DAIKIN FXSQ15A2VEB - Air Conditioning

FXSQ15A2VEB - Air Conditioning DAIKIN - Free user manual and instructions

Find the device manual for free FXSQ15A2VEB DAIKIN in PDF.

📄 140 pages English EN Download 💬 AI Question 12 questions ⚙️ Specs
Notice DAIKIN FXSQ15A2VEB - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product type Ceiling cassette air conditioner (indoor unit for VRV system)
Brand Daikin
Model FXSQ15A2VEB
Refrigerant R410A (GWP 1975)
Power supply 220-240 V, 50/60 Hz, single-phase
Minimum circuit amperage (MCA) 0.4 A
Maximum fuse amperage (MFA) 16 A
Ceiling opening dimensions (W x D) 550 x 588 mm
Adjustable external static pressure Up to 150 Pa (depending on setting)
Main functions Cooling, heating (with heat pump), ventilation, automatic airflow adjustment, wired or wireless remote controller (optional)
Maintenance and cleaning Washable air filter (water or vacuum); filter cleaning indicator; heat exchanger cleaning by qualified personnel
Safety Ground fault circuit interrupter, fuses (T 3.15 A / 5 A / 6.3 A), forced stop via external input, automatic restart after power cut
Spare parts and repairability Spare parts available via Daikin network; replacement air filter optional; remote control optional
General information Installation and maintenance by certified technician; compliant with EN378 standard; sound level < 70 dB(A)
Supplied accessories Metal bracket, drain hose, washers, sealing pads, insulation, installation manual

Frequently Asked Questions - FXSQ15A2VEB DAIKIN

What type of refrigerant does the FXSQ15A2VEB use?
The FXSQ15A2VEB uses refrigerant R410A with a global warming potential (GWP) of 1975.
How to clean the air filter?
Clean the filter using a vacuum cleaner or by washing with water and a neutral detergent. Let it dry in the shade before reinstalling. Press the filter reset button after cleaning.
What to do if an error code appears on the remote controller?
Refer to the manual to identify the code: for example, R8 = indoor unit power supply error, C1 = transmission error, UH = outdoor unit power off. Contact a technician if necessary.
Can a wireless remote controller be installed for this model?
Yes, an optional wireless remote controller can be used. The distance between the remote controller and the indoor unit must be sufficient to avoid interference from fluorescent lamps.
How to adjust the external static pressure?
The external static pressure is adjusted via the remote controller in field setting mode (mode 13/23, 1st code 6, 2nd code according to desired pressure). There is also an automatic airflow adjustment.
What is the maximum lift height of the drain pump?
The drain pump can lift water up to 625 mm. The recommended height is 300 mm to reduce noise.
What to do before a long shutdown period?
Run the unit in fan mode for half a day to dry the interior, then turn off the main power switch.
How to perform a forced stop from outside?
Connect a dry contact to terminals T1 and T2 of the transmission terminal block. Set the remote controller to mode 12, 1st code 1, 2nd code 01 (forced stop) or 02 (run/stop).
What precautions are there for brazing refrigerant pipes?
When brazing, circulate nitrogen at 0.02 MPa in the pipes to prevent oxide formation. Use equipment suitable for R410A.
How to test operation after installation?
Start the unit in cooling mode and check water drainage. If an error code appears (e.g., U3), the operation test is not complete. Refer to the outdoor unit manual.

User questions about FXSQ15A2VEB DAIKIN

2 questions about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

What is the replacement filter for the Daikin FXSQ15A2VEB air conditioner?
Frequently Asked Questions - 3 d
Response Notice-Facile

The replacement filter (or replacement air filter) is an optional spare part for the Daikin FXSQ15A2VEB air conditioner. It is the air filter that needs to be regularly cleaned or replaced to maintain the performance of the unit.

When to replace the filter?

According to the manual, the filter should be replaced when the dust becomes impossible to clean. The unit's display will alert you when it is time to clean the air filter.

