Emko ESM-3712-CN - Temperature Controller

ESM-3712-CN - Temperature Controller Emko - Free user manual and instructions

Find the device manual for free ESM-3712-CN Emko in PDF.

📄 80 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Emko ESM-3712-CN - page 1
View the manual : Français FR Deutsch DE English EN Español ES Italiano IT
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Digital ON/OFF Cooling Controller
Model ESM-3712-CN
Brand Emko
Dimensions (Housing) 76 x 34.5 x 71 mm
Panel Cutout 71 x 29 mm
Weight Approximately 0.2 kg
Power Supply 100-240 V~ (±15%, +10%) 50/60 Hz, 2.5 VA (other options available: 24 V~, 115 V~, 230 V~, 10-30 V---)
Sensor Input Type NTC (10 kΩ at 25°C) or PTC (1000 Ω at 25°C)
Number of Relay Outputs 3 (compressor, defrost, fan)
Compressor Output 16 (8) A @ 250 V~, resistive load
Defrost Output 5 A @ 250 V~, resistive load
Fan Output 5 A @ 250 V~, resistive load
Display 4-digit red LED (14 mm)
LED Indicators S (green), P (green), °C (yellow), °F (yellow), Alarm (red), Defrost output (red), Fan output (red), Compressor output (red)
Internal Buzzer ≥83 dB
Communication Modbus RTU (RS-485) and ProKey
Operating Temperature -30°C to +80°C
Operating Humidity 90% RH max (non-condensing)
Protection Rating IP65 (front), IP20 (rear), NEMA 4X
Housing Material Plastic
Cleaning With a cloth moistened with ethyl alcohol or water; do not use hydrocarbon-based solvents
Warranty 2 years from delivery date
Manufacturer Emko Elektronik Sanayi ve Ticaret A.S., Bursa, Turkey
Standards CE, EHC

Frequently Asked Questions - ESM-3712-CN Emko

How to set the set temperature?
From the main screen, press the SET key to display the set temperature. Use the ▲ and ▼ keys to change the value, then press SET again to save.
How to perform a manual defrost?
From the main screen, press the defrost key for 3 seconds. Manual defrost starts if the defrost time is ≥ 1 and the defrost output is inactive.
What to do if the display shows 'E1' or 'E2'?
The E1 (cabinet sensor) or E2 (evaporator sensor) messages indicate a probe failure. Check the sensor connection. If the problem persists, replace the probe.
How to change the defrost time?
Press the defrost key to display the defrost time. Use the ▲ and ▼ keys to adjust the value (0 to 999 minutes), then press SET to confirm.
What is the required supply voltage?
The standard model operates on 100-240 V~ (±15%, +10%) 50/60 Hz. Check the device label to verify the specific voltage.
How to install the controller in a panel?
Cut an opening of 71 x 29 mm in the panel. Insert the unit from the front, then fix it with the supplied brackets. Tighten until fully secured.
Can I use a PTC probe with this model?
Yes, the device accepts NTC or PTC probes. The input type must be set in the parameters (code BC=12 for PTC, BC=18 for NTC).
How to reset the audible alarm?
Press the ▼ key to mute the buzzer. The visual alarm remains active until the alarm condition is resolved.
What accessories are available?
Optional accessories include an RS-485 communication module and a ProKey programming key for parameter transfer.
How to protect settings with a password?
In programming mode, set the PAS (password) parameter to a value from 1 to 999. The password will be required to access parameters.

User questions about ESM-3712-CN Emko

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Temperature Controller in PDF format for free! Find your manual ESM-3712-CN - Emko and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ESM-3712-CN by Emko.

USER MANUAL ESM-3712-CN Emko

  • 4 Digits Display
  • NTC Input or PTC Input (Must be determined in order.)
  • 3 output for compressor, defrost and fan controls
  • 2 sensor input for cabinet and evaporator
  • Configurable digital input
    -ON/OFFControl
  • Separately adjustable 2 offset value for cabinet and evaporator sensor
  • Set value boundaries
  • Operation selection of compressor operate continuously, stops or operates periodically in case of cabinet probe defect
  • Compressor protection delays
  • Selectable defrost function (hot gas or electric)
  • Adjustable defrost time from front panel
  • Manual defrost from front panel
  • Defrost parameters
  • Alarm parameters
  • Fan can be operated depending on compressor and defrost
  • Fan can be operated depending on evaporator temperature or (cabinet - evaporator ) temperature
  • Adjustable internal buzzer according to the defrost, cabinet prob defect and alarm status
  • Defrost time and/or manual defrost and/or temperature set value protection
  • Password protection for programming mode
  • Installing parameters using Prokey
  • Remote access, data collecting and controlling with Modbus RTU
  • Having CE mark according to European Norms

1.Preface

ESM-3712-CN series cooling controllers are designed for controlling cooling process. They can be used in many applications with their easy-use, On / Off control form and defrost properties. Some application and application fields which they are used are below:

Application Fields

Food

Machine production industries

etc...

Applications

Refrigerators

Air Conditioning

Storages

Freezers

etc...

1.1 Environmental Ratings

Emko ESM-3712-CN - Environmental Ratings - 1

Emko ESM-3712-CN - Environmental Ratings - 2

Emko ESM-3712-CN - Environmental Ratings - 3

Emko ESM-3712-CN - Environmental Ratings - 4

Operating Temperature : -30 to 80 °C

Max. Operating Humidity : 90% Rh (non-condensing)

Altitude: Up to 2000 m.

