Baxi 90 F - Boiler

90 F - Boiler Baxi - Free user manual and instructions

Find the device manual for free 90 F Baxi in PDF.

📄 172 pages English EN 💬 AI Question
Notice Baxi 90 F - page 23

User questions about 90 F Baxi

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

L'email reste privé : il sert seulement à vous prévenir si quelqu'un répond à votre question.

No questions yet. Be the first to ask one.

Download the instructions for your Boiler in PDF format for free! Find your manual 90 F - Baxi and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. 90 F by Baxi.

USER MANUAL 90 F Baxi

PERICOLO ALTA TENSIONE

As constantly strives to improve its products, it reserves the right to modify the information contained in this document at any time and without prior notice. This document is issued purely for the sake information and should not be considered as a contract with third parties.

DESCRIPTION OF SYMBOLS

Baxi 90 F - DESCRIPTION OF SYMBOLS - 1

WARNING

Risk of damage to or malfunction of the appliance. Pay special attention to the warnings concerning danger to people.

Baxi 90 F - WARNING - 1

DANGER-HIGH VOLTAGE

Live components - electrocution hazard.

Baxi 90 F - DANGER-HIGH VOLTAGE - 1

IMPORTANT INFORMATION

Information to read with particular care as it is useful for the correct operation of the boiler.

1. INTRODUCTION

The boiler can independently manage up to three heating circuits by using external accessories such as room units, remote controls and external modules. The boiler electronics comprises a wide range of functions for personalising and managing various system types. To assure correct system operation, a number (from 1 to 3) must be assigned to each accessory in order to allow the boiler board to recognise it.

Baxi 90 F - INTRODUCTION - 1

To use the AVS75.391 accessory the remote control unit (available as an accessory) is required.

2.DESCRIPTION OF ACCESSORY

Using this accessory, the device is able to handle:

  • Heating circuits at different temperatures;
    Solar plant;
  • Other specific applications (swimming pool heating, DHW circulation pump, connection to biomass system, etc.).

This accessory can directly manage the circuit components (pump, temperature sensor, mixing valve, etc.) up to a maximum of 3 independent relay outlets, 2 temperature sensors and 1 control input. Some predefined functions can be used to simplify system configuration.

Baxi 90 F - 2.DESCRIPTION OF ACCESSORY - 1

The Remote Control must be used to set the parameters of the described configurations. To change the parameters and the connections in the instrument panel terminal blocks, consult the boiler instructions manual.

2.1 WALL INSTALLATION REQUIREMENTS

Before starting installation:

  • Disconnect the mains power supply.
  • Make sure enough air circulates outside the box to disperse the heat produced by the AVS 75 accessory.
  • Do not expose the unit to splashes of water or heat sources.

Baxi 90 F - WALL INSTALLATION REQUIREMENTS - 1

Only power the unit after completing installation.

2.2 WALL INSTALLATION

Mount the device on the wall with the two pressure screws supplied with the accessory, using the holes in the junction box. Connect the unit to the master boiler and the accessories as described in section 3. To secure it, see the measurements indicated in the figure to the side.

A Camp for power cable
B Holes for wall-mounting
CGrommets for external electrical accessories

Baxi 90 F - WALL INSTALLATION - 1

Only power the unit after completing installation.

Baxi 90 F - WALL INSTALLATION - 2

3. ELECTRICAL CONNECTIONS

Baxi 90 F - ELECTRICAL CONNECTIONS - 1

Pass the cables connecting the boiler to the accessories using the relative grommets holes on the bottom of the boiler.

3.1 BOILER ELECTRICAL CONNECTIONS

  • Connect the device to a 230V single-phase power supply with earth.
  • This appliance must only be installed by a qualified installer.
  • Before switching on, make sure all the electrical connections have been made correctly.
  • Carefully read the boiler instructions manual.
  • Connect the 2-pin terminal block of the AVS75 unit to the boiler terminal block M2 (2-3) using a "HAR H05 VV-F" 2 × 0.5 ~mm harmonicised cable with a maximum length of 150 ~m .

