Camille Bauer Sineax A210 - Measuring equipment

Sineax A210 - Measuring equipment Camille Bauer - Free user manual and instructions

Find the device manual for free Sineax A210 Camille Bauer in PDF.

📄 32 pages English EN 💬 AI Question
Notice Camille Bauer Sineax A210 - page 20
View the manual : Français FR Deutsch DE English EN

User questions about Sineax A210 Camille Bauer

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

L'email reste privé : il sert seulement à vous prévenir si quelqu'un répond à votre question.

No questions yet. Be the first to ask one.

Download the instructions for your Measuring equipment in PDF format for free! Find your manual Sineax A210 - Camille Bauer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Sineax A210 by Camille Bauer.

USER MANUAL Sineax A210 Camille Bauer

(outgoing low tariff) (outgoing high tariff) (incoming low tariff) (incoming high tariff)

(outgoing low tariff) (outgoing high tariff) (incoming low tariff) (incoming high tariff)

> 2 s (retour au niveau d’affi chage)20 Brief description The A 210/A 220 are panel mounting instruments for monitoring AC systems with dimensions 96 x 96 mm (A 210) and 144 x 144 mm (A 220). The following measurements are acquired: voltages, currents, frequency, and phase angles in single phase or 3 phase systems. From these, the active power, reactive power, apparent power, active energy, reactive energy, and the power factor and the neutral current can be calculated. With the use of voltage and current transformers, the instrument can be used for measurements in medium and high voltage systems. The transformation ratios are confi gurable for the direct display of all measurements. The A 210/A 220 instrument is used as a display with two S0 pulse or limit value outputs. Technical data (for more detailed information please see data sheet, download under www.camillebauer.com) Measuring inputs Nominal frequency: 50, 60 Hz Nominal input voltage: Phase-phase: 500 V Phase - N: 290 V Nominal input current: 5 A or 1 A Continuous overload withstand 10 A at 346 V single phase AC system 10 A at 600 V three phase system Short duration overload withstand Input variable Number of applications Duration

overload Interval between two overloads 577 V LN 10 1 s 10 s 100 A 10 1 s 100 s 100 A 5 3 s 5 min Measuring ranges U, I, S: ≤ 120% of nominal value P, Q: ≤ ± 120% of nominal value F: 45 to 65 Hz cosϕ: ± 1 Pulse/Limit value outputs Depending on the function selected, the two digital outputs can be used either as pulse outputs for active and reactive energy or as limit signals. The outputs are passive, and are galvanically isolated from all the other circuits by opto-couplers. They are suitable to drive tariff devices (S0-standard DIN 43 864) or 24 V-relais.

ext ≤ 40 V DC (OFF: leakage current ≤ 0.1 mA)

≤ 150 mA (ON: terminal voltage ≤ 1.2 V)

ext Limit value outputs Any measured value can be allocated to the limit values. Impulse outputs Active and reactive energy impulses can be generated for driving electronic and electromechanical energy meters. Power supply DC, AC power pack 50 to 400 Hz 100 to 230 V AC/DC ±15% or 24 to 60 V AC/DC ±15% (UL) 85 to 125 V DC Power input: 3 VA (without extension module) A marked and easily accessible current limiting switch has to be arranged in the vicinity of the device for turning off the power supply. Fusing should be 10 Amps or less and must be rated for the available voltage and fault current. Reference conditions acc. to IEC 688 resp. EN 60 688 Sine 50 - 60 Hz, 15 - 30°, application group II Measurement accuracy (related to nominal value) Current, voltage ± 0.5% Power ± 1.0% Power factor ± 1.0% Energy ± 1.0% Frequency ± 0.02 Hz (abs.) Environmental conditions Operating temperature: -10 to +55 °C Storage temperature: -25 to +70 °C Relative humidity: ≤ 75% Altitude: 2000 m max. Indoor use statement Safety Protection class: II (voltage inputs with protection impedances) Measuring category: III Pollution degree: 2 Measurement voltage: 300 V Test voltage: Between current inputs, power supply, digital outputs, terminals of the plugged-in module: 3700 V / 50 Hz / 1 min. At voltage inputs:

Module connections: The pin rail at the back is connected to the voltage inputs via a protec- tion impedance. Only the permitted modules can be plugged-in! Enclosure protection: IP 20 Note of maintenance No maintenance is required. Display The measurement display is 3 digit resp. 4 digit (frequency) and right justifi ed, with the exception of the energy values which are 8 digits. The left-hand 7-segment display is for the sign or an abbreviation. Abbreviations: Maximal value Minimal value Average value Max. average value Minimal value for power factor; the worst out of the 3 values of P1, P2, or P3 is displayed Neutral current Inductive Capacitive Incoming Outgoing Interval active power Interval reactive power Interval apparent power21 Last interval; t-0 , ... Previous interval; t-1, -2, -3, -4 Overload, out of range indicator ∑ System value Δ Delta voltage Energy meter High tariff Low tariff Current time t t-0 t-1 t-2 t-3 t-4 Interval 0 Interval 1 Interval 2 Interval 3 Interval 4 Zero value suppression PF resp. cosϕ: Display ---, if Sx < 0.2% Snenn Currents: Display 0, if Ix < 0.1% Inenn Commissioning The multi-functional power monitor is made operational by swit- ching on the power supply. The following appears sequentially on the display:

1. Segment tests: all the segments of the displays and all the LEDs

3. The 3 line voltages at switching on.

Loss of the power supply All the values configured remain during a loss of the power supply. On reconnecting the power supply, the last mode selected is displayed. Electrical connections Safety Disconnects The mains supply power to the instrument must be installed downstream from a switched current limiting device. The circuit protection device should be 20 Amps or less, and must be rated for the available voltage and fault current; 5 Amp fuses are preferred. WARNING All mains supply power to the instrument must be installed downstream from a switched current limiting device. The circuit protection device should be 20 Amps or less, and must be rated for the available voltage and fault current; 5 Amps are preferred. The national provisions (e.g. in Germany VDE 0100 “Conditions concerning the erection of heavy current facilities with rated voltages below 1000 V”) have to be observed in the installation and material selection of electric lines! When using external PT’s or CT’s refer to the manufacturer’s information for connections for vol- tage and current monitoring. The electrical connections are identical for the SINEAX A 210 and A 220.

Power supply Pulse / Limit value outputs Measuring input, acc. to measuring mode Jumper 1 2 +

SINEAX A210 UL: 3~300V 5A 50/60Hz CAT III IEC: 3~500/290V 5A 50/60Hz CAT III Mat: 149783/1234567/001 Man: 10/02 NLBxxxx 100-230V AC 85-125V DC 50-400Hz 3VA 210-121200 No. 1 Symbol Meaning Device may only be disposed of in a professional manner! Double insulation, device of protection class 2 CE conformity mark. The device fulfi lls the require- ments of the applicable EC directives. Products with this mark comply with both the Canadian (CSA) and the American (UL) requirements Caution! General hazard point. Read the operating instructions. General symbol: Input General symbol: Output General symbol: Power supply CAT III Measurement category CAT III for current and vol- tage inputs22 System/ application Terminals

4 wire 3 phase symmetric load I: L1 Connect the voltage according to the following table for current measurement in L2 or L3: Current trans. Terminals 2 11 L2 1 3 L2 N L3 1 3 L3 N 4 wire 3 phase asymmetric load 3 single-pole insulated voltage transformers in high-voltage system

Single phase AC system

3wire 3 phase symmetric load I: L1 Connect the voltage according to the following table for current measurement in L2 or L3: Current Terminals 2 5 8 transf. L2 1 3 L2 L3 L1 L3 1 3 L3 L1 L2

Active power system P 125 kW ∑ Maximum value P max.

Power factor PF2, cosϕ

Power factor PF3, cosϕ

Power factor system PF, cosϕ

Units display System display Up key Down key Key for programming and display 7-segment display top centre bottom Display and operating are identical for the SINEAX A 210 and A 220 Determination of measured quantities: The calculation of the measurements is made in accordance with DIN 40 110, with the exception of the reactive power. This is calculated by the SINEAX A 210/A 220 as a signed value. Transducers and displays can possibly display different values for the reactive power in the same power system. The reason is the different calculation methods.24 Display levels Within a level (1, 2, 3 …) you can change the 3 displays to the next mode (a, b, c, ...) with the

key. From the last mode, the display changes to mode a again. Change to the next level with the and keys. 4 wire asymmetric load

11 Pint0 Pint1 Pint2 Pint3 Pint4 12 Qint0 Qint1 Qint2 Qint3 Qint4 13 Sint0 Sint1 Sint2 Sint3 Sint4 Operating Brightness 13 levels: continuous pressing of the key (darker), or the key (brighter). Delete / Clear To delete the min. or max. values, or the energy values of the dis- played measurements, press the keys at the same time. Locking The reset function for the energy meters can be locked by setting the jumper at the rear of the instrument to the position LOCK.