Forbidden Conditions:

Corrosive atmosphere

Explosive atmosphere

Home applications (The unit is only for industrial applications)

1.2 General Specifications

Emko ESM-3712-CN - General Specifications - 1

1.3 Installation

A visual inspection of this product for possible damage occurred during shipment is recommended before installation.

It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.

If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and separate the electrical connection of the device from the system.

The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse as required.

Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure

Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented.

Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in malfunction, electric shock or fire.

Do not use the unit in combustible or explosive gaseous atmospheres.

During putting equipment in hole on the metal panel while mechanical installation some metal burrs can cause injury on hands, you must be careful.

Montage of the product on a system must be done with it's fixing clamps. Do not do the montage of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the montage.

It is your responsibility if this equipment is used in a manner not specified in this instruction manual.

1.4 Warranty

EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.

1.5 Maintenance

Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts.

Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case.

1.6 Manufacturer Company

Manufacturer Information:

Emko Elektronik Sanayi ve Ticaret A.S.

Bursa Organize Sanayi Bolgesi, (Fethiye OSB Mah.) Ali Osman Sonmez Bulvari,

  1. Sokak, No:3 16215 BURSA - TÜRKIYE

Phone:+902242611900 Fax:+902242611912

Repair and maintenance service information:

Emko Elektronik Sanayi ve Ticaret A.Ş.

Bursa Organize Sanayi Bolgesi, (Fethiye OSB Mah.) Ali Osman Sonmez Bulvari,

  1. Sokak, No:3 16215 BURSA - TÜRKIYE

Phone: +90 224 261 1900 Fax: +90 224 261 1912

2. General Description

Emko ESM-3712-CN - General Description - 1

2.1 Front View and Dimensions of ESM-3712-CN Cooling Controller

Emko ESM-3712-CN - Front View and Dimensions of ESM-3712-CN Cooling Controller - 1

2.2 Panel Cut-Out

Emko ESM-3712-CN - Panel Cut-Out - 1

2.3 Panel Mounting and Removing

Emko ESM-3712-CN - Panel Mounting and Removing - 1

Emko ESM-3712-CN - Panel Mounting and Removing - 2

1-Before mounting the device in your panel, make sure that the cut-out is of the right size.

2-Insert the device through the cut-out. If the mounting clamps are on the unit, put out them before inserting the unit to the panel.

3- Insert the mounting clamps to the fixing sockets that located left and right sides of device and make the unit completely immobile within the panel

1-Pull mounting clamps from left and right fixing sockets.
2-Pull the unit through the front side of the panel

Before starting to remove the unit from panel, power off the unit and the related system.

3. Optimal Accessories

1.RS-485 Module

Emko ESM-3712-CN - 1.RS-485 Module - 1

RS-485 Communication Interface

2.PROKEY Programming Module

Emko ESM-3712-CN - 2.PROKEY Programming Module - 1

The device is programmed (Upload or Download) by using the parameters.

3.1 Using Prokey

TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE '0'.
IF PrC=1 AND BUTTON IS PRESSED ERRMESSAGE WILL BE SHOWN. 10s. LATER
DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET BUTTON TO TURN BACK TO MAIN OPERATION SCREEN.

DOWNLOADING FROM DEVICE TO PROKEY

  1. The device is programmed by using parameters.
  2. Energize the device then put in PROKEY and press button. Message is shown on the display. When the loading has finished, message is shown.
  3. Press any button to turn back to main operation screen.

4.Remove the PROKEY.

NOTE: message is shown when an error occurs while programming. If you want to reload, put in PROKEY and press button. If you want to quit, remove PROKEY and press button. The device will turn back to main operation screen.

DOWNSLOADING FROM PROKEY TO DEVICE

  1. Switch off the device.
    2.Put in PROKEY then energize the device.

  2. When the device is energized, the parameter values in PROKEY, start downloading to the device automatically. At first, message is shown on the display, when loading has finished, end message is shown.

  3. After 10 second device starts to operate with new parameter values.
    5.Remove the PROKEY.

NOTE: Err message is shown when an error occurs while programming. If you want to reload, switch off the device and put in PROKEY then energize the device. If you want to quit remove PROKEY and press button. The device will turn back to main operation screen.

4. Electrical Wiring Diagram

Emko ESM-3712-CN - Electrical Wiring Diagram - 1

4.1 Supply Voltage Input Connection of the Device

Emko ESM-3712-CN - Supply Voltage Input Connection of the Device - 1

Note-1: External fuse is recommended.
Note-2 : Stranded cable cross section: 1,5 mm^2 ,Solid cable cross-section: 2,5 mm^2 The stripping length is 7 to 9mm.
Note-3 : Supply cables must comply with the requirements of IEC 60277 or IEC 60245

4.2 Device Label and Connection Diagram

Emko ESM-3712-CN - Device Label and Connection Diagram - 1

5.Front Panel Definition and Accessing to the Menus

Emko ESM-3712-CN - 5.Front Panel Definition and Accessing to the Menus - 1

BUTTON DEFINITIONS

  1. Increment Button :
    In main operation screen, press this button to display evaporator sensor temperature.
    It is used to increase the value in the Set screen, Defrost screen and Programming mode.

  2. Decrement, Silencing Buzzer and Downloading to Prokey Button :

** It is used to decrease the value in the Set screen, Defrost screen and Programming mode.
It is used to silence the buzzer.
If Prc = 0 , it is used to download from device to prokey.

