ESM-3712-CN - Temperature Controller Emko - Free user manual and instructions
Find the device manual for free ESM-3712-CN Emko in PDF.
User questions about ESM-3712-CN Emko
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Temperature Controller in PDF format for free! Find your manual ESM-3712-CN - Emko and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ESM-3712-CN by Emko.
USER MANUAL ESM-3712-CN Emko
ESM-3712-CN 77x35 DIN Size Cooling Controller Instruction Manual. ENG ESM-3712-CN 01 V08 04/22- 4 Digits Display- NTC Input or PTC Input (Must be determined in order.)- 3 output for compressor, defrost and fan controls- 2 sensor input for cabinet and evaporator - Configurable digital input- ON / OFF Control- Separately adjustable 2 offset value for cabinet and evaporator sensor- Set value boundaries- Operation selection of compressor operate continuously, stops or operates periodically in case of cabinet probe defect- Compressor protection delays- Selectable defrost function (hot gas or electric )- Adjustable defrost time from front panel- Manual defrost from front panel- Defrost parameters- Alarm parameters- Fan can be operated depending on compressor and defrost- Fan can be operated depending on evaporator temperature or(cabinet - evaporator ) temperature- Adjustable internal buzzer according to the defrost, cabinet prob defect and alarm status- Defrost time and/or manual defrost and/or temperature set value protection- Password protection for programming mode- Installing parameters using Prokey- Remote access, data collecting and controlling with Modbus RTU - Having CE mark according to European Norms ESM-3712-CN 77 x 35 DIN Size Digital , ON / OFF Cooling Controller ENGLISH AEMKOENGLISH Operating Temperature : -30 to 80 °CMax. Operating Humidity : 90% Rh (non-condensing) Altitude : Up to 2000 m.Forbidden Conditions:Corrosive atmosphereExplosive atmosphereHome applications (The unit is only for industrial applications) 1.2 General Specifications1.Preface ESM-3712-CN series cooling controllers are designed for controlling cooling process. They can be used in many applications with their easy-use, On / Off control form and defrost properties. Some application and application fields which they are used are below:Application Fields Food Machine production industries etc...Applications RefrigeratorsAir ConditioningStoragesFreezersetc...
1.1 Environmental Ratings
WA visual inspection of this product for possible damage occurred during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product. If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and separate the electrical connection of the device from the system. The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse as required. Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can be prevented. Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in malfunction, electric shock or fire. Do not use the unit in combustible or explosive gaseous atmospheres. During putting equipment in hole on the metal panel while mechanical installation some metal burrs can cause injury on hands, you must be careful. Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the montage. It is your responsibility if this equipment is used in a manner not specified in this instruction manual. EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely. Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or water to clean the external plastic case.
1.6 Manufacturer Company
2.1 Front View and Dimensions of ESM-3712-CN Cooling Controller
ESM-3712CN ENGLISH1-Before mounting the device in your panel, make sure that the cut-out is of the right size. 2-Insert the device through the cut-out. If the mounting clamps are on the unit, put out them before inserting the unit to the panel.3- Insert the mounting clamps to the fixing sockets that located left and right sides of device and make the unit completely immobile within the panel1-Pull mounting clamps from left and right fixing sockets.2-Pull the unit through the front side of the panelBefore starting to remove the unit from panel, power off the unit and the related system.
2.3 Panel Mounting and Removing
1.Switch off the device.2.Put in PROKEY then energize the device.3.When the device is energized, the parameter values in PROKEY, start downloading to the device automatically. At first, message is shown on the display, when loading has finished, message is shown.4.After 10 second device starts to operate with new parameter values.5.Remove the PROKEY.
DOWNLOADING FROM DEVICE TO PROKEY1.The device is programmed by using parameters. 2.Energize the device then put in PROKEY and press button. Message is shown on the display. When the loading has finished, message is shown.3.Press any button to turn back to main operation screen.4.Remove the PROKEY.DOWNLOADING FROM PROKEY TO DEVICE NOTE: message is shown when an error occurs while programming. If you want to reload, put in PROKEY and press button. If you want to quit, remove PROKEY and press button. The device will turn back to main operation screen.NOTE: message is shown when an error occurs while programming. If you want to reload, switch off the device and put in PROKEY then energize the device. If you want to quit remove PROKEY and press button. The device will turn back to main operation screen.TO USE PROKEY, VALUE OF THE PrC PARAMETER MUST BE ‘0’.IF PrC=1 AND BUTTON IS PRESSED MESSAGE WILL BE SHOWN. 10s. LATER DEVICE TURNS BACK TO THE MAIN OPERATION SCREEN OR YOU CAN PRESS SET BUTTON TO TURN BACK TO MAIN OPERATION SCREEN. ENGLISH6 ENGLISH PROKEYRS-485
4.2 Device Label and Connection Diagram
4. Electrical Wiring Diagram
4.1 Supply Voltage Input Connection of the Device
Note-1 : External fuse is recommended. Make sure that the power supply voltage is the same indicated on the instrument. Switch on the power supply only after that all the electrical connections have been completed. Supply voltage range must be determined in order. While installing the unit, supply voltage range must be controlled and appropriate supply voltage must be applied to the unit.
