2 Safety instructions

The manufacturer will not be held liable for claims for damage resulting from the following:

  • Faulty assembly or connection
  • Damage to the appliance resulting from mechanical influences and excess voltage
  • Alterations to the device without express permission from the manufacturer
  • Use for purposes other than those described in the operating manual

Note the following basic safety information when using electrical devices to protect against:

Electric shock
- Fire hazards
Injury

2.1 General safety

  • During construction of a 230V_AC socket distribution circuit, it is absolutely essential to have a circuit breaker (residual current circuit breaker) installed and a grounding bridge set by a trained professional, see chapter "Connect multiple appliances" on page 48.
  • Electronic devices are not toys!

Keep electrical appliances out of reach from children or infirm persons. Do not let them use the appliances without supervision.

  • Persons (including children) whose physical, sensory or mental capabilities or lack of experience and knowledge prevents them from using the appliance safely should not use this appliance without initial supervision or instruction by a responsible person.
  • Use the device only as intended.
  • Do not operate the device in a damp or wet environment.
  • Do not operate the device near any flammable materials.
  • Do not operate the device in areas that are potentially explosive.
  • Maintenance and repair work may only be carried out by qualified personnel who are familiar with the risks involved and the relevant regulations.

2.2 Safety when installing the device

  • Ensure the device is standing firmly.
    The device must be set up and fastened in such a way that it cannot tip over or fall down.
  • Take the precautions necessary to ensure that children cannot interfere with operation. Dangerous situations may occur which cannot be recognised by children!
  • Do not expose the device to a heat source (such as direct sunlight or heating). Avoid additional heating of the device in this way.

For installation on boats

  • If electrical devices are incorrectly installed on boats, corrosion damage might occur. Have the inverter installed by a specialist (marine) electrician.

Electrical cables

  • If cables have to be fed through metal walls or other walls with sharp edges, use ducts or wire bushings to prevent damage.
  • Do not lay cables which are loose or bent next to electrically conductive material (metal).
  • Do not pull on the cables.
  • Do not lay the 230 ~V mains cable and the 12 / 24 ~V DC cable in the same duct.
  • Fasten the cables securely.
  • Lay the cables so that they cannot be tripped over or damaged.

2.3 Operating the appliance safely

  • Operate the device only if you are certain that the housing and the cables are undamaged.
  • Make sure the air inlets and outlets of the device are not covered.
  • Ensure good ventilation.
  • Do not connect the 230 ~V output of the inverter (fig. 2 4, page 4) to a different 230 ~V source.
  • Even after the fuse triggers, parts of the inverter remain live.
  • Always disconnect the power supply when working on the device.

3 Scope of delivery

No. in fig. 1, page 3Description
1Inverter
2Holders MSP 702, MSP 704, MSP 1012, MSP 1024, MSP 1512, MSP 1524: 4 holders MSP 2012, MSP 2024, MSP 2512, MSP 2524: 6 holders
3Connection cable with safety plug (for 230 VACsupply)
4Connection cable with safety coupling (for 230 VACoutput)
5Exhaust adapter MSP 702, MSP 704, MSP 1012, MSP 1024, MSP 1512, MSP 1524: one exhaust adapter each MSP 2012, MSP 2024, MSP 2512, MSP 2524: two exhaust adapters each.
6Cable socket
7Hexagon socket wrench
-Fastening material
-Operating instructions

4 Accessories

DescriptionItem number
Remote controlMCR-7
Remote controlMCR-9

5 Target group for this manual

The „Connecting the inverter“ auf Seite 45 chapter is intended exclusively for trained professionals who are familiar with the relevant VDE (German Engineering Society) regulations.

All other chapters are intended for the users of the device.

6 Intended use

The SinePower inverters are used to convert a direct current of 12V or 24V into a 230V AC supply of 50Hz .

12V:

SinePower MSP 702, Item no. MSP700-012

SinePower MSP 1012, Item no. MSP1000-012

SinePower MSP 1512, Item no. MSP1500-012

SinePower MSP 2012, Item no. MSP2000-012

SinePower MSP 2512, Item no. MSP2500-012

24V:

SinePower MSP 704, Item no. MSP700-024

SinePower MSP 1024, Item no. MSP1000-024

SinePower MSP 1524, Item no. MSP1500-024

SinePower MSP 2024, Item no. MSP2000-024

SinePower MSP 2524, Item no. MSP2500-024

DOMETIC MSP 1512 - Intended use - 1

Warning!