  1. Defrost Button :

** In the main operation screen; if this button pressed, defrost time value will be displayed.
**In the main operation screen; if this button pressed for 3 seconds, manual defrost starts.

  1. Set Button :

** In the main operation screen; if this button pressed, set value will be displayed. Value can be changed using increment and decrement buttons. When Set button pressed again, value is saved and returns back to main operating screen.

** To access the programming screen; in the main operation screen, press this button for 5 seconds.
** It is used to saving value in the Set screen, Defrost screen and programming screen.

LED DEFINITIONS

  1. Compressor output led :

** This led indicates that compressor output is active. If any of compressor protection time active, this led blinks

6.Defrost output led :

** This led indicates that defrost output is active.
Blinks once in a second while Defrost delay time.
Blinks (5 Hz) while entering Defrost time value.

7.Fan output led :

** This led indicates that fan output is active.
** Blinks once in a second while Fan delay time.

8.Alarm led :

** It is active when low alarm and high alarm statuses.
9.Celcius led :
** Indicates that device is in °C mode.

10.Fahrenheit led :

** Indicates that device is in °F mode.
11.Set led :
Indicates that device is in Set value changing mode.
12.Program led :
Blinks once in a second in programming mode.

6. Changing and Saving Temperature Set Value

Emko ESM-3712-CN - Changing and Saving Temperature Set Value - 1
Main Operating Screen

When SET button pressed "S" led will be active and temperature set value will be displayed.

Emko ESM-3712-CN - Changing and Saving Temperature Set Value - 2
SET Value Screen

Temperature set value can be changed with increment and decrement buttons.

Emko ESM-3712-CN - Changing and Saving Temperature Set Value - 3
SET Value Screen

When SET button pressed temperature set value can be saved.

Emko ESM-3712-CN - Changing and Saving Temperature Set Value - 4
Main Operating Screen

"S" will be inactive and goes back to main operation screen.

Temperature set value parameter (Default=10) MODBUS ADDRESS:40001

Temperature set value, can be programmed between minimum temperature set value Su1 and maximum temperature set value SuH .

6.1 Changing and Saving Defrost Time Set Value

Emko ESM-3712-CN - Changing and Saving Defrost Time Set Value - 1
Main Operating Screen

When defrost button is pressed, defrost time set value is shown and defrost output led starts to fast blink (5 Hz).

Emko ESM-3712-CN - Changing and Saving Defrost Time Set Value - 2
Defrost Time Value Screen

Change the defrost time set value with increment and decrement buttons.

Emko ESM-3712-CN - Changing and Saving Defrost Time Set Value - 3
Defrost Time Value Screen

Press set button for saving the defrost time set value

Emko ESM-3712-CN - Changing and Saving Defrost Time Set Value - 4
Main Operating Screen

Defrost time set value is saved, defrost output led stop the fast blink (5 Hz), main operation screen is shown.

Emko ESM-3712-CN - Changing and Saving Defrost Time Set Value - 5

If no operation is performed in defrost time set value changing mode and temperature set value changing mode for 20 seconds, device turns to main operation screen automatically.

6.2 Programming Mode Parameter List

Emko ESM-3712-CN - Programming Mode Parameter List - 1

Temperature Unit Selection Parameter (Default = 0) MODBUS ADDRESS:40002

Emko ESM-3712-CN - Programming Mode Parameter List - 2

°C selected.
°F selected.

Emko ESM-3712-CN - Programming Mode Parameter List - 3

Decimal Seperator Enabling Parameter (Default = 0) MODBUS ADDRESS:40003

Emko ESM-3712-CN - Programming Mode Parameter List - 4

Disable. Enable.

Emko ESM-3712-CN - Programming Mode Parameter List - 5

Hysteresis Parameter for Compressor Output (Default = 1) MODBUS ADDRESS:40004

from 1 to 20^ for NTC (-50^, 100^) or PTC (-50^, 150^) from 1 to 36^ for NTC (-58^, 212^) or PTC (-58^, 302^) from 0.1 to 10.0^ for NTC (-50.0^, 100.0^) or PTC (-50.0^, 150.0^) from 0.1 to 18.0^ for NTC (-58.0^, 212.0^) or PTC (-58.0^, 302.0^)

In ON/OFF control algorithm temperature value is tried to keep equal to set value by opening or closing the last control element. ON/OFF controlled system, temperature value oscillates continuously. Temperature value's oscillation period or amplitude around set value changes according to controlled system. For reducing oscillation period of temperature value, a threshold zone is formed below or around set value and this zone is named hysteresis.

Emko ESM-3712-CN - Hysteresis Parameter for Compressor Output (Default = 1)   MODBUS ADDRESS:40004 - 1

Emko ESM-3712-CN - Hysteresis Parameter for Compressor Output (Default = 1)   MODBUS ADDRESS:40004 - 2

Minimum Temperature Set Value Parameter(Default = Minimum Value of Device Scale) MODBUS ADDRESS:40005

Temperature set value can not be lower than this value. This parameter value can be adjusted from minimum value of device scale to maximum temperature set value parameter & H

Emko ESM-3712-CN - Minimum Temperature Set Value Parameter(Default = Minimum Value of Device Scale) MODBUS ADDRESS:40005 - 1

Maximum Temperature Set Value Parameter (Default = Maximum Value of Device Scale) MODBUS ADDRESS:40006

Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter to maximum value of the device scale.

