HAYWARD SumHeat Fi - Pump

SumHeat Fi - Pump HAYWARD - Free user manual and instructions

Find the device manual for free SumHeat Fi HAYWARD in PDF.

📄 436 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice HAYWARD SumHeat Fi - page 52
Pick your language and provide your email: we'll send you a specifically translated version.
BrandHayward
ModelSumHeat Fi (series HP5171DT3 to HP5301ET3)
Product typeHeat pump for swimming pool
Dimensions (L x W x H)From 780 x 730 x 868 mm to 846 x 920 x 1024 mm depending on model
WeightFrom 75 to 123 kg depending on model
Power supplySingle-phase 230 V ~ 50 Hz or three-phase 400 V 3N ~ 50 Hz depending on model
RefrigerantR32 (HFC), Safety group A2L, GWP 675
Heating capacity (min-max)From 2.87 kW to 31.20 kW depending on model and conditions
COP (min-max)From 4.79 to 15.00 depending on model and conditions
Water temperature rangeHeating: +12 °C to +40 °C; Cooling: +8 °C to +40 °C
Outdoor temperature rangeHeating: -15 °C to +43 °C; Cooling: +7 °C to +43 °C
Sound level (at 1 m)From 49.3 to 62.5 dB(A) depending on model and speed
Hydraulic connection50 mm (2 x union connectors supplied)
Nominal water flowFrom 7.2 to 13.1 m³/h depending on model
Main functionsHeat/cool mode, Full Inverter regulation, silent mode, programmable timer, touch screen, automatic lock
Annual maintenanceEvaporator cleaning (soft brush or water jet), check cables, connections and sealing, by a certified professional
WinterizingPower off, drain condenser, seal inlet/outlet, cover with winter cover
Electrical protectionType D circuit breaker + 30 mA residual current device mandatory
Spare partsAvailable from dealer; exploded views in the manual (section 6.4)
Warranty2 years against manufacturing defects (excluding wear parts and frost damage)
StandardsCE compliant, NF C15-100 (France), R32 according to F-Gas regulation

Frequently Asked Questions - SumHeat Fi HAYWARD

What is the recommended maximum set temperature?
It is recommended not to exceed 32 °C to avoid damaging the pool liner.
How to adjust the water flow with the by-pass valve?
Adjust the by-pass valve to obtain a difference of 2 °C between the inlet and outlet water temperature. View temperatures on the touch screen.
What to do in case of error code E03?
Code E03 indicates a water flow fault. Check that the filtration pump is running, that the valves are open, and that the by-pass is not too closed. If the problem persists, contact a professional.
How to winterize the heat pump?
Turn the unit to OFF mode, cut off the power, drain the condenser using the drain plug, close the by-pass valve, unscrew the union connectors, remove residual water with compressed air, seal the connectors, and cover the unit with the winter cover.
Can I use the heat pump in cooling mode?
Yes, the heat pump is reversible. Select cooling mode on the touch screen. The water temperature range in cooling mode is +8 °C to +40 °C.
How to activate silent mode?
Press the silent mode button on the touch screen to activate it manually. You can also program a timer for automatic activation at certain hours. In silent mode, the fan speed is reduced for quieter operation.
What is the minimum installation distance from the pool?
According to French standard NF C15-100, the heat pump must be installed at least 3.5 meters from the water. Check local regulations for other countries.
How often should I have the unit serviced?
An annual maintenance by a certified professional is recommended. It includes evaporator cleaning, checking electrical connections, refrigerant circuit tightness, and proper condensate drainage.
Can I install the heat pump myself?
No, installation and electrical connection must be carried out by a certified professional in accordance with applicable standards. Improper installation may void the warranty and pose safety risks.
How to lock the touch screen to prevent settings changes?
The screen locks automatically after one minute (adjustable from 1 to 10 minutes). To unlock, press the screen for 2 seconds and enter the code 22. You can disable this lock in settings.

User questions about SumHeat Fi HAYWARD

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Pump in PDF format for free! Find your manual SumHeat Fi - HAYWARD and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. SumHeat Fi by HAYWARD.

USER MANUAL SumHeat Fi HAYWARD

natural_image Exterior view of a modern industrial water filter unit (no visible text or symbols)

HAYWARD SumHeat Fi - 1

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

natural_image Exterior view of a modern industrial water heater (no visible text or symbols)

HAYWARD SumHeat Fi - 2

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

3.3 Raccordement hydraulique

text_image = = Ⓧ L N ⊕ Alimentation générale 230V~/50Hz

HAYWARD SumHeat Fi - Raccordement hydraulique - 1

text_image = = == R S T N ⊕ ⊗⊗⊗⊗⊗⊗⊗

Alimentation générale 400V 3N\~ / 50Hz

HAYWARD SumHeat Fi - Raccordement hydraulique - 2

text_image 01-01 2017 10:15:00 26.5°C IN OUT 26.5°C 2 S OUT 28.8°C >>

4. INTERFACE UTILISATEUR (suite)

text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - INTERFACE UTILISATEUR (suite) - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5°C OUT 28.8°C Mode Silence désactivé

Réglage du Timer
HAYWARD SumHeat Fi - INTERFACE UTILISATEUR (suite) - 2

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C

HAYWARD SumHeat Fi - INTERFACE UTILISATEUR (suite) - 3

HAYWARD SumHeat Fi - INTERFACE UTILISATEUR (suite) - 4

text_image 01-01 2017 10:15:00 26.5°C IN OUT 26.5 °C OUT 28.8 °C

4. INTERFACE UTILISATEUR (suite)

text_image ACL-in ACN-in ACN-out FAN Driver Board CN1 CN BLK 46GB 48GB 48GB 12V Y/G FM1 BLK GND YEL 46GB WHT 48GB RED 12V BLG GND YEL 48GB WHT 48GB RED 12V Controller WiFi N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N M A L I N O P R S T U V W X Y Z X X Y Z X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ALIMENTATION générale 220-240V~50Hz E E V 5 CN9 MAIN BOARD CN9 CN11 A13 A12 CT IT HP FS CN8 CN13 A11A3A5A7A9 E.W.K. VHT. RED. Presup sensor de pression (PS) AT OT SUT LP B.K. Slt. Rt. Slt. 3.4. RED BLK WHT U V W V COMP

LEGENDE

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. ANNEXES (suite)

6.3 Raccordements priorité chauffage Pompe Triphasé

HAYWARD SumHeat Fi - Raccordements priorité chauffage Pompe Triphasé - 1

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. ANNEXES (suite)

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - ANNEXES (suite) - 1

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

RepDésignation P/NHP5171DT3HP5211DT3HP5251DT3HP5301DT3
1Moteur ventilateur DCHWX20000330381
HWX20000330402 n/an/an/a
2Capot protection moteur HWX20000220320
3Panneau supérieur ABSHWX80900736n/an/a
HWX80900737 n/a
HWX80900718 n/an/an/a
4Protection latérale droiteHWX80704158n/an/a
HWX80705113 n/a
HWX80705110 n/an/an/a
5/ / / / / /
6Plaque de protectionHWX32012210724n/an/a
HWX32002210071 n/a
HWX32004210137 n/an/an/a
7Prise de pression 90 mm - 1/2"HWX20000140153
8Détendeur électroniqueHWX20000140451n/an/a
HWX20000140449 n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/an/a
9Filtre ∅12.9-∅12.9 (∅28)HWX20000140027
10Prise de pression 95 mm - 7/16"HWX20000140512
11Prise de pression 40 mm - 1/2"HWX20000140150
12Vanne 4 voiesHWX20041437n/an/a
HWX20011491 n/a
13Capteur de pressionHWX20000360274
14Sonde température Évap/Air/Eau 5k-800 mm HWX20003202
15Sonde Refoulement Compresseur 50k-600 mmHWX20000320145
16Détecteur de débit d'eauHWX83000069
17/ / / / / /
18Panneau AvantHWX80900738n/an/a
HWX80900739 n/a
HWX80900710 n/an/an/a
19Écran tactile couleurHWX95005310612
20Trappe d'accès électriqueHWX20000220247
21Panneau boîtier électriqueHWX80702647n/an/a
HWX80702644 n/a
HWX80702645 n/an/an/ax
22Pressostat haute pression NC 3.2MPa/4.4 MPaHWX20000360187
23Pressostat basse pression NO 0.15 MPa/0.05 MPaHWX20000360054
24/ / / / / /
25Condenseur Titane PVCHWX32009120085n/an/a
HWX32002120023 n/an/a
HWX32016120012 n/an/a
HWX32016120011n/an/a
26/ / / / / /
27CompresseurHWX80100046n/an/a
HWX80100069 n/a
HWX30101000006 n/an/an/a
28Protection latérale gaucheHWX32012210729n/an/a
HWX80705114 n/a
HWX80705111n/an/a

6. ANNEXES (suite)

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HAYWARD SumHeat Fi - ANNEXES (suite) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - ANNEXES (suite) - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

RepDésignation P/NHP5171DT3HP5211DT3HP5251DT3HP5301DT3
29/ / / / /
30Connecteur carré fileté 50 mm HWX20031379
31Coude PVC ∅ 50 mm HWX20011359
32Support vertical droit/gaucheHWX32000210086n/a n/a n/a
HWX80702346 n/an/a
HWX80702656 n/an/a n/a
33Evaporateur à ailetteHWX32012120155n/a n/a n/a
HWX80600429 n/an/a n/a
HWX32003120028n/a n/an/a
HWX32004120013n/a n/a n/a
34Protection arrièreHWX32012210730n/a n/a n/a
HWX80705115n/an/a
HWX80705112n/a n/a n/a
35/ / / / /
36Hélice Ventilateur ∅ 522 mmHWX20000270062n/a n/a n/a
Hélice Ventilateur ∅ 560 mmHWX35072195 n/an/a
Hélice Ventilateur ∅ 600 mmHWX20000270057n/an/an/a
37Grille de protection ventilateurHWX32012210732n/a n/a n/a
HWX32003210142n/an/a
HWX80700160 n/an/a n/a
38Carte électronique MèreHWX72200033171Dn/a n/a n/a
HWX72200033211Dn/an/a n/a
HWX72200033251Dn/a n/an/a
HWX72200033301Dn/a n/a n/a
39Carte Inverter ventilateurHWX82300485
40Bornier 4 connexionsHWX20003909
41Carte filtreHWX3020100007
42Relais K2HWX20000360297
43Bornier L-N-GNDHWX20000390223
44Bornier 4 pôlesHWX20000390046
45Bobine réactanceHWX82500009n/a n/a n/a
HWX20000370030n/a
46/ / / / /
47/ / / / /
48Carte Inverter compresseurHWX82300149n/a n/a n/a
HWX82300019 n/a
49Résistance PTC 100 ΩHWX20000320113n/a
50/ / / / /
51/ / / / /
52Contacteur de puissanceHWX200003600619n/a
53Bouteille de liquideHWX20000140579n/an/a

6. ANNEXES (suite)

HP5211ET3 / HP5251ET3 / HP5301ET3
HAYWARD SumHeat Fi - ANNEXES (suite) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - ANNEXES (suite) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

RepDésignation P/N HP5211ET3 HP5251ET3 HP5301ET3
1 MMoteur ventilateur DCHWX20000330381n/a
HWX20000330402 n/an/a
2 Capot protection moteur HWX20000220320√ √
3 Panneau supérieurHWX80900737n/a
HWX80900718 n/an/a
4 Protection latérale droiteHWX80705113n/a
HWX80705110 n/an/a
5 / // /
6 Plaque de protectionHWX32002210071n/a
HWX32004210137 n/an/a
7 Prise de pression 90 mm - 1/2"HWX20000140153√ √
8 Détendeur électroniqueHWX20000140449n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/a
9 Filtre ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Prise de pression 95 mm - 7/16"HWX20000140512√ √
11Prise de pression 40 mm - 1/2"HWX20000140150√ √
12Vanne 4 voiesHWX20011491√ √
13Capteur de pressionHWX20000360274√ √
14Sonde température Évap/Air/Eau 5k-800 mmHWX20003202√ √
15Sonde Refoulement Compresseur 50k-600 mmHWX20000320145√ √
16Détecteur de débit d'eauHWX83000069√ √
17/// / /
18Panneau AvantHWX80900739n/a
HWX80900710 n/an/a
19Écran tactile couleurHWX95005310612√ √
20Trappe d'accès électriqueHWX20000220247√ √
21Panneau boîtier électriqueHWX80702644n/a
HWX80702645 n/an/a
22Pressostat haute pression NC 3.2 MPa/4.4 MPaHWX20000360187√ √
23Pressostat basse pression NO 0.15 MPa/0.05 MPaHWX20000360054√ √
24/// / /
25Condenseur Titane PVCHWX32002120023n/an/a
HWX32016120012 n/an/a
HWX32016120011n/an/a
26/// / /
27CompresseurHWX80100069n/a
HWX30101000006 n/an/a
28Protection latérale gaucheHWX80705114n/a
HWX80705111n/an/a
29/// / /
30Connecteur carré fileté 50 mmHWX20031379√ √
31Coude PVC ∅ 50 mmHWX20011359√ √
32Support vertical droit/gaucheHWX80702346n/a
HWX80702656 n/an/a
33Évaporateur à ailetteHWX80600429n/an/a
HWX32003120028 n/an/a
HWX32004120013 n/an/a
34Protection arrièreHWX80705115n/a
HWX80705112 n/an/a
35/// / /

6. ANNEXES (suite)

HP5211ET3 / HP5251ET3 / HP5301ET3
HAYWARD SumHeat Fi - ANNEXES (suite) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - ANNEXES (suite) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

6. ANNEXES (suite)

HP5211ET3 / HP5251ET3 / HP5301ET3

RepDésignation P/N HP5211ET3 HP5251ET3 HP5301ET3
36Hélice Ventilateur ∅ 560 mm HWX35072195n/a
Hélice Ventilateur ∅ 600 mm HWX20000270057 n/a n/a
37Grille de protection ventilateurHWX32003210142n/a
HWX80700160 n/a n/a
38Carte électronique MèreHWX72200033211En/a n/a
HWX72200033251E n/an/a
HWX72200033301E n/an/a
39Carte Inverter ventilateurHWX82300485
40Bornier 4 connexionsHWX20003909
41Carte filtreHWX82300074
42Relais K2HWX20000360297
43Bornier R-R-T-N-GNDHWX20000390180
44Bornier 4 pôlesHWX20000390046
45Bobine réactanceHWX20000370030
46 /////
47 /////
48Carte Inverter compresseurHWX82300112n/a
HWX302010000012n/a n/a
49Carte condensateurHWX302010000014
50Bornier L-N-GND réactanceHWX20000390223
51Bouteille de liquideHWX20000140579 n/a

6. ANNEXES (suite)

CONDITIONS DE GARANTIE

natural_image Exterior view of a modern industrial water filter unit (no visible text or symbols)

HAYWARD SumHeat Fi - CONDITIONS DE GARANTIE - 1

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

Installation & Instruction Manual

CONTENTS

1. GENERAL INSTRUCTIONS - SAFETY 1

2. SPECIFICATIONS 5

2.1 Technical data for the swimming pool heat pump unit 5
2.2 Operating range 7
2.3 Dimensions 8

3. INSTALLATION AND CONNECTION 9

3.1 Functional Diagram 9
3.2 Pompe à chaleur 10
3.3 Hydraulic connection 11
3.4 Electrical connection 12
3.5 Initial start-up 14
3.6 Water flow setting 16

4. USER INTERFACE 17

4.1 General presentation 17
4.2 Setting the Date and Time 18
4.3 Timer function settings 18
4.4 Setting and visualisation of the set point 20
4.5 Locking and unlocking the touch screen 21
4.6 SILENT function settings 22

5. MAINTENANCE AND WINTERISING 25

5.1 Maintenance 25
5.2 Winterising 25

6. APPENDIX 26

6.1 Electrical diagrams 26
6.2 Heating priority wiring for monophasic pump 32
6.3 Heating priority wiring for three phases pump 33
6.4 Exploded view and spare parts 34
6.5 Troubleshooting guide 42
6.6 Recording base 45
6.7 End of life of the device 46

1. GENERAL INSTRUCTIONS - SAFETY

Thank you for purchasing the Hayward heat pump for swimming pools. The Hayward SUMHEAT FULL INVERTER heat pump has been designed to strict manufacturing standards meeting the highest levels of quality required.

Hayward heat pumps offer you exceptional performance throughout your bathing season by adapting wattage, power usage and noise levels to the heating requirements of your swimming pool thanks to FULL INVERTER control logic.

HAYWARD SumHeat Fi - GENERAL INSTRUCTIONS - SAFETY - 1

Read the instructions in this manual carefully before using the device.

This manual includes all the necessary information for installation, trouble-shooting and maintenance.

Read this manual carefully before opening the unit or doing any maintenance work on it. The manufacturer of this product shall on no account accept any liability for injury to a user or damage to the unit further to any errors made during installation, trouble-shooting or unnecessary maintenance. It is particularly important to follow the instructions given in this manual at all times.

After having read this manual, keep it for future usage.