There is no power supply switch on the device. So a power supply switch must be added to the supply voltage input. Power switch must be two poled for seperating phase and neutral, On/Off condition of power supply switch is very important in electrical connection. External fuse that on Vpower supply inputs must be on phase connection. External fuse that on Zpower supply inputs must be on (+) connection.
5.Front Panel Definition and Accessing to the MenusBUTTON DEFINITIONS1. Increment Button : ** In main operation screen, press this button to display evaporator sensor temperature.** It is used to increase the value in the Set screen, Defrost screen and Programming mode.2. Decrement, Silencing Buzzer and Downloading to Prokey Button :** It is used to decrease the value in the Set screen, Defrost screen and Programming mode.** It is used to silence the buzzer.** If Prc =0, it is used to download from device to prokey. 3. Defrost Button :** In the main operation screen; if this button pressed, defrost time value will be displayed.**In the main operation screen; if this button pressed for 3 seconds, manual defrost starts.4. Set Button :** In the main operation screen; if this button pressed, set value will be displayed. Value can be changed using increment and decrement buttons. When Set button pressed again, value is saved and returns back to main operating screen.** To access the programming screen; in the main operation screen, press this button for 5 seconds.** It is used to saving value in the Set screen, Defrost screen and programming screen.LED DEFINITIONS 5. Compressor output led : ** This led indicates that compressor output is active. If any of compressor protection time active, this led blinks6.Defrost output led : ** This led indicates that defrost output is active. ** Blinks once in a second while Defrost delay time.** Blinks (5 Hz) while entering Defrost time value.7.Fan output led : ** This led indicates that fan output is active. ** Blinks once in a second while Fan delay time.8.Alarm led : ** It is active when low alarm and high alarm statuses.9.Celcius led : ** Indicates that device is in C mode.10.Fahrenheit led : ** Indicates that device is in F mode.11.Set led : ** Indicates that device is in Set value changing mode.12.Program led : **Blinks once in a second in programming mode .
7ENGLISH 6. Changing and Saving Temperature Set Value6.1 Changing and Saving Defrost Time Set ValueMain Operating ScreenWhen SET button pressed ‘’S’’ led will be active and temperature set value will be displayed.SET Value ScreenTemperature set value can be changed with increment and decrement buttons.When SET button pressed temperature set value can be saved.‘’S’’ will be inactive and goes back to main operation screen.Main Operating ScreenTemperature set value parameter (Default=10) MODBUS ADDRESS:40001Temperature set value, can be programmed between minimum temperature set value and maximum temperature set value .When defrost button is pressed, defrost time set value is shown and defrost output led starts to fast blink (5 Hz).Press set button for saving the defrost time set valueDefrost time set value is saved, defrost output led stop the fast blink (5 Hz), main operation screen is shown.Main Operating ScreenDefrost Time Value ScreenDefrost Time Value Screen If no operation is performed in defrost time set value changing mode and temperature set value changing mode for 20 seconds, device turns to main operation screen automatically. Change the defrost time set value with increment and decrement buttons.Main Operating ScreenSET Value Screen
Hysteresis Parameter for Compressor Output ( Default = 1 )MODBUS ADDRESS:40004from 1 to 20°C for NTC (-50°C, 100°C) or PTC (-50°C, 150°C)from 1 to 36°F for NTC (-58°F, 212°F) or PTC (-58°F, 302°F)from 0.1to 10.0°C for NTC (-50.0°C,100.0°C) or PTC (-50.0°C,150.0°C)from 0.1 to 18.0°F for NTC (-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F)Defrost Time Parameter It can be adjusted from 0 to 999 minutes.If it is selected 0 automatic or manual defrost is not performed.( Default =10 ) MODBUS ADDRESS:40011Defrost Repeat Cycle Parameter It can be adjusted from 1 to 99 hours.( Default = 1 ) MODBUS ADDRESS:40012I n O N / O F F c o n t r o l a l g o r i t h m , temperature value is tried to keep equal to set value by opening or closing the last control element. ON/OFF controlled system, temperature value oscillates continuously. Temperature value’s oscillation period or amplitude around set value changes according to controlled system. For reducing oscillation period of temperature value, a threshold zone is formed below or around set value and this zone is named hysteresis.