Normal filter maintenance

Before replacing it, the filter can be cleaned in two ways:

  • Use a vacuum cleaner
  • Wash with water and a neutral detergent (a soft brush if very dirty, then let it dry in the shade)

Ordering the replacement filter

Replacement air filters are available optionally and can be ordered through the Daikin distribution network. Feel free to contact an authorized Daikin dealer to obtain the reference compatible with your FXSQ15A2VEB model.

Tip: After cleaning the filter, press the filter reset button to reset the maintenance indicator.

Respond (be the first)
What type of filter does the DAIKIN FXSQ15A2VEB air conditioner contain?
Frequently Asked Questions - 3 d
Response Notice-Facile

The DAIKIN FXSQ15A2VEB contains a washable air filter, which can be cleaned and reused.

Filter characteristics

This filter guarantees a dust recovery efficiency of at least 50% (according to the gravimetric standard) when the unit is installed with a suction duct.

How to clean the filter

You have two options for maintenance:

  • With a vacuum cleaner: simply vacuum the filter to remove dust
  • Water washing: if the filter is heavily soiled, wash it with water and a neutral detergent, then let it dry in the shade before reinstalling it

Cleaning indicator

The unit has a light indicator that alerts you when it is time to clean the air filter. Follow this signal to maintain the efficiency of your air conditioner.

Filter replacement

If cleaning is no longer sufficient and the filter is too worn, optional replacement filters are available from the DAIKIN authorized distributor network.

Respond (be the first)

Download the instructions for your Air Conditioning in PDF format for free! Find your manual FXSQ15A2VEB - DAIKIN and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. FXSQ15A2VEB by DAIKIN.

USER MANUAL FXSQ15A2VEB DAIKIN

INSTALLATION AND OPERATION MANUAL

DAIKIN FXSQ15A2VEB - INSTALLATION AND OPERATION MANUAL - 1

System air conditioners

Installation and operation manual VRV System air conditioners

Daikin Industries Czech Republic s.r.o.

01 (G) declares under its sole responsibility that the air conditioning models to which this declaration relates:
02 (B) erklaf auf seine allgemeine Verantwortung das die Modelle der Klimageräte für die dieser Erfahrung bestimm ist. 03 (C) definiert es an eine gewichtete variable, zu der variable nicht standardisierte variabeler Definition.
M (m) warkhard hisdi ene axisie ueantvortgelikhd de da amondioning unita wason dge warkring he
05 (E) declares bala su unica responsabilitad que los modeos de aire acondicionado a los cuales hace reference la de
06 (1) dichiarare sotso sua responsabilita che i condizionator modello a cui e rifita esta dichiarazione;
07 @8 5nKwE PE ANKOBOTIK Tng cUOuN on ta oVtA uau KIpaATIKUv CooKEuON Oa omOc AovpePoi n mopo
08 (P) declares so sua exclusiva responsabildte que os modeos de ar concionacion a que esta declaracao se refere:

FXSQ15A2VEB, FXSQ20A2VEB, FXSQ25A2VEB, FXS
FXSQ100A2VEB, FXSQ125A2VEB, FXSQ140A2VEB,

FXSQ15A2VEB, FXSQ20A2VEB, FXSQ25A2VEB, FXSQ32A2VEB, FXSQ40A2VEB, FXSQ50A2VEB, FXSQ63A2VEB, FXSQ80A2VEB,

01in conformità with the following standard(s) or other normative document(s), provided that these are used in accordance with our instructions:08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 372 373 374 375 376 377 378 379 380 381 382 383 384 385 386 387 388 389 390 391 392 393 394 395 396 397 398 399 400 401 402 403 404 405 406 407 408 409 410 411 412 413 414 415 416 417 418 419 420 421 422 423 424 425 426 427 428 429 430 431 432 433 434 435 436 437 438 439 440 441 442 443 444 445 446 447 448 449 450 451 452 453 454 455 456 457 458 459 460 461 462 463 464 465 466 467 468 469 470 471 472 473 474 475 476 477 478 479 480 481 482 483 484 485 486 487 488 489 490 491 492 493 494 495 496 497 498 499 500 501 502 503 504 505 506 507 508 509 510 511 512 513 514 515 516 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 553 554 555 556 557 558 559 560 561 562 563 564 565 566 567 568 569 570 571 572 573 574 575 576 577 578 579 580 581 582 583 584 585 586 587 588 589 590 591 592 593 594 595 596 597 598 599 600 601 602 603 604 605 606 607 608 609 610 611 612 613 614 615 616 617 618 619 620 621 622 623 624 625 626 627 628 629 630 631 632 633 634 635 636 637 638 639 640 641 642 643 644 645 646 647 648 649 650 651 652 653 654 655 656 657 658 659 660 661 662 663 664 665 666 667 668 669 670 671 672 673 674 675 676 677 678 679 680 681 682 683 684 685 686 687 688 689 690 691 692 693 694 695 696 697 698 699 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718 719 720 721 722 723 724 725 726 727 728 729 730 731 732 733 734 735 736 737 738 739 740 741 742 743 744 745 746 747 748 749 750 751 752 753 754 755 756 757 758 759 760 761 762 763 764 765 766 767 768 769 770 771 772 773 774 775 776 777 778 779 780 781 782 783 784 785 786 787 788 789 790 791 792 793 794 795 796 797 798 799 800 801 802 803 804 805 806 807 808 809 810 811 812 813 814 815 816 817 818 819 820 821 822 823 824 825 826 827 828 829 830 831 832 833 834 835 836 837 838 839 840 841 842 843 844 845 846 847 848 849 850 851 852 853 854 855 856 857 858 859 860 861 862 863 864 865 866 867 868 869 870 871 872 873 874 875 876 877 878 879 880 881 882 883 884 885 886 887 888 889 890 891 892 893 894 895 896 897 898 899 800 801 802 803 804 805 806 807 808 809 810 811 812 813 814 815 816 817 818 819 820 821 822 823 B

DAIKIN FXSQ15A2VEB - Daikin Industries Czech Republic s.r.o. - 1

DAIKIN FXSQ15A2VEB - Daikin Industries Czech Republic s.r.o. - 2

DAIKIN INDUSTRIES CZECH REPUBLIC s.r.o.

U Nové Hospody 1/1155, 301 00 Plzen Skvrnany,

Czech Republic

Tetsuya Baba

Managing Director
Pilsen, 2nd of March 2015

Contents Page

Before installation. 1

Important information regarding the refrigerant used. 2

Selecting installation site. 2

Preparations before installation. 2

Indoor unit installation 3

Installing the duct 3

Refrigerant piping work 4

Drain piping work 5

Electric wiring work 6

Wiring example and how to set the remote controller 7

Wiring example 7

Field setting. 8

Installation of the decoration panel. 10

Test operation. 10

Maintenance. 10

Disposal requirements 11

Wiring diagram. 12

DAIKIN FXSQ15A2VEB - Contents Page - 1

READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFICALLY DESIGNED FOR USE WITH THE EQUIPMENT AND HAVE THEM INSTALLED BY A PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE AND INFORMATION.

The English text is the original instruction. Other languages are translations of the original instructions.

DAIKIN FXSQ15A2VEB - Contents Page - 2

Installation must be done by a licensed technician. The choice of materials and installation must comply with the applicable national and international regulations.

Before installation

  • Leave the unit inside its packaging until you reach the installation site. Where unpacking is unavoidable, use a sling of soft material or protective plates together with a rope when lifting, this to avoid damage or scratches to the unit.
    When unpacking the unit or when moving the unit after unpacking, be sure to lift the unit by holding on to the hanger bracket without exerting any pressure on other parts, especially on refrigerant piping, drain piping and other resin parts.
    Refer to the installation manual of the outdoor unit for items not described in this manual.
    Caution concerning refrigerant series R410A:

The connectable outdoor units must be designed exclusively for R410A.
- Do not place objects in direct proximity of the outdoor unit and do not let leaves and other debris accumulate around the unit. Leaves are a hotbed for small animals which can enter the unit. Once in the unit, such animals can cause malfunctions, smoke or fire when making contact with electrical parts.