Baxi 90 F - BOILER ELECTRICAL CONNECTIONS - 1

3.2 ELECTRICAL CONNECTIONS OF EXTERNAL ACCESSORIES

To connect the AVS75 accessory to the external accessories proceed as follows (use "HAR H05 VV-F" harmonised cables with a cross-section of 1mm^2 ):

MIXED CIRCUIT CASE (see diagram chap. 3.2.1)

  • Connect the mixed zone pump to the QX23 connector on the AVS75.
  • Connect the mixed zone delivery sensor to the BX21 connector on the AVS75 (QAD36 supplied).
  • Connect the mixing valve to the QX22-QX21 connector
  • Connect the ambient thermostat to the H2 connector on the AVS75.
  • Connect the safety thermostat to the FX23 connector.

DHW SOLAR PLANT CASE (see diagram chap. 3.2.2)

  • Connect the solar plant pump to the QX23 connector on the AVS75.
  • Connect the solar boiler sensor to the BX22 connector on the AVS75.
  • Connect the solar panel sensor to the BX21 connector on the AVS75.
KEY TO CONNECTORS
N⊕L (L-N)AVS 75 power input
X50Connector linking the SIEMENS electronic board to the AVS 75 accessory.
X30Connector for linking another accessory via a flat cable.
T (QX21⊕N)230V programmable relay output
T (QX22⊕N)230V programmable relay output
S (QX23⊕N)230V programmable relay output
C (EX21-FX23-L)connection to safety thermostat (only for mixed zones)
n (H2-M)12VDC digital or 0-10VDC analogue programmable input.
n (BX21-M)NTC 10K / Pt1000 sensor programmable input
n (BX22-M)NTC 10K / Pt1000 sensor programmable input

Baxi 90 F - ELECTRICAL CONNECTIONS OF EXTERNAL ACCESSORIES - 1

3.2.1 MIXED CIRCUIT CASE

A FLOW PROBE QAD36 C MIXED ZONE PUMP
B MIXING VALVE D SAFETY THERMOSTAT

Baxi 90 F - MIXED CIRCUIT CASE - 1

Baxi 90 F - MIXED CIRCUIT CASE - 2

For a mixed zone, connect the safety thermostat between terminals FX23 - L and jumper terminals EX21 - FX23. The circuit pump connected to relay QX23 is thus internally connected in series to the safety thermostat.

If the relay output QX23 must be used for functions other than those required for the mixed zone, jumper terminals FX23 - L.

To make settings, enter the parameters menu on the Remote Control as indicated below:

KEY TO FIGURE MENU

1Enduser3Engineer
2Commissioning4OEM

The procedure for accessing the four menus in order to programme the boiler board and/or the Remote Control is the following:

from the main menu C.
A and C (hold down for approx. 6 seconds)
menu 1-2-3-4 (see figure to side and key).
- C to go back one menu at a time to the main menu.

Baxi 90 F - MIXED CIRCUIT CASE - 3

KEY FUNCTIONS FOR EDITING PARAMETERS

BMenu II / scroll the menu parameters / select the parameter value
BEnter the chosen menu / select the parameter to edit / confirm the selected value
CReturn to the previous menu

In all the presented configurations, if a Remote Control or a room unit is used, set them to room unit 1 in order to manage the DHW functions and the boiler stand- by, as well heating zone 1. If they are set as room unit 2 or room unit 3 only heating zones 2 and 3 respectively can be managed. See the instructions manual of the respective accessories for the configuration procedure.

Baxi 90 F - KEY FUNCTIONS FOR EDITING PARAMETERS - 1

After each system configuration process, carry out the following procedure for saving the components to the boiler.

  • Access menu 2 as indicated at the beginning of this section.

  • B Configuration B programme row 6200 then B.
    B Yes then B to confirm.

Baxi 90 F - KEY FUNCTIONS FOR EDITING PARAMETERS - 2

If the appliance is connected to an underfloor system, install a limit thermostat to prevent the latter from overheating.

The AVS 75 accessory can be configured to manage a low temperature circuit. The AVS 75 can therefore control the pump, the mixing valve and the flow sensor of the selected heating circuit as shown in the following schemes.

Baxi 90 F - KEY FUNCTIONS FOR EDITING PARAMETERS - 3

For a low temperature system, reduce the maximum CH temperature setpoint on the boiler by setting parameter 741 (see section 8.1) to a value not greater than 45^ .