Authorised personnel

- The installation, electrical connections, maintenance and repairs of the device must be carried out by an accredited professional in accordance with the regulatory texts and the rules of the art in effect in the country where the device is installed (see § 3.4).

For any intervention on the cooling circuit, the professional must hold a certificate of competence in handling refrigerants.

For France:

- Low-voltage electrical installation according to NF-C 15-100.

- Legislation on the handling of refrigerants: Decree 2007/737 and its implementation orders.

1. GENERAL INSTRUCTIONS - SAFETY (continued)

This product contains refrigerant gas R32

HAYWARD SumHeat Fi - This product contains refrigerant gas R32 - 1

This device contains R32.

Never use a refrigerant other than R32. Any other gaseous body mixed with R32 could cause abnormally high pressure and lead to a failure or pipes bursting and injuring people.

During repairs or maintenance operations, use copper tubes that comply with Standard NF EN 12375-1 and with European Pressure Equipment Directive 97/23/EC.

As the heat pump is pressurized, never pierce the pipes or attempt any brazing. There is a risk of explosion.

Never expose the device to flames, sparks or other sources of ignition. It could explode and cause serious or even fatal injuries.

To detect refrigerant leaks: do not use a halide lamp or any other detector that uses an open flame. Do not use potential sources of ignition under any circumstances.

This product contains fluorinated greenhouse gases regulated by the Kyoto protocol. Do not release these gases into the atmosphere.

Security unit: A2L.

GWP(1) value: 675, based in the 4th report of the IPCC.

The quantity of refrigerant, based on the F-Gas regulation no. 517/2014, is stated on the unit's rating plate.

Any intervention on the cooling circuit must be carried out by an accredited professional as mentioned hereinabove.

Periodic inspections for leaks of refrigerant may be required by European or local legislation. Please contact your local distributor for more information.

  • Warning, refrigerants can be odourless.
  • Do not pierce or heat the pipes, risk of explosion and serious burns.
  • Do not use a method for accelerating the defrosting or cleaning process other than those recommended by the manufacturer.
  • The device must be stored in a room that does not contain any source of ignition operating on a permanent basis (for example, open flames, gas device or electric radiator that is operating).

(1) Global warming potential

1. GENERAL INSTRUCTIONS - SAFETY (continued)

Installation conditions

  • This heat pump is designed exclusively to heat swimming pool water; do not use this equipment for any other purpose.
  • Do not attempt to install this device by yourself.
  • If you detect a fault or any abnormal situation, do not install the heat pump and contact your dealer immediately.
  • If kept in storage, the heat pump should be kept in a well-ventilated room with a floor area of more than A_(m^2) as calculated by the following formula:
    M is the quantity of refrigerant in the device in kg, and h0 is the storage height. If stored no the floor, h0 = 0.6 m.
  • This product was designed exclusively for domestic use and installation outdoors. The air that escapes from the product must be able to flow freely and must not be used for other purposes such as heating or cooling a room or building.
  • Check the power cable. If the power cable is damaged, it has to be replaced by the manufacturer, its after-sales service or by a qualified and authorised person.
  • Grounding connection of the device and its continuity are mandatory. The ground wire has to be longer than the other wires in order to prevent the risks of electric shock in the event the cable is pulled out. The electrical installation must be equipped with a differential protection of 30 mA (see § 3.4).
  • Make sure the support provided for the unit is strong enough to bear the weight of the unit.
  • Failure to comply with recommendations will invalidate the warranty.

$$ A _ {\min} = (M / (2. 5 \times 0. 2 2 7 5 9 \times h 0)) ^ {2}. $$

Instructions for servicing - maintenance

Maintenance operations must be carried out once per year in order to guarantee the longevity and the good working condition of the heat pump.

  • Maintenance and the different operations must be carried out at the recommended times and frequencies as specified in this manual.
  • Only use genuine spare parts.
  • Check the power cable. If the power cable is damaged, it has to be replaced by the manufacturer, its after-sales service or by a qualified and authorised person.
  • Verify the grounding connection of the device and its continuity.
  • Clean the coil with the help of a soft brush or jet of air or water. Warning, never use a high pressure cleaner.

1. GENERAL INSTRUCTIONS - SAFETY (continued)

  • Verify that the drains flow well.
  • Verify the tightening of the hydraulic and electrical connections
  • Verify the hydraulic sealing of the condenser.
  • Have the leak-tightness of the cooling circuit to the leak detector checked by an accredited professional.

HAYWARD SumHeat Fi - GENERAL INSTRUCTIONS - SAFETY (continued) - 1

Before any maintenance operation, the heating pump must be disconnected from any electrical current source. The maintenance operations must only be carried out by personnel that is qualified and authorised to handle liquid refrigerants.

Instructions for winterising

  • Put the heat pump in "OFF" mode.
  • Cut the power supply to the heat pump.
  • Empty the condenser with the help of the drain to avoid any risk of deterioration. (high risk of freezing).
  • Close the by-pass valve and unscrew the entry/exit connection unions.
  • Eliminate the maximum amount of residual stagnant water from the condenser with the help of an air gun.
  • Close the water entry and exit areas of the heating pump to avoid introducing foreign bodies.
  • Cover the heating pump with a dedicated winterising case.

HAYWARD SumHeat Fi - Instructions for winterising - 1

Any damage caused by poor winterising maintenance will lead to cancellation of the warranty.

Conditions for use

This device can be used by children aged 8 years and over as well as by persons who have reduced, physical, sensory or mental capacities, or who lack experience or knowledge, if they are correctly monitored or if instructions pertaining to the use of the device in complete safety have been given to them and the risks incurred are understood.

Children must not play with the device.

Cleaning and maintenance by the user must not be carried out by children without surveillance.

2.1 Technical data for the swimming pool heat pump unit

ModelsSUMHEAT Full InverterHP5171DT3 HP5211DT3 HP525IDT3 HP5301DT3
Supply voltageV / Ph / Hz220 V - 240 V~ / 1 h / 50 Hz
RefrigerantType HFC - R32 - (CH2F2)
Security unitType A2L
Loadkg 0.8 1.35 1.65 1.8
Mass in teqCO2teqCO20.54 0.91 1.11 1.22
Leak check frequency/No specific frequency, but an annual check is recommended
Min--Max heating capacity (a)kW 3.65-- 17.05 6.35 -- 21.47 5.10 -- 24.307.74 -- 30.30
Min--Max electric input power (a)kW 0.24-- 2.47 0.46 -- 2.80 0.37 -- 3.79 0.59-- 4.98
Min--Max continuous current rating (a)A 1.58-- 10.78 2.81 -- 12.24 2.29 -- 16.573.48 -- 21.77
Max--Min continuous power (COP) (a)/ 15 -- 6.8913.66 -- 7.65 13.52 -- 6.41 13.03 -- 6.07
Min--Max heating capacity (b)kW 2.87-- 12.63 4.76 -- 16.49 3.90 -- 18.965.53 -- 22.36
Min--Max electric input power(b)kW 0.43-- 2.41 0.64 -- 2.88 0.62 -- 3.78 0.86-- 4.67
Max--Min continuous power (COP) (b)/6.58 -- 5.24 7.49 -- 5.72 6.33 -- 5.01 6.45 -- 4.79
Maximum continuous currentA15.5 17.7 22.623
Fuse ratingaM 16202525
Circuit-breaker curve DD 16202525
Starting currentA< CMS
Hydraulic connectionmm50 mm
Nominal water flow (a)m3/h7.29.2 10.5 13.1
Max. loss of head on waterkPa8171546
Compressor/Mitsubishi Panasonic Mitsubishi
Type/Double Rotary
Quantity/1
Coil resistance at 20°COhm0.95 0.88 0.88 0.49
Fan/Axial
Quantity1
Diametermm522 560 560 600
Number of blades/3
Motor/DC Inverter
Quantity/1
Rotation speedTr/min600 -- 700500 -- 700600 -- 750500 -- 700
Silent mode speedTr/min400
Sound pressure level at 1 meterdB(A)49.3 -- 51.855.9 -- 58.354.6 -- 59.9TBD
Sound pressure level at 10 metersdB(A)32.8 -- 35.140.3 -- 42.539.1 -- 44.4TBD
Unit's net dimensions (L-W-H)mm780 x 730 x 868797 x 777 x 965846 x 920 x 1024
Weightkg75101 101 123

(a) Dry air 27^ - Relative humidity 78% - Water inlet temperature 26^ .

(b) Dry air 15°C - Relative humidity 71% - Water inlet temperature 26°C

2. SPECIFICATIONS (continued)

ModelsSUMHEAT Full InverterHP5211ET3 HP5251ET3 HP5301ET3
Supply voltageV / Ph / Hz380 V - 415 V~ / 3 ph / 50 Hz
RefrigerantType HFC - R32 - (CH2F2)
Security unitType A2L
Loadkg 1.351.65 1.8
Mass in teqCO2teqCO20.91 1.11 1.22
Leak check frequency /No specific frequency, but an annual check is recommended
Min--Max heating capacity (a)kW6.24 -- 22.10 6.02-- 24.50 8.12 -- 31.20
Min--Max electric input power (a)kW0.46 -- 3.07 0.41-- 3.67 0.59 -- 5.08
Min--Max continuous current rating (a)A1.00 -- 5.10 0.90-- 5.81 1.21 -- 8.23
Max--Min continuous power (COP) (a)/13.70 -- 7.19 14.53-- 6.68 13.72 -- 6.14
Min--Max heating capacity (b)kW4.84 -- 16.92 4.55-- 19.55 5.52 -- 23.05
Min--Max electric input power(b)kW0.68 -- 3.10 0.63-- 3.68 0.79 -- 4.94
Max--Min continuous power (COP) (b)/7.10 -- 5.46 7.18-- 6.42 6.98 -- 4.66
Maximum continuous current A8.7 11.7 13.3
Fuse rating aM101216
Circuit-breaker curve DD101216
Starting currentA< CMS
Hydraulic connectionmm50 mm
Nominal water flow (a)m3/h9.1 10.5 12.6
Max. loss of head on waterkPa171546
Compressor/PanasonicPanasonicMitsubishi
Type/Double Rotary
Quantity/1
Coil resistance at 20°COhm0.88 0.88 0.49
Fan/Axial
Quantity1
Diametermm560 560 600
Number of blades/3
Motor/DC Inverter
Quantity/1
Rotation speedTr/min500 -- 700600 -- 750500 -- 700
Silent mode speedTr/min500 400 400
Sound pressure level at 1 meterdB(A)56.4 -- 6155.2 -- 59.7 55.659.3
Sound pressure level at 10 metersdB(A)40.9 -- 45.4 40.944.2 36.1 -- 42.2
Unit's net dimensions (L-W-H) mm797 x 777 x 965846 x 920 x 1024
Weightkg101 101 123

(a) Dry air 27°C - Relative humidity 78% - Water inlet temperature 26°C.

(b) Dry air 15°C - Relative humidity 71% - Water inlet temperature 26°C

2. SPECIFICATIONS (continued)

2.2 Operating range

Use the swimming pool heat pump unit within the following ranges of temperature and humidity to ensure safe and efficient operation.

Heating mode HAYWARD SumHeat Fi - Operating range - 1 ng modeHAYWARD SumHeat Fi - Operating range - 2
Outside temperature -15°C – +43°C+7°C – +43°C
Water temperature +12°C – +40°C+8°C – +40°C
Relative humidity < 80% < 80%
Setting range from the set point +15°C – +32°C+8°C – +32°C

HAYWARD SumHeat Fi - Operating range - 3

If the temperature or humidity does not correspond to these conditions, the security measures could be activated and the swimming pool heat pump unit may no longer work.

HAYWARD SumHeat Fi - Operating range - 4

The maximum heating temperature is set at 32^ C to prevent damage to the liners. Hayward cannot be held responsible if used at a temperature above +32^ C.

2. SPECIFICATIONS (continued)

2.3 Dimensions

Models:

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HP5211ET3 / HP5251ET3 / HP5301ET3

HAYWARD SumHeat Fi - Models: - 1

Unit: mm

Model MarkHP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3
A867,5 965965 1024 965965 1024
B730 777777 920 777777 920
C780 797797 846 797797 846
610 650650 680 650650 680
D120 120120 150 120120 150
E204 204204 242 204204 242
F87 85 8586 85 85 86

3. INSTALLATION AND CONNECTION

3.1 Functional Diagram

HAYWARD SumHeat Fi - Functional Diagram - 1

flowchart
graph TD
    A["Water inlet valve"] --> B["Water outlet valve"]
    B --> C["Chlorinator cell (or other treatment)"]
    C --> D["Water outlet"]
    D --> E["Pump filtration"]
    E --> F["Filter"]
    F --> G["By-pass valve"]
    G --> A

Note: The swimming pool heat pump unit is sold without any treatment or filtration equipment. The components presented in the diagram are spare parts to be supplied by the installer.

3. INSTALLATION AND CONNECTION (continued)

3.2 Pompe à chaleur

HAYWARD SumHeat Fi - Pompe à chaleur - 1

Place the heat pump outdoors and away from any enclosed technical space.

Choose a location that is preferably sunlit and sheltered from dominant winds.

The device must be perfectly accessible for later installation and maintenance work.

Placed under a shelter, the minimum required distances mentioned below must be respected in order to avoid any risk of air recirculation and a deficiency in the unit's overall performance.

HAYWARD SumHeat Fi - Pompe à chaleur - 2

Preferably, install the heat pump on a flat and dissociated cement block.

The maximum installation distance between the unit and the swimming pool is 15 metres.

The total length of the piping to and from the unit is 30 metres.

Insulate both the above ground and buried hydraulic piping.

The heat pump must be installed at a minimum distance from the pool in compliance with NF C 15-100 (3.5 m from the water for France) or in compliance with installation standards applicable in other countries.

Do not install the heat pump close to a heat source.

For installation in snowy regions we recommend sheltering the machine to avoid snow accumulating on the evaporator.

HAYWARD SumHeat Fi - Pompe à chaleur - 3

text_image Unit: mm 700 mm 700 mm 700 mm Air inlet Air inlet Air inlet Air outletAir outlet

3. INSTALLATION AND CONNECTION (continued)

3.3 Hydraulic connection

The unit is supplied with two 50 mm ∅ union connections. Connect the water inlet to the heat pump coming from the filtration group then connect the water outlet to the heat pump at the water conduit going to the pool. Install a by-pass valve between the heat pump entrance and exit. (see diagram below).

HAYWARD SumHeat Fi - Hydraulic connection - 1

text_image Water inlet Ø 50 mm Water outlet Ø 50 mm

HAYWARD SumHeat Fi - Hydraulic connection - 2

If an automatic distributor or an electrolyser is used, it should be installed imperatively after the heat pump with the goal of protecting the titanium condenser against an elevated concentration of chemicals.

HAYWARD SumHeat Fi - Hydraulic connection - 3

Be sure to install the by-pass valve and the supplied union connections at the water inlet and outlet level in order to simplify purging during the winter period and to facilitate access when disassembling for maintenance.

3. INSTALLATION AND CONNECTION (continued)

3.4 Electrical connection

HAYWARD SumHeat Fi - Electrical connection - 1

Electrical installation and wiring for this equipment must be in conformity with local installation standards.

F NF C15-100 GB BS7671:1992
D D N VDE 0100-702 EW EVHS-HD 384-7-702
A Ö VE 8001-4-702 H MSZ 2364-702/1994/MSZ 10-553 1/1990
E U NE 20460-7-702 1993,RECBT ITC-BT-31 2002M MSA HD 384-7-702.S2
IRL Wiring Rules + IS HD 384-7-702 PL PN-IEC 60364-7-702:1999
ICEI 64-8/7CZCSN 33 2000 7-702
LUX384-7.702 S2SKSTN 33 2000-7-702
NLNEN 1010-7-702SLOSIST HD 384-7-702.S2
P R SIUEE TR T$ IEC 60364-7-702

HAYWARD SumHeat Fi - Electrical connection - 2

Verify that the available electrical power supply and the network frequency correspond to the required operating current taking into account the appliance's specific location, and the current required to supply any other appliance connected to the same circuit.

HAYWARD SumHeat Fi - Electrical connection - 3

text_image HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 230V~ +/- 10% 50 Hz 1 Phase HP5211ET3 HP5251ET3 HP5301ET3 400V~ +/- 10% 50 Hz 3 Phases Check that the phases balance does not exceed 2%

See the corresponding wiring diagram in the appendix § 6.1.

The connection box is behind the front panel.

  • There are three L-N-GND connections for powering single-phase models.
  • Five R-S-T-N-GND connections serve for the power supply of the three-phase models.

Terminals (1-2) are for controlling filter pump (K2 relay). Terminals (3-4), normally closed, are for remote on/off control.