Emko ESM-3712-CN - Maximum Temperature Set Value Parameter (Default = Maximum Value of Device Scale) MODBUS ADDRESS:40006 - 1

Cabinet Sensor Offset Parameter (Default = 0) MODBUS ADDRESS:40007

From -20 to 20^ for NTC(-50°C, 100°C) or PTC(-50°C, 150°C),
From -36 to 36^ for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),
From -10.0 to 10.0^ for NTC(-50.0°C, 100.0°C) or PTC(-50.0°C, 150.0°C),
From -18.0 to 18.0^ for NTC(-58.0°F, 212.0°F) or PTC(-58.0°F, 302.0°F).
Evaporator Sensor Selection Parameter (Default =1) MODBUS ADDRESS:40008

Emko ESM-3712-CN - Cabinet Sensor Offset Parameter (Default = 0) MODBUS ADDRESS:40007 - 1

Emko ESM-3712-CN - Cabinet Sensor Offset Parameter (Default = 0) MODBUS ADDRESS:40007 - 2

Evaporator sensor is inactive.
Evaporator sensor is active.

Emko ESM-3712-CN - Cabinet Sensor Offset Parameter (Default = 0) MODBUS ADDRESS:40007 - 3

Evaporator Sensor Offset Parameter (Default = 0) MODBUS ADDRESS:40009

If evaporator sensor selection parameter [525] is 1, then this parameter is observed.

From -20 to 20^ for NTC(-50°C, 100°C) or PTC(-50°C, 150°C),

From -36 to 36^ for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),

From -10.0 to 10.0^ for NTC(-50.0°C, 100.0°C) or PTC(-50.0°C, 150.0°C),

From -18.0 to 18.0^ for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F).

Emko ESM-3712-CN - Evaporator Sensor Offset Parameter (Default = 0) MODBUS ADDRESS:40009 - 1

Defrost Type Selection Parameter (Default =0) MODBUS ADDRESS:40010

Emko ESM-3712-CN - Defrost Type Selection Parameter (Default =0) MODBUS ADDRESS:40010 - 1

Electric defrost.

Emko ESM-3712-CN - Defrost Type Selection Parameter (Default =0) MODBUS ADDRESS:40010 - 2

Hot gas defrost.

Emko ESM-3712-CN - Defrost Type Selection Parameter (Default =0) MODBUS ADDRESS:40010 - 3

Defrost Time Parameter(Default = 10 )MODBUS ADDRESS:40011

It can be adjusted from 0 to 999 minutes.

If it is selected 0 automatic or manual defrost is not performed.

Defrost Repeat Cycle Parameter (Default = 1) MODBUS ADDRESS:40012

It can be adjusted from 1 to 99 hours.

Emko ESM-3712-CN - Defrost Time Parameter(Default = 10 )MODBUS ADDRESS:40011 - 1

Defrost Stopping Temperature Parameter (Default = 2°C) MODBUS ADDRESS:40013

For evaporator sensor selection parameter 525 is 1 (evaporator sensor is active), while defrost operation, if evaporator temperature reaches to temperature that defined at this parameter in a shorter time than dt parameter, then defrost operation stops.

Emko ESM-3712-CN - Defrost Stopping Temperature Parameter (Default = 2°C) MODBUS ADDRESS:40013 - 1

Defrost at Power On Selection and Defrost Delay Parameter (Default = no) MODBUS ADDRESS:40014

It can be adjust from 0 to 99 minutes. When tihs parameter is 0, if decrement button is pressed, n o is observed. In this condition system goes through a defrost cycle at the end of the defrost repeat cycle time after power on.If this parameter value is between 0 and 99, then system goes through a defrost cycle at the end of the this parameter time after power on.

Emko ESM-3712-CN - Defrost at Power On Selection and Defrost Delay Parameter (Default = no) MODBUS ADDRESS:40014 - 1

Display Status During Defrost Parameter (Default = 3) MODDBUS ADRESS:40015

The cabinet temperature value is displayed during defrost.
Cabinet temperature value at the start of the defrost is displayed during defrost.
Temperature set value is displayed during defrost.
is displayed to indicate the defrost is in progress.

Emko ESM-3712-CN - Display Status During Defrost Parameter (Default = 3)   MODDBUS ADRESS:40015 - 1

Displaying Current Temperature Delay After Defrost Parameter (Default = 0) MODDBUS ADRESS:40016

This parameter defines the delay for displaying current temperature being active after defrost. It can be adjusted from 0 to 255 minutes.

Emko ESM-3712-CN - Displaying Current Temperature Delay After Defrost Parameter (Default = 0)   MODDBUS ADRESS:40016 - 1

Dripping Time Parameter (Default = 2) MODBUS ADDRESS:40017

This parameter defines for dripping time after defrost. It can be adjusted from 0 to 15 minutes.

Emko ESM-3712-CN - Dripping Time Parameter (Default = 2) MODBUS ADDRESS:40017 - 1

Temperature Alarm Delay After Dripping Parameter (Default = 0) MODBUS ADDRESS:40018

This parameter defines the delay for temperature alarm being active after dripping time completion. It can be adjusted from 0 to 15 minutes.

Emko ESM-3712-CN - Temperature Alarm Delay After Dripping Parameter (Default = 0) MODBUS ADDRESS:40018 - 1

Compressor Start Delay at Power On Parameter (Default = 0) MODBUS ADDRESS:40019

When power is first applied to the device, This time delay must be expired for activation of compressor. It can be adjusted from 0 to 20 minutes.

Emko ESM-3712-CN - Compressor Start Delay at Power On Parameter (Default = 0)   MODBUS ADDRESS:40019 - 1

Compressor Start-Start Delay Parameter (Default = 0) MODBUS ADDRESS:40020

This time delay must be expired between two activation of the compressor. It can be adjusted from 0 to 20 minutes.