Baxi 90 F - KEY FUNCTIONS FOR EDITING PARAMETERS - 4

Edit the parameter governing the closing of the mixing valves, depending on the model used, according to the following instructions.

Baxi 90 F - KEY FUNCTIONS FOR EDITING PARAMETERS - 5

The diagrams shown below refer to boilers with power less than 35kW . For boilers with power over 35kW , there must be a hydraulic separator upstream from the boiler and the zones must be equipped with zone pumps to replace the electrovalve.

5.1 SCHEME 1

Low temperature zone with ambient unit - heating circuit (1) High temperature zone with ambient thermostat - heating circuit (2)

1 External sensor - terminal block M2 (4-5) on boiler
2 Low temperature zone mixing valve (QX21-N-QX22)
3 Low temperature circuit pump (QX23-N)
4 Low temperature circuit probe (BX21-M)
5 Low temperature circuit safety thermostat (FX23-L)
6 Ambient unit - terminal block M2 (1-2-3) on boiler
7 Electrovalve or externally powered high temperature zone pump
8 High temperature zone ambient thermostat (for connection see chapter 7.1)

Baxi 90 F - SCHEME 1 - 1

Enter menu 2 from the control panel, as described in section 4, and make the following settings:

MENUPROGRAMME ROWVALUE TO SET DESCRIPTION
CONFIGURATION5715 On Heating circuit 2 enable
5977Room thermostat CH2Enable thermostat for circuit 2 (contact 1-2 terminal block M1)
6020 Tems / mode CH1 Low temperature zone enable
6024Limit thermostat CHEX21 input enabled as low temperature zone protection
6046Heat generation lockH2 input enabled as low temperature zone protection
HEATING CIRCUIT 1742---Modulating flow temperature enable (low temperature zone)
834Default 180 sMixing valve close time

The room unit can directly control the low temperature zone according to the required room temperature. If, when turning the knob B on the main menu, the display visualises the boiler flow temperature instead of the ambient temperature, parameter 742 has not been set correctly.

5.2 SCHEME 2

More than one low temperature zone with ambient thermostat and shared room unit - heating circuit(1) High temperature zone with ambient thermostat - heating circuit (2)

1 External sensor - terminal block M2 (4-5) of boiler
2 Low temperature zone mixing valve (QX21-N-QX22)
3 Low temperature circuit pump (QX23-N)
4 Low temperature circuit probe (BX21-M)
5 Low temperature circuit safety thermostat (FX23-L)
6 Room unit - terminal block M2 (1-2-3) of boiler
7 Low temperature zone ambient thermostat input (H2-M - for connection see chapter 7.4)
8 Electrovalve or externally powered high temperature zone pump
9 High temperature zone ambient thermostat (for connection see chapter 7.1)

Baxi 90 F - SCHEME 2 - 1

Enter menu 2 from the control panel, as described in section 4, and make the following settings:

MENUPROGRAMME ROWVALUE TO SET DESCRIPTION
CONFIGURATION5715 On Heating circuit 2 enable
5977Room thermostat CH2Enable thermostat for circuit 2 (contact 1-2 terminal block M1)
6020 Tems / mode CH1 Low temperature zone enable
6024Limit thermostat CHEX21 input enabled as low temperature zone protection
6046Room thermostat CH1H2 input enabled as low temperature zone room thermostat
HEATING CIRCUIT 171035°CRoom setpoint (low temperature zone)
834Default 180 sMixing valve close time

Set the comfort temperature to it maximum value (35^) to ensure the low temperature zones work correctly. This ensures that the room unit does not block the heat demand of the individual room thermostats managing the subzones.

In this case, the room unit manages the low temperature system, but it cannot be used to manage the temperature of one of the rooms. Turn knob B to display the boiler flow temperature. The heating circuit operates with a fixed flow.

5.3 SCHEME 3

Low - heating circuit (1) and high temperature - heating circuit (2) zones with ambient thermostat.