HAYWARD SumHeat Fi - Electrical connection - 4

text_image = = L N ÷ Power supply 230V~ / 50Hz

HAYWARD SumHeat Fi - Electrical connection - 5

text_image K2 === 1342 Dry contact 7 A max potential free. Priority heating function Remote A1 On/Off contact

3. INSTALLATION AND CONNECTION (continued)

HAYWARD SumHeat Fi - INSTALLATION AND CONNECTION (continued) - 1

text_image ===== R S T N ÷

Power supply 400V 3N\~ / 50Hz

HAYWARD SumHeat Fi - INSTALLATION AND CONNECTION (continued) - 2

text_image K2 ==== 1342 Dry contact 7 A max potential free

Priority heating function

HAYWARD SumHeat Fi - INSTALLATION AND CONNECTION (continued) - 3

Never use an electrical plug for the power supply.

The electrical power supply must have, in a suitable manner, an omnipolar protection device of the D-curve circuit breaker type as well as a 30mA protection differential circuit breaker (see following table).

Models HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3
Power supply V/Ph/Hz230V~ 50Hz230V~ 50Hz230V~ 50Hz230V~ 50Hz
D-Curve circuit breakerA 1620 25 25
Cable sectionmm ^2 3G2.53G43G43G4
ModelsHP5211ET3HP5251ET3HP5301ET3
Power supply V/Ph/Hz400V 3N~ 50Hz400V 3N~ 50Hz400V 3N~ 50Hz
D-Curve circuit breakerA101216
Cable section mm^2 5G2.55G2.55G2.5

HAYWARD SumHeat Fi - INSTALLATION AND CONNECTION (continued) - 4

Use an RO 2V/R 2V or equivalent power cord.

HAYWARD SumHeat Fi - INSTALLATION AND CONNECTION (continued) - 5

The cables sections are given for a maximum length of 25 m. They must however be checked and adjusted according to the installation conditions.

HAYWARD SumHeat Fi - INSTALLATION AND CONNECTION (continued) - 6

Always shut down the main power supply before opening the electrical control box.

After a cut-off of the power supply, wait 10 minutes before accessing the active internal parts of the equipment (power stored in the capacitors).

3. INSTALLATION AND CONNECTION (continued)

3.5 Initial start-up

Start-up procedure - After installation is complete, follow these steps:

1) Rotate the fans by hand to verify that they can turn freely by hand, and that the turbine is correctly affixed to the motor shaft.
2) Ensure that the unit is connected correctly to the main power supply (see the wiring diagram in the appendix).
3) Activate the filtration pump.
4) Verify that all water valves are open and that the water flows toward the unit before switching on the heating or cooling mode.
5) Verify that the drainage hose is correctly affixed and that it causes no obstructions.
6) Activate the unit power supply, then press the On/Off button 📄 on the control panel.
7) Ensure that the alarm signal ( ) does not light up red. If necessary see the troubleshooting guide (see § 6.4).
8) Set the water flow using the by-pass valve (see § 3.6 and 2.1), as provided for by each model, to obtain an Entry/Exit temperature of 2^ C.
9) After running for several minutes, verify that the air exiting the unit is cool (between 5 and 10°).
10) With the unit operating, turn off the filter pump. The unit should automatically turn off and display error code E03 (See § 6.4).
11) Allow the unit and the pool pump to run 24 hours per day until the desired water temperature has been reached. When the set water inlet temperature is reached, the unit will turn off. It will automatically restart (as long as the pool pump is running) if the pool temperature is at least 0.5^ C below the set temperature.

Water flow switch - The unit is equipped with a flow switch that turns on the heat pump when the pool filtration pump is running, and deactivates it when the filtration pump is out of order. If the water is low, the E03 alarm code will appear on the regulator (See § 6.4).

3. INSTALLATION AND CONNECTION (continued)

Time delay - The unit is equipped with a time delay of 3 minutes in order to protect the control circuit components, to eliminate restart cycling and contactor chatter. Thanks to this time delay, the unit automatically restarts approximately 3 minutes after each control circuit interruption. Even a brief power interruption will activate the restart time delay.

3. INSTALLATION AND CONNECTION (continued)

3.6 Water flow setting

With the water entry and exit valves being open, adjust the by-pass valve in order to obtain a difference of 2^ between the inflow and outflow temperature (see principle diagram § 3.1). You can verify the switch by seeing the entry/exit temperatures directly on the control panel.

HAYWARD SumHeat Fi - Water flow setting - 1

text_image 01-01 2017 10:15:00 26.5°C IN SET 26.0°C OUT 28.0°C

Water inlet temperature Water outlet temperature

Note: Opening the by-pass valve creates a weaker flow, which leads to an increase in T .

Closing the by-pass valve creates a stronger flow, which leads to a decrease in T .

4. USER INTERFACE

4.1 General presentation

The heat pump is equipped with a digital control panel with a touch screen, electronically connected and pre-set at the factory in heating mode.

HAYWARD SumHeat Fi - General presentation - 1

text_image 21345 01-01 2017 10:15:00 26.5°C IN SET 26.0°C OUT 28.0°C 12a 10a1112b10b10c

Legend

1 AHAYWARD SumHeat Fi - General presentation - 2(blinking red)
2 LHAYWARD SumHeat Fi - General presentation - 3d screen
3 DHAYWARD SumHeat Fi - General presentation - 4
4 HHAYWARD SumHeat Fi - General presentation - 5
5 OHAYWARD SumHeat Fi - General presentation - 6de temperature
6HAYWARD SumHeat Fi - General presentation - 7Recording base (Water temperature and power consumption)
7 RHAYWARD SumHeat Fi - General presentation - 8ng settings and saving
8 SHAYWARD SumHeat Fi - General presentation - 9up / Increase
9 SHAYWARD SumHeat Fi - General presentation - 10down / Decrease
10 CHAYWARD SumHeat Fi - General presentation - 11ating mode selection
10aHAYWARD SumHeat Fi - General presentation - 12ng mode
10bHAYWARD SumHeat Fi - General presentation - 13ng mode
10cHAYWARD SumHeat Fi - General presentation - 14matic mode
11 WHAYWARD SumHeat Fi - General presentation - 15Output temperature
12 SHAYWARD SumHeat Fi - General presentation - 16ting silence mode
12aHAYWARD SumHeat Fi - General presentation - 17ng silence mode timer
12bHAYWARD SumHeat Fi - General presentation - 18Silence mode and activation light
13 OHAYWARD SumHeat Fi - General presentation - 19version °C / °F
14 VHAYWARD SumHeat Fi - General presentation - 20Input temperature
15HAYWARD SumHeat Fi - General presentation - 21Setting the Timer date and time ON/OFF
16 DHAYWARD SumHeat Fi - General presentation - 22st mode
17 OHAYWARD SumHeat Fi - General presentation - 23Off

4. USER INTERFACE (continued)

OFF Mode

When the heating pump is in sleep mode (OFF Mode), the button is grey.

ON Mode

When the heating pump is running or regulating (ON Mode), the button lights up green.

4.2 Setting the Date and Time

HAYWARD SumHeat Fi - Setting the Date and Time - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5°C OUT 28.8°C Timer 2

HAYWARD SumHeat Fi - Setting the Date and Time - 2

text_image Back to the previous screen 4 00-00 2017 00:00:00 WED 31-72 2017 00:00:00 1 2 3 4 5 6 7 8 9 0 Quit without saving Back Confirm

HAYWARD SumHeat Fi - Setting the Date and Time - 3

Enter all the fields (Day/Month/Year, Hour/Minute/Second before confirming, otherwise the changes will not be saved.

4.3 Timer function settings

Setting this function is necessary if you would like to run the heat pump for a shorter period than what is defined by the filtration clock. Therefore, you can program a deferred start and an anticipated stop or simply stop a certain timeframe from running (at night, for example).

It is possible to set one Start Timer and one Stop Timers.

4. USER INTERFACE (continued)

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 1

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 2

Blue highlighting = Activated

Grey = Deactivated

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 3

The setting step is "hour to hour".

  • Once the start time has been set, press (step 6) to activate the Timer. The symbol and time now have blue highlighting.
  • Repeat steps 3 to 6 to set and activate the stop time ( )
  • When the settings are complete, the operating range of the heat pump is highlighted in green and the highlight range is yellow.
  • Press twice on to return to the main screen.

4. USER INTERFACE (continued)

4.4 Setting and visualisation of the set point

HAYWARD SumHeat Fi - Setting and visualisation of the set point - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5°C OUT 28.8°C

In Mode "OFF" or Mode "ON"

Press the button to display the set point, then press on pour to set the set point you wish.

Confirm by pressing and you will return to the main screen automatically.

HAYWARD SumHeat Fi - In Mode "OFF" or Mode "ON" - 1

The setting is made with a precision of 0.5^ .

HAYWARD SumHeat Fi - In Mode "OFF" or Mode "ON" - 2

It is recommended to never exceed 32^ C to avoid alteration of the liners.

4. USER INTERFACE (continued)

4.5 Locking and unlocking the touch screen

The control screen locks automatically after one minute (default setting). It is possible to adjust the time before the screen locks automatically to between 1 and 10 minutes, or simply to cancel this function.

HAYWARD SumHeat Fi - Locking and unlocking the touch screen - 1

3) Set the time to between 1 and 10 minutes. Saving is automatic.
4) Press twice to return to the main screen.
5) To deactivate automatic locking press

To unlock the screen, press (anywhere) on the screen for 2s.

Enter the code "22" and confirm by pressing EN

HAYWARD SumHeat Fi - Locking and unlocking the touch screen - 2

text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C >>

4. USER INTERFACE (continued)

4.6 SILENT function settings

Silence mode enables the heat pump to be used in economic and very silent mode when the heating needs are low (maintaining the pool temperature or need for ultra-silent operation).

This function can be Activated/Deactivated manually or using a Timer.

Manual Activation

HAYWARD SumHeat Fi - Manual Activation - 1

4. USER INTERFACE (continued)

Manual Deactivation
HAYWARD SumHeat Fi - USER INTERFACE (continued) - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 2

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 3

text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 4

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C Silence mode deactivated

Setting the Timer
HAYWARD SumHeat Fi - USER INTERFACE (continued) - 5

text_image 01-01 2017 10:15:00 26.5°C IN 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 6

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 7

text_image 01-01 2017 10:15:00 26.5°C IN OUT 26.5 °C OUT 28.8 °C

4. USER INTERFACE (continued)

Setting the Timer (continued)
HAYWARD SumHeat Fi - USER INTERFACE (continued) - 1

text_image Mute Timer ON OFF 1 00:00 2 00:00 Mute Timer ON OFF 1 2 3 4 5 6 7 8 9 0 20:00 || 08:00 Confirm

1) Start time, input and confirmation.
2) End time, input and confirmation.
3) Confirm.

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 2

text_image Mute Timer 6 10 12 14 8 16 6 18 4 20 2 22 0 24 ON ON 20:00 08:00

4) Activation.
5) Deactivation.
6) Back to the main screen.

HAYWARD SumHeat Fi - USER INTERFACE (continued) - 3

The setting step is "hour to hour". Once the Timer is activated, it is active 7 days a week.

5.1 Maintenance

These maintenance operations must be carried out once per year in order to guarantee the longevity and the good working condition of the heat pump.

  • The maintenance and repairs of the device must be carried out by an accredited professional in accordance with the regulatory texts and the rules of the art in effect in the country where the device is installed (see § 3.4).
    For any intervention on the cooling circuit, the professional must hold a certificate of competence in handling refrigerants.
  • Check the power cable. If the power cable is damaged, it has to be replaced by the manufacturer, its after-sales service or by a qualified and authorised person.
  • Verify the grounding connection of the device and its continuity.
  • Clean the coil with the help of a soft brush or jet of air or water. Warning, never use a high pressure cleaner.
  • Verify that the drains flow well.
  • Verify the tightening of the hydraulic and electrical connections
  • Verify the hydraulic sealing of the condenser.
  • Have the leak-tightness of the cooling circuit to the leak detector checked by an accredited professional.

HAYWARD SumHeat Fi - Maintenance - 1

Before any maintenance operation, the heating pump must be disconnected from any electrical current source. The maintenance operations must only be carried out by personnel that is qualified and authorised to handle liquid refrigerants.

5.2 Winterising

  • Put the heat pump in "OFF" mode.
  • Cut the power supply to the heat pump.
  • Empty the condenser with the help of the drain to avoid any risk of deterioration. (high risk of freezing).
  • Close the by-pass valve and unscrew the entry/exit connection unions.
  • Eliminate the maximum amount of residual stagnant water from the condenser with the help of an air gun.
  • Close the water entry and exit areas of the heating pump to avoid introducing foreign bodies.
  • Cover the heating pump with a dedicated winterising case.

HAYWARD SumHeat Fi - Winterising - 1

Any damage caused by poor winterising maintenance will lead to cancellation of the warranty.

6. APPENDIX

6.1 Electrical diagrams

HP5171DT3

HAYWARD SumHeat Fi - HP5171DT3 - 1

text_image ACL-in ACN-out ACN-in ACN-out FAN DRIVER BOARD CN1 CN4 BLK 46GB 48GA 12V BLK GND YEL 46GB RED 12V BLK GND YEL 46GB RED 12V Controller W-L 46GB W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA W-L 48GA M1 M2 M3 M4 M5 M6 M7 M8 M9 M10 M11 M12 M13 M14 M15 M16 M17 M18 M19 M20 M21 M22 M23 M24 M25 M26 M27 M28 M29 M30 M31 M32 M33 M34 M35 M36 M37 M38 M39 M40 M41 M42 M43 M44 M45 M46 M47 M48 M49 M50 M51 M52 M53 M54 M55 M56 M57 M58 M59 M60 MN1 N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N-N Power supply 220-240V~/50Hz K2 1 2 3 4 Dry Contact 7 A max Remote ON/OFF connection ACN-NDN Controler K2 W-L 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V MAIN BOARD CN9 CN11 CN13 CN2 CN8 CN607 CN604 CN708 CN708 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN607 CN608 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN708 CN

REMARKS:

PS: PRESSURE SENSOR

AT: AIR TEMPERATURE SENSOR

OT: OUTLET WATER TEMPERATURE SENSOR

SUT: SUCTION TEMPERATURE SENSOR

LP: LOW PRESSURE SWITCH

FS: WATER FLOW SWITCH

HP: HIGH PRESSURE SWITCH

IT: WATER INLET TEMPERATURE SENSOR

CT: EVAPORATOR TEMPERATURE SENSOR

ET: DISCHARGE TEMPERATURE SENSOR

EEV: ELECTRONIC EXPANSION VALVE

FM1: DC FAN MOTOR

4V: 4 WAYS VALVE

K2: DRY CONTACT 7 A MAX

COMP: COMPRESSOR

6. APPENDIX (continued)

HP5211DT3 / HP5251DT3
HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image ACL-04 EMI VCL In RED L BLU N Y/G POWER SUPPLY 220-240V-/50Hz ACN-OUT ACN1 L N Z Y/G TM1 K2 1 2 3 4 Dy Contact 7 A max Remote ON/OFF connection HP OHP Controller WiFi N Main Board CN9 CN11 A13 A12 A11 5V 6V 5V EEV CCN13 A4A6A8A10 A1A3A5A8A9 Pressure sensor (PS) RED BLK WHT AT OT SUT LP AT SUT LP FS CN8 CN13 ET STT STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt STt

REMARKS:

PS: PRESSURE SENSOR EEV: ELECTRONIC EXPANSION VALVE

AT: AIR TEMPERATURE SENSOR

OT: OUTLET WATER TEMPERATURE SENSOR

SUT: SUCTION TEMPERATURE SENSOR

LP: LOW PRESSURE SWITCH

FS: WATER FLOW SWITCH

IT: WATER INLET TEMPERATURE SENSOR

CT: EVAPORATOR TEMPERATURE SENSOR

ET: DISCHARGE TEMPERATURE SENSOR

FM1: DC FAN MOTOR

HP: HIGH PRESSURE SWITCH

OHP: THERMAL PROTECTION

4V: 4 WAYS VALVE

K2: DRY CONTACT 7 A MAX.

PTC: THERMISTOR

KM1: COMPRESSOR SWITCH

COMP: COMPRESSOR

6. APPENDIX (continued)

HP5301DT3
HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image TO POWER SUPPLY 220-240V~/50Hz EDI ACN-50V YIG RED L BLU N K2 1 1 2 3 4 Dry Contact / A max Stamps ON/OFF connection Fan Driver Board CN1 CN4 BLK YEL OUT1 4X5A1 4X5A1 12V Controler ELK CND VE_4688 MHT 469A+ HLD 12V BLK CND YEL 4698- MHT 469A+ RED 12V WiFi N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N CPS Drive Board CN814 2V 2ND A CN834W Y U CN888P P2 CN867PC ACNAOL 11.2 L 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 KM1 electric reactor Main Board CN9 CN11 EYV 5V CN9 ATR KX WHT 5V A13 A12 A11 A10 A9A6A5A7A9 A1A3A5A7A9 CPIC KM1 Pressure sensor (PS) ETt CT t HP FS CN8 AT OT SUT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP UT LP AT OP U V W COMP

REMARKS:

PS: PRESSURE SENSOR

AT: AIR TEMPERATURE SENSOR

OT: OUTLET WATER TEMPERATURE SENSOR

SUT: SUCTION TEMPERATURE SENSOR

LP: LOW PRESSURE SWITCH

FS: WATER FLOW SWITCH

HP: HIGH PRESSURE SWITCH

IT: WATER INLET TEMPERATURE SENSOR

CT: EVAPORATOR TEMPERATURE SENSOR

ET: DISCHARGE TEMPERATURE SENSOR

EEV: ELECTRONIC EXPANSION VALVE

FM1: DC FAN MOTOR

4V: 4 WAYS VALVE

K2: DRY CONTACT 7 A MAX.