Precautions

Do not install or operate the unit in rooms mentioned below.

  • Places with mineral oil, or filled with oil vapour or spray like in kitchens. (Plastic parts may deteriorate.)
  • Where corrosive gas like sulphurous gas exists. (Copper tubing and brazed spots may corrode.)
  • Where volatile flammable gas like thinner or gasoline is used.
  • Where machines generating electromagnetic waves exist. (Control system may malfunction.)
  • Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot (e.g. in factories). Also in vehicles or vessels.

  • Do not install accessories on the casing directly. Drilling holes in the casing may damage electrical wires and consequently cause fire.
    This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be supervised to ensure that they do not play with the appliance.

This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
Sound pressure level is less than 70dB(A).

Accessories

Check if the following accessories are included with your unit.

Metal clamp 1 pieceDrain hose 1 pieceWasher for hanging bracket 8 pieces1 2 Medium sealing pad 2 pieces
Large sealing pad 1 pieceInsulation for fitting for liquid pipe 1 piece for gas pipe 1 pieceLong sealing 2 piecesInstallation and operation manual
Screws for duct flanges 1 set 40 pieces.4 tie wraps

Screws for fixing panels are attached to the air inlet panel.

Optional accessories

There are two types of remote controllers: wired and wireless. Select a remote controller according to customer request and install in an appropriate place. Refer to catalogues and technical literature for selecting a suitable remote controller.
- When installing bottom suction: air inlet panel and canvas connection for the air inlet panel.

For the following items, take special care during construction and check after installation is finished

Tick ✓ when checked
Is the indoor unit fixed firmly?The unit may drop, vibrate or make noise.
Is the gas leak test finished?It may result in insufficient cooling or heating.
Is the unit fully insulated and checked for air leaks?Condensate water may drip.
Does drainage flow smoothly?Condensate water may drip.
Does the power supply voltage correspond to that shown on the name plate?The unit may malfunction or components may burn out.
Are wiring and piping correct?The unit may malfunction or components may burn out.
Is the unit safely grounded?Dangerous at electric leakage.
Is the wiring size according to specifications?The unit may malfunction or components may burn out.
Is nothing blocking the air outlet or inlet of either the indoor or outdoor units?It may result in insufficient cooling or heating.
Are refrigerant piping length and additional refrigerant charge noted down?The refrigerant charge in the system might not be clear.
Are the air filters fixed property (when installing with rear duct)?Maintenance of the air filters can be impossible.
Is the external static pressure set?It may result in insufficient cooling or heating.

Notes to the installer

  • Read this manual carefully to ensure correct installation. Be sure to instruct the customer how to properly operate the system and show him/her the enclosed operation manual.
    Explain to the customer what system is installed on the site. Be sure to fill out the appropriate installation specifications in the chapter "What to do before operation" of the outdoor unit operation manual.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Refrigerant type: R410A

GWP(1) value: 1975

(1) GWP = global warming potential

Periodical inspections for refrigerant leaks may be required depending on European or local legislation. Please contact your local dealer for more information.

Selecting installation site

(See figure 1 and figure 2)

1 Select an installation site where the following conditions are fulfilled and that meets your customer's approval.
- Where optimum air distribution can be ensured.
- Where nothing blocks air passage.
- Where condensate water can be properly drained.
- Where the false ceiling is not noticeably on an incline.
- Where sufficient clearance for maintenance and service can be ensured.
- Where there is no risk of flammable gas leaking.
- The equipment is not intended for use in a potentially explosive atmosphere.
- Where piping between indoor and outdoor units is possible within the allowable limit. (Refer to the installation manual of the outdoor unit.)
- Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is kept.)
- When installing the wireless remote controller kit, the distance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room. The indoor unit must be installed as far as possible away from fluorescent lights.
- Do not place objects that are susceptible to moisture directly beneath the indoor or outdoor units. Under certain conditions, condensation on the main unit or refrigerant pipes, air filter dirt or drain blockage may cause dripping, resulting in fouling or failure of the object concerned.