1 External sensor - terminal block M2 (4-5) of boiler
2 Low temperature zone mixing valve (QX21-N-QX22)
3 Low temperature circuit pump (QX23-N)
4 Low temperature circuit probe (BX21-M)
5 Low temperature circuit safety thermostat (FX23-L)
6 Low temperature zone room thermostat input (H2-M)
7 Electrovalve or externally powered high temperature zone pump
8 High temperature zone ambient thermostat (for connection see chapter 7.1)

Baxi 90 F - SCHEME 3 - 1

Enter menu 2 from the control panel, as described in section 4, and make the following settings:

MENUPROGRAMME ROWVALUE TO SET DESCRIPTION
CONFIGURATION5715 On Heating circuit 2 enable
5977Room thermostat CH2Enable thermostat for circuit 2 (contact 1-2 terminal block M1)
6020 Tems / mode CH1 Low temperature zone enable
6024Limit thermostat CHEX21 input enabled as low temperature zone protection
6046Room thermostat CH1H2 input enabled as low temperature zone room thermostat
HEATING CIRCUIT 1834Default 180 sMixing valve close time

6. ZONE HEATING SYSTEM

If it is not necessary to manage mixed systems, the AVS75 accessory can be used to command zone pumps/electrovalves, as illustrated below:

Baxi 90 F - ZONE HEATING SYSTEM - 1

To avoid frequent starting and stopping, raise the minimum temperature setpoint of the boiler in the heating mode by setting parameters 740, 1040 and 1340 (see section 8.1) to not less than 45^ .

6.1 SCHEME 4

Two zones with ambient unit heating circuits (1 and 2) and 1 zone with room thermostat heating circuit (3).

1External sensor - terminal block M2 (4-5) of boiler5Circuit 2 ambient unit - terminal block M2 (1-2-3) of boiler
2Circuit 1 zone pump or electrovalve (QX21-N)*6Electrovalve or externally powered circuit 3 zone pump
3Circuit 1 ambient unit - terminal block M2 (1-2-3) of boiler7Circuit 3 ambient thermostat (for connection see chapter 7.1)
4Electrovalve or circuit 2 zone pump (QX22-N)*

Baxi 90 F - SCHEME 4 - 1
* The AVS 75 accessory cannot directly command a 3-wire electrovalve. A relay with an exchange contact must be used instead.

Baxi 90 F - SCHEME 4 - 2

Room units 3 and 5 are connected in parallel.

The ambient units can directly control their respective zones according to the desired room temperature. Enter menu 2 from the control panel, as described in section 4, and make the following settings:

MENUPROGRAMME ROWVALUE TO SETDESCRIPTION
CONFIGURATION5715OnHeating circuit 2 enable
5721OnHeating circuit 3 enable
5977Room thermostat CH3Enable thermostat for circuit 3 (contact 1-2 terminal block M1)
6020Multifunctional-
6030Heating pump CH1 Q2Circuit 1 pump/electrovalve control
6031Heating pump CH2 Q6Circuit 2 pump/electrovalve control
HEATING CIRCUIT 1742---Enable modulating flow temperature (heating circuit 1)
HEATING CIRCUIT 21042---Enable modulating flow temperature (heating circuit 2)

The room units can directly control their respective zones according to the desired room temperature. If, when turning the knob B on the main menu, the display visualises the boiler flow temperature instead of the ambient temperature, parameters 742, 1042 and 1034 have not been set correctly.

6.2 SCHEME 5

1External sensor - terminal block M2 (4-5) of boiler5Circuit 2 ambient unit - terminal block M2 (1-2-3) of boiler
2circuit 1 zone electrovalve (QX21-N)*6circuit 3 zone electrovalve (QX21-N)*
3Circuit 1 ambient unit - terminal block M2 (1-2-3) of boiler7Circuit 3 ambient unit - terminal block M2 (1-2-3) of boiler
4circuit 2 zone electrovalve (QX22-N)*

Baxi 90 F - SCHEME 5 - 1

  • The AVS 75 accessory cannot directly command a 3-wire electrovalve. A relay with an exchange contact must be used instead.

Baxi 90 F - SCHEME 5 - 2

Room units 3 - 5 and 7 are connected in parallel.