Emko ESM-3712-CN - Compressor Start-Start Delay Parameter (Default = 0)   MODBUS ADDRESS:40020 - 1

Minimum Compressor OFF Time Parameter (Default = 0)MODBUS ADDREDS:40021 When compressor is inactive, this time delay must be expired for activation of the compressor. It can be adjusted from 0 to 20 minutes.

Minimum Compressor ON Time Parameter (Default = 0) MODBUS ADRES:40022 When compressor is active, this time delay must be expired for deactivation of the compressor. It can be adjusted from 0 to 20 minutes.

Emko ESM-3712-CN - Minimum Compressor OFF Time Parameter (Default = 0)MODBUS ADDREDS:40021 When compressor is inactive, this time delay must be expired for activation of the compressor. It can be adjusted from 0 to 20 minutes. - 1

Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40023

Emko ESM-3712-CN - Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40023 - 1

Compressor is OFF in case of cabinet probe defect.

Compressor is ON in case of cabinet probe defect.

Compressor operates periodically according to Pon and PoF time periods in case of cabinet probe defect.

Emko ESM-3712-CN - Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40023 - 2

Compressor Active Time in Case of Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40024

If cabinet probe defect parameter P_df is 2, then this parameter is observed. It can be adjusted from 99 minutes.

Emko ESM-3712-CN - Compressor Active Time in Case of Cabinet Probe Defect Parameter (Default = 0)   MODBUS ADDRESS:40024 - 1

Compressor Inactive Time in Case of Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40025

If cabinet probe defect parameter |P_dF| is 2, then this parameter is observed. It can be adjusted from L_dF to 99 minutes.

Emko ESM-3712-CN - Compressor Inactive Time in Case of Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40025 - 1

Temperature Alarm Function Selection Parameter (Default = 0) MODBUS ADRES:40026

Emko ESM-3712-CN - Temperature Alarm Function Selection Parameter (Default = 0)   MODBUS ADRES:40026 - 1

Temperature alarm function is inactive.

Absolute alarm is selected. If temperature lower than Aol and higher than HvH , then alarm is on.

Emko ESM-3712-CN - Temperature Alarm Function Selection Parameter (Default = 0)   MODBUS ADRES:40026 - 2

Relative alarm is selected. Alarm operates according to the set value. If cabinet temperature value is below (Set -RUL) or above (Set +Huh), alarm occurs.

Emko ESM-3712-CN - Temperature Alarm Function Selection Parameter (Default = 0)   MODBUS ADRES:40026 - 3

Temperature Alarm Minimum Parameter (Default = Minimum Value of Device Scale) MODBUS ADRES:40027

For = 1 , this parameter value can be adjusted from minimum value of device scale to temperature alarm maximum parametervalue.For = 2 , this parameter value can be adjusted O to %50 of the device scale.

Emko ESM-3712-CN - Temperature Alarm Minimum Parameter (Default = Minimum Value of Device Scale) MODBUS ADRES:40027 - 1

Temperature Alarm Maximum Parameter (Default = Maximum Value of Device Scale) MODBUS ADRES:40028

For RLS = 1 , this parameter value can be adjusted from temperature alarm minimum parameter R_L value to maximum value of device scale. For RLS = 2 , this parameter value is can be adjusted 0 to %50 of the device scale.

Emko ESM-3712-CN - Temperature Alarm Maximum Parameter (Default = Maximum Value of Device Scale) MODBUS ADRES:40028 - 1

Temperature Alarm On Delay Time Parameter(Default = 0) MODBUS ADDRESS:40029

Temperature Alarm On Delay Time can be defined with this parameter. It can be adjusted from 0 to 99 minutes.

Emko ESM-3712-CN - Temperature Alarm On Delay Time Parameter(Default = 0)   MODBUS ADDRESS:40029 - 1

Temperature Alarm Delay After Power On Parameter(Default = 0) MODBUS ADDRESS:40030

When power is first applied to the device, this time delay must be expired for activation of temperature alarm. It can be adjusted from 0 to 99 minutes.

Emko ESM-3712-CN - Temperature Alarm Delay After Power On Parameter(Default = 0)   MODBUS ADDRESS:40030 - 1

Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031

Emko ESM-3712-CN - Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031 - 1

Fan is OFF.

Fan is ON.

Fan operates according to the evaporator sensor temperature value.

Fan operates according to the ( cabinet - evaporator ) temperature value.

Emko ESM-3712-CN - Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031 - 2

Fan Stopping Temperature Parameter(Default = 2°C) MODBUS ADDRESS:40032 Fan stopping temperature can be defined with this parameter. It can be adjusted from minimum value to maximum value of device scale.

Emko ESM-3712-CN - Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031 - 3

Hsyteresis Parameter for Fan Output (Default = 1) MODBUS ADDRESS:40033 From 1 to 20^ for NTC (-50^, 100^) , from 1 to 36^ for NTC (-58^, 212^) , from 0.1 to 10.0^ for NTC (-50.0^, 100.0^) , from 0.1 to 18.0^ for NTC (-58.0^, 212.0^)

Emko ESM-3712-CN - Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031 - 4

Fan Activity Selection According to the Compressor and Defrost (Default = 0) MODBUS ADDRESS:40034

Emko ESM-3712-CN - Fan Activity Selection According to the Compressor and Defrost (Default = 0) MODBUS ADDRESS:40034 - 1

Fan operates according to the parameter.