PTC: THERMISTOR

KM1: COMPRESSOR SWITCH

COMP: COMPRESSOR

6. APPENDIX (continued)

HP5211ET3 / HP5251ET3
HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image To power supply 380-415V/3N~50Hz Dry Contact Remote 7 A max. ON/OFF Fan Driver Board CN1 CN4 BLK OUT5 OUT4 OUT3 OUT2 RLY1 Main Board CN9 CN11 A13 A12 A10 A8 A6 A4 A2 CN8 CN13 Pressure sensor (PS) Controller WiFi YIG-FM1 R-RED S BLK T WHIT N BLU YIG K2 1 2 3 4 5 6 7 8 HP ORP N N N N N N N N N N 4V N K2 R DCP-IN DCN-IN CCN2 DCN-OUT DCN-OUT CPS Driver Board U W ST REX BLK WY U V WY COMP

REMARKS:

PS: PRESSURE SENSOR

AT: AIR TEMPERATURE SENSOR

OT: OUTLET WATER TEMPERATURE SENSOR

SUT: SUCTION TEMPERATURE SENSOR

LP: LOW PRESSURE SWITCH OHP: THERMAL PROTECTION

FS: WATER FLOW SWITCH

IT: WATER INLET TEMPERATURE SENSOR

CT: EVAPORATOR TEMPERATURE SENSOR

ET: DISCHARGE TEMPERATURE SENSOR

EEV: ELECTRONIC EXPANSION VALVE

FM1: DC FAN MOTOR

HP: HIGH PRESSURE SWITCH

4V: 4 WAYS VALVE

K2: DRY CONTACT 7 A MAX.

COMP: COMPRESSOR

6. APPENDIX (continued)

HP5301ET3
HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image To power supply 380-415V/3N-/50Hz Dry Contact Remote 7 A max. ON/OFF Fan Driver Board CN4 BLK 486BT 12V 485DT 12V BLK 6W AMT 450V LCD 12V Controller WiFi R RED S BLK T WHT N BLU Y/G R C N A F M I R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C C R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C N R C S T- S CNP B2 CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V CNP B1 12V

REMARKS:

PS: PRESSURE SENSOR

AT: AIR TEMPERATURE SENSOR

OT: OUTLET WATER TEMPERATURE SENSOR

SUT: SUCTION TEMPERATURE SENSOR

LP: LOW PRESSURE SWITCH

FS: WATER FLOW SWITCH

HP: HIGH PRESSURE SWITCH COMP: COMPRESSOR

IT: WATER INLET TEMPERATURE SENSOR

CT: EVAPORATOR TEMPERATURE SENSOR

ET: DISCHARGE TEMPERATURE SENSOR

EEV: ELECTRONIC EXPANSION VALVE

FM1: DC FAN MOTOR

4V: 4 WAYS VALVE

K2: DRY CONTACT 7 A MAX.

Page left intentionally blank

6. APPENDIX (continued)

6.2 Heating priority wiring for monophasic pump

HAYWARD SumHeat Fi - Heating priority wiring for monophasic pump - 1

Remove the front panel to access the terminal board.

HAYWARD SumHeat Fi - Heating priority wiring for monophasic pump - 2

text_image 230 V~ N 50 Hz Ph 1L1 3L2 5L3 13N0 A1 230V/45-60 Hz 16(4) 250- R 3d Made in Germany Dye contact 7 A max K2 = = × L N ⊕ × × × Power supply 230V~ / 50Hz Monophasic pump

Terminals 1 and 2 deliver a potential-free dry contact, 230V\~ / 50 Hz, no polarity.

Wire terminals 1 and 2 as indicated in the diagram above, to activate the operation of the filtration pump in 2-minute cycles each hour if the temperature of the pool is lower than the set point.

HAYWARD SumHeat Fi - Heating priority wiring for monophasic pump - 3

Never connect the power supply of the filtration up directly to terminals 1 and 2.

HAYWARD SumHeat Fi - Heating priority wiring for monophasic pump - 4

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. APPENDIX (continued)

6.3 Heating priority wiring for three phases pump

HAYWARD SumHeat Fi - Heating priority wiring for three phases pump - 1

Remove the front panel to access the terminal board.

HAYWARD SumHeat Fi - Heating priority wiring for three phases pump - 2

text_image 400V 3N~ 50 Hz NL3L2L1 1L13L25L3A113N0 2T14T2 6T3A214N0 230V/45-60 Hz 15(4) 250- R 3d Made in Germany 4587 2138 Dry contact 7 A max K2 L3 L2 L1 Three phases pump Power supply 430V 3N ~ / 50Hz

Terminals 1 and 2 deliver a potential-free dry contact, 230V\~ / 50 Hz, no polarity.

Wire terminals 1 and 2 as indicated in the diagram above, to activate the operation of the filtration pump in 2-minute cycles each hour if the temperature of the pool is lower than the set point.

HAYWARD SumHeat Fi - Heating priority wiring for three phases pump - 3

natural_image Technical line drawing of a mechanical assembly with internal components and an upward arrow indicator (no text or symbols)

HAYWARD SumHeat Fi - Heating priority wiring for three phases pump - 4

Never connect the power supply of the filtration gap directly to terminals 1 and 2.

6. APPENDIX (continued)

6.4 Exploded view and spare parts

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HAYWARD SumHeat Fi - Exploded view and spare parts - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - Exploded view and spare parts - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

MarkDescription P/NHP5171DT3HP5211DT3HP5251DT3HP5301DT3
1 Fan MotorHWX20000330381n/a
HWX20000330402 n/an/an/a
2 Motor cover HWX20000220320
3 ABS upper panelHWX80900736n/an/a
HWX80900737 n/an/a
HWX80900718 n/an/an/a
4 Right-hand lateral protectionHWX80704158n/an/a
HWX80705113 n/an/a
HWX80705110 n/an/an/a
5/ / / // /
6 Guard plateHWX32012210724n/an/a
HWX32002210071 n/an/a
HWX32004210137 n/an/an/a
7Pressure tap 90 mm 1/2"HWX20000140153
8Electronic expansion valveHWX20000140451n/an/a
HWX20000140449 n/an/an/a
HWX20000140442 n/an/an/a
HWX20000140401 n/an/an/a
9Filter ∅12.9-∅12.9 (∅28)HWX20000140027
10Pressure Tap 95 mm 7/16"HWX20000140512
11Pressure Tap 40 mm 1/2"HWX20000140150
124 ways valveHWX20041437n/an/a
HWX20011491 n/a
13Pressure sensorHWX20000360274
14Coil/air/water temp sensor 5k-800 mmHWX20003202
15Compressor discharge probe 50k-600 mmHWX20000320145
16Water flow detectorHWX83000069
17/ / / // /
18Front panelHWX80900738n/an/a
HWX80900739 n/an/a
HWX80900710 n/an/an/a
19Color touchscreenHWX95005310612
20Black electric access hatchHWX20000220247
21Electrical box coverHWX80702647n/an/a
HWX80702644 n/an/a
HWX80702645 n/an/an/ax
22High pressure switch NC 3.2MPa/4.4MPaHWX20000360187
23Low pressure switch NO 0.15MPa/0.05MPaHWX20000360054
24/ / / // /
25Titanium/PVC condenserHWX32009120085n/an/a
HWX32002120023 n/an/an/a
HWX32016120012 n/an/an/a
HWX32016120011n/an/an/a
26/ / / // /
27CompressorHWX80100046n/an/a
HWX80100069 n/an/a
HWX30101000006 n/an/an/a
28Left-hand lateral protectionHWX32012210729n/an/a
HWX80705114 n/an/a
HWX80705111n/an/an/a

6. APPENDIX (continued)

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDIX (continued) - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

6. APPENDIX (continued)

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

MarkDescription P/NHP5171DT3HP5211DT3HP5251DT3HP5301DT3
29//////
30Square 50 mm threaded connector HWX20031379✓ ✓✓ ✓
31PVC elbow ∅ 50 mm HWX20011359✓ ✓✓ ✓
32Left/right vertical supportHWX32000210086n/a n/a n/a
HWX80702346 n/an/a
HWX80702656 n/an/a n/a
33Fin coilHWX32012120155n/a n/a n/a
HWX80600429 n/an/a n/a
HWX32003120028n/a n/an/a
HWX32004120013n/a n/a n/a
34Rear protectionHWX32012210730n/a n/a n/a
HWX80705115n/an/a
HWX80705112n/a n/a n/a
35//////
36Fan blade ∅ 522 mmHWX20000270062n/a n/a n/a
Fan blade ∅ 560 mmHWX35072195 n/an/a
Fan blade ∅ 600 mmHWX20000270057n/an/an/a
37Fan protection grilleHWX32012210732n/a n/a n/a
HWX32003210142n/an/a
HWX80700160 n/an/a n/a
38MotherboardHWX72200033171Dn/a n/a n/a
HWX72200033211Dn/an/a n/a
HWX72200033251Dn/a n/an/a
HWX72200033301Dn/a n/a n/a
39Ventilator Inverter cardHWX82300485✓ ✓✓ ✓
40Terminal block 4 connectionsHWX20003909✓ ✓✓ ✓
41Filter boardHWX3020100007✓ ✓✓ ✓
42K2 relayHWX20000360297✓ ✓✓ ✓
43Terminal block L-N-GNDHWX20000390223✓ ✓✓ ✓
444-position terminal blockHWX20000390046✓ ✓✓ ✓
45Reactance coilHWX82500009n/a n/a n/a
HWX20000370030n/a✓ ✓
46/////
47/////
48Compressor Inverter cardHWX82300149n/a n/a n/a
HWX82300019 n/a✓ ✓
49PTC 100 Ω resistor HWX20000320113 n/a✓ ✓
50/////
51/////
52Power switchHWX200003600619n/a✓ ✓
53Bottle of liquidHWX20000140579n/an/a

6. APPENDIX (continued)

HP5211ET3 / HP5251ET3 / HP5301ET3

HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDIX (continued) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

MarkDescription P/N HP5211ET3 HP5251ET3 HP5301ET3
1 DC Fan MotorHWX20000330381n/a
HWX20000330402 n/an/a
2 Motor cover HWX20000220320√ √
3Upper panelHWX80900737n/a
HWX80900718 n/a n/a
4Right-hand lateral protectionHWX80705113n/a
HWX80705110 n/a n/a
5 / / / /
6 Guard plateHWX32002210071n/a
HWX32004210137 n/an/a
7 Pressure tap 90 mm 1/2"HWX20000140153√ √
8 Electronic expansion valveHWX20000140449n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/a
9Filter ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Pressure Tap 95 mm 7/16"HWX20000140512√ √
11Pressure Tap 40 mm 1/2"HWX20000140150√ √
124 ways valveHWX20011491√ √
13Pressure sensorHWX20000360274√ √
14Coil/air/water temp sensor 5k-800 mmHWX20003202√ √
15Compressor discharge probe 50k-600 mmHWX20000320145√ √
16Water flow detectorHWX83000069√ √
17/ / / / /
18Front panelHWX80900739n/a
HWX80900710 n/a n/a
19Color touchscreenHWX95005310612√ √
20Black electric access hatchHWX20000220247√ √
21Electrical box coverHWX80702644n/a
HWX80702645 n/a n/a
22High pressure switch NC 3.2MPa/4.4MPaHWX20000360187√ √
23Low pressure switch NO 0.15MPa/0.05MPa HWX20000360054√ √
24/ / / / /
25Condenseur Titane PVCHWX32002120023n/an/a
HWX32016120012 n/an/a
HWX32016120011n/a n/a
26/ / / / /
27CompressorHWX80100069n/a
HWX30101000006 n/an/a
28Left-hand lateral protectionHWX80705114n/a
HWX80705111n/a n/a
29/ / / / /
30Square 50 mm threaded connectorHWX20031379√ √
31PVC elbow ∅ 50 mmHWX20011359√ √
32Left/right vertical supportHWX80702346n/a
HWX80702656 n/a n/a x
33Fin coilHWX80600429n/an/a
HWX32003120028 n/an/a
HWX32004120013 n/an/a
34Protection arrièreHWX80705115n/a
HWX80705112 n/a n/a

6. APPENDIX (continued)

HP5211ET3 / HP5251ET3 / HP5301ET3
HAYWARD SumHeat Fi - APPENDIX (continued) - 1

text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDIX (continued) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

6. APPENDIX (continued)

HP5211ET3 / HP5251ET3 / HP5301ET3

MarkDescription P/N HP5211ET3 HP5251ET3 HP5301ET3
35 // / / /
36Fan blade ∅ 560 mm HWX35072195n/a
Fan blade ∅ 600 mm HWX20000270057 n/an/a
37 FFan protection grilleHWX32003210142n/a
HWX80700160n/an/a
38MotherboardHWX72200033211En/an/a
HWX72200033251En/an/a
HWX72200033301En/an/a
39Ventilator Inverter cardHWX82300485
40Terminal block 4 connectionsHWX20003909
41Filter boardHWX82300074
42K2 relayHWX20000360297
43Terminal block L-N-GNDHWX20000390180
444-position terminal blockHWX20000390046
45Reactance coilHWX20000370030
46 // / / /
47 // / / /
48Compressor Inverter cardHWX82300112n/a
HWX302010000012n/an/a
49Capacitor boardHWX302010000014
50L-N-GND reactance terminal boardHWX20000390223
51Bottle of liquidHWX20000140579 n/a

6. APPENDIX (continued)

6.5 Troubleshooting guide

HAYWARD SumHeat Fi - Troubleshooting guide - 1

Certain operations must be carried out by an authorized technician.

If there is a fault on the heat pump, the symbol 🔍 appears blinking red in the left hand corner of the screen.

Press the symbol 🔍 to access the list of errors.

Refer to following table.

HAYWARD SumHeat Fi - Troubleshooting guide - 2

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C Fault records Protection/Fault Time E08 Communication Fault 01-01-17 15:06 Error codes Description Date and time of appearance

HAYWARD SumHeat Fi - Troubleshooting guide - 3

Once the problem has been resolved the error is cancelled automatically and the triangle changes to solid grey.

HAYWARD SumHeat Fi - Troubleshooting guide - 4

To delete the error list, press on then return to the previous screen by pressing on

6. APPENDIX (continued)

ProblemError codesDescription Solution
Water inlet sensor fault P01The sensor is open or has short-circuited.Check the blue AIN6 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Water outlet sensor fault P02Check the red AIN7 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Outside temperature sensor fault P04Check the AIN9 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
De-icing sensor fault P05Check the yellow AIN8 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Compressor aspiration sensor defectP07Check the green AIN5 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Resistance fault 6.8 kΩ P09Check the AIN11 connector on the board and measure the resistance; replace it if R < 6.8 kΩ
Compressor discharge sensor fault P081Check the black AIN12 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Discharge temperature too high P082Discharge temperature > 120°CMeasure the discharge temperature at the outlet of the compressor; if measured temperature < 120°C, replace the sensor. Perform a non-condensable test
High pressure protection E01 The sensor is open or has short-circuited.Verify the AIN4 connectors on the card or replace the sensor
Check the water flow
Check the water flow detector
Check the valve opening
Check the by-pass
Check the evaporator is not clogged
Water temperature too hot
Incondensable problem after maintenance, empty and evacuate the cooling circuit
Fluid load too high, remove fluid into a liquid bottle
Low pressure protection E02 The sensor is open or has short-circuited.Check the AIN3 connections on the card or replace the sensor
Large coolant leak, search for the leak with the detector
Air flow too low, check the ventilator rotation speed
Check the evaporator is not clogged, clean its surface

6. APPENDIX (continued)

ProblemError codesDescription Solution
Flow sensor fault E03 The sensor is open or has short-circuited.Check the AIN2 connections on the card or replace the sensor
Lack of water, check the filtration pump operation
Check the stop valve opening
Check the by-pass adjustment
Water outlet temperature fault E05Applies only in Cold mode, Water outlet temperature < 4°CStop the heat pump, serviceability limit reached
Input/Output temperature difference >13°CE06Applicable in Cold mode onlyLack of water, check the filtration pump operation
Check the stop valve opening
Check the by-pass adjustment
Antifreeze protection Cold mode E07Water output temperature < 4°CCheck the red AIN7 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Stop the heat pump, drain the condenser, high risk of it freezing.
Communication problem E08No communication between the printed circuit board and the user interfaceCheck the connectors - see the wiring diagram
Level 1 antifreeze protection E192°< Water temperature < 4° and Air temperature < 0°Stop heat pump operation, empty the condenser to avoid freezing, by default the heat pump starts the filtration pump to avoid icing over
Level 2 antifreeze protection E29Water temperature < 2° and Air temperature < 0°Stop heat pump operation, empty the condenser to avoid freezing, by default the heat pump starts the filtration pump and the heat pump to avoid icing over.
DC1 fan motor fault F031 Motor jammed or faulty connectionCheck free rotation; check CN1 connectors; replace the motor
The heat pump does not start F08 Possibly an inversion or lack of phaseReverse two phases on the R-S-T terminal block.Check the connection and tightness of the phases.
Exterior temperature too low TPOutdoor temperature too low, < H34 (-15°C fault)Check the AIN9 connector on the board and measure the sensor's resistance; if it is under 100 Ω or over 500 kΩ, replace it.
Check the value of parameter H34
Pressure sensor fault PP The sensor is open or short-circuitingCheck the connections see electrical diagram

6. APPENDIX (continued)

6.6 Recording base

From the main screen, press on 📄 to access the history of water input and output temperature recordings.