Never use the inverter on vehicles where the positive terminal of the battery is connected to the chassis.

7 Technical description

The inverters can be operated wherever

a 12 V DC connection

(SinePower MSP 702, MSP 1012, MSP 1512, MSP 2012, MSP 2512)

a 24 V DC connection

(SinePower MSP 704, MSP 1024, MSP 1524, MSP 2024, MSP 2524)

is available. The light weight and compact construction of this device allow for easy installation in mobile homes, commercial vehicles or motor and sailing yachts.

The output voltage corresponds to the household voltage from the socket (pure sine wave).

The inverter has a 230VAC priority circuit. If an external 230VAC voltage is connected, this will have priority. If no external 230V_AC voltage is connected, then the connected battery will be used as the power supply.

Please observe the values for constant output power and peak output power as indicated in chapter "Technical data" on page 53. Never connect devices that have a higher power requirement.

DOMETIC MSP 1512 - Technical description - 1

Note

Note when connecting devices with an electrical drive (such as power drills and refrigerators), that they often require more power than is indicated on the type plate.

The inverter has various protective mechanisms.

  • High voltage shutdown: The inverter shuts itself off when the voltage exceeds the cut-off value. It restarts when the voltage returns to the restart value.
  • Low voltage shutdown: The inverter shuts itself off when the voltage sinks below the cut-off value. It restarts when the voltage rises to the restart value.
  • High temperature shutdown: The inverter switches off when the temperature inside the device or the temperature on the cooling element exceeds a cut-off value. It restarts when the voltage rises to the restart value.

DOMETIC MSP 1512 - Note - 1

Note

The individual values are found in chapter "Technical data" on page 53.

The inverter can be switched into an energy saving mode (Standby), so that the battery connected to the inverter does not discharge too quickly.

The inverter can be connected to an exhaust system with the included exhaust adapter. This allows the warm exhaust to be diverted outside.

The connection cable can be attached to the back of the device via the cable socket.

The inverter can be turned on and off with an external switch (not included in package).

The manufacturer offers a remote control as an accessory for the inverter.

7.1 Description of the device

The inverter has the following connections, display and control elements:

No. in fig. 2, page 4Element
1Main switch 0 / Off: device is switched off I / On: device is switched on II / Remote: Device can be turned on and off with an external switch or control-led with a remote control (accessory)
2The “Power Status” LED displays the operational status
3The “Load Level” LED displays the power being supplied
4The “Input Level” LED displays the input voltage range
5Drill holes for securing the exhaust adapter
No. in fig. 3, page 4Element
1DIP switch for switching to energy-saving mode
2Fuse
3230 VAC input jack
4230 VAC output jack
5Earth terminal
6Remote Port II for connecting a remote control (accessory)
7Remote Port I for connecting to an external switch, for turning the device on and off
8DC terminal (positive pole)
9DC terminal (negative pole)

7.2 Status indications

"Input Level" LED (fig. 2 4, page 4)

The "Input Level" LED shows the present range of the input voltage.

DisplayInput voltage
MSP 702, MSP 1012, MSP 1512, MSP 2012, MSP 2512MSP 704, MSP 1024, MSP 1524, MSP 2024, MSP 2524
Red, slowly flashing10.3 – 10.6 V20.5 – 21.2 V
Red10.6 – 11.0 V21.2 – 21.8 V
Orange11.0 – 12.1 V21.8 – 24.1 V
Green12.1 – 14.2 V24.1 – 28.6 V
Orange, flashing14.2 – 15.0 V28.6 – 30.0 V
Red, flashing> 15.0 V> 30.0 V

"Load Level" LED (fig. 2 3, page 4)

The "Load Level" LED shows the power presently being supplied by the inverter.

DisplayPower
MSP 702MSP 1012MSP 1512
MSP 704MSP 1024MSP 1524
Off0 – 56 W0 – 80 W0 – 120 W
Green56 – 230 W80 – 330 W120 – 495 W
Orange230 – 525 W330 – 750 W495 – 1125 W
Red525 – 672 W750 – 960 W1125 – 1450 W
Red, flashing> 672 W> 960 W> 1450 W
DisplayPower
MSP 2012MSP 2512
MSP 2024MSP 2524
Off0 – 160 W0 – 240 W
Green160 – 660 W240 – 990 W
Orange660 – 1500 W990 – 2250 W
Red1500 – 1920 W2250 – 2880 W
Red, flashing> 1920 W> 2880 W

"Power Status" LED (fig. 2, page 4)

The "Power Status" LED shows the operating status of the inverter.