2 Ensure that a protective guard is installed on air suction and air outlet side to prevent that the fan blades or heat exchanger be touched.

The protection must comply with relevant European and national regulations.

3 Use suspension bolts for installation. Check whether the ceiling is strong enough to support the weight of the indoor unit. If there is a risk, reinforce the ceiling before installing the unit.

1 Service space
2 Drain pipe
3 Power supply wiring port
4 Transmission wiring port
5 Maintenance drain outlet
6 Gas pipe
7 Liquid pipe

Preparations before installation

1 Relation of ceiling opening to unit and suspension bolt position. (See figure 5)

Model A (mm) B (mm)
15~32 550 588
40~50 700 738
63~80 1000 1038
100~125 1400 1438

1 Indoor unit
2 Pipe
3 Suspension bolt pitch (x4)
4 Suspension bolt pitch distance

For installation, choose one of the possibilities as listed further.

Standard rear suction (See figure 6a)

1 Ceiling surface
2 Ceiling opening
3 Service access panel (optional accessory)
4 Air filter
5 Air inlet duct
6 Duct service opening
7 Interchangeable plate

Installation with rear duct and duct service opening (See figure 6b)

Installation with rear duct, no duct service opening (See figure 6c)

DAIKIN FXSQ15A2VEB - Standard rear suction (See figure 6a) - 1

Before installation of the unit (in case of installation with duct, but no duct service opening): modify the position of the air filters.

1 Remove the air filter(s) at the outside of the unit
2 Remove the interchangeable plate
3 Install the air filter(s) from the inside of the unit
4 Reinstall the interchangeable plate

DAIKIN FXSQ15A2VEB - Standard rear suction (See figure 6a) - 2

DAIKIN FXSQ15A2VEB - Standard rear suction (See figure 6a) - 3
NOTE

When installing an air inlet duct, select fixing screws that shall stick out maximum 5mm at the inside of the flange to protect the air filter from damage during maintenance of the filter.

1 Air inlet duct
2 Inside of the flange
3 Fixing screw

DAIKIN FXSQ15A2VEB - Standard rear suction (See figure 6a) - 4

Mounting the air inlet panel with a canvas connection (See figure 7a)

Mounting the air inlet panel directly (See figure 7b)

1 Ceiling surface
2 Ceiling opening
3 Air inlet panel (Optional accessory)
4 Indoor unit (Back side)
5 Canvas connection for air inlet panel (Optional accessory)

Model A (mm)

15~32 610
40~50 760
63~80 1060
100~125 1460

Bottom suction (See figure 7c)

DAIKIN FXSQ15A2VEB - Bottom suction (See figure 7c) - 1
NOTE

The unit can be used with bottom suction by replacing the interchangeable plate by the air filter holding plate.

1 Air filter holding plate with air filter(s)
2 Interchangeable plate

DAIKIN FXSQ15A2VEB - Bottom suction (See figure 7c) - 2
NOTE

For other installation than standard installation, contact your Daikin dealer for details.

2 The fan speed for this indoor unit is preset to provide standard external static pressure.

3 Install the suspension bolts.

(Use M10 size bolt for the suspension bolt.) Use anchors for existing ceilings, and a sunken insert, sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to bear the weight of the unit.

Installation example

(See figure 3)

1 Anchor
2 Ceiling slab
3 Long nut or turn-buckle
4 Suspension bolt
5 Indoor unit

All the above parts are field supplied.
For other installation than standard installation, contact your dealer for details.

Indoor unit installation

When installing optional accessories (except for the air inlet panel), read also the installation manual of the optional accessories. Depending on the field conditions, it may be easier to install optional accessories before the indoor unit is installed.