HAYWARD SumHeat Fi - Recording base - 1

This data is available for 60 days.

Press on to access the compressor frequency.

HAYWARD SumHeat Fi - This data is available for 60 days. - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5°C OUT 28.8°C Water input temperature curve Water output temperature curve Temperature 30.5°C 30.5°C 40°C 35°C 30°C 25°C 20°C 15°C 10°C

HAYWARD SumHeat Fi - This data is available for 60 days. - 2

line Comp.Frequency | Time | Comp.Frequency (Hz) | |---|---| | 0h | 45 | | 6h | 55 | | 12h | 60 | | 18h | 90 | | 24h | 90 |

Press on to return to the main screen.

WARRANTY CONDITIONS

All HAYWARD products are guaranteed to be free from manufacturing or material faults for a period of two years as from the date of purchase. Any claim made under the terms of the warranty must be accompanied by a dated proof of purchase. We therefore recommend that you keep your invoice.

The HAYWARD warranty is limited to the repair or replacement, at HAYWARD's discretion, of faulty products, provided they have been used under normal conditions, as described in their user guide, and that the product has not been modified in any way and has been used only with HAYWARD components and parts. Frost and chemical damage are not covered.

No other costs (transportation, labour, etc.) are covered by the warranty.

HAYWARD cannot be held liable for any direct or indirect damage caused by the incorrect installation, connection or operation of a product.

Please contact your retailer if you want to make a claim under the terms of the warranty and request the repair or replacement of an item. No equipment returned to our factory will be accepted without our prior written agreement.

Worn parts are not covered by the warranty.

6.7 End of life of the device

HAYWARD SumHeat Fi - End of life of the device - 1

The symbol of the crossed-out dustbin concerning the treatment and the reclamation of electrical and electronic waste means that the products must not be disposed of with household waste, bulky items or in a landfill under no circumstances.

At the end of life, the device must undergo selective collection so that it can be recycled or reclaimed. A specific circuit for recovering this type of products is set up in the countries of the European Union and in Norway.

Contact the installer or the local representative to have this device collected, dismantled and recycled.

Retreating the refrigerant, oil and other parts has to be carried out by a qualified accredited professional in accordance with current local and national legislation.

If the product contains batteries that bear this symbol, this means that the batteries can contain harmful or polluting substances. In this case, take the batteries to a used battery collection point.

SUMHEAT FULL INVERTER

UNIDAD DE BOMBA DE CALOR PARA PISCINAS

HAYWARD SumHeat Fi - SUMHEAT FULL INVERTER - 1

natural_image Exterior view of a modern industrial water filter unit (no visible text or symbols)

HAYWARD SumHeat Fi - SUMHEAT FULL INVERTER - 2

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

text_image 01-01 2017 10:15:00 26.5°C IN OUT 26.5°C 2 S OUT 28.8°C >>
text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - SUMHEAT FULL INVERTER - 3

text_image 01-01 2017 10:15:00 ! 26.5°C IN 26.5 °C OUT 28.8 °C Modo silencioso desactivado
text_image Alim Temperature Driver General 380-415V/3N^v/50Hz R RED S BLK T WHT N BLU YIG K2 L 2 3 4 1 2 3 4 Dry Contact Remote 7 A max. ON/OFF 5 6 7 8 HP HP OPF N N N N N N N N N N 4V 4V K2 electric reactor CPS Driver Board DCP IN DCM-IN CNK2 4 2 KCH-OUT KSH-CNKID AC-OUT DCR-OUT R2 S9 U V WIS T REF: BLK VW U V W COMP Main Board CN9 CN11 A13 A12 A10 A8 A6 A4 A2 CN8 FS CN13 RFD BLK WHT Pressure sensor (PS) EEV CN4 GN0 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 YH 48X1 Y H YIG C#1 BJA5ND YEL-48XB RLD-12V BJA5ND YEL-48XB RLD-12V Controller WiFi

LEYENDA

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEYENDA - 1

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

RepDesignación Ref.HP5171DT3HP5211DT3HP5251DT3HP5301DT3
1Motor ventilador CCHWX20000330381n/a
HWX20000330402 n/an/an/a
2Capós de protección del motor HWX20000220320
3Panel superior ABSHWX80900736n/an/a
HWX80900737 n/an/a
HWX80900718 n/an/an/a
4Protección lateral derechaHWX80704158n/an/a
HWX80705113 n/an/a
HWX80705110 n/an/an/a
5/ / / / / /
6Placa de protecciónHWX32012210724n/an/a
HWX32002210071 n/an/a
HWX32004210137 n/an/an/an/a
7Toma de presión de 90 mm - 1/2"HWX20000140153
8Arrancador electrónicoHWX20000140451n/an/a
HWX20000140449 n/an/an/a
HWX20000140442 n/an/an/a
HWX20000140401 n/an/an/an/a
9Filtro ∅12.9-∅12.9 (∅28)HWX20000140027
10Toma de presión 95 mm - 7/16"HWX20000140512
11Toma de presión 40 mm - 1/2"HWX20000140150
12Válvula 4 víasHWX20041437n/an/a
HWX20011491 n/a
13Sensor de presiónHWX20000360274
14Sonda de temperatura Evap/aire/agua 5k 800mmHWX20003202
15Sonda de descarga compresor 50k-600 mmHWX20000320145
16Detector del caudal de aguaHWX83000069
17/ / / / / /
18Panel delanteroHWX80900738n/an/a
HWX80900739 n/an/a
HWX80900710 n/an/an/a
19Pantalla táctil en colorHWX95005310612
20Trampilla de acceso eléctricoHWX20000220247
21Panel de caja eléctricaHWX80702647n/an/a
HWX80702644 n/an/a
HWX80702645 n/an/an/ax
22Presostato de alta presión NC 3.2 MPa/4.4MPaHWX20000360187
23Presostato baja presión NO 0.15M Pa/0.05 MPaHWX20000360054
24/ / / / / /
25Condensador de titanio/PVCHWX32009120085n/an/a
HWX32002120023 n/an/an/a
HWX32016120012 n/an/an/a
HWX32016120011n/an/an/a
26/ / / / / /
27CompresorHWX80100046n/an/a
HWX80100069 n/an/a
HWX30101000006 n/an/an/a
28Protección lateral izquierdaHWX32012210729n/an/a
HWX80705114 n/an/a
HWX80705111n/an/an/a
29/ / / / / /
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEYENDA - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEYENDA - 3

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

RepDesignación Ref. HP5211ET3 HP5251ET3 HP5301ET3
1 MMotor ventilador CCHWX20000330381n/a
HWX20000330402 n/an/a
2 Capós de protección del motor HWX20000220320√ √
3 Panel superiorHWX80900737n/a
HWX80900718 n/an/a
4 Protección lateral derechaHWX80705113n/a
HWX80705110 n/an/a
5 / // /
6 Placa de protecciónHWX32002210071n/a
HWX32004210137 n/an/a
7Toma de presión 90 mm - 1/2"HWX20000140153√ √
8 Arrancador electrónicoHWX20000140449n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/a
9 Filtró ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Toma de presión 95 mm - 7/16"HWX20000140512√ √
11Toma de presión 40 mm - 1/2"HWX20000140150√ √
12Válvula 4 víasHWX20011491√ √
13Sensor de presiónHWX20000360274√ √
14Sonda de temperatura Evap/aire/agua 5k 800mmHWX20003202√ √
15Sonda de descarga compresor 50k-600 mmHWX20000320145√ √
16Detector del caudal de aguaHWX83000069√ √
17/// / /
18Panel delanteroHWX80900739n/a
HWX80900710 n/an/a
19Pantalla táctil en colorHWX95005310612√ √
20Trampilla de acceso eléctricoeHWX20000220247√ √
21Panel de caja eléctricaHWX80702644n/a
HWX80702645 n/an/a
22Presostato de alta presión NC 3.2 MPa/4.4 MPaHWX20000360187√ √
23Presostato baja presión NO 0.15 MPa/0.05 MPaHWX20000360054√ √
24/// / /
25Condensador de titanio/PVCHWX32002120023n/an/a
HWX32016120012 n/an/a
HWX32016120011n/an/a
26/// / /
27CompresorHWX80100069n/a
HWX30101000006 n/an/a
28Protección lateral izquierdaHWX80705114n/a
HWX80705111n/an/a
29/// / /
30Conector cuadrado roscado 50 mmHWX20031379√ √
31Codo de PVC ∅ 50 mmHWX20011359√ √
32Soporte vertical derecho/izquierdoHWX80702346n/a
HWX80702656 n/an/a
33Evaporador de aletaHWX80600429n/an/a
HWX32003120028 n/an/a
HWX32004120013 n/an/a
34Protección traseraHWX80705115n/a
HWX80705112 n/an/a
35/// / /
text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEYENDA - 4

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46
natural_image Exterior view of a modern industrial water heater (no visible text or symbols)

HAYWARD SumHeat Fi - LEYENDA - 5

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

text_image ===== R S T N ÷
text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - LEYENDA - 6

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C Modo silêncio desactivado

Configurar o temporizador
HAYWARD SumHeat Fi - LEYENDA - 7

text_image 01-01 2017 10:15:00 26.5°C IN 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - LEYENDA - 8

HAYWARD SumHeat Fi - LEYENDA - 9

text_image 01-01 2017 10:15:00 26.5°C IN OUT 26.5 °C OUT 28.8 °C
text_image ACL-out ACL-in ACN-out ACN-in ACN-in FAN DRIVER BOARD DN1 CN1 BLK 46GB 46GA 12V Y/G FM1 BLK GND YEL 48GB WLT 48MA RED 12V BLG GND YLL 48NU- WLT 48EA- RED 12V Controller WiFi N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N M A L I N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O N O NO C P S D R I V E A B C D E F G H I J K I L M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M N M M NM NC07 CN604 CN708 L1 L2 L1 AC-N AC-L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L L U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V WU V V V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W U V W UVW CCMP

LEGENDA

PS : SENSOR DE PRESSÃO CT : SONDA TEMPERATURA EVAPORADOR

AT : SONDA DE TEMPERATURA DO AR

ET : SONDA DE TEMPERATURA DE DESCARGA

OT : SONDA DE TEMPERATURA SAÍDA DE ÁGUA

flowchart
graph TD
    A["Main Board"] --> B["Alimentação geral 380-415V/3N°V / 50Hz"]
    A --> C["CPS Driver Board"]
    A --> D["Pressure sensor (PS)"]
    A --> E["Controller"]
    A --> F["WiFi"]
    A --> G["Fan Driver Board"]
    A --> H["Dry Contact Remote 7 A max. ON/OFF"]
    A --> I["DCP-N"]
    A --> J["DCP-OUT"]
    A --> K["DCP-OUT"]
    A --> L["DCP-OUT"]
    A --> M["DCP-OUT"]
    A --> N["DCP-OUT"]
    A --> O["DCP-OUT"]
    A --> P["DCP-OUT"]
    A --> Q["DCP-OUT"]
    A --> R["DCP-OUT"]
    A --> S["DCP-OUT"]
    A --> T["DCP-OUT"]
    A --> U["DCP-OUT"]
    A --> V["DCP-OUT"]
    A --> W["DCP-OUT"]
    A --> X["DCP-OUT"]
    A --> Y["DCP-OUT"]
    A --> Z["DCP-OUT"]
    A --> AA["DCP-OUT"]
    A --> AB["DCP-OUT"]
    A --> AC["DCP-OUT"]
    A --> AD["DCP-OUT"]
    A --> AE["DCP-OUT"]
    A --> AF["DCP-OUT"]
    A --> AG["DCP-OUT"]
    A --> AH["DCP-OUT"]
    A --> AI["DCP-OUT"]
    A --> AJ["DCP-OUT"]
    A --> AK["DCP-OUT"]
    A --> AL["DCP-OUT"]
    A --> AM["DCP-OUT"]
    A --> AN["DCP-OUT"]
    A --> AO["DCP-OUT"]
    A --> AP["DCP-OUT"]
    A --> AQ["DCP-OUT"]
    A --> AR["DCP-OUT"]
    A --> AS["DCP-OUT"]
    A --> AT["DCP-OUT"]
    A --> AU["DCP-OUT"]
    A --> AV["DCP-OUT"]
    A --> AW["DCP-OUT"]
    A --> AX["DCP-OUT"]
    A --> AY["DCP-OUT"]
    A --> AZ["DCP-OUT"]
    A --> BA["DCP-OUT"]
    A --> BB["DCP-OUT"]
    A --> BC["DCP-OUT"]
    A --> BD["DCP-OUT"]
    A --> BE["DCP-OUT"]
    A --> BF["DCP-OUT"]
    A --> BG["DCP-OUT"]
    A --> BH["DCP-OUT"]
    A --> BI["DCP-OUT"]
    A --> BJ["DCP-OUT"]
    A --> BK["DCP-OUT"]
    A --> BL["DCP-OUT"]
    A --> BM["DCP-OUT"]
    A --> BN["DCP-OUT"]
    A --> BO["DCP-OUT"]
    A --> BP["DCP-OUT"]
    A --> BQ["DCP-OUT"]
    A --> BR["DCP-OUT"]
    A --> BS["DCP-OUT"]
    A --> BT["DCP-OUT"]
    A --> BU["DCP-OUT"]
    A --> BV["DCP-OUT"]
    A --> BW["DCP-OUT"]
    A --> BX["DCP-OUT"]
    A --> BY["DCP-OUT"]
    A --> BZ["DCP-OUT"]
    A --> CA["DCP-OUT"]
    A --> CB["DCP-OUT"]
    A --> CC["DCP-OUT"]
    A --> CD["DCP-OUT"]
    A --> CE["DCP-OUT"]
    A --> CF["DCP-OUT"]
    A --> CG["DCP-OUT"]
    A --> CH["DCP-OUT"]
    A --> CI["DCP-OUT"]
    A --> CJ["DCP-OUT"]
    A --> CK["DCP-OUT"]
    A --> CL["DCP-OUT"]
    A --> CM["DCP-OUT"]
    A --> CN["DCP-OUT"]
    A --> CO["DCP-OUT"]
    A --> CP["DCP-OUT"]
    A --> CR["DCP-OUT"]
    A --> CS["DCP-OUT"]
    A --> CT["DCP-OUT"]
    A --> CU["DCP-OUT"]
    A --> CV["DCP-OUT"]
    A --> CW["DCP-OUT"]
    A --> CX["DCP-OUT"]
    A --> CY["DCP-OUT"]
    A --> CZ["DCP-OUT"]

LEGENDA

PS : SENSOR DE PRESSÃO CT : SONDA TEMPERATURA EVAPORADOR

AT : SONDA DE TEMPERATURA DO AR

ET : SONDA DE TEMPERATURA DE DESCARGA

OT : SONDA DE TEMPERATURA SAÍDA DE ÁGUA

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 1

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

RepDesignação RefHP5171DT3HP5211DT3HP5251DT3HP5301DT3
1Motor do ventiladorHWX20000330381n/a
HWX20000330402 n/an/an/a
2Tampa de proteção do motor HWX20000220320
3Painel superior ABSHWX80900736n/an/a
HWX80900737 n/an/a
HWX80900718 n/an/an/a
4Proteção lateral direitaHWX80704158n/an/a
HWX80705113 n/an/a
HWX80705110 n/an/an/a
5/ / / / / /
6Placa de proteçãoHWX32012210724n/an/a
HWX32002210071 n/an/a
HWX32004210137 n/an/an/a
7Medição da pressão 90 mm 1/2"HWX20000140153
8Regulador electrónicoHWX20000140451n/an/a
HWX20000140449 n/an/an/a
HWX20000140442 n/an/an/a
HWX20000140401 n/an/an/a
9Filtro ∅12.9-∅12.9 (∅28)HWX20000140027
10Medição da pressão 95 mm 7/16"HWX20000140512
11Medição da pressão 40 mm 1/2"HWX20000140150
12Válvula de 4 viasHWX20041437n/an/a
HWX20011491 n/a
13Sensor de pressãoHWX20000360274
14Sonda temperatura Evapo/ar/água 5k-800 mmHWX20003202
15Sonda de descarga compressor 50k-600 mm HWX20000320145
16Detector de débito de águaHWX83000069
17/ / / / / /
18Painel dianteiroHWX80900738n/an/a
HWX80900739 n/an/a
HWX80900710 n/an/an/a
19Ecrã táctil coloridoHWX95005310612
20Alçapão de acesso eléctricoHWX20000220247
21Painel da caixa elétricaHWX80702647n/an/a
HWX80702644 n/an/a
HWX80702645 n/an/an/ax
22Pressóstato de alta pressão NC 3.2 MPa/4.4 MPaHWX20000360187
23Pressóstato de baixa pressão NO 0.15 MPa/0.05 MPaHWX20000360054
24/ / / / / /
25Condensador Titânio/PVCHWX32009120085n/an/a
HWX32002120023 n/an/an/a
HWX32016120012 n/an/an/a
HWX32016120011n/an/a
26/ / / / / /
27CompressorHWX80100046n/an/a
HWX80100069 n/an/a
HWX30101000006 n/an/an/a
28Proteção lateral esquerdaHWX32012210729n/an/a
HWX80705114 n/an/a
HWX80705111n/an/a
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