DisplayInput voltage
Orange, constantly litNormal operation with battery power supply
Orange, slowly flashingEnergy-saving mode
Green, constantly litexternal supply via 230 VAC voltage
Red, quickly flashingInput voltage too high
Red, slowly flashingInput voltage too low
Red, occasionally flashingOverheating
Red, constantly litExcessive load

8 Fastening the inverter

You can fasten the inverter using the holders supplied.

When selecting the installation location, observe the following instructions:

  • The inverter can be mounted horizontally or vertically.
  • The inverter must be installed in a place that is protected from moisture.
  • The inverter may not be installed in the presence of flammable materials.
  • The inverter may not be installed in a dusty environment.
  • The place of installation must be well-ventilated. A ventilation system must be present for installations in small, closed spaces. The minimum clearance around the inverter must be at least 25~cm .
  • The air intake on the underside or the air outlet on the back side of the inverter must remain clear.
  • For ambient temperatures higher than 40^ (such as in engine or heating compartments, or direct sunlight), the heat from the inverter under load can lead to the automatic shut-off of the inverter.
  • The installation surface must be level and sufficiently strong.

You must be able to support the weight of the inverter.

  • Make sure you have adequate space for the cable connections underneath the device when choosing a mounting location.

DOMETIC MSP 1512 - Fastening the inverter - 1

Note

With the cable socket, you can secure the connection cable to the back side of the device. After running the cable, secure it with cable ties to the clips on the cable socket.

DOMETIC MSP 1512 - Note - 1

Caution

Before drilling any holes, ensure that no electrical cables or other parts of the vehicle can be damaged by drilling, sawing and filing.

Fastening the inverter horizontally

Clip two holders on the left bar and two on the lower right bar (fig. 4, page 5).
You can move the holders as required.
Fasten the inverter by screwing one screw through each hole in the holders.
Lay the cable socket (fig. 5 1, page 5) with the clip over the edge on the back side of the inverter (fig. 5 2, page 5).
Screw the cable socket on with one screw in each of the four holes.

Fastening the inverter vertically

Clip two holders on the left bar and two on the lower right bar (fig. 4, page 5).
You can move the holders as required.
Screw the cable socket (fig. 6 1, page 6) on to the wall with one screw in each of the four holes.
Slide the inverter (fig. 6 2, page 6) onto the cable socket, so that the edge on the back of the inverter is pinched between the wall and the clip on the cable socket.
Fasten the inverter by screwing one screw through each hole in the holder.

9 Connecting the inverter to the exhaust system

You can connect the inverter to an exhaust system. Thereby the warm exhaust is driven out of the internal chamber.

Set the exhaust adapter (fig. 7 2, page 6) on the front side of the inverter (fig. 7 1, page 6) over the fan, so that the screws fit into the screw holes.
Attach the exhaust adapter using the supplied screws.
Connect the hose support (not included, fig. 3, page 6) to the exhaust adapter.
Attach the exhaust system hose (fig. 7 4, page 6) to the hose support.

DOMETIC MSP 1512 - Connecting the inverter to the exhaust system - 1

Note

SinePower MSP 2012, MSP 2024, MSP 2512 and MSP 2524 are equipped with two fans. With these devices, mount an exhaust adapter in front of each fan and attach an exhaust hose.

10 Connecting the inverter

DOMETIC MSP 1512 - Connecting the inverter - 1

Caution - danger of electrocution!

Incorrectly connecting the inverter can be fatal for the user. The device can only be connected by a trained professional who is familiar with the relevant VDE (German Engineering Society) regulations.

This chapter is solely intended for trained professionals who are familiar with the relevant VDE (German Engineering Society) regulations!

10.1 Notes on connecting

DOMETIC MSP 1512 - Notes on connecting - 1

Warning!

Never use the inverter on vehicles where the positive terminal of the battery is connected to the chassis.

DOMETIC MSP 1512 - Warning! - 1

Caution - danger of electrocution!

If you wish to connect more than one user to the inverter and install a socket distributor loop, you must arrange a circuit breaker (residual current circuit breaker) and set a grounding bridge in the inverter, see chapter "Connect multiple appliances" on page 48.

