Alphacool Eiszeit 2000 Chiller - Computer cooling system

Eiszeit 2000 Chiller - Computer cooling system Alphacool - Free user manual and instructions

Find the device manual for free Eiszeit 2000 Chiller Alphacool in PDF.

📄 44 pages English EN Download 💬 AI Question
Notice Alphacool Eiszeit 2000 Chiller - page 3
View the manual : Français FR Deutsch DE English EN
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about Eiszeit 2000 Chiller Alphacool

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Computer cooling system in PDF format for free! Find your manual Eiszeit 2000 Chiller - Alphacool and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Eiszeit 2000 Chiller by Alphacool.

USER MANUAL Eiszeit 2000 Chiller Alphacool

Parameter Adjustment 8-11

Flow Alarm 12

Fault Indication

Technical Specification 15

German Manual 17

French Manual

Security Advice

Please ensure the power supply and electrical outlet are securely connected and that the grounding wire is connected.

The average operating current of the chiller is small, but the instantaneous operating current could be up to 10 amps.

Please make sure there is a stable and normal voltage for the working chiller!

The standard operating voltage for the chiller is 220 V.

Mismatched power frequency can cause damage to the chiller!

Be sure you can run a machine with 50 Hz.

To protect the pump, it is strongly advised that you do not run the chiller without having water in the water reservoir!

The machine is packaged without water in the tank, so make sure the tank has enough water inside before starting it otherwise the pump can be damaged. When the water level is below the green (NORMAL) range of the water level gauge, the cooling capacity of our chiller will go down slightly, hence please ensure the water level is within the green (NORMAL) range. Do not drain the water by circulating the pump!

Please be sure that the air inlet and air outlet have good ventilation!

There must be at least 30 cm from obstructions to the air outlet in the back of the cooler and at least 8 cm between obstructions and the side air inIet.

The fi Iter screen must be regularly cleaned!

It's essential to unpick and clean the dust gauze, or a serious blockage could cause a breakdown to the chiIler.

Please pay attention to the effect of the condensate water!

When there is higher ambient humidity, and when the water temperature is lower than the ambient temperature, condensation will appear on the surface of the water circulation pipes and the cooled components. If this occurs, setting a higher water temperature or keeping connected pipes and cooled parts warm is recommended.

Parts Introduction

Alphacool Eiszeit 2000 Chiller - Parts Introduction - 1

text_image Front Fillport Power Switch Display Flow Alarm (red) Normal Flow (green) CCOOL CHILLER 2000 EISZEIT Back Water Inlet Water Outlet Alarm Output Terminal Power Socket (with fuse) Air Inlet (with fi Iter) Water Level Gauge Air Outlet Water Drain

Installation

Open the Fillport to fill in cooling water

Keep observing the water level gauge while adding water slowly. For the cooling of carbon steel equipment, the water should be added an appropriate amount of anti-corrosion additives. Working in cold areas, it's better to use noncorrosive antifreeze fluid.

Connect the water in- and outlet to your cooling circuit Use two GI/4 fi ttings to connect the chiller with tubes.

Plug in power, turn on the power switch

Do not start up without water in the water reservoir!

  1. The first time of operating may cause more bubbles in the tube leading to a flow alarm. It will go back to normal after a few minutes of operating.
  2. Check whether the system leaks immediately!
  3. If the water temperature is below the set value, it is normal the fans and other components do not work. The temperature controller will automatically control the working condition of the compressor, magnetic valve, fans and other parts based on the set controlling parameters.
  4. According to different conditions it may take more time to start the compressor and other single components. So do not turn off and on again frequently to avoid damaging parts.

Installation

Alphacool Eiszeit 2000 Chiller - Installation - 1

text_image FULL NORMAL ALARM FULL NORMAL ALARM

4

Check the water level

The first startup of the new chiller empties the air in the water tubes, leading to a small water level decline in the reservoir. Observe the water level for a period of time and add adequate water if necessary. A rapid water level drop may be a sign of system leakage.

5

Adjust parameters of the temperature controller

The machine uses an intelligent thermostat. Normally, users should not need to adjust it. If it becomes necessary to do so, please refer to the "Parameter adjustment" chapter.

Parameters Adjustment - control panel

The new intelligent temperature controller does not need to be adjusted under normal circumstances. It will self-adjust controlling parameters according to room temperature for meeting equipment cooling requirements.