OFF TemperatureControlOutput Set HSt Time HSt Time Minimum Temperature Set Value Parameter(Default =Minimum Value of Device Scale) MODBUS ADDRESS:40005Temperature set value can not be lower than this value. This parameter value can be adjusted from minimum value of device scale to maximum temperature set value parameterMaximum Temperature Set Value Parameter(Default = Maximum Value of Device Scale) MODBUS ADDRESS:40006Temperature set value can not be greater than this value.This parameter value can be adjusted from minimum temperature set value parameter to maximum value of the device scale.Cabinet Sensor Offset Parameter ( Default = 0 ) MODBUS ADDRESS:40007From -20 to 20 °C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C),From -36 to 36 °F for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),From -10.0 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C),From -18.0 to 18.0°F for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F).Defrost Type Selection Parameter ( Default =0 ) MODBUS ADDRESS:40010Electric defrost.Hot gas defrost.Evaporator Sensor Selection Parameter ( Default =1 ) MODBUS ADDRESS:40008Evaporator sensor is inactive.Evaporator sensor is active.Evaporator Sensor Offset Parameter ( Default = 0 ) MODBUS ADDRESS:40009If evaporator sensor selection parameter is 1, then this parameter is observed.From -20 to 20°C for NTC(-50°C, 100°C) or PTC(-50°C, 150°C) , From -36 to 36°F for NTC(-58°F, 212°F) or PTC(-58°F, 302°F),From -10.0 to 10.0°C for NTC(-50.0°C,100.0°C) or PTC(-50.0°C,150.0°C), From -18.0 to 18.0 °F for NTC(-58.0°F,212.0°F) or PTC(-58.0°F,302.0°F).Decimal Seperator Enabling Parameter ( Default = 0 ) MODBUS ADDRESS:40003Disable.Enable.Temperature Unit Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40002°C selected.°F selected. 9ENGLISH Defrost Stopping Temperature Parameter (Default = 2°C) MODBUS ADDRESS:40013 For evaporator sensor selection parameter is 1 (evaporator sensor is active), while defrost operation, if evaporator temperature reaches to temperature that defined at this parameter in a shorter time than parameter, then defrost operation stops. Defrost at Power On Selection and Defrost Delay Parameter It can be adjust from 0 to 99 minutes. When tihs parameter is 0, if decrement button is pressed, is observed. In this condition system goes through a defrost cycle at the end of the defrost repeat cycle time after power on.If this parameter value is between 0 and 99, then system goes through a defrost cycle at the end of the this parameter time after power on. ( Default = ) MODBUS ADDRESS:40014 Compressor Start Delay at Power On Parameter ( Default = 0 ) MODBUS ADDRESS:40019 When power is first applied to the device,This time delay must be expired for activation of compressor. It can be adjusted from 0 to 20 minutes. Minimum Compressor OFF Time Parameter ( Default = 0 )MODBUS ADDREDS:40021 When compressor is inactive, this time delay must be expired for activation of the compressor. It can be adjusted from 0 to 20 minutes. Cabinet Probe Defect Parameter ( Default = 0 ) MODBUS ADDRESS:40023 Compressor Active Time in Case of Cabinet Probe Defect Parameter (Default = 0) MODBUS ADDRESS:40024 If cabinet probe defect parameter is 2, then this parameter is observed. It canbe adjusted from to 99 minutes. Compressor is OFF in case of cabinet probe defect. Compressor is ON in case of cabinet probe defect. Compressor operates periodically according to and time periods in case of cabinet probe defect. Compressor İnactive Time in Case of Cabinet Probe Defect Parameter ( Default = 0 ) MODBUS ADDRESS:40025 If cabinet probe defect parameter is 2, then this parameter is observed. It canbe adjusted from to 99 minutes. Compressor Start-Start Delay Parameter ( Default = 0 ) MODBUS ADDRESS:40020 This time delay must be expired between two activation of the compressor. It can be adjusted from 0 to 20 minutes. Display Status During Defrost Parameter ( Default = 3 ) MODDBUS ADRESS:40015 The cabinet temperature value is displayed during defrost. Cabinet temperature value at the start of the defrost is displayed during defrost. Temperature set value is displayed during defrost. is displayed to indicate the defrost is in progress. Dripping Time Parameter This parameter defines for dripping time after defrost.