  • When installed in vehicles or boats, the inverter must be connected to the chassis or earth.
  • Before connecting, set the main switch (fig. 2 1, page 4) to "Off".
  • When setting up a socket distribution circuit (mains set-up), you must comply with VDE 0100.
  • Only use copper cables.
  • Keep the cables as short as possible. The cables cannot be longer than 1.8 ~m .
  • After running the cable, secure it with cable ties to the clips on the cable socket.
  • Keep to the required cable cross section and fit a cable fuse as close to the battery as possible on the positive cable (see table).

DOMETIC MSP 1512 - Caution - danger of electrocution! - 1

Warning!

If you do not fit a fuse to the positive cable, the cables can overload, which might result in a fire.

DeviceRequired cable cross sectionCable fuse
MSP 70225 mm²100 A
MSP 70415 mm²50 A
MSP 101235 mm²200 A
MSP 102425 mm²100 A
MSP 151235 mm²200 A
MSP 152425 mm²100 A
MSP 201270 mm²250 A
MSP 202455 mm²150 A
MSP 251295 mm²400 A
MSP 252470 mm²200 A

10.2 Connecting the inverter to the battery

DOMETIC MSP 1512 - Connecting the inverter to the battery - 1

Warning!

Do not reverse the polarity. Reversing the polarity of the battery connections will cause a great spark and the internal fuses will melt. The fuses should only be replaced by an electrician!

DOMETIC MSP 1512 - Warning! - 1

Note

Tighten the nuts and bolts to a torque of 12 - 13Nm . Loose connections may cause overheating.

Set the main switch (fig. 2 1, page 4) to "Off".

Unscrew the four fastening screws (fig. 8 2, page 7) from the back side of the device with the included hexagon socket wrench.
Take off the hood (fig. 8 1, page 7).
Guide the plus cable through the “POS (+)” opening and the minus cable through the “NEG (-)” opening in the hood.
Loosen the safety bolt slightly(fig. 8 3, page 7).
Push the cable lug (fig. 8 5, page 7) of the positive cable between the spring washer (fig. 8 4, page 7) and the positive terminal (fig. 3 6, page 4).
Screw the safety bolt back in.
Connect the negative cable to the negative terminal (fig. 3 7, page 4).
Connect the earth terminal (fig. 3 5, page 4) to the chassis with a cable having a diameter of at least 16mm^2
Replace the hood of the device and tighten the screws.
Lay the positive cable from the inverter to the positive terminal of the vehicle battery and connect it there.
Lay the negative cable from the inverter to the negative terminal of the vehicle battery and connect it there.

10.3 Connecting the 230 V power cable

Connect the 230VAC connection cable with safety coupling (fig. 1 3, page 3) to the 230VAC output jack (fig. 3 3, page 4).
Connect the safety plug to the 230 V AC mains

10.4 Connect the 230V output cables

DOMETIC MSP 1512 - Connect the 230V output cables - 1

Caution - danger of electrocution!

Before connecting the 230V_AC output cable make sure the inverter is switched off at the main switch.

Connect the 230VAC connection cable with safety coupling (fig. 1 4, page 3) to the 230VAC output jack (fig. 3 4, page 4).

10.5 Connect multiple appliances

The device is equipped at delivery with galvanic isolation. For the safe operation of multiple appliances, it is essential that a circuit breaker (residual current circuit breaker) is built into the socket distribution circuit, see sample circuit diagram in fig. 10, page 8.

Sample circuit diagram legend:

No. in fig. 10, page 8Explanation
1230 VAC power source
2additional devices, e.g. battery charger, refrigerator
3DC power source (battery)
4Inverter
5Set grounding bridge (At delivery: not set, shown by dotted line)
6Circuit breaker (residual current circuit breaker)
7Socket distribution circuit for appliances

DOMETIC MSP 1512 - Connect multiple appliances - 1

Caution - danger of electrocution!

If you wish to connect more than one appliance to the inverter and install a socket distribution circuit, you must arrange a circuit breaker (residual current circuit breaker) and set a grounding bridge in the inverter.

Install a residual current circuit breaker in the socket distribution circuit.

Set grounding bridge

Unscrew the four fastening screws (fig. 9 2, page 7) from the back side of the device with the included hexagon socket wrench.
Take off the hood (fig. 9 1, page 7).
Unscrew the grounding screw (fig. 9 4, page 7).
Screw the screw into the pre-drilled hole to the left (fig. 9 3, page 7).
Replace the hood of the device and tighten the screws.