The room units can directly control their respective zones according to the desired room temperature. Enter menu 2 from the Remote Control, as described in section 4, and make the following settings:

MENUPROGRAMME ROWPARAMETER VALUE TO SET DESCRIPTION
CONFIGURATION5715Temps / mode CH2OnHeating circuit 2 enable
5721Temps / mode CH3OnHeating circuit 3 enable
5977Function input H5NoneDisable thermostat in terminal block M1 (1-2) on board
6020Function extension module 1Multifunctional-
6030Relay output QX21 module 1Heating pump CH1 Q2Circuit 1 pump/electrovalve control
6031Relay output QX22 module 1Heating pump CH2 Q6Circuit 2 pump/electrovalve control
6032Relay output QX23 module 1Heating pump CH3 Q20Circuit 3 pump/electrovalve control
HEATING CIRCUIT 1742Flow temp setpoint room stat ---Enable modulating flow temperature (heating circuit 1)
HEATING CIRCUIT 21042Flow temp setpoint room stat---Enable modulating flow temperature (heating circuit 2)
HEATING CIRCUIT 31342Flow temp setpoint room stat---Enable modulating flow temperature (heating circuit 3)

The room units can directly control their respective zones according to the desired room temperature. If, when turning the knob B on the main menu, the display visualises the boiler flow temperature instead of the ambient temperature, parameters 742, 1042 or 1342 have not been set correctly.

7. ELECTRICALLY CONNECTING THE AMBIENT THERMOSTAT

Baxi 90 F - ELECTRICALLY CONNECTING THE AMBIENT THERMOSTAT - 1

The operating temperature is the same for all circuits.

Baxi 90 F - ELECTRICALLY CONNECTING THE AMBIENT THERMOSTAT - 2

The relays can be replaced with valves equipped with micro limit switches and vice versa.

7.1 CASE - 1 - Connecting a single ambient thermostat in a high temperature zone.

Connect the ambient thermostat to the external electric network (230V) which will supply the zone valve (or pump) and the relay coil; connect the relay contact to the boiler M1 terminal block (1-2).

Baxi 90 F - CASE - 1 - Connecting a single ambient thermostat in a high temperature zone. - 1

7.2 CASE - 2 - Connecting ambient thermostats for a high temperature multi-zone system.

Connect the ambient thermostat in parallel to the external electric network (230V) which will supply the zone valve (or pump) and the relay coils; connect the relay contacts in parallel to the boiler M1 terminal block (1-2).

Baxi 90 F - CASE - 2 - Connecting ambient thermostats for a high temperature multi-zone system. - 1

7.3 CASE - 3 - Connecting ambient thermostats for a low temperature multi-zone system.

Connect the ambient thermostats in parallel to the external electric network (230V) which will supply the zone valves (or pumps) and the relay coil; connect the relay contact to the AVS75 H2-M terminal blocks.

Baxi 90 F - CASE - 3 - Connecting ambient thermostats for a low temperature multi-zone system. - 1

7.4 CASE - 4 - Connecting ambient thermostats for a low temperature multi-zone system with micro limit switches in the zone valves.

Connect the ambient thermostats in parallel to the external electric network (230V) which will supply the zone valves; connect the micro switch contacts in parallel to the AV75 H2-M terminal blocks.

Baxi 90 F - CASE - 4 - Connecting ambient thermostats for a low temperature multi-zone system with micro limit switches in the zone valves. - 1

8. DHW SOLAR PLANT

In this configuration, the AVS 75 accessory can manage the solar circuit pump, the manifold sensor and the storage boiler sensor (relative to the solar plant) according to the following scheme:

1solar storage heater sensor B31 (BX22-M)3solar circuit pump Q5 (QX23-N)
2solar storage heater manifold B6 (BX21-M)4storage boiler sensor B3 - terminal block M2 (9-10) on board

Baxi 90 F - DHW SOLAR PLANT - 1

Baxi 90 F - DHW SOLAR PLANT - 2

Use specific sensors for this application (supplied as an accessory).