Fan operates according to the E S parameter, but fan is stopped if compressor is stops.

Emko ESM-3712-CN - Fan Activity Selection According to the Compressor and Defrost (Default = 0) MODBUS ADDRESS:40034 - 2

Fan operates according to the parameter, but fan is stopped during defrost and dripping time.

Emko ESM-3712-CN - Fan Activity Selection According to the Compressor and Defrost (Default = 0) MODBUS ADDRESS:40034 - 3

Fan operates according to the parameter.If compressor stops, during defrost and dripping operations fan stops.

Emko ESM-3712-CN - Fan Activity Selection According to the Compressor and Defrost (Default = 0) MODBUS ADDRESS:40034 - 4

Fan Delay Time After Completion of Dripping Time Parameter (Default = 2) MODBUS ADDRESS:40035

Fan Delay Time After Completion of Dripping Time is defined with this parameter. It can be adjusted from 0 to 15 minutes.

Emko ESM-3712-CN - Fan Delay Time After Completion of Dripping Time Parameter (Default = 2)   MODBUS ADDRESS:40035 - 1

Digital Input Contact Selection Parameter (Default = 1) MODBUS ADDRESS:40036

Emko ESM-3712-CN - Digital Input Contact Selection Parameter (Default = 1) MODBUS ADDRESS:40036 - 1

Digital input is inactive.

NO "normally open" digital input is active when the contact is closed.

NC "normally close" digital input is active when the contact is opened.

Emko ESM-3712-CN - Digital Input Contact Selection Parameter (Default = 1) MODBUS ADDRESS:40036 - 2

Digital Input Function Selection Parameter (Default = 0) MODBUS ADDRESS:40037 If digital input contact selection parameter value = 0 , this parameter is not observed.

Emko ESM-3712-CN - Digital Input Function Selection Parameter (Default = 0) MODBUS ADDRESS:40037 If digital input contact selection parameter value = 0 , this parameter is not observed. - 1

When the digital input is active, fan is stopped. screen will be displayed.

When the digital input is active, compressor is stopped. screen will be displayed and defrost operation will be disabled. If Buzzer function selection parameter buf = 2 or 4 buzzer is active.

Emko ESM-3712-CN - Digital Input Function Selection Parameter (Default = 0) MODBUS ADDRESS:40037 If digital input contact selection parameter value = 0 , this parameter is not observed. - 2

When the digital input is active, first fan stops, 10 seconds later compressor stops. l will be displayed at main operation screen.

When the digital input is active, defrost starts.

Emko ESM-3712-CN - Digital Input Function Selection Parameter (Default = 0) MODBUS ADDRESS:40037 If digital input contact selection parameter value = 0 , this parameter is not observed. - 3

When the digital input is active, alarm will be active. H will be displayed at main operation screen. If Buzzer function selection parameter b = 2 or 4 buzzer is active.

Emko ESM-3712-CN - Digital Input Function Selection Parameter (Default = 0) MODBUS ADDRESS:40037 If digital input contact selection parameter value = 0 , this parameter is not observed. - 4

Digital Input Effect Time Parameter (Default = - - ) MODBUS ADDRESS:40038

If digital input contact selection parameter value dct = 0 , this parameter is not observed. For digital input function selection parameter dfn = 0 or 2, maximum effect time of digital input is determined with this parameter. It can be adjusted from 0 to 120 minutes. When this parameter is 0, if decrement button is pressed, is observed. In this condition the effect will be ended when digital input is deactive.

Emko ESM-3712-CN - Digital Input Effect Time Parameter (Default = - - ) MODBUS ADDRESS:40038 - 1

Buzzer Function Selection Parameter (Default = 0) MODBUS ADDRESS:40039

Emko ESM-3712-CN - Buzzer Function Selection Parameter (Default = 0) MODBUS ADDRESS:40039 - 1

Buzzer is inactive.

Buzzer is active during defrost operation.

Buzzer is active if an alarm occurs.

Buzzer is active during cabinet sensor failures.

Buzzer is active during defrost, alarm or cabinet sensor failures.

Emko ESM-3712-CN - Buzzer Function Selection Parameter (Default = 0) MODBUS ADDRESS:40039 - 2

Buzzer Active Time (Default = - - - ) MODBUS ADDRESS:40040

If buzzer function selection parameter value bw = 0 , this parameter is not observed. Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99 minutes. When this parameter is 1, if decrement button is pressed, is observed. In this condition buzzer is active till buzzer silence button is pressed.

Emko ESM-3712-CN - Buzzer Active Time (Default = - - - ) MODBUS ADDRESS:40040 - 1

Button Protection Parameter (Default = 0) MODBUS ADDRESS:40041

Emko ESM-3712-CN - Button Protection Parameter (Default = 0) MODBUS ADDRESS:40041 - 1

There is no protection.

Defrost time set value can not be changed and manual defrost is not available.

Temperature set value can not be changed.

Defrost time set value and temperature set value can not be changed and manual defrost is not available.

Defrost time can not be changed, Defrost ON/OFF operation is available.

Emko ESM-3712-CN - Button Protection Parameter (Default = 0) MODBUS ADDRESS:40041 - 2

Communication Mode Selection Parameter( Default = 0 ) MODBUS ADRESS:40042

Emko ESM-3712-CN - Communication Mode Selection Parameter( Default = 0 ) MODBUS ADRESS:40042 - 1

PROKEY communication selected.

RS485 communication selected.