10.6 Install external switch to turn device on and off

DOMETIC MSP 1512 - Install external switch to turn device on and off - 1

Note

Connect the external switch to the inverter using a connection cable with Western telephone jack. Observe the PIN configuration on the plug for the connection cable.

Cut a connection cable to size according to the following circuit diagrams:

  • external switch, voltage supply from the inverter: fig. 11, page 9
  • Control unit with relay or transistor circuit (TR): fig. 12, page 9
  • external switch with voltage supply from the battery (BAT) of the vehicle: fig. 13, page 9
  • external switch with its own voltage supply (DC POWER) e.g. from the ignition: fig. 14, page 9

Connect the external on/off switch with the connection cable on the remote port (fig. 3 7, page 4).

10.7 Connecting the remote control (accessory)

DOMETIC MSP 1512 - Connecting the remote control (accessory) - 1

Caution - risk of damage!

Attach the connection to the remote control only in the Remote-Port II and not in the Remote-Port I. False connections can damage the device!

Ensure that the remote control and inverter require the same input voltage!

Connect the remote control (accessory) to the Remote Port II (fig. 3 6, page 4).

11 Using the inverter

Connect your appliance to the inverter.

Switch on at the device

Set the main switch (fig. 2 1, page 4) to the "ON" position.
✓ During the self-test, the built-in speaker emits tones and the LEDs flash in various colours.
After the self-test, the "Input Level" (fig. 2 4, page 4) and "Status" (fig. 2 2, page 4) LEDs light up green.

Using an external switch or remote control (accessory).

You can also switch the inverter on and off with a connected external switch or with a remote control (accessory).

Set the main switch (fig. 2 1, page 4) to "Remote".
If the inverter is switched on via an external switch or the remote control, the green "Power Status" LED (fig. 2, page 4) lights up.

Observe the following when using the device (see also chapter "Troubleshooting" on page 52)

The inverter switches off if:

  • The battery voltage falls below 10.5 ~V / 21 ~V
  • The battery voltage rises above 15.3 ~V / 30.6 ~V
    the inverter overheats,
  • there is an overload (short circuit).

DOMETIC MSP 1512 - Observe the following when using the device (see also chapter "Troubleshooting" on page 52) - 1

Note

If the device is operated at too high a load, there may be repeated attempts to switch on. As soon as the device is correctly operated again, the inverter automatically switches on again (recovery function). If the condition is still not satisfactory after several minutes, switch off the inverter and inspect the connected consumer device.

DOMETIC MSP 1512 - Note - 1

Note

When operating the inverter at a high load for lengthy periods, it is advisable to start the engine in order to recharge the vehicle battery.

11.1 Set energy saving mode (Standby)

In energy saving mode, the inverter does not release any voltage, thereby preserving the battery. If a connected appliance requires power which is more than the pre-set power value, the inverter reverts to normal operation.

You can switch to energy-saving mode using the DIP switches S1, S2 and S3 (fig. 3 1, page 4) and set the power value.

The switch positions for your inverter can be found in the following table:

Energy-saving mode up toDIP switch
MSP 702 MSP 704MSP 1012 MSP 1024 MSP 1512 MSP 1524MSP 2012 MSP 2024 MSP 2512 MSP 2524S1S2S3
PowerOffOffOffOffOffOff
15 W20 W40 WOnOffOff
25 W40 W80 WOffOnOff
40 W55 W125 WOnOnOff
50 W75 W170 WOffOffOn
65 W95 W210 WOnOffOn
75 W115 W245 WOffOnOn
85 W135 W280 WOnOnOn

11.2 Switch between 50 Hz and 60 Hz.

The output voltage can be switched between 50Hz and 60Hz with the DIP switch S4 (fig. 3 1, page 4).

DOMETIC MSP 1512 - Switch between 50 Hz and 60 Hz. - 1

Warning!

Only adjust the S4 DIP switch when the respective frequency for the output voltage should be used.

Set the S4 DIP switch (fig. 3 1, page 4) according to the following table:

Output voltage frequencyS4 DIP switch
50 HzOff
60 HzOn

12 Cleaning and caring for the inverter

DOMETIC MSP 1512 - Cleaning and caring for the inverter - 1

Caution

Do not use sharp or hard objects or cleaning agents for cleaning as these may damage the device.