1 Install the indoor unit temporarily.

  • Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and washer from the upper and lower sides of the hanger bracket. (See figure 4)

1 Nut (field supply)
2 Washer for hanger bracket (supplied with the unit)
3 Tighten (double nut)

2 Check if the unit is horizontally levelled.

  • Do not install the unit tilted. The indoor unit is equipped with a built-in drain pump and float switch. (If the unit is tilted against condensate flow, the float switch may malfunction and cause water to drip.)
  • Check if the unit is levelled at all four corners with a water level or a water-filled vinyl tube as shown in figure 9.

1 Water level
2 Vinyl tube

3 Tighten the upper nut.

Installing the duct

Connect the duct supplied in the field.

Air inlet side

  • Attach the duct and intake-side flange (field supply).
  • Connect the flange to the main unit with accessory screws (7).
  • Wrap the intake-side flange and duct connection area with aluminum tape or something similar to prevent air escaping.

DAIKIN FXSQ15A2VEB - Air inlet side - 1

When attaching a duct to the intake side, be sure to attach an air filter inside the air passage on the intake side. (Use an air filter whose dust collecting efficiency is at least 50% in a gravimetric technique.)

The included filter is not used when the intake duct is attached.

DAIKIN FXSQ15A2VEB - Air inlet side - 2

Air outlet side

  • Connect the duct according to the air inside of the outlet-side flange.
  • Wrap the outlet-side flange and the duct connection area with aluminum tape or something similar to prevent air escaping

DAIKIN FXSQ15A2VEB - Air outlet side - 1

  • Be sure to insulate the duct to prevent condensation from forming. (Material: glass wool or polyethylene foam, 25mm thick)
  • Use electric insulation between the duct and the wall when using metal ducts to pass metal laths of the net or fence shape or metal plating into wooden buildings.
  • Be sure to explain about the way of maintaining and cleaning local procurements (air filter, grille (both air outlet and suction grille), etc.) to your customer.

Refrigerant piping work

For refrigerant piping of outdoor unit, refer to the installation manual supplied with the outdoor unit.

Before rigging tubes, check which type of refrigerant is used.

DAIKIN FXSQ15A2VEB - Refrigerant piping work - 1

Installation shall be done by a licensed refrigeration technician, the choice of materials and installation shall comply with the applicable national and international codes. In Europe, EN378 is the applicable standard that shall be used.

Use a pipe cutter and flare suitable for the used refrigerant.
To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end, or cover it with tape.
Use copper alloy seamless pipes (ISO 1337).
The outdoor unit is charged with refrigerant.
To prevent water leakage, execute heat insulation work completely on both sides of the gas and liquid piping. When using a heat pump, the temperature of the gas piping can reach up to approximately 120°C , use insulation which is sufficiently heat resistant.
- Be sure to use both a spanner and torque wrench together when connecting or disconnecting pipes to/from the unit.

1 Torque wrench
2 Spanner
3 Piping union
4 Flare nut

DAIKIN FXSQ15A2VEB - Refrigerant piping work - 2

  • Do not mix anything other than the specified refrigerant, such as air, etc..., inside the refrigerant circuit.
    Use annealed material only for flare connections.
    Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque. (Overtightening may damage the flare and cause leaks.)

Table 1

Pipe gauge (mm)Tightening torque (N·m)Flare dimension A (mm)Flare shape
Ø6.4 15~178.7~9.150°2
Ø9.5 33~3912.8~13.2
Ø12.7 50~6016.2~16.6
Ø15.9 63~7519.3~19.7

When connecting the flare nut, coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly.

DAIKIN FXSQ15A2VEB - Refrigerant piping work - 3

If the refrigerant gas leaks during the work, ventilate the area. A toxic gas is emitted by the refrigerant gas being exposed to a fire.
Make sure there is no refrigerant gas leak. A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater, cooking stove, etc.
Finally, insulate as shown in the figures below.