Emko ESM-3712-CN - Communication Mode Selection Parameter( Default = 0 ) MODBUS ADRESS:40042 - 2

Slave ID Parameter (Default = 1) MODBUS ADDRESS=40043

Device communication address parameter (1 to 247).

Emko ESM-3712-CN - Slave ID Parameter (Default = 1) MODBUS ADDRESS=40043 - 1

Programming Mode Accessing Password (Default = 0) MODBUS ADDRESS:40044

It is used for accessing to programming mode. It can be adjusted from 0 to 999. If it is 0, password is not entered for accessing to the parameters. If password is '12' only, can be accessible.

6.3 Operation Graphics of ESM-3712-CN Cooling Controller

1- Defrost time parameter value ≥ 1 Defrost repeat cycle parameter value ≥ 1 Defrost at power on selection and defrost delay parameter value ≥ 1 Dripping time parameter value ≥ 1

Emko ESM-3712-CN - Operation Graphics of ESM-3712-CN Cooling Controller - 1

2- Compressor start delay at power on parameter value PoS ≥ 1 ,
Compressor start - start delay parameter value Std ≥ 1 ,
Minimum compressor OFF time parameter value CoF ≥ 1 ,
Minimum compressor ON time parameter value Con ≥ 1 ;

Emko ESM-3712-CN - Operation Graphics of ESM-3712-CN Cooling Controller - 2

6.4 Entering To The Programming Mode, Changing and Saving Parameter Main Operating Screen

Emko ESM-3712-CN - Entering To The Programming Mode, Changing and Saving Parameter Main Operating Screen - 1

When SET button is pressed for 5 seconds, "P" led starts to blink. If programming mode entering password is different from 0, programming mode entering screen will be observed.

Note1: If programming mode accessing password is 0, Temperature Unit Selection Screen is observed instead of programming screen accessing password

Emko ESM-3712-CN - Entering To The Programming Mode, Changing and Saving Parameter Main Operating Screen - 2

Programming Mode Entering Screen

Press SET button for accessing to the password entering screen.

Emko ESM-3712-CN - Programming Mode Entering Screen - 1

Password Entering Screen

Enter programming mode accessing password with increment and decrement buttons.

Emko ESM-3712-CN - Password Entering Screen - 1

Password Entering Screen Press SET/OK button for entering the password.

Note-2: If programming mode accessing password is 0 parameter values can be seen. But parameter values can not be changed.

Emko ESM-3712-CN - Password Entering Screen - 2
Programming Screen

Press SET button for accessing to the parameter value. Press increment button for accessing to the next parameter, press decrement button for accessing to the previous parameter

Emko ESM-3712-CN - Password Entering Screen - 3

Compressor Output Hysteresis Parameter Value

Change the value with increment and decrement buttons.

Emko ESM-3712-CN - Compressor Output Hysteresis Parameter Value - 1

Compressor Output Hysteresis Parameter Value

Press set button for saving the parameter.

Emko ESM-3712-CN - Compressor Output Hysteresis Parameter Value - 1

Compressor Output Hysteresis Parameter

Press increment button for accessing to the next parameter, press decrement button for accessing to the previous parameter

Emko ESM-3712-CN - Compressor Output Hysteresis Parameter - 1

If no operation is performed in programming mode for 20 seconds, device turns to main operation screen automatically..

7. Failure Messages in ESM-3712-CN Cooling Controller

1-5b1 message blinking.Cabinet temperature sensor failure ensor connection is wrong or there is no sensor connection. While this message shown on this display, if buzzer function selection parameter buF is 3 or 4, internal buzzer starts to operate.

7. Failure Messages in ESM-3712-CN Cooling Controller

2-56b2 message blinking.

Evaporator temperature sensor failure. sensor connection is wrong or there is no sensor connection.

3- message blinking.

For absolute alarm, if cabinet temperature sensor value is lower than temperature alarm minimum parameter R_UL value and for relative alarm, if cabinet temperature sensor value is lower than (Temperature Set - R_UL ), then AL message starts to blink. If buzzer function selection parameter is 2 or 4, internal buzzer starts to operate.

4- message blinking.

For absolute alarm, if cabinet temperature sensor value is higher than temperature alarm maximum parameter RuH value and for relative alarm, if cabinet temperature sensor value is higher than (Temperature Set +RuH ), then RH message starts to blink. If buzzer function selection parameter b_uF is 2 or 4, internal buzzer starts to operate.

5- Rd, message blinking.

When the digital input is active and digital input function selection parameter value dF_n is 0 or 2, message starts to blink.

6- [B, n] message blinking.

When the digital input is active and digital input function selection parameter value is 1 or 4 message starts to blink. If buzzer function selection parameter is 2 or 4, internal buzzer starts to operate.

8. Manual Defrost Operation with Defrost Button

Emko ESM-3712-CN - Manual Defrost Operation with Defrost Button - 1
3 sn.