RepDesignação RefHP5171DT3HP5211DT3HP5251DT3HP5301DT3
29/ / / / /
30Conector quadrado roscado 50 mm HWX20031379
31Curva PVC ∅ 50 mm HWX20011359
32Suporte vertical direito/esquerdoHWX32000210086n/a n/a n/a
HWX80702346 n/an/a
HWX80702656 n/an/a n/a
33Evaporador de alhetaHWX32012120155n/a n/a n/a
HWX80600429 n/an/a n/a
HWX32003120028n/a n/an/a
HWX32004120013n/a n/a n/a
34Proteção traseiraHWX32012210730n/a n/a n/a
HWX80705115n/an/a
HWX80705112n/a n/a n/a
35/ / / / /
36Hélice ventilador ∅ 522 mmHWX20000270062n/a n/a n/a
Hélice ventilador ∅ 560 mmHWX35072195 n/an/a
Hélice ventilador ∅ 600 mmHWX20000270057n/an/an/a
37Grelha de proteção do ventiladorHWX32012210732n/a n/a n/a
HWX32003210142n/an/a
HWX80700160 n/an/a n/a
38Placa eletrónica mãeHWX72200033171Dn/a n/a n/a
HWX72200033211Dn/an/a n/a
HWX72200033251Dn/a n/an/a
HWX72200033301Dn/a n/a n/a
39Mapa Ventilador InverterHWX82300485
40Terminal de 4 ligaçõesHWX20003909
41Placa filtroHWX3020100007
42Relés K2HWX20000360297
43Terminal L-N-GNDHWX20000390223
44Terminal 4 pinosHWX20000390046
45Bobina reatânciaHWX82500009n/a n/a n/a
HWX20000370030n/a
46/ / / / /
47/ / / / /
48Mapa Ventilador compressorHWX82300149n/a n/a n/a
HWX82300019 n/a
49Resistência PTC 100 ΩHWX20000320113n/a
50/ / / / /
51/ / / / /
52Contator de potênciaHWX200003600619n/a
53Garrafa de líquidoHWX20000140579n/an/a
text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 3

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

RepDesignação Ref HP5211ET3 HP5251ET3 HP5301ET3
1 MMotor do ventiladorHWX20000330381n/a
HWX20000330402 n/an/a
2 TTampa de proteção do motor HWX20000220320√ √
3 PPainel superior ABSHWX80900737n/a
HWX80900718 n/an/a
4 PProteção lateral direitaHWX80705113n/a
HWX80705110 n/an/a
5 // / / /
6 PPlaca de proteçãoHWX32002210071n/a
HWX32004210137 n/an/a
7 MMedição da pressão 90 mm 1/2»HWX20000140153√ √
8 RRegulador electrónicoHWX20000140449n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/a
9 FFiltro ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Medição da pressão 95 mm 7/16"HWX20000140512√ √
11Medição da pressão 40 mm 1/2"HWX20000140150√ √
12Válvula de 4 viasHWX20011491√ √
13Sensor de pressãoHWX20000360274√ √
14Sonda temperatura Evapo/ar/água 5k-800 mmHWX20003202√ √
15Sonda de descarga compressor 50 k-600 mmHWX20000320145√ √
16Detector de débito de águaHWX83000069√ √
17/// / /
18Painel dianteiroHWX80900739n/a
HWX80900710 n/an/a
19Ecrã táctil coloridoHWX95005310612√ √
20Alçapão de acesso eléctricoHWX20000220247√ √
21Painel da caixa elétricaHWX80702644n/a
HWX80702645 n/an/a
22Pressóstato de alta pressão NC 3.2 MPa/4.4 MPaHWX20000360187√ √
23Pressóstato de baixa pressão NO 0.15 MPa/0.05 MPaHWX20000360054√ √
24/// / /
25Condensador Titânio/PVCHWX32002120023n/an/a
HWX32016120012 n/an/a
HWX32016120011n/an/a
26/// / /
27CompressorHWX80100069n/a
HWX30101000006 n/an/a
28Proteção lateral esquerdaHWX80705114n/a
HWX80705111n/an/a
29/// / /
30Conector quadrado roscado 50 mmHWX20031379√ √
31Curva PVC ∅ 50 mmHWX20011359√ √
32Suporte vertical direito/esquerdoHWX80702346n/a
HWX80702656 n/an/a
33Evaporador de alhetaHWX80600429n/an/a
HWX32003120028 n/an/a
HWX32004120013 n/an/a
34Proteção traseiraHWX80705115n/a
HWX80705112 n/an/a
35/// / /
text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 4

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46
natural_image Exterior view of a modern industrial water heater (no visible text or symbols)

HAYWARD SumHeat Fi - LEGENDA - 5

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

text_image ===== R S T N ⊕/÷ ⊗⊗⊗⊗⊗⊗

Allgemeine Stromversorgung 400V 3N\~50Hz

HAYWARD SumHeat Fi - LEGENDA - 6

text_image OUT2 ==== 1342 Potentialfreier Tetrahedron 7.4 Ares
text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - LEGENDA - 7

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C Ruhemodus deaktiviert
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 8

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

NrBeschreibung Ref.HP5171DT3HP5211DT3HP5251DT3HP5301DT3
1Motor Ventilator DCHWX20000330381
HWX20000330402 n/an/an/a
2Motor-Schutzhaube HWX20000220320
3Obere Wand ABSHWX80900736n/an/a
HWX80900737 n/a
HWX80900718 n/an/an/a
4Seitenabdeckung rechtsHWX80704158n/an/a
HWX80705113 n/a
HWX80705110 n/an/an/a
5/ / / // /
6SchutzplatteHWX32012210724n/an/a
HWX32002210071 n/a
HWX32004210137 n/an/an/a
7Druckanschluss 90 mm - 1/2"HWX20000140153
8Elektronischer SensorHWX20000140451n/an/a
HWX20000140449 n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/an/a
9Filter ∅12.9-∅12.9 (∅28)HWX20000140027
10Druckanschluss 95 mm - 7/16"HWX20000140512
11Druckanschluss 40 mm - 1/2"HWX20000140150
124-Wege-VentilHWX20041437n/an/a
HWX20011491 n/a
13DrucksensorHWX20000360274
14Temperatursensor Evapo/Luft/Wasser 5k-800 mmHWX20003202
15Abgabekompressorsensor 50k-600 mm HWX20000320145HWX83000069
16Sensor des WasserdurchsatzesHWX83000069
17/ / / // /
18Schild VorneHWX80900738n/an/a
HWX80900739 n/a
HWX80900710 n/an/an/a
19Farb-TouchscreenHWX95005310612
20Elektrische Zugangsklappe SchwarzHWX20000220247
21SchaltkastenHWX80702647n/an/a
HWX80702644 n/a
HWX80702645 n/an/an/ax
22Druckregler Hochdruck NC 3.2 MPa/4.4 MPa HWX20000360187
23Druckregler Niedrigdruck NO 0.15 MPa/0.05 MPaHWX20000360054
24/ / / // /
25Titan/PVC--KondensatorHWX32009120085n/an/a
HWX32002120023 n/an/a
HWX32016120012 n/an/a
HWX32016120011n/an/a
26/ / / // /
27KompressorHWX80100046n/an/a
HWX80100069 n/a
HWX30101000006 n/an/an/a
28Seitenabdeckung linksHWX32012210729n/an/a
HWX80705114 n/a
HWX80705111n/an/a
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 9

text_image A 48 47 38 42 39 43 44 45 49 40 41 46
text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 10

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

NrBeschreibung Ref. HP5211ET3 HP5251ET3 HP5301ET3
1 MMotor Ventilator DCHWX20000330381n/a
HWX20000330402 n/an/a
2 MMotor-Schutzhaube HWX20000220320√ √
3 CObere PlatteHWX80900737n/a
HWX80900718 n/a n/a
4Seitenabdeckung rechtsHWX80705113n/a
HWX80705110 n/a n/a
5 // / / /
6SchutzplatteHWX32002210071n/a
HWX32004210137 n/an/a
7Druckanschluss 90 mm - 1/2"HWX20000140153√ √
8Elektronischer SensorHWX20000140449n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/a
9Filter ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Druckanschluss 95 mm - 7/16"HWX20000140512√ √
11Druckanschluss 40 mm - 1/2"HWX20000140150√ √
124-Wege-VentilHWX20011491√ √
13DrucksensorHWX20000360274√ √
14Temperatursensor Evapo/Luft/Wasser 5k-800 mmHWX20003202√ √
15Abgabekompressorsensor 50k-600 mmHWX20000320145√ √
16Sensor des WasserdurchsatzesHWX83000069√ √
HWX83000012 n/a n/a
17/ / / / /
18Schild VorneHWX80900739n/a
HWX80900710 n/a n/a
19Farb-TouchscreenHWX95005310612√ √
20Elektrische Zugangsklappe SchwarzHWX20000220247√ √
21SchaltkastenHWX80702644n/a
HWX80702645 n/a n/a
22Druckregler Hochdruck NC 3.2 MPa/4.4 MPaHWX20000360187√ √
23Druckregler Niedrigdruck NO 0.15 MPa/0.05 MPaHWX20000360054√ √
24/ / / / /
25Titan/PVC--KondensatorHWX32002120023n/an/a
HWX32016120012 n/an/a
HWX32016120011n/a n/a
26/ / / / /
27KompressorHWX80100069n/a
HWX30101000006 n/an/a
28Seitenabdeckung linksHWX80705114n/a
HWX80705111n/a n/a
29/ / / / /
30Rechteckiger Steckverbinder mit Gewinde 50 mmHWX20031379√ √
31Kniestück PVC ∅ 50 mmHWX20011359√ √
32Vertikale Stütze rechts/linksHWX80702346n/a
HWX80702656 n/a n/a
33FlügelevaporatorHWX80600429n/an/a
HWX32003120028 n/an/a
HWX32004120013 n/an/a
34Schutzabdeckung hintenHWX80705115n/a
HWX80705112 n/a n/a
35/ / / / /
text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - LEGENDA - 11

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46
natural_image Exterior view of a modern industrial water heater (no visible text or symbols)

HAYWARD SumHeat Fi - LEGENDA - 12

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

natural_image Technical line drawing of a mechanical or electrical component with grid pattern and mounting brackets (no text or symbols)

HAYWARD SumHeat Fi - LEGENDA - 13

natural_image Technical line drawing of a mechanical component with labeled dimension A (no text or symbols beyond label)

HAYWARD SumHeat Fi - LEGENDA - 14

text_image C Ø B

Unit : mm

Merkteken\ModellHP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3HP5301ET3
A867,5 965965 1024 965 965 1024
B730 777777 920 777777 920
C780 797797 846 797797 846
610 650650 680 650650 680
D120 120120 150 120120 150
E204 204204 242 204204 242
F87 85 8586 85 85 86

3. INSTALLATIE EN AANSLUITING

3.1 Basisschema

HAYWARD SumHeat Fi - Basisschema - 1

flowchart
graph TD
    A["Water tank"] --> B["Kraan voor waterafvoer"]
    B --> C["Bypass klep"]
    C --> D["Filter"]
    D --> E["Water afvoer"]
    E --> F["Wet"]
    F --> G["Zwembad"]
    G --> H["Filterpomp"]
    H --> I["Water afvoer"]
    I --> J["Elektrolysetoestel (of andere behandeling)"]
    J --> K["Kraan voor waterefoer"]
    K --> B
text_image ===== R S T N ÷

Algemene voeding 400V 3N\~ 50Hz

HAYWARD SumHeat Fi - Basisschema - 2

text_image K2 === 1342 Droog contact 7 A max. drotatrical contact

In Modus "OFF" of "ON"

Handmatige deactivering
HAYWARD SumHeat Fi - In Modus "OFF" of "ON" - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C

HAYWARD SumHeat Fi - In Modus "OFF" of "ON" - 2

HAYWARD SumHeat Fi - In Modus "OFF" of "ON" - 3

text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - In Modus "OFF" of "ON" - 4

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8°C Stille modus gedeactiveerd
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - In Modus "OFF" of "ON" - 5

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3 - 1

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3 - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3 - 3

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46
natural_image Exterior view of a modern industrial water heater (no visible text or symbols)

HAYWARD SumHeat Fi - HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3 - 4

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

text_image = = ⊗ L N ⊕ ⊗ ⊗ ⊗
text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3 - 5

text_image To Power Supply generate 300-415V/3N·/ 50Hz Dry Contact Remote 7 A max. ON/OFF Fan Driver Board CN4 BLK 12V Y/G Controller WiFi Main Board CPS Driver Board DCP-N DCP-OUT DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N DCP-OUT DCP-N

LEGENDA

PS : SENSORE DI PRESSIONE

AT : SONDA TEMPERATURA ARIA

OT : SONDA TEMPERATURA ACQUA IN USCITA

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. APPENDICI (segue)

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. APPENDICI (segue)

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDICI (segue) - 1

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

Num.Designazione Rif.HP5171DT3HP5211DT3HP5251DT3HP5301DT3
1Motore ventola DCHWX20000330381
HWX20000330402 n/an/an/a
2Coperchio di protezione del motore HWX20000220320
3Pannello superiore ABSHWX80900736n/an/a
HWX80900737 n/an/a
HWX80900718 n/an/an/a
4Protezione laterale destraHWX80704158n/an/a
HWX80705113 n/an/a
HWX80705110 n/an/an/a
5///////
6Piastra protettivaHWX32012210724n/an/a
HWX32002210071 n/an/a
HWX32004210137 n/an/an/a
7Rilevamento Pressione 90 mm - 1/2"HWX20000140153
8Riduttore di pressione elettronicoHWX20000140451n/an/a
HWX20000140449 n/an/an/a
HWX20000140442 n/an/an/a
HWX20000140401 n/an/an/a
9Filtro ∅12.9-∅12.9 (∅28)HWX20000140027
10Rilevamento pressione 95 mm - 7/16"HWX20000140512
11Rilevamento pressione 40 mm - 1/2"HWX20000140150
12Valvola 4 vieHWX20041437n/an/a
HWX20011491 n/a
13Sensore di PressioneHWX20000360274
14Sonda temperatura evapo/aria/acqua 5k-800 mmHWX20003202
15Sonda scarico compressore 50k-600 mmHWX20000320145
16Rilevatore portata acquaHWX83000069
17/////
18Pannello anterioreHWX80900738n/an/a
HWX80900739 n/an/a
HWX80900710 n/an/an/a
19Touch screen a coloriHWX95005310612
20Portello d'accesso scatola elettricaHWX20000220247
21Quadro quadro elettricoHWX80702647n/an/a
HWX80702644 n/an/a
HWX80702645 n/an/an/ax
22Pressostato Alta pressione NC 3.2 MPa/4.4 MPaHWX20000360187
23Pressostato Bassa pressione NO 0.15 MPa/0.05 MPaHWX20000360054
24/////
25Condensatore Titanio/PVCHWX32009120085n/an/a
HWX32002120023 n/an/an/a
HWX32016120012 n/an/an/a
HWX32016120011n/an/a
26/////
27CompressoreHWX80100046n/an/a
HWX80100069 n/an/a
HWX30101000006 n/an/an/a
28Protezione laterale sinistraHWX32012210729n/an/a
HWX80705114 n/an/a
HWX80705111n/an/a

6. APPENDICI (segue)

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HAYWARD SumHeat Fi - APPENDICI (segue) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDICI (segue) - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