Occasionally clean the device with a damp cloth.

13 Troubleshooting

DOMETIC MSP 1512 - Troubleshooting - 1

Note

If you have detailed questions on the specifications of the inverter please contact the manufacturer.

DOMETIC MSP 1512 - Note - 1

Warning!

Do not open the device. You risk sustaining an electric shock by doing this.

No output voltage

The "Power Status" LED (fig. 2, page 4) displays the fault in red:

LED displayCauseRemedy
Quick flashingInput voltage too highThe inverter is only intended for the voltage indi-cated.
Slow flashingInput voltage too lowThe battery needs charging. Check the cables and connections.
Occasional flash-ingOverheatingSwitch off the inverter and the appliance. Wait 5 to 10 minutes and switch the inverter on again without any appliances. Reduce the load and make sure the inverter has better ventilation. Then switch the appliance back on.
Constantly litShort circuit or reversed polarity Excessive loadSwitch off the inverter and remove the appliance. Then switch the inverter back on without the appliance. If no excessive load is now shown, then there is a short circuit in the appliance or the total load was higher than the power specified on the data sheet. Check the cables and connections.

14 Guarantee

The statutory warranty period applies. If the product is defective, please contact the manufacturer's branch in your country (see the back of the instruction manual for the addresses) or your retailer.

For repair and guarantee processing, please include the following documents when you send in the device:

A copy of the receipt with purchasing date
A reason for the claim or description of the fault

15 Disposal

If possible, always take the packaging material for recycling.

DOMETIC MSP 1512 - Disposal - 1

If you wish to finally dispose of the device, ask your local recycling centre or specialist dealer for details about how to do this in accordance with the applicable disposal regulations.

16 Technical data

UJAECO SinePower
MSP 702MSP 704MSP 1012MSP 1024
Item no.MSP700-012MSP700-024MSP1000-012MSP1000-024
Rated input voltage12 V DC24 V DC12 V DC24 V DC
Output power700 W1000 W
Peak output power1400 W2000 W
Output voltage230 V AC pure sine wave
Output frequency50 Hz
Idle current consumption1.2 A0.6 A1.25 A0.65 A
Standby current consumption0.25 A0.15 A0.25 A0.15 A
Input voltage range10.5 V – 15 V21 V – 30 V10.5 V – 15 V21 V – 30 V
Efficiency up to90 %92 %90 %93 %
Ambient temperature for operation0 °C – 40 °C
Ambient temperature for storage-30 °C – +70 °C
Dimensions W x D x H190 x 380 x 90 mm225 x 435 x 117 mm
Weight5.5 kg7.6 kg
MSP 1512MSP 1524MSP 2012MSP 2024
Item no.MSP1500-012MSP1500-024MSP2000-12MSP2000-024
Rated input voltage12 V DC24 V DC12 V DC24 V DC
Output power1500 W2000 W
Peak output power3000 W4000 W
Output voltage230 V AC pure sine wave
Output frequency50 Hz
Idle current consumption1.4 A0.7 A2.3 A1.1 A
Standby current consumption0.28 A0.15 A0.6 A0.3 A
Input voltage range10.5 V – 15 V21 V – 30 V10.5 V – 15 V21 V – 30 V
Efficiency up to90 %93 %90 %93 %
Ambient temperature for operation0 °C – 40 °C
Ambient temperature for storage-30 °C – +70 °C
Dimensions W x D x H225 x 465 x 117 mm349 x 516 x 116 mm
Weight8.4 kg15.5 kg
UAEco SinePower
MSP 2512MSP 2524
Item no.MSP2500-012MSP2500-024
Rated input voltage12 V DC24 V DC
Output power2500 W
Peek output power5000 W
Output voltage230 V AC pure sine wave
Output frequency50 Hz
Idle current consumption2.4 A1.5 A
Standby current consumption0.6 A0.35 A
Input voltage range10.5 V – 15 V21 V – 30 V
Efficiency up to90 %93 %
Ambient temperature for operation0 °C – 40 °C
Ambient temperature for storage-30 °C – +70 °C
Dimensions W x D x H349 x 546 x 116 mm
Weight16.9 kg

High voltage shutdown

DeviceHigh voltage
ShutdownRestart
MSP 702, MSP 1012, MSP 1512, MSP 2012, MSP 251215.3 V14.3 V
MSP 704, MSP 1024, MSP 1524, MSP 2024, MSP 252430.6 V28.6 V