Piping insulation procedure

DAIKIN FXSQ15A2VEB - Piping insulation procedure - 1
Gas piping Liquid piph

DAIKIN FXSQ15A2VEB - Piping insulation procedure - 2

1 Piping insulation material (field supply)
2 Flare nut connection
3 Insulation for fitting (delivered with the unit)
4 Piping insulation material (main unit)
5 Main unit
6 Clamp (field supply)
7 Medium 1 sealing pad for gas piping (delivered with the unit) Medium 2 sealing pad for liquid piping (delivered with the unit)
A Turn seams up
B Attach to base
C Tighten the part other than the piping insulation material
D Wrap over from the base of the unit to the top of the flare nut connection

DAIKIN FXSQ15A2VEB - Piping insulation procedure - 3

For local insulation, be sure to insulate local piping all the way into the pipe connections inside the unit.

Exposed piping may cause condensation or may cause burns when touched.

Cautions for brazing

  • Be sure to carry out a nitrogen blow when brazing. Brazing without carrying out nitrogen replacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes, adversely affecting valves and compressors in the refrigerating system and preventing normal operation.
    When brazing while inserting nitrogen into the piping, nitrogen must be set to 0.02MPa with a pressure-reducing valve (=just enough so that it can be felt on the skin).

DAIKIN FXSQ15A2VEB - Cautions for brazing - 1

1 Refrigerant piping
2 Part to be brazed
3 Taping
4 Hands valve
5 Pressure-reducing valve
6 Nitrogen

Drain piping work

Installation of drain piping

Install the drain piping as shown in the figure and take measures against condensation. Improperly rigged piping could lead to leaks and eventually wet furniture and belongings.

DAIKIN FXSQ15A2VEB - Installation of drain piping - 1
1 Hanging bar

Install the drain pipes.

  • Keep piping as short as possible and slope it downwards at a gradient of at least 1/100 so that air may not remain trapped inside the pipe.
  • Keep pipe size equal to or greater than that of the connecting pipe (vinyl pipe of 25mm nominal diameter and 32mm outer diameter).
  • Push the supplied drain hose as far as possible over the drain socket.

DAIKIN FXSQ15A2VEB - Installation of drain piping - 2

1 Drain socket (attached to the unit)
2 Drain hose (supplied with the unit)

  • Tighten the metal clamp until the screw head is less than 4mm from the metal clamp part as indicated in the illustration.

DAIKIN FXSQ15A2VEB - Installation of drain piping - 3

1 Drain socket (attached to the unit)
2 Drain hose (supplied with the unit)
3 Metal clamp (supplied with the unit)
4 Large sealing pad (supplied with the unit)
5 Drain piping (field supply)

  • Wrap the supplied large sealing pad over the metal clamp and drain hose to insulate and fix it with clamps.
  • Insulate the complete drain piping inside the building (field supply).
  • If the drain hose cannot be sufficiently set on a slope, fit the hose with drain raising piping (field supply).

How to perform drain piping

(See figure 10)

1 Ceiling slab
2 Hanger bracket
3 Adjustable range
4 Drain raising pipe
5 Drain hose (supplied with the unit)
6 Clamp metal (supplied with the unit)

1 Connect the drain hose to the drain raising pipes, and insulate them.
2 Connect the drain hose to the drain outlet on the indoor unit, and tighten it with the clamp.

Installation A (mm)
Rear suction installation 231
When canvas duct is installed 350-530
When air inlet panel is directly installed231

Precautions

  • Install the drain raising pipes at a height of less than 625mm
  • Install the drain raising pipes at a right angle to the indoor unit and no more than 300mm from the unit.
  • To prevent air bubbles, install the drain hose level or slightly tilted up (≤75 mm).
  • The drain pump mounted in this unit is the high lift type. The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes. Therefore a drain pump height of 300mm is recommended.

NOTE

DAIKIN FXSQ15A2VEB - Installation of drain piping - 4

The incline of attached drain hose should be 75mm or less so that the drain socket does not have to withstand additional force.