Num.Designazione Rif.HP5171DT3HP5211DT3HP5251DT3HP5301DT3
29/ / / / /
30Connettore quadrato filettato 50 mm HWX20031379
31Gomito di PVC ∅ 50 mm HWX20011359
32Supporto verticale destro/sinistroHWX32000210086n/a n/a n/a
HWX80702346 n/an/a
HWX80702656 n/an/a n/a
33Evaporatore a piastreHWX32012120155n/a n/a n/a
HWX80600429 n/an/a n/a
HWX32003120028 n/a n/an/a
HWX32004120013 n/a n/a n/a
34Protection arrièreHWX32012210730n/a n/a n/a
HWX80705115n/an/a
HWX80705112n/a n/a n/a
35/ / / / /
36Elica ventilatore ∅ 522 mmHWX20000270062n/a n/a n/a
Elica ventilatore ∅ 560 mmHWX35072195 n/an/a
Elica ventilatore ∅ 600 mmHWX20000270057 n/a n/a n/a
37Griglia di protezione ventilatoreHWX32012210732n/a n/a n/a
HWX32003210142 n/an/a
HWX80700160 n/an/a n/a
38Scheda madre elettronicaHWX72200033171Dn/a n/a n/a
HWX72200033211Dn/an/a n/a
HWX72200033251Dn/a n/an/a
HWX72200033301Dn/a n/a n/a
39Scheda Inverter ventolaHWX82300485
40Morsettiera 4 connessioniHWX20003909
41Scheda filtroHWX3020100007
42Relè K2HWX20000360297
43Morsettiera L-N-GNDHWX20000390223
44Morsettiera 4 poliHWX20000390046
45Bobina di reattanzaHWX82500009n/a n/a n/a
HWX20000370030 n/a
46/ / / / /
47/ / / / /
48Scheda Inverter compressoreHWX82300149n/a n/a n/a
HWX82300019 n/a
49Resistenza PTC 100 Ω HWX20000320113n/a
50/ / / / /
51/ / / / /
52Contattore di potenzaHWX200003600619n/a
53Bombola di liquidoHWX20000140579 n/an/a

6. APPENDICI (segue)

HP5211ET3 / HP5251ET3 / HP5301ET3
HAYWARD SumHeat Fi - APPENDICI (segue) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDICI (segue) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

Num.Designazione Rif. HP5211ET3 HP5251ET3 HP5301ET3
1Motore ventola DCHWX20000330381n/a
HWX20000330402 n/an/a
2Coperchio di protezione del motore HWX20000220320√ √
3Pannello anteriore superioreHWX80900737n/a
HWX80900718 n/a n/a
4Protezione laterale destraHWX80705113n/a
HWX80705110 n/a n/a
5/// /
6Piastra protettivaHWX32002210071n/a
HWX32004210137 n/an/a
7Rilevamento Pressione 90 mm - 1/2"HWX20000140153√ √
8Riduttore di pressione elettronicoHWX20000140449n/an/a
HWX20000140442 n/an/a
HWX20000140401 n/an/a
9Filtro ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Rilevamento Pressione 95 mm - 7/16"HWX20000140512√ √
11Rilevamento Pressione 40 mm - 1/2"HWX20000140150√ √
12Valvola 4 vieHWX20011491√ √
13Sensore di PressioneHWX20000360274√ √
14Sonda temperatura evapo/aria/acqua 5k-800 mmHWX20003202√ √
15Sonde de refoulement compresseur 50k-600 mmHWX20000320145√ √
16Rilevatore portata acquaHWX83000069√ √
17/// /
18Pannello anterioreHWX80900739n/a
HWX80900710 n/a n/a
19Touch screen a coloriHWX95005310612√ √
20Portello d'accesso scatola elettricaHWX20000220247√ √
21Quadro quadro elettricoHWX80702644n/a
HWX80702645 n/a n/a
22Pressostato Alta pressione NC 3.2 MPa/4.4 MPaHWX20000360187√ √
23Pressostato Bassa pressione NO 0.15 MPa/0.05 MPaHWX20000360054√ √
24/// /
25Condensatore Titanio/PVCHWX32002120023n/an/a
HWX32016120012 n/an/a
HWX32016120011n/a n/a
26/// /
27CompressoreHWX80100069n/a
HWX30101000006 n/an/a
28Protezione laterale sinistraHWX80705114n/a
HWX80705111n/a n/a
29/// /
30Connettore quadrato filettato 50 mmHWX20031379√ √
31Gomito di PVC ∅ 50 mmHWX20011359√ √
32Supporto verticale destro/sinistroHWX80702346n/a
HWX80702656 n/a n/a
33Evaporatore a piastreHWX80600429n/an/a
HWX32003120028 n/an/a
HWX32004120013 n/an/a
34Protezione posterioreHWX80705115n/a
HWX80705112 n/a n/a
35/// /

6. APPENDICI (segue)

HP5211ET3 / HP5251ET3 / HP5301ET3
HAYWARD SumHeat Fi - APPENDICI (segue) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - APPENDICI (segue) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

6. APPENDICI (segue)

HP5211ET3 / HP5251ET3 / HP5301ET3

Num.Designazione Rif. HP5211ET3 HP5251ET3 HP5301ET3
36Elica ventilatore ∅ 560 mm HWX35072195n/a
Elica ventilatore ∅ 600 mm HWX20000270057 n/an/a
37Griglia di protezione ventilatoreHWX32003210142n/a
HWX80700160 n/a n/a
38Carte électronique MèreHWX72200033211En/a n/a
HWX72200033251E n/an/a
HWX72200033301E n/an/a
39Scheda Inverter ventola HWX82300485√ √
40Morsettiera 4 connessioniHWX20003909√ √
41Scheda filtroHWX82300074√ √
42Relè K2HWX20000360297√ √
43Morsettiera R-R-T-N-GNDHWX20000390180√ √
44Morsettiera 4 poliHWX20000390046√ √
45Bobina di reattanzaHWX20000370030√ √
46 /////
47/////
48Scheda Inverter compressoreHWX82300112n/a
HWX302010000012n/a n/a
49Scheda condensatoreHWX302010000014√ √
50Morsettiera L-N-GND reattanzaHWX20000390223√ √
51Bombola di liquidoHWX20000140579 n/a

6. APPENDICI (segue)

natural_image Exterior view of a modern industrial water heater (no visible text or symbols)

HAYWARD SumHeat Fi - APPENDICI (segue) - 1

text_image R32

HP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3

5. VEDLIKEHOLD OG VINTERKLARGJ∅RING 25

1. GENERELLE FORHOLDSREGLER (fortsetter)

Dette produktet inneholder kjølegassen R32

HAYWARD SumHeat Fi - Dette produktet inneholder kjølegassen R32 - 1

Dette apparatet inneholder R32.

(1) Globalt oppvarmingspotensial

1. GENERELLE FORHOLDSREGLER (fortsetter)

Betingelser for installering

1. GENERELLE FORHOLDSREGLER (fortsetter)

2. SPESIFIKASJONER (fortsetter)

ModellerSUMHEAT Full InverterHP5211ET3 HP5251ET3 HP5301ET3
Tilførselsspenning V / Ph / Hz380 V - 415 V ~ / 3 ph / 50 Hz
Kuldemedium Type HFC - R32 - (CH2F2)
Sikkerhetsgruppe Type A2L
Last kg 1,35 1,65 1,8
Masse i teqCO2teqCO20,91 1,11 1,22
Hyppighet for lekkasjekontroll / Er ikke påkrevet, men årlig kontroll anbefales
Oppvarmingskapasitet Min--Maks (a) kW 6,24 --22,10 6,02 -- 24,50 8,12 -- 31,20
Absorbert elektrisk effekt Min--Maks (a)kW0,46 -- 3,070,41 -- 3,670,59 -- 5,08
Nominell strømverdi Min--Maks (a)A1,00 -- 5,100,90 -- 5,811,21 -- 8,23
COP Maks--Min (a)/13,70 -- 7,19 14,53 -- 6,68 13,72 -- 6,14
Oppvarmingskapasitet Min--Maks (b) kW 4,84 --16,92 4,55 -- 19,55 5,52 -- 23,05
Absorbert elektrisk effekt Min--Maks (b)kW0,68 -- 3,100,63 -- 3,680,79 -- 4,94
COP Maks--Min (b)/7,10 -- 5,467,18 -- 6,426,98 -- 4,66
Maksimum strømverdiA8,7 11,7 13,3
SikringsstørrelseaM101216
Effektbryter Kurve DD101216
StartstrømA< CMS
Hydraulisk tilkoplingmm50 mm
Nominell vannstrøm (a)m3/h9,1 10,5 12,6
Fall i vantrykk (maks.)kPa171546
Kompressor/PanasonicPanasonicMitsubishi
Type/Dobbeltroterende
Antall/1
Svingningsmotstand ved 20°COhm0,880,880,49
Vifte/Axial
Antall1
Diametermm560 560 600
Antall rotor/3
Motor/DC-omformer
Antall/1
RotasjonshastighetOmdr/min500 -- 700600 -- 750500 -- 700
Hastighet i Silent ModeOmdr/min500400400
Lydtrykknivå ved 1 mdB(A)56,4 -- 6155,2 -- 59,755,6 -- 59,3
Lydtrykknivå ved 10 mdB(A)40,9 -- 45,440,9 -- 44,236,1 -- 42,2
Enhetens dimensjoner, netto (L-I-H)mm797 x 777 x 965846 x 920 x 1024
Vektkg101 101 123

2. SPESIFIKASJONER (fortsetter)

2.2 Driftsområde

2. SPESIFIKASJONER (fortsetter)

2.3 Dimensjoner

Modeller:

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HP5211ET3 / HP5251ET3 / HP5301ET3

HAYWARD SumHeat Fi - Dimensjoner - 1

natural_image Technical line drawing of a mechanical or electrical component with grid pattern and mounting bracket (no text or symbols)

HAYWARD SumHeat Fi - Dimensjoner - 2

natural_image Technical line drawing of a mechanical component with labeled dimension A (no text or symbols beyond the label)

HAYWARD SumHeat Fi - Dimensjoner - 3

text_image C Ø B

Enhet : mm

Model NummerHP5171DT3 HP5211DT3 HP5251DT3 HP5301DT3 HP5211ET3 HP5251ET3 HP5301ET3
A867,5 965965 1024 965965 1024
B730 777777 920 777777 920
C780 797797 846 797797 846
610 650650 680 650650 680
D120 120120 150 120120 150
E204 204204 242 204204 242
F87 85 8586 85 85 86

3. INSTALLERING OG TILKOBLING

3.1 Skjematisk diagram

HAYWARD SumHeat Fi - Skjematisk diagram - 1

flowchart
graph TD
    A["Reactor with Ventil til vannutløp"] --> B["Ventil til vannutløp"]
    B --> C["Bypass ventil"]
    C --> D["Filter"]
    D --> E["Basseng pumpe"]
    E --> F["Return av vann"]
    F --> G["Klordoseringscelle (eller annen behandling)"]
    G --> H["Ventil til vanninnløp"]
    H --> I["Bypass ventil"]
    I --> A

3. INSTALLERING OG TILKOBLING (fortsetter)

3.2 Varmepumpe

HAYWARD SumHeat Fi - Varmepumpe - 1

3. INSTALLERING OG TILKOBLING (fortsetter)

3.3 Vanntilkobling

3. INSTALLERING OG TILKOBLING (fortsetter)

3.4 Elektrisk tilkobling

HAYWARD SumHeat Fi - Elektrisk tilkobling - 1

3. INSTALLERING OG TILKOBLING (fortsetter)

HAYWARD SumHeat Fi - INSTALLERING OG TILKOBLING (fortsetter) - 1

text_image ===== R S T N ÷

3. INSTALLERING OG TILKOBLING (fortsetter)

3. INSTALLERING OG TILKOBLING (fortsetter)

3. INSTALLERING OG TILKOBLING (fortsetter)

4. BRUKERGRENSESNITT (fortsetter)

OFF-modus

Når varmepumpen er i standby (OFF-modus) knappen ledtonet.

ON-modus

Når varmepumpen er i drift eller under innstilling (ON-modus) knappen lyser grønt.

HAYWARD SumHeat Fi - ON-modus - 1

4. BRUKERGRENSESNITT (fortsetter)

HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 1

HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 2

Blå marking = Aktivert

Nedtonet = Deaktivert

HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 3

4. BRUKERGRENSESNITT (fortsetter)

4. BRUKERGRENSESNITT (fortsetter)

4. BRUKERGRENSESNITT (fortsetter)

4. BRUKERGRENSESNITT (fortsetter)

Manuell deaktivering
HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 1

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C

HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 2

HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 3

text_image 01-01 2017 10:15:00 26.5°C IN SET 26.5°C OUT 28.8°C

HAYWARD SumHeat Fi - BRUKERGRENSESNITT (fortsetter) - 4

text_image 01-01 2017 10:15:00 26.5°C IN 26.5 °C OUT 28.8 °C Silence-modus er deaktivert

4. BRUKERGRENSESNITT (fortsetter)

6. VEDLEGG (fortsetter)

HP5211DT3 / HP5251DT3
HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image Hovedstrahnforsyning 220-240V~J50Hz ACL-out EMI ACN-out KCN-in RL BLU N Y/G RED L K2 1 2 3 4 5 6 7 8 HP OHP Controller WiFi Main Board CN9 CN11 A13 A12 A10 A8 A6 A4 A2 A13 CN13 CN814 CN817 CN815 CN804 CN806 CN867 KM1 K2 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V 4V

MERKNADER

PS : TRYKKSENSOR EEV : ELEKTRONISK EKSPANSJONSVENTIL

AT : SENSOR FOR LUFTTEMPERATUR

OT : TEMPERATURSENSOR TIL VANNUTL∅P

SUT : SENSOR FOR SUGETEMPERATUR

LP : LAVTRYKKSBRYTER

FS : VANNSENSOR

IT : TEMPERATURSENSOR TIL VANNINNL∅P

CT : SENSOR FOR FORDAMPET TEMPERATUR

ET : TEMPERATURSENSOR FOR UTLADNING

FM1 : VIFTEMOTOR DC

HP : H∅YTRYKKSBRYTER

OHP : VARMEBESKYTTELSE

4V : 4-VEIS VENTIL

K2 : POTENSIALFRI KONTAKT, MAKS. 7A

PTC : TERMISTOR

KM1: KOMPRESSORKONTAKTOR

COMP : KOMPRESSOR

6. VEDLEGG (fortsetter)

HP5301DT3
HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image ACL-001 ACN-OUT2 ACL-N YIG RED L BLU N Hoveystromforsyning 220-240V~J50Hz Dry Contact A max Remote DN/OFF connection K2 T 1 2 3 4 Controller BLK OND VE 486B WHT 485A- RED 12V BLK OND WHT 485A- RED 12V WiFi N AC-N1 N OUT5 OUT4 OUT3 OUT2 RLY1 CN9 CN11 12V CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN10 CN13 A13 A12 A11 A4A6A2A10 A1A3A5A7A9 Pressure sensor (PS) LED K WHT AT OT SUT LP ET CT IT HP FS CN8 CN8M CN8B8 CN8C7 CN8C7/ACN ACL KM1 L4 L3 PTC KM1 L2 L1 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2 N1 N0 N3 N2

MERKNADER

PS : TRYKKSENSOR

AT : SENSOR FOR LUFTTEMPERATUR

OT : TEMPERATURSENSOR TIL VANNUTL∅P

SUT : SENSOR FOR SUGETEMPERATUR

LP : LAVTRYKKSBRYTER

FS : VANNSENSOR

HP : H∅YTRYKKSBRYTER

IT : TEMPERATURSENSOR TIL VANNINNL∅P

CT : SENSOR FOR FORDAMPET TEMPERATUR

ET : TEMPERATURSENSOR FOR UTLADNING

EEV : ELEKTRONISK EKSPANSJONSVENTIL

FM1 : VIFTEMOTOR DC

4V : 4-VEIS VENTIL

K2 : POTENSIALFRI KONTAKT, MAKS. 7 A

PTC : TERMISTOR

KM1 : KOMPRESSORKONTAKTOR

COMP: KOMPRESSOR

6. VEDLEGG (fortsetter)

HP5211ET3 / HP5251ET3
HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image Hovedstromforsyning 380-415V/3N-/50Hz R RED S BLK T WHT N BLU Y/G K2 1 2 3 4 Dry Contact Remote 7 A max. ON/OFF 5 6 7 8 HP OH ON OHP R EVI A B C N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N FAN DRIVER BOARD CN1 CN4 GND BLK +55BT TCL +35A1WHTT 12V Y/G-FM EEV CN9 YEL-458B VEL-458B VEL-458B VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VEL-458A VFL-CNDI Controler WiFi Main Board CN11 A13 A12 CT IT FS CN8 CN13 CN13 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN2 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN8 CN62 B C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D C N D U V W COMP Pressure sensor (PS) AT OT SUT LP

MERKNADER

PS : TRYKKSENSOR

AT : SENSOR FOR LUFTTEMPERATUR

OT : TEMPERATURSENSOR TIL VANNUTL∅P

SUT : SENSOR FOR SUGETEMPERATUR

LP : LAVTRYKKSBRYTER

FS : VANNSENSOR

IT : TEMPERATURSENSOR TIL VANNINNL∅P

CT : SENSOR FOR FORDAMPET TEMPERATUR

ET : TEMPERATURSENSOR FOR UTLADNING

EEV : ELEKTRONISK EKSPANSJONSVENTIL

FM1 : VIFTEMOTOR DC

HP : H∅YTRYKKSBRYTER

OHP : VARMEBESKYTTELSE

4V : 4-VEIS VENTIL

K2 : POTENSIALFRI KONTAKT, MAKS. 7A

COMP: KOMPRESSOR

6. VEDLEGG (fortsetter)

HP5301ET3
HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image Hovedstromforsyning 380-415V/3N·v./50Hz Dry Contact Remote 7 A max. ON/OFF Fan Driver Board CN4 BLX Y/G Controller WiFi Main Board CPS Driver Board DCP-R DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-OUT DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-1 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-2 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-3 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-4 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-5 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6 DCP-6