Low voltage shutdown

DeviceLow voltage warningLow voltage
ShutdownRestart
MSP 702, MSP 1012, MSP 1512, MSP 2012, MSP 251211.0 V10.2 V12.7 V
MSP 704, MSP 1024, MSP 1524, MSP 2024, MSP 252422.0 V20.3 V25.4 V

High temperature shutdown

Internal temperatureTemperature on cooling element
Shutdown atRestart atShutdown atRestart at
70 °C45 °C90 °C60 °C

Certifications

The device has the e13 certification

DOMETIC MSP 1512 - Certifications - 1

DOMETIC MSP 1512 - Certifications - 2

Variations, technical improvements and delivery options reserved.

7 Description technique

10.1 Consignes relatives au raccordement

DOMETIC MSP 1512 - Consignes relatives au raccordement - 1

Avertissement !

10.5 Conectar various aparatos

Dometic Italy S.p.A.

Via Virgilio, 3

I-47100 Forli

+390543754901

+39054375

Mail: info@dometicwta.com

Overseas + Middle East

DOMETIC MSP 1512 - Overseas + Middle East - 1

WAECO Pacific Pty. Ltd.

1 John Duncan Court

Varsity Lakes QLD 4227

+61755076000

+61755076001

Mail: sales@waeco.com.au

DOMETIC MSP 1512 - WAECO Pacific Pty. Ltd. - 1

Dometic Switzerland AG

Riedackerstrasse 7a

CH-8153 Rümlang (Zürich)

+41448187171

+41 44 8187191

Mail: info@dometic-waeco.ch

DOMETIC MSP 1512 - Dometic Switzerland AG - 1

Dometic Norway AS

Skolmar 24

N-3232 Sandefjord

+4733428450

+47 33428459

Mail: firmapost@waeco.no

DOMETIC MSP 1512 - Dometic Norway AS - 1

WAECO Impex Ltd.

Suites 2207-2211 · 22/F · Tower 1

The Gateway · 25 Canton Road

Tsim Sha Tsui · Kowloon

Hong Kong

+852 24632750

+852 24639067

Mail: info@waeco.com.hk

DOMETIC MSP 1512 - WAECO Impex Ltd. - 1

Dometic Denmark A/S

Nordensvej 15, Taulov

DK-7000 Fredericia

+4575585966

+4575586307

Mail: info@waeco.dk

DOMETIC MSP 1512 - Dometic Denmark A/S - 1

Domatic Benelux B.V.

Ecustraat 3

NL-4879 NP Etten-Leur

+31765029000

+31765029090

Mail: info@dometic.nl

DOMETIC MSP 1512 - Domatic Benelux B.V. - 1

WAECO Impex Ltd.

Taipei Office

2 FL-3 · No. 56 Tunhua South Rd, Sec 2

Taipei 106, Taiwan

+886227014090

+886227060119

Mail: marketing@waeco.com.tw

DOMETIC MSP 1512 - WAECO Impex Ltd. - 1

Dometic Spain S.L.

Avda. Sierra del Guadarrama, 16

E-28691 Villanueva de la Canada

Madrid

+34 902 111 042

+34 900 100 245

Mail: info@dometic.es

DOMETIC MSP 1512 - Dometic Spain S.L. - 1

Dometic Scandinavia AB

Gustaf Melins gata 7

Regional Office Middle East

PO Box 74775

Dubai, United Arab Emirates

+97143212160

+97143212170

Mail: info@dometic.ae

DOMETIC MSP 1512 - Dometic Scandinavia AB - 1

Domicic S.N.C.

Dometic House - The Brewery

Blandford St. Mary

DorsetDT119LS

+448446260133

+448446260143

Mail: sales@dometic-waeco.co.uk

DOMETIC MSP 1512 - Domicic S.N.C. - 1

Dometic Finland OY

Mestarintie 4

FIN-01730 Vantaa

+358207413220

+35897593700

Mail: info@dometic.fi

DOMETIC MSP 1512 - Dometic Finland OY - 1

www.waeco.com

Table of contents Cliquez un titre pour y accéder
Manual assistant
Powered by ChatGPT
Waiting for your message
Product information

Brand : DOMETIC

Model : MSP 1512

Category : Air-conditioner