Enter menu 2 from the Remote Control, as described in section 4, and make the following settings:

MENUPROGRAMME ROWVALUE TO SETDESCRIPTION
CONFIGURATION6020Solar HWSolar function enable

The following parameters can be used. If solar panels with vacuum tubes are used, enable the specific safety function (parameters 3830, 3831):

MENUPROGRAMME ROWVALUE TO SETDESCRIPTION
CONFIGURATION3810 Default 8°CTemperature difference between manifold and solar sensor storage boiler for solar pump activation
3811 Default 4°CTemperature difference between manifold and solar sensor storage boiler for solar pump deactivation
3850 Default “---”Temperature above which the manifold pump circulates (only if the maximum temperature of the storage boiler is not reached)
Access menu 3 section 5.2)
SOLAR3830 Default “---”Maximum stop time of solar pump if the manifold temperature reaches its maximum value (parameter 3850) within the minimum circulation time (parameter 3831)
3831 Default 30s Minimumcirculation time of manifold pump

Baxi 90 F - DHW SOLAR PLANT - 3

When the symbol appears on the display, it means that the solar plant pump is heating the storage boiler.

9. PARAMETERS SETTING

9.1 HEATING SYSTEM

Remote ControlCR 1, 2, 3 HEATING CIRCUIT MENUFactory settingMinimumMaximum
CR1CR2CR3
70010001300Off: the boiler lights when the room temperature is < 6°C Timed: the room temperature depends on the set time band Reduced: the room temperature is reduced On: the room temperature is comfort-Comfort--
71010101310Comfort room temperature°C20ReducedMaximum comfort
71210121312Reduced room temperature°C16Anti-freezeComfort
71410141314Anti-freeze room temperature°C64Reduced
72010201320Climate curve selection for external sensor-1.50.14
73010301330With an external sensor and in the automatic operating mode, automatic heating control activates (ON-OFF) depending on the set temperature (external)°C---830
74010401340Minimum flow value (e.g.: with the modulating flow function enabled)°C258Maximum setpoint
74110411341Maximum flow value (e.g.: with the modulating flow function enabled)°C80Minimum setpoint95
74210421342Flow temperature with room unit (- = modulating flow enable)°C80Minimum setpointMaximum setpoint
75010501350Importance of room temperature with respect to the external temperature and vice-versa (room influence function): - %: pure climate 1.99 %: climate with room offset 100 %: pure room% 501100
76010601360Boiler off differential depending on the required room temperature°C0.50.54
80911091409The boiler pump and the circuit pump remain active 24h-no--
83411341434Closing time of low temperature mixing valves18030873
85011501450The 'manual' function is recommended-off
85111511451Flow temperature for dry screed function°C25095
85511551455Current flow temperature of dry screed function°C---
85611561456Day of the week during activation of dry screed function----

CR = Heating Circuit

9.2 DHW SYSTEM

Remote ControlDHW CIRCUIT MENUFactory settingMinimumMaximum
1600Operating mode Off = setpoint equal to anti-freeze setpoint On = rated setpoint Eco = pre-heating disabled-on --
1610 DHW rated setpoint °C 60 35 60
1612 Reduced DHW setpoint °C 35 8 60
1620Hourly programming enable-24h/day--
1640Anti-legionellosis function operating mode: Off Periodically Fixed weekday-off --
1641N° days between one anti-legionellosis function and the next (1...7)-7--
1642Anti-legionellosis function day (Monday...Sunday)-Monday--
1644Anti-legionellosis start time-------
1660 DHW recirculation pump operating mode-Hot water release--
1663Temperature at which the DHW pump stops°C45860

9.3 SUNDRY PARAMETERS

Control panelCONFIGURATION MENUFactory setting
5710Heating circuit 1 enableon
5721Heating circuit 3 enableoff
5730Setting of DHW sensor depending on the type of boiler(stORAGE or instantaneous)
5731Type of actuator for DHW priority controlDiverting valve
5970DHW priority sensor (for instantaneous boilers)-
5971Home position of contact-
5973Parameters for determining DHW demand water flow-
5974-
5975-
5976-
5977Input for ambient thermostat of one of the heating circuitsRoom thermostat CH1
5978-
6020Multifunction: the inputs and outputs can be configured manually-
6021Heating circuit 1, 2 or 3: manages a mixed zone (1, 2 or 3 - chapter 5)Return temp controller: not used-
6022Solar HW: manages a solar plant with 2 sensors and pump (section 7)Primary contr/system pump: not used-
6024Input for low temperature circuit safety thermostat (module 1)-
6026Input for low temperature circuit safety thermostat (module 2)-
6028Input for low temperature circuit safety thermostat (module 3)-
6030...6038See section 9-
6040...6045See section 9-
6046...6068See section 9-
6097Type of sensor used for solar manifoldPt 1000
6200Saving of all the sensors connected in the boiler and accessories (section 4)-
6212Manufacturer information-
6213Manufacturer information-
6215Manufacturer information-
6217Manufacturer information-
6230Manufacturer information-
6231Manufacturer information-
6704Internal code display enableyes
6705Internal code of current error-
6706Burner phase during which the error appeared-
6710External alarm reset (section 9)no
6800Last error-
6805Internal code of last error-
6806Burner phase of last error-
6810 to 6996 Error log-