While defrost time parameter value ≥ 1 button protection parameter value P_rt = 0 or 2 and defrost output is inactive, in main operation screen if defrost button is pressed for 3 seconds manual defrost will be active

8.1 Manual Defrost Operation with Digital Input

Emko ESM-3712-CN - Manual Defrost Operation with Digital Input - 1

While digital input function selection parameter value = 3 if digital input contact selection parameter value = 1 (normally open NO) and the K switch is getting closed, or if digital input contact selection parameter value = 2 (normally close NC) and the K switch is getting opened manual defrost will be active

9.Modbus Adresses of Device Status Parameters (Read Input Register)

MODBUS ADRES:30001

MODBUS ADRES:30002

MODBUSADRES:30003

Cabinet Temperature Value

Evaporator Temperature Value

MODBUS ADRES:30004

Led Status : 0.bit°C Led, 4.bit Fan Led, 5.bit Defrost Led, 6.bit Compressor Led, 7.bit Alarm Led 13.bit Programming Led. 14.bit Set Led

Device Status : 0.bit Alarm Status, 1.bit Buzer Status

MODBUS ADRES:30005

2.bit Cabinet Sensor Lost Status, 3.bit Evaporator Sensor Lost Status

7.bit Defrost Status
Output Status: 0.bit Compressor O
1.bit Defrost Output
2.bit Fan Output

MODBUS ADRES:30006

Device Type and Version

10. Specifications

Protection Against

Mechanical Impacts : 1 Joule (IK06)

Device Type : Cooling Controller

Housing&Mounting : 76 mm x 34.5 mm x71 mm plastic housing for panel

Panel cut-out is 71 × 29 ~mm

Protection Class

:NEMA 4X (IP65 at front, IP20 at rear)

10. Specifications

Weight

Environmental Ratings

Storage / Operating Temperature

Storage / Operating Humidity

Installation

Overvoltage Category

Pollution Degree

Operating Conditions

Supply Voltage and Power

Temperature Sensor Inputs

NTC Input Type or PTC Input Type

Accuracy

Sensor Break Protection

Sampling Cycle

Control Form

Relay Outputs

Display

LED

Internal Buzzer

Approvals

Approximately 0.2Kg

: Standard, indoor at an altitude of less than 2000 meters with none condensing humidity.

-40°C to +85°C / -30°C to +80°C

: 90 % max. (None condensing)

: Fixed installation

:II.

: II, office or workplace, none conductive pollution

: Continuous

:100-240V~(%15, +%10) 50/60Hz - 2.5VA

:230V~(%15)50/60Hz-2.5VA

:115V~(±%15)50/60Hz-2.5VA

:24V~(%15)50/60Hz-2.5VA

:24V\~(±%15)50/60Hz-2.5VA,10-30V---2.5W

:NTC or PTC

:NTC (10 kΩ @25 °C) or PTC (1000 Ω @25 °C)

: ±1 % of full scale for thermoresistance

: Upscale

: 3 samples per second

:ON/OFF

: 16(8) A@250 V ~ at resistive load(Compressor Output)

5 A@250 V ~ at resistive load(Defrost and Fan Output)

: 14 mm Red 4 digit LED Display

: S (Green), P (Green), C (Yellow), F(Yellow), Alarm(Red), Defrost Output (Red), Fan Output (Red) Compressor Output (Red),

:≥83dB

Emko ESM-3712-CN - Approvals - 1

11. Ordering Information

ESM-3712-CN (T7x35 DIN Size)A B C D E F G H I J K L U V W Z
Supply VoltageA
1100-240V~(-%15, +%10) 50/60Hz - 2.5VA
224V~±%15) 50/60Hz - 2.5VA
324V~ (±%15) 50/60Hz - 2.5VA
4115V~ (±%15) 50/60Hz - 2.5VA
5230V~ (±%15) 50/60Hz - 2.5VA
810 - 30 V ---2.5W
9Customer
BCInput TypeScale(°C)
12PTC (Note-1)-50°C/-58°F;150°C/302°F
18NTC (Note-1)-50°C/-58°F;100°C/212°F
ECompressor Output
1Relay Output (16(8) A@250 V~at resistive load, 1 NO)
FGDefrost Output
01Relay Output (5 A@250 V~at resistive load, 1 NO)
Fan OutputHl
01Relay Output (5 A@250 V~at resistive load, 1 NO)
VTemp. Sensor which is given with ESM-3712-CN
0None
1PTC-M6L40.K1.5 (PTC Air Probe with 1.5 mt silicon cable)
2PTCS-M6L30.K1.5.1/8" (PTC Liquid Probe with1.5 mt silicon cable)
3NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with 1.5 m cable for cooling application)
4NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with 1.5 m cable for cooling application)
9Customer

All order information of ESM-3712-CN Cooling Controller are given on the table at left. User may form appropriate device configuration from information and codes that at the table and convert it to the ordering codes.

Firstly, supply voltage then other specifications must be determined. Please fill the order code blanks according to your needs.

Please contact us, if your needs are out of the standards.

Note-1: If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the device. For this reason, if input type is selected as PTC, sensor type (V = 0,1 or 2) or if input type is selected as NTC, sensor type (V =0,3 or 4) must be declared in ordering information.

Emko ESM-3712-CN - Ordering Information - 1

$$ \begin{array}{r c l} \sim & \Rightarrow \text {V a c}, \ \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline \hline & \Rightarrow \text {V d c} \end{array} $$

$$ \Rightarrow \mathrm {V d c} \text {o r V a c} \text {c a n b e a p p l i e d} \sim $$

EMKO

Your Technology Partner

Thank you very much for your preference to use Emko Elektronik products, please visit our web page to download detailed user manual.

www.emkoelektronik.com.tr

Emko ESM-3712-CN - EMKO - 1

Atmosphere corrosive

Remarque-3: Supply cables must comply with the requirements of IEC 60277 or IEC 60245

Désactiver.
Activer.

Emko ESM-3712-CN - EMKO - 2

Note-3: Supply cables must comply with the requirements of IEC 60277 or IEC 60245

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Emko

Model : ESM-3712-CN

Category : Temperature Controller