MERKNADER

PS : TRYKKSENSOR

AT : SENSOR FOR LUFTTEMPERATUR

OT : TEMPERATURSENSOR TIL VANNUTL∅P

SUT : SENSOR FOR SUGETEMPERATUR

LP : LAVTRYKKSBRYTER

FS : VANNSENSOR

HP : H∅YTRYKKSBRYTER

IT : TEMPERATURSENSOR TIL VANNINNL∅P

CT : SENSOR FOR FORDAMPET TEMPERATUR

ET : TEMPERATURSENSOR FOR UTLADNING

EEV : ELEKTRONISK EKSPANSJONSVENTIL

FM1 : VIFTEMOTOR DC

4V : 4-VEIS VENTIL

K2 : POTENSIALFRI KONTAKT, MAKS. 7 A

COMP : KOMPRESSOR

6. VEDLEGG (fortsetter)

6.2 Kobling med prioritet på enfaset varmepumpe

HAYWARD SumHeat Fi - Kobling med prioritet på enfaset varmepumpe - 1

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. VEDLEGG (fortsetter)

6.3 Kobling med prioritet på trefaset varmepumpe

HAYWARD SumHeat Fi - Kobling med prioritet på trefaset varmepumpe - 1

natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)

6. VEDLEGG (fortsetter)

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

Nr.Betegnelse Ref.HP5171DT3HP5211DT3HP5251DT3HP5301DT3
1Viftemotor DCHWX20000330381Gjelder ikke
HWX20000330402Gjelder ikkeGjelder ikkeGjelder ikke
2Deksel for motoren HWX20000220320
3∅vre deksel ABSHWX80900736Gjelder ikkeGjelder ikkeGjelder ikke
HWX80900737 Gjelder ikkeGjelder ikke
HWX80900718 Gjelder ikke Gjelder ikke
4Deksel for høyre sideHWX80704158Gjelder ikkeGjelder ikkeGjelder ikke
HWX80705113 Gjelder ikkeGjelder ikke
HWX80705110 Gjelder ikke Gjelder ikke
5/// / / /
6BeskyttelsesplateHWX32012210724Gjelder ikkeGjelder ikkeGjelder ikke
HWX32002210071 Gjelder ikkeGjelder ikke
HWX32004210137 Gjelder ikke Gjelder ikke
7Trykktilkobling 90 mm 1/2"HWX20000140153
8Elektronisk ekspansjonsventilHWX20000140451Gjelder ikkeGjelder ikkeGjelder ikke
HWX20000140449 Gjelder ikkeGjelder ikkeGjelder ikke
HWX20000140442 Gjelder ikke Gjelder ikkeGjelder ikke
HWX20000140401 Gjelder ikke Gjelder ikke
9Filter ∅12.9-∅12.9 (∅28)HWX20000140027
10Trykktilkobling 95 mm 7/16"HWX20000140512
11Trykktilkobling 40 mm 1/2"HWX20000140150
124-veisventilHWX20041437xGjelder ikkeGjelder ikkeGjelder ikke
HWX20011491 Gjelder ikke
13TrykksensorHWX20000360274
14Fordamper/luft/vann-temperatursensor 5k 800mmHWX20003202
15Kompressorutladningssonde 50k-600 mmHWX20000320145
16Sensor for vannstrømningHWX83000069
17/// / / /
18Fremre panelHWX80900738Gjelder ikkeGjelder ikkeGjelder ikke
HWX80900739 Gjelder ikkeGjelder ikke
HWX80900710 Gjelder ikke Gjelder ikke
19Berøringsskjerm med fargerHWX95005310612
20Trappe elektrisk tilgangHWX20000220247
21Elektrisk boks panelHWX80702647Gjelder ikkeGjelder ikkeGjelder ikke
HWX80702644 Gjelder ikkeGjelder ikke
HWX80702645 Gjelder ikke Gjelder ikke
22Høytrykkspressostat NC 3.2 MPa/4.4 MPaHWX20000360187
23Strømningsbegrenser NO 0.15 MPa/0.05 MPaHWX20000360054
24/// / / /
25Kondensator Titanium/PVCHWX32009120085Gjelder ikkeGjelder ikkeGjelder ikke
HWX32002120023 Gjelder ikkeGjelder ikkeGjelder ikke
HWX32016120012 Gjelder ikke Gjelder ikkeGjelder ikke
HWX32016120011 Gjelder ikke
26/// / / /
27KompressorHWX80100046Gjelder ikkeGjelder ikkeGjelder ikke
HWX80100069 Gjelder ikkeGjelder ikke
HWX30101000006 Gjelder ikke Gjelder ikke
28Deksel for venstre sideHWX32012210729Gjelder ikkeGjelder ikkeGjelder ikke
HWX80705114 Gjelder ikkeGjelder ikke
HWX80705111Gjelder ikkeGjelder ikkeGjelder ikke

6. VEDLEGG (fortsetter)

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46

HP5171DT3 / HP5211DT3 / HP5251DT3 / HP5301DT3

Nr.Betegnelse Ref.HP5171DT3HP5211DT3HP5251DT3HP5301DT3
29 // / / / /
30Firkantet koblingsstykke med gjenge 50 mm HWX20031379
31PVC bøy ∅ 50 mm HWX20011359
32Vertikalt støtte høyre/venstreHWX32000210086Gjelder ikkeGjelder ikkeGjelder ikke
HWX80702346 Gjelder ikkeGjelder ikke
HWX80702656 Gjelder ikke Gjelder ikke
33Vinget fordamperHWX32012120155Gjelder ikkeGjelder ikkeGjelder ikke
HWX80600429 Gjelder ikkeGjelder ikkeGjelder ikke
HWX32003120028 Gjelder ikkeGjelder ikke
HWX32004120013 Gjelder ikke
34Deksel for baksidenHWX32012210730Gjelder ikkeGjelder ikkeGjelder ikke
HWX80705115Gjelder ikkeGjelder ikke
HWX80705112Gjelder ikkeGjelder ikkeGjelder ikke
35 // / / / /
36Vifteproprell ∅ 522 mmHWX20000270062Gjelder ikkeGjelder ikkeGjelder ikke
Vifteproprell ∅ 560 mmHWX35072195 Gjelder ikkeGjelder ikke
Vifteproprell ∅ 600 mmHWX20000270057Gjelder ikkeGjelder ikkeGjelder ikke
37Beskyttelsesgitter for viftenHWX32012210732Gjelder ikkeGjelder ikkeGjelder ikke
HWX32003210142 Gjelder ikkeGjelder ikke
HWX80700160 Gjelder ikke Gjelder ikke
38Elektronisk hovedkortHWX72200033171DGjelder ikkeGjelder ikkeGjelder ikke
HWX72200033211DGjelder ikkeGjelder ikkeGjelder ikke
HWX72200033251DGjelder ikkeGjelder ikkeGjelder ikke
HWX72200033301DGjelder ikkeGjelder ikkeGjelder ikke
39Kort for Inverter vifteHWX82300485
40Terminal 4 tilkoplingerHWX20003909
41FilterkortHWX3020100007
42Relé K2HWX20000360297
43Terminal L-N-GNDHWX20000390223
444-polet klemmeHWX20000390046
45Spole reaktansHWX82500009Gjelder ikkeGjelder ikkeGjelder ikke
HWX20000370030 Gjelder ikke
46 // / / / /
47 // / / / /
48Kort for Inverter kompressorHWX82300149Gjelder ikkeGjelder ikkeGjelder ikke
HWX82300019 Gjelder ikke
49PTC-motstand 100 ΩHWX20000320113Gjelder ikke
50 // / / / /
51 // / / / /
52KontaktorHWX200003600619 Gjelder ikke
53Beholder med væskeHWX20000140579Gjelder ikkeGjelder ikke

6. VEDLEGG (fortsetter)

HP5211ET3 / HP5251ET3 / HP5301ET3

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

HP5211ET3 / HP5251ET3 / HP5301ET3

Nr.Betegnelse Ref. HP5211ET3 HP5251ET3 HP5301ET3
1Viftemotor DCHWX20000330381Gjelder ikke
HWX20000330402 Gjelder ikke Gjelder ikke
2Deksel for motoren HWX20000220320√ √
3∅vre panelHWX80900737Gjelder ikke
HWX80900718 Gjelder ikke Gjelder ikke
4Deksel for høyre sideHWX80705113Gjelder ikke
HWX80705110 Gjelder ikke Gjelder ikke
5/ / / //
6BeskyttelsesplateHWX32002210071Gjelder ikke
HWX32004210137 Gjelder ikke Gjelder ikke
7Trykktilkobling 90 mm - 1/2"HWX20000140153√ √
8Elektronisk starterHWX20000140449Gjelder ikkeGjelder ikke
HWX20000140442 Gjelder ikkeGjelder ikke
HWX20000140401 Gjelder ikke Gjelder ikke
9Filter ∅12.9-∅12.9 (∅28)HWX20000140027√ √
10Trykktilkobling 95 mm - 7/16"HWX20000140512√ √
11Trykktilkobling 40 mm - 1/2"HWX20000140150√ √
124-veisventilHWX20011491√ √
13TrykksensorsHWX20000360274√ √
14Fordamper/luft/vann-temperatursensor 5k 800mmHWX20003202√ √
15Kompressorutladningssonde 50k-600 mm HWX20000320145√ √
16Sensor for vannstrømningHWX83000069√ √
17// / //
18Fremre panelHWX80900739Gjelder ikke
HWX80900710 Gjelder ikke Gjelder ikke
19Berøringsskjerm med fargerHWX95005310612√ √
20Trappe elektrisk tilgangHWX20000220247√ √
21Elektrisk boks panelHWX80702644Gjelder ikke
HWX80702645 Gjelder ikke Gjelder ikke
22Høytrykkspressostat NC 3.2 MPa/4.4 MPaHWX20000360187√ √
23Strømningsbegrenser NO 0.15 MPa/0.05 MPa HWX20000360054√ √
24// / //
25Kondensator Titanium/PVCHWX32002120023Gjelder ikkeGjelder ikke
HWX32016120012 Gjelder ikkeGjelder ikke
HWX32016120011Gjelder ikke Gjelder ikke
26// / //
27KompressorHWX80100069Gjelder ikke
HWX30101000006 Gjelder ikke Gjelder ikke
28Deksel for venstre sideHWX80705114Gjelder ikke
HWX80705111Gjelder ikke Gjelder ikke
29// / //
30Firkantet koblingsstykke med gjenge 50 mmHWX20031379√ √
31PVC bøy ∅ 50 mmHWX20011359√ √
32Vertikalt støtte høyre/venstreHWX80702346Gjelder ikke
HWX80702656 Gjelder ikke Gjelder ikke
33Vinget fordamperHWX80600429Gjelder ikkeGjelder ikke
HWX32003120028 Gjelder ikkeGjelder ikke
HWX32004120013 Gjelder ikke Gjelder ikke
34Deksel for baksidenHWX80705115Gjelder ikke
HWX80705112 Gjelder ikke Gjelder ikke
35// / //

6. VEDLEGG (fortsetter)

HP5211ET3 / HP5251ET3 / HP5301ET3

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 1

text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - VEDLEGG (fortsetter) - 2

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46

6. VEDLEGG (fortsetter)

HP5211ET3 / HP5251ET3 / HP5301ET3

Nr.Betegnelse Ref. HP5211ET3 HP5251ET3 HP5301ET3
36Vifteproprell ∅ 560 mm HWX35072195Gjelder ikke
Vifteproprell ∅ 600 mm HWX20000270057 Gjelderikke Gjelder ikke
37Beskyttelsesgitter for viftenHWX32003210142Gjelder ikke
HWX80700160 Gjelder ikke Gjelder ikke
38Elektronisk hovedkortHWX72200033211EGjelder ikke Gjelder ikke
HWX72200033251E Gjelder ikkeGjelder ikke
HWX72200033301E Gjelder ikke Gjelder ikke
39Kort for Inverter vifteHWX82300485√√
40Terminal 4 tilkoplingerHWX20003909√√
41FilterkortHWX82300074√√
42Relé K2HWX20000360297√√
43Terminal R-R-T-N-GNDHWX20000390180√√
444-polet klemmeHWX20000390046√√
45Spole reaktansHWX20000370030√√
46 /////
47/////
48Kort for Inverter kompressorHWX82300112Gjelder ikke
HWX302010000012Gjelder ikke Gjelder ikke
49KondensatorkortHWX302010000014√√
50Terminal L-N-GND reaktansHWX20000390223√√
51Beholder med væske HWX20000140579 Gjelder ikke

6. VEDLEGG (fortsetter)

6. VEDLEGG (fortsetter)

Feil Feilkoder Beskrivelse Løsning
Feil i temperatursensor til vanninnløpP01Sensoren er åpen eller det er en kortslutning.Sjekk den blå AIN6 kontakten på kortet, og mål motstanden på sonden. Hvis den er mindre enn 100 Ω eller større enn 500 kΩ, må du skifte den ut.
Feil i temperatursensor til vannutløpP02Sjekk den røde AIN7 kontakten på kortet, og mål motstanden på sonden. Hvis den er mindre enn 100 Ω eller større enn 500 kΩ, må du skifte den ut.
Feil på avrimingssensor P04Sjekk AIN9 kontakten på kortet, og mål motstanden på sonden. Hvis den er mindre enn 100 Ω eller større enn 500 kΩ, må du skifte den ut.
Feil på sensor til utendørstemperaturP05Sjekk den gule AIN8 kontakten på kortet, og mål motstanden på sonden. Hvis den er mindre enn 100 Ω eller større enn 500 kΩ, må du skifte den ut.
Feil på kompressor aspirationssensorP07Sjekk den grønne AIN5 kontakten på kortet, og mål motstanden på sonden. Hvis den er mindre enn 100 Ω eller større enn 500 kΩ, må du skifte den ut.
Feil motstand 6.8 kΩ P09Sjekk AIN11 kontakten på kortet og mål motstanden, skift ut hvis Motstanden < 6.8 kΩ
Feil på kompressorutladningsføler P081Sjekk den svarte AIN12 kontakten på kortet, og mål motstanden på sonden. Hvis den er mindre enn 100 Ω eller større enn 500 kΩ, må du skifte den ut.
For høy utladetemperatur P082 Utladetemperatur > 120°CMål utladetemperaturen ved utgangen av kompressoren, hvis den målte temperaturen < 120°C, må sonden skiftes ut.Ta en test for ikke-kondensbare gasser
HøytrykksbeskyttelseE01Sensoren er åpen eller det er en kortslutning.Sjekk CN30/HP koblingen på kortet eller bytt sensor
Sjekk vannmengden
Sjekk detektoren for vannmengde
Sjekk at ventilene er åpne
Sjekk by-passventilen
Sjekk at fordamperen ikke er tett
Vanntemperaturen er for høy
Kondensproblemer etter vedlikeholdsarbeid, tøm hele kjølekretsen
For stor væskemengde, tøm noe væske ut i en flaske
LavtrykksbeskyttelseE02Sensoren er åpen eller det er en kortslutning.Sjekk AI/DI03 koblingen på kortet eller bytt sensor
Stor lekkasje med kjølevæske, foreta en lekkasjetest med detektor
Luftmengden er for lav, sjekk hastigheten til vifterotasjonen
Sjekk at fordamperen ikke er tett, rengjør den på overflaten

6. VEDLEGG (fortsetter)

6. VEDLEGG (fortsetter)

6.6 Lagringsbase

natural_image Exterior view of a modern office building (no signage)

HAYWARD SumHeat Fi - Lagringsbase - 1

text_image R32

HP5171DT3HP5211DT3HP5251DT3HP5301DT3HP5211ET3HP5251ET3HP5301ET3

text_image ===== R S T N ⊕ ⊗⊗⊗⊗⊗⊗
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
natural_image Technical line drawing of a mechanical device with internal components and an upward arrow indicator (no text or symbols)
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - Lagringsbase - 2

text_image A 48 47 38 42 39 43 44 45 49 40 41 46
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - Lagringsbase - 3

text_image A 48 47 38 42 39 43 44 45 49 40 41 46
text_image Exploded view diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - Lagringsbase - 4

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46
text_image Technical diagram of a mechanical assembly with numbered components and labeled parts

HAYWARD SumHeat Fi - Lagringsbase - 5

text_image A 48 47 45 50 38 42 49 41 40 39 44 43 46
natural_image Simple line drawing of a trash bin with crossed lines indicating no waste or restriction (no text or symbols)
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HAYWARD

Model : SumHeat Fi

Category : Pump