10. SUNDRY FUNCTIONS

As well as the above settings, the inputs and outputs can also be configured according to system requirements. The following examples consider the relay QX21 and sensor BX21 output of the accessory, though the same applies to relays QX22, QX23 and the sensor BX22. In all cases, set the accessory to "Multifunctional".

MENUPROGRAMME ROWPARAMETER VALUE TOSET DESCRIPTION
CONFIGURATION6020Extension module 1 functionMultifunctional Solar function enable

If a storage boiler is used in the DHW circuit, the circulation pump can be controlled. This function is limited by the hourly programming of the DHW system. To minimise circulation losses, the function activates the pump for 10 minutes followed by a 20 minute pause. Enter menu 2 from the control panel, as described in section 4:

MENUPROGRAMME ROWVALUE TO SET DESCRIPTION
CONFIGURATION6030Circulating pump Q4DHW recirculation pump enable (relay QX21 output)
6040 HWcirculation sensor B39 DHWrecirculation sensor enable (sensor BX21)
DHW CIRCUIT1663factory setting = 45°CDHW temperature below which the pump is enabled (recirculation setpoint)

10.2 SOLAR PLANT FOR SWIMMING POOL

Heating a swimming pool with solar panels can be achieved as follows.

1Solar storage heater sensor B31 (BX22-M)5Swimming pool pump (QX21-N)
2Solar storage heater manifold B6 (BX21-M)6Swimming pool heating return sensor – terminal block M2 in boiler
3Solar circuit pump Q5 (QX23-N)7Swimming pool
4Storage boiler sensor B3 – terminal block M2 (9-10) of boiler

Baxi 90 F - SOLAR PLANT FOR SWIMMING POOL - 1

Baxi 90 F - SOLAR PLANT FOR SWIMMING POOL - 2

Use specific sensors for this application (supplied as an accessory).

Configure the system as described in section 8. At this point the DHW system is configured to use solar panels. Enter menu 2 from the Remote Control, as described in section 4:

MENUPROGRAMME ROWVALUE TO SETDESCRIPTION
CONFIGURATION5931Swimming pool sensor B13Swimming pool sensor enable (BX2 sensor input)
6030Solar ctrl elem swi pool K18Swimming pool heating pump enable (relay QX21 output)
DHW CIRCUIT6046Release swi pool solarSwimming pool heating activation (e.g.: via float or manual command)

It is important to use contact H2 as it assures correct system operation, allowing heat exchange with the swimming pool only if the latter allows it to do so. Make sure the swimming pool is full of water and operative.

10.3 GENERIC HEAT DEMAND

A generic heat demand does not come from one of the three available heating circuits and/or from the DHW circuit. This type of demand is called user demand and is used to provide heat to external units such as heating water in a swimming pool.

To enable this function, perform the following configuration procedure. Enter menu 2 from the Remote Control, as described in section 4:

MENUPROGRAMME ROWVALUE DESCRIPTION
CONFIGURATION6030Cons circuit pump VK1 Q15External demand 1 pump enable (relay QX21 output)
6046Consumer request VK1 External demand 1 contact
USER CR11859 factory setting = 70°C Heating flow temperature for external demand 1

If the user demand is provided via a 0-10 V analogue signal, set parameter 6046 to "User demand CR1 10V". Also set signal characteristics using the following parameters:

6049Valore tens. 1 H2 modulo 16050Valore 1 H2 modulo 16051Valore tens. 2 H2 modulo 16052Valore 2 H2 modulo 1

10.4 OTHER CONFIGURATIONS

Further configurations are summarised below:

QX21 relay

Alarm output K10Alarm (e.g.: condominium)
System pump Q14Pump active at every heating or external demand
Time setting 5 K13Contact commanded from “aux hourly programme”
Refrigeration request K28 CoolingDemand from chiller circuit 1
Water refill K34Boiler automatic filling valve
Fan shutdown K38External fan control

BX21 sensor

Buffer sensor B4Storage boiler sensor for heating (higher)
Buffer sensor B41Storage boiler for heating (lower)
Buffer sensor B42Third storage boiler probe for heating (half of storage boiler)

H2 input

Error/alarm messageExternal alarm signal
Boiler flow switchBoiler flow switch command (only to use if not on the boiler)
Boiler temp limiterBoiler thermostat command (only to use if not on the boiler)
Consumer request VK1 10VExternal demand 1 with 0-10V signal (*)
Pressure measurement 10VPressure measurement with 0-10V signal (*)
Preselected output 10VBoiler power adjustment according to 0-10V signal (*)
  • To use the functions set the characteristics of the analogue signal using the following parameters present in the Configuration menu of the Remote Control:
6049Voltage value 1 H2 module 16050Funct value 1 H2 module 16051Voltage value 2 H2 module 16052Funct value 2 H2 module 1

Baxi 90 F - OTHER CONFIGURATIONS - 1

The illustrated configurations also apply to the other board relays/sensors/Input, such as relay QX1 (row 5890) or sensors BX2 (row 5931) and BX3 (row 5932).

11. LIST OF FAULTS

EFault Description of fault
10External probe sensorHeating circuit enabled with no command (thermostat, room unit or external unit) or external probe faulty
84 B$B, address conflict 2 or moreroom units configured for the same heating circuit
98 Additional module 1 AVS 75 accessory not detected or recognised
99 Additional module 2 AVS 75 accessory not detected or recognised
373 Additional module 3 AVS 75 accessory not detected or recognised
30 Flow sensor 1 Mixed circuit 1 sensor not detected
32 Flow sensor 2 Mixed circuit 2 sensor not detected
260 Flow sensor 3 Mixed circuit 3 sensor not detected
335 BX21 no function BX21 sensor not configured
336 BX22 no function BX22 sensor not configured
324 BX same sensorsTwo or more sensors configured for the same function
52 DHW 2 sensor DHW solar sensornot detected
73 Manifold 1 probe Solar manifold sensor not detected
57 DHW circulation sensor DHW circulation sensor not detected
243 Swimming pool sensor Swimming pool sensor not detected
25 Wood boiler sensor Biomass boiler sensor not detected
346 No Q10 boiler pump Biomass boiler pump not detected

12. TECHNICAL SPECIFICATIONS

Power inputInput voltageAC 230 V (±10 %)
Operating frequency50/60 Hz
Power input4 VA
Power supply fuse (power supply and outputs)max. 10 AT
CablesRigid or flexible wire (braided or with ferrule)-
one-pole0.5...2.5 mm²
two-pole0.5...1.5 mm²
Operating dataSoftware classA
Operating mode EN 60 7301b (automatic operation)
InputsDigital input H2-
very low safety voltage for clean contact-
low voltage contact-
voltage with contact openDC 12 V
current with contact closedDC 3 mA
Analogue input H2-
Very low protection voltage-
rangeDC 0..10 V
internal resistance> 100 kW
Input LAC 230 V (±10%)
internal resistance> 100 kW
Input sensors BX21, BX22NTC 10k
permitted connection cables (copper)-
cross-sectionmm²0.250.50.751.01.5
maximum lengthm20406080120
OutputsOutput relay-
current rangeAC 0.02...2 (2) A
maximum starting current15 A for ≤1 s
maximum current (for all relays)AC 6 A
voltage rangeAC 24...230 V (for clean contact)
InterfaceBSBconnection with 2 cables, not interchangeable
length of base unit - peripheralsmax. 200 m
total lengthmax. 400 m (maximum capacity of cable 60nF)
cable cross-section0.5 mm²

SOMMAIRE

2.1 CONDITIONS REQUISES POUR L'INSTALLATION AU MUR

10.3 VŠEOBECNÍ POŽADAVEK TEPLA

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Baxi

Model : 90 F

Category : Boiler