  • = Default) Meaning Hints 4-line system, unbalanced load 3-line system, unbalanced load 4-line system, balanced load 3-line system, balanced load Single-line system System configuration Primary voltage of an external transformer on the voltage (line-to-line voltage)

First you enter any 3-digit number followed by the appropriate power unit selection in steps of factor 10 Secondary voltage of an external transformer on the voltage input (line-to-line voltage)

Primary current of an external transformer on the current input

Secondary current of an external transformer on the current input

100 V to 999 kV 100 V to 999 V

(4 lines unbalanced) (3 lines unbalanced) (4 lines balanced) (3 lines balanced) (1 line)

Parameters overview Programming All parameters may be displayed at any time. For modifi cations the jumper on the backside of the device must be removed (not on position LOCK). The following table shows all parameters with their adjustable ranges or possible selections respectively. The black numbers give a cross- reference to the appropriate diagram position on page 30. Starting at the measurands display by pressing the key

you may change to the menu level. Afterwards you can select the desired menu item by pressing the key

shortly. Use to enter the level where the desired parameter is dis played. Pressing

shortly will force the selectable element to fl ash. The fl ashing content may be modifi ed using the keys or . Press

for a longer time to leave the parameter or menu level. All settings will remain non-volatile stored even in case of power- fail. Hints: First you have to set the system confi guration and the transformer ratios because further measurand selections, alarm limit settings etc. will depend on them. The programming may be modifi ed via an optional extension mo- dule as well. Locking the confi guration Place the jumper in the LOCK position. The confi guration of all parameters is disabled. LOCK Factory Default Brightness: (mid setting) Limit value / S01: Off Limit value / S02: Off Transformer ratio: 1 : 1 Jumper: Not in the LOCK position Connecting mode: 4 wire asymmetric load Synchronizing interval: 15 min.26 Topmost display Middle display No. Undermost display (Selection,

  • = default) Meaning Hints Operating mode of both digital outputs “out.1” and “out.2”

Output switched-off Simulation via interface module is still possible Energy pulse output The output generates energy pulses depending on the rate set under . The meter measurands to output may be selected under .

Alarm output If the alarm limit is exceeded the output will be active (current flows). If the measur- and is below limit the output will be passive. The source of the monitored is selected under . (mode) Alarm supervision source This selection is presented only if operating mode is set to ALM previously

Frequency Neutral current Apparent power interval Reactive power interval Active power interval Power factor (cos ϕ) Apparent power Reactive power Active power Line-neutral voltage

Voltage Average current (bimetal) Phase current Line-to-line voltage Alarm limit for ON-state The maximum values of the alarm limits depend on the possible measuring range (fixed by hardware), converted into possible primary values given by the selected system configuration and transformation ratios. Alarm limit for OFF-state

Line Type 1L', '3Lb', '4Lb' '4Lu''3Lu' : 'A.on'= OR-operation of line-measurands 'A.off'= AND-operation of line-measurands

  • = default) Meaning Hints Source of energy meters for pulse output

Reactive energy capacitive, low tariff Reactive energy capacitive, high tariff Reactive energy inductive, low tariff Reactive energy inductive, high tariff Active energy outgoing, low tariff Active energy outgoing, high tariff Active energy incoming, low tariff Active energy incoming, high tariff Number of pulses per displayed energy unit. After entering a number from 1 to 5000 you may input the scaling: Basic unit (-), kilo (k), Mega (M) or Giga (Mk) (energy rate) Time interval in minutes for the calculation of power intervals 0 = Interval controlled via the bus

(outgoing low tariff) (outgoing high tariff) (incoming low tariff) (incoming high tariff)

1 to 5000 / Wh to GWh 1 to 60 min. For external synchronization, the value displayed is not relevant

Examples Example 1: Programming the system confi guration (3-line, unbalanced load

Press (present setting is displayed)

Press / to select desired setting

(takes over new setting). Display stops fl ashing.

(transformer ratio menu)28

Press (present setting of primary voltage)

(leftmost digit fl ashes)

Press / until desired number appears

Press / until desired number appears

(rightmost digit fl ashes)

Press / until desired number appears

Press / until the decimal point is on the desired position and the kilo/Mega display is correct

Press (present setting of secondary voltage)

14. Programming procedure same as for primary

Press until the topmost display as shown

Press (present setting of synchronization interval in minutes)

Press / until desired number appears

(right digit fl ashes)

Press / until desired number appears

3. Use or to set the fl ashing content.

5. Change to the next parameter by pressing or and go

go back to menu level with and go on with 1. Return to measurands display: Press

EC DECLARATION OF CONFORMITY

EC DECLARATION OF CONFORMITY

  • with extension module
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Camille Bauer

Model : Sineax A210

Category : Measuring equipment