Alphacool Eiszeit 2000 Chiller - Parameters Adjustment - control panel - 1

text_image D1 D2 88.8 °C RST ▲ SET ▼

D1, D2: Indicators of thermostat working state

D1ON: Thermostat works in intelligent control modeOFF: Thermostat works in constant temperature control modeFLASHES: Thermostat is working in parameter setting mode or displaying room temperature
D2ON: Chiller works in refridge rating stateOFF: Chiller works in the insulation working stateFLASHES: Chiller works in energy-saving state

(1) Press ▲ to show the room temperature. Holding the button for 6 seconds to display the restore defaults
(2) ▲▼ keys are for adjusting the controller parameters
(3) RST: Enter button
(4) SET: Function setting key

Parameters Adjustment - Settings

Restore to factory settings

Before machine startup, press and keep holding ▲▼ buttons while turning the chiller on. Release the buttons when the controller displays „rE“. After 6 seconds the device works in normal order with parameter settings restored to factory settings.

General settings

Press SET to enter the user-defined state. (Meanwhile, D1 flashes to indicate the controller is in parameters setup status)

(1) Under intelligent mode, the control panel displays the temperature difference value between water and air (F1)

(2) Under constant temperature mode, the control panel displays the set temperature value (F0)

Change settings with ▲▼ and press enter (RST) to save and exit. The new parameters take effect now. Or press SET to exit without saving parameters.

If there is no more action within 20 seconds, the controller will automatically exit modifying status without saving.

Advanced settings

(1) Press and hold ▲ + SET for 5 seconds until „0“ is displayed. Then press ▲ to select the password which has been set before (factory setting is 8). Press SET, if the password is correct, „F0“ is shown and you're entering set status. (D1 fl ashes to indicate the controller is in parameters setup status). If you choose the wrong password the panel returns to temperature display.

(2) In setup state press ▲ or ▼ to switch between functions and select with SET. After selecting an option, the original settings are displayed. Modify them with ▲▼. Press SET to save and return to previous setup menu. Press RST to save and return to temperature display. If no button is pressed within 20 seconds, the controller will automatically exit modifying status without saving.

Note:

(1) parameters setting condition: System still runs under original parameters
(2) constant temperature control mode: Water temperature is controlled by F0 parameters
(3) intelligent control mode: Water temperature depends on room temperature and parameters

Parameter List

Settings Overview

OrderDisplayed CodeItemRange Factory settingsNote
1F0 Temperature settingF9 ~ F825affects temperature in constant control mode
2F1Temperature diffence value-15 ~ +5-2affects temperature in intelligent control mode
3F2Cooling hysteresis0.1 ~ 3.00.8
4F3Control mode0 ~ 111: intelligent0: constant
5F4Alarm for too highwater temperature1 ~ 2010
6F5Alarm for too low water temperature1 ~ 2015
7F6Alarm for too high room temperature40 ~ 2045
8F7Password00 ~ 998
9F8highest allowed water temperatureF0 ~ 4030
10F9lowest allowed water temperature1 ~ F920

Settings - example of use

Switch to constant temperature mode

(1) Hold down ▲ + SET for 5 seconds, until it shows "0". Set the value with ▲ and select the password you have set (Factory default is 8). Press SET; if the password is correct the display will show „F0“ and you will be in the settings menu. (Display D1 will blink to show parameter mode) If the password is incorrect, you will be returned to the temperature display.
(2) In the settings menu, press ▲ to reach menu point "F3". Press SET to apply settings. The display will read "1"(Intelligent mode). With ▼, change the value to "0" (constant temperature mode).
(3) Confirm your selection with SET to save your selection and return to the settings menu Or Use RST to save your settings and return to the home screen. If you do not press any keys within 20 seconds, you will automatically leave settings mode without saving.

Set water temperature - in constant temperature mode

(1) The heat exchanger is running in constant temperature mode.
(2) Press SET; the display will now read "F3". Change the value with ▼ to "F0" and confirm your selection with SET.
(3) The set temperature value will be displayed. Using ▲▼, set this value to your liking.
(4) Confirm your selection with SET to save your selection and return to the settings menu.

Or

Use RST to save your settings and return to the home screen.

If you do not press any keys within 20 seconds, you will automatically leave settings mode without saving.

Flow Alarm

In order to guarantee the equipment will not be damaged while cooling water circulation is out of control, the chiller has a low-flow alarm security feature. The flow alarm is connected to the normally open and normally closed relay contacts, requiring operating current less than 5 A, working voltage less than 300 V.