(Default = 2) MODBUS ADDRESS:40017 can be adjusted from 0 to 15 minutes. Temperature Alarm Delay After Dripping Parameter (Default = 0) MODBUS ADDRESS:40018 This parameter defines the delay for temperature alarm being active after dripping time completion. It can be adjusted from 0 to 15 minutes. Minimum Compressor ON Time Parameter ( Default = 0 )MODBUS ADRES:40022 When compressor is active, this time delay must be expired for deactivation of the compressor. It can be adjusted from 0 to 20 minutes. Displaying Current Temperature Delay After Defrost Parameter This parameter defines the delay for displaying current temperature being active after defrost. ( Default = 0 ) MODDBUS ADRESS:40016 It can be adjusted from 0 to 255 minutes. 10ENGLISH Temperature Alarm Maximum Parameter (Default =Maximum Value of Device Scale ) MODBUS ADRES:40028 For = 1, this parameter value can be adjusted from temperature alarm minimum parameter value to maximum value of device scale.For = 2, this parameter value is can be adjusted 0 to %50 of the device scale. Temperature Alarm On Delay Time Parameter Temperature Alarm On Delay Time can be defined with this parameter. It can be adjusted from 0 to 99 minutes. (Default = 0) MODBUS ADDRESS:40029 Temperature Alarm Delay After Power On Parameter It can be adjusted from 0 to 99 minutes. (Default = 0) MODBUS ADDRESS:40030 When power is first applied to the device, this time delay must be expired for activation of temperature alarm. Fan Operation Selection Parameter (Default = 1) MODBUS ADDRESS:40031 Fan is OFF. Fan is ON. Fan operates according to the evaporator sensor temperature value. Fan Stopping Temperature Parameter Fan stopping temperature can be defined with this parameter. (Default = 2°C) MODBUS ADDRESS:40032 It can be adjusted from minimum value to maximum value of device scale. Hsyteresis Parameter for Fan Output (Default = 1 ) MODBUS ADDRESS:40033 From 1 to 20°C for NTC (-50°C, 100°C) , from 1 to 36°F for NTC (-58°F, 212°F), from
0.1 to 10.0°C for NTC (-50.0°C,100.0°C), from 0.1 to 18.0°F for NTC (-58.0°F,212.0°F)
Fan Activity Selection According to the Compressor and Defrost (Default = 0) MODBUS ADDRESS:40034 Fan operates according to the parameter. Fan operates according to the parameter, but fan is stopped if commpressor is stops. Fan operates according to the parameter, but fan is stopped during defrost and dripping time. Fan operates according to the parameter.If compressor stops, during defrost and dripping operations fan stops. Fan Delay Time After Completion of Dripping Time Parameter (Default = 2) MODBUS ADDRESS:40035 Fan Delay Time After Completion of Dripping Time is defined with this parameter. It can be adjusted from 0 to 15 minutes. Fan operates according to the ( cabinet - evaporator ) temperature value. Temperature Alarm Minimum Parameter For = 1, this parameter value can be adjusted from minimum value of device scale to temperature alarm maximum parameter value. For = 2, this parameter value can be adjusted 0 to %50 of the device scale. (Default = Minimum Value of Device Scale) MODBUS ADRES:40027 Relative alarm is selected. Alarm operates according to the set value. If cabinet temperature value is below ( Set - ) or above ( Set + ), alarm ocurs. Temperature Alarm Function Selection Parameter ( Default = 0 ) MODBUS ADRES:40026 Temperature alarm function is inactive. Absolute alarm is selected. If temperature lower than and higher than , then alarm is on. 11ENGLISH Digital Input Contact Selection Parameter ( Default = 1 ) MODBUS ADDRESS:40036 Digital input is inactive. NO “normally open” digital input is active when the contact is closed. NC “normally close” digital input is active when the contact is opened. Digital Input Function Selection Parameter If digital input contact selection parameter ( Default = 0 ) MODBUS ADDRESS:40037 value = 0, this parameter is not observed. When the digital input is active, fan is stopped. screen will be displayed. When the digital input is active, compressor is stopped. screen will be displayed and defrost operation will be disabled. If Buzzer function selection parameter = 2 or 4 buzzer is active. When the digital input is active, first fan stops, 10 seconds later compressor stops. will be displayed at main operation screen. When the digital input is active, defrost starts. When the digital input is active, alarm will be active. will be displayed at main operation screen. If Buzzer function selection parameter = 2 or 4 buzzer is active. Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40039 Buzzer is inactive. Buzzer is active during defrost operation. Buzzer is active if an alarm occurs. Buzzer is active during cabinet sensor failures. Buzzer is active during defrost, alarm or cabinet sensor failures. Button Protection Parameter ( Default = 0 ) MODBUS ADDRESS:40041 There is no protection. Defrost time set value can not be changed and manual defrost is not available. Temperature set value can not be changed. Defrost time set value and temperature set value can not be changed and manual defrost is not available. Buzzer Active Time If buzzer function selection parameter Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99 minutes. When this parameter is 1, if decrement button is pressed, is observed. In this condition buzzer is active till buzzer silence button is pressed. ( Default = ) MODBUS ADDRESS:40040 value = 0, this parameter is not observed. Programming Mode Accessing Password It is used for accessing to programming mode. It can be adjusted from 0 to 999. If it is 0, password is not entered for accessing to the parameters. If password is ‘12’ only , , can be accesible. ( Default = 0 ) MODBUS ADDRESS:40044 Digital Input Effect Time Parameter If digital input contact selection parameter ( Default = ) MODBUS ADDRESS:40038 value = 0, this parameter is not observed. For digital input function selection parameter = 0 or 2, maximum effect time of digital input is determined with this parameter. It can be adjust from 0 to 120 minutes. When this parameter is 0, if decrement button is pressed, is observed. In this condition the effect will be ended when digital input is deactive. Defrost time can not be changed,Defrost ON/OFF operation is available. PROKEY communication selected. Communication Mode Selection Parameter( Default = 0 ) MODBUS ADRESS:40042 RS485 communication selected. Slave ID Parameter ( Default = 1 ) MODBUS ADDRESS=40043 Device communication address parameter (1 to 247). 12ENGLISH
6.3 Operation Graphics of ESM-3712-CN Cooling Controller
Power Hst SET Comp.Output Led
6.4 Entering To The Programming Mode, Changing and Saving Parameter
1- message blinking . Sno sensor connection. While this message shown on this display, if buzzer function selection parameter is 3 or 4, internal buzzer starts to operate. .Cabinet temperature sensor failure ensor connection is wrong or there is
Evaporator temperature sensor failure. sensor connection is wrong or there is no sensor connection. message blinking.
8. Manual Defrost Operation with Defrost Button
8.1 Manual Defrost Operation with Digital Input
Protection Against Mechanical Impacts : 1 Joule (IK06) Device Type : Cooling Controler Housing&Mounting : 76 mm x 34.5 mm x71 mm plastic housing for panel Panel cut-out is 71 x 29 mm Protection Class :NEMA 4X (IP65 at front, IP20 at rear )
All order information of ESM-3712-CN Cooling Controller are given on the table at left. User may form appropriate device configuration from information and codes that at the table and convert it to the ordering codes. Firstly, supply voltage then other specifications must be determined. Please fill the order code blanks according to your needs. Please contact us, if your needs are out of the standards.V Ş Vac, Z Ş VdcŞ Vdc or Vac can be appliedW
Relay Output ( 16(8) A@250 V V at resistive load, 1 NO )Compressor Output Temp. Sensor which is given with ESM-3712-CN Supply VoltageAInput Type Scale(°C)ESM-3712-CN (77x35 DIN Size)
NTC-M5L20.K1.5 (NTC Sensor, thermoplastic moulded with
Relay Output ( 5 A@250 V V at resistive load, 1 NO )Defrost Output
Relay Output ( 5 A@250 V V at resistive load, 1 NO )Fan OutputHI
NTC-M6L50.K1.5 (NTC Sensor, stainless steel housing with
Customer Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is selected as NTC, sensor type (V =0,3 or 4) must be declared in ordering information.
PTC-M6L40.K1.5 (PTC Air Probe with 1.5 mt silicon cable)
PTC (Note-1) Your Technology Partner www.emkoelektronik.com.tr Thank you very much for your preference to use Emko Elektronik products, please visit our web page to download detailed user manual.
EasyManual