Wiring diagram - output ports
Alphacool Eiszeit 2000 Chiller - Flow Alarm - 1

text_image L Flow-sw KM BZ Red light Green light S-HP S-HP H-HP H2 H3 H1 Output ports diagram N Alarm output ports

Flow alarm causes

Condition\DisplayNORMAL LEDALARM LED BuzzerOUT H1, H2OUT H1, H3
pump works properlyONOFF OFFno soundON
Blocked water circulation loopOFFONsoundsONOFF
Water shortage alarmOFFONsoundsONOFF
Faulted pumpOFFONsoundsONOFF
Power interruptionONOFF

Alarm - Fault Indication

Error messages

DisplayE1E2E3 E4E5
Meaningroom temperature too highwater temperature too highwater temperature too lowRoom temperature sensor failureWater temperature sensor failure

When alarm occurs, the error code will be displayed.

The alarm sound will be suspended by pressing any button, but the alarm code remains on display until the alarming condition is eliminated.

Troubleshooting

Failure Fault Cause Approach
Machine turned on but not receiving power Power cord is not plugged in placeCheck and ensure the power interface and the power plug is plugged in place and in good contact.
Fuse burnt-outPull out the fuse box from the power supply interface of the chiller, check the fuse, replace with spare fuse, if necessary and check whether the power supply voltage is stable. Check and ensure the power interface and the power plug is plugged in place and in good contact.
Flow Alarm (red LED on) - no water flow despite everything being connected properlyWater level is too lowCheck the water level gauge, add water until the level is in the green area. Also check whether water circulation tube leaks
Water circulation tubes are blocked or tubes are deformed by bendingCheck water circulation tubes. They should not be bent or twisted.

Alarm - Fault Indication

Failure Fault CauseApproach
Ultra-high temperature alarm Blocked dust gauze, bad thermolysisUnpick and wash the dust gauze regularly.
Poor ventilation for air outlet and inletEnsure a smooth ventilation for air outlet and inlet.
Voltage is extremely low or unstableImprove the power supply circuit or use a voltage regulator.
Improper parameter settings on thermostatReset controlling parameters or restore factory settings.
Power is switched on frequentlyEnsure there is suffi cient time for refrigeration (more than 5 minutes).
Excessive heat loadReduce the heat load or use other model with larger cooling capacity.
Alarm for ultra-high room temperatureThe working ambient temperature is too high for the chillerImprove the ventilation to guarantee the machine is running under 40°C.
Serious problems with condensate waterWater temperature is much lower than ambient temperature, with high humidityIncrease water temperature or preserve heat for pipeline.
Water drains slowly from drain during water changingFillport is not openOpen the Fillport.

Technical Specification

Model Chiller 2000
Voltage 220V
Frequency 50 Hz
Current 2.4 ~ 3.3 A
Compressor Power 0.49 / 0.57 KW (0.66 / 0.77 HP)
Refrigeration Capacity 1.41 / 1.70 KW
Refrigerant R-134a
Refrigerant Charge 380 g
Noise level 65 db(A)
Precision ± 0.3 °C
Reducer Capillary
Protection Over current protection for compressor, flow alarm, over temperature alarm
Pump Power0.03 KW
Reservoir Capacity9 L
Inlet / OutletG I/4 Inner threads
max. Lift10 m
max. Flow10 L/min
Netto Gewicht29 kg
Dimension56 x 28 x 47 cm (L x W x H)

Alphacool Eiszeit 2000 Chiller - Alarm - Fault Indication - 1

Deutsch

Inhaltsverzeichnis

Englische Anleitung

Deutsche Anleitung

natural_image Line drawing of a kitchen appliance with a lid and ventilation grilles (no text or symbols)
natural_image Technical line drawing of a mechanical assembly with gears and shafts (no text or symbols)
natural_image Line drawing of a server unit with fan and power connector (no text or symbols)
text_image FULL FULL NORMAL NORMAL ALARM ALARM

4

text_image L Flow-sw KM BZ Red light Green light L-HX L-HY L-C-X H-HX H2 H3 H1 Output ports diagram N Alarm output ports

Conf i guration 36-39

Alerte de débit 40

natural_image Line drawing of a kitchen appliance with a lid and ventilation grilles (no text or symbols)

1

natural_image Technical line drawing of a mechanical assembly with gears and shafts (no text or symbols)

2

natural_image Line drawing of a power outlet with fan and plug, no text or symbols present

3

text_image FULL FULL NORMAL NORMAL ALARM ALARM

4

Vérifi er niveau de liquide

General Manager: Fabian Noelte

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Alphacool

Model : Eiszeit 2000 Chiller

Category : Computer cooling system