To ensure a downward slope of 1:100, install hanging bars every 1 to 1.5m

When unifying multiple drain pipes, install the pipes as shown in figure 11. Select converging drain pipes whose gauge is suitable for the operating capacity of the unit.

1 T-joint converging drain pipes

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

  • Add approximately 1 l of water gradually through the air discharge outlet. Check for water leaks.

Method of adding water. See figure 8.

1 Water inlet
2 Portable pump
3 Water inlet cover
4 Bucket (adding water through water inlet)
5 Drain outlet for maintenance (with rubber drain plug)
6 Refrigerant pipes

DAIKIN FXSQ15A2VEB - Testing of drain piping - 1

Caution for drain socket

Do not remove the drain pipe plug. Water might leak out.

The drain outlet is only used to discharge water if the drain pump is not used or before maintenance. Gently put in and out the drain plug. Excessive force may deform the drain socket of the drain pan.

Pulling out the plug

DAIKIN FXSQ15A2VEB - Caution for drain socket - 1
1 Drain plug

Do not wiggle the plug up and down

Pushing in the plug

DAIKIN FXSQ15A2VEB - Caution for drain socket - 2

Set the plug and push it by using a crosshead screwdriver

First perform electric wiring work as instructed in "Electric wiring work" on page 6 and how to set the remote controller as explained in "Wiring example and how to set the remote controller" on page 7.

When electric wiring work is finished

Check drainage flow during COOL running, explained in "Test operation" on page 10.

When electric wiring work is not finished

Remove the switch box cover and connect the single-phase power supply and the remote controller to the terminals. (Refer to "Electric wiring work" on page 6 for switch box attachment/detachment.) (Refer to figure 12 and figure 14)

1 Switch box cover
2 Transmission wiring port
3 Power supply wiring port
4 Wiring diagram
5 Switch box
6 Plastic clamp
7 Remote controller wiring
8 Terminal board for unit transmission wiring
9 Power supply wiring
10 Indoor PC board 1
11 Power supply terminal board
12 Transmission wiring between units
13 Indoor PC board 2
14 Long sealing
15 Wiring

Next, press the inspection/test operation button the remote controller. The unit will engage the test operation mode. Press the operation mode selector button until selecting fan operation

  1. Then, press the on/off button the indoor unit fan and drain pump will start up. Check that the water has drained from the unit. Press go back to the first mode.

Electric wiring work

General instructions

All field wiring and components must be installed by a licensed electrician and must comply with relevant European and national regulations.
Use copper wire only.
- Follow the "Wiring diagram" attached to the unit body to wire the outdoor unit, indoor units and the remote controller. For details on hooking up the remote controller, refer to the "Installation manual of the remote controller".
All wiring must be performed by an authorized electrician.
- Attach the earth leakage circuit breaker and fuse to the power supply line.
A main switch or other means for disconnection, having a contact separation in all poles, must be incorporated in the fixed wiring in accordance with relevant local and national legislation. Note that the operation will restart automatically if the main power supply is turned off and then turned back on again.
Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit, the capacity of the earth leakage breaker and fuse and for wiring instructions.
■ Be sure to ground the air conditioner.
Do not connect the ground wire to:

  • gas pipes: might cause explosions or fire if gas leaks.
  • telephone ground wires or lightning rods: might cause abnormally high electric potential in the ground during lightning storms.
  • plumbing pipes: no grounding effect if hard vinyl piping is used.

Make sure that earth wire between the pull relief and terminal is longer than other wires.
- Be sure that the shape of the power supply cable and any other cable, before entering unit, should be as shown in this figure.
All cables entering the unit should be fixed by tie wraps (accessory).
Use long sealing (accesory) to block entrance of switch box as shown in figure 12.

DAIKIN FXSQ15A2VEB - General instructions - 1

Electrical characteristics

ModelHzVoltsVoltage rangePower supply
MCAMFA
1550/60220-240/220±10%0.416 A
200.4
250.4
320.4
400.8
500.8
630.9
801.0
1001.5
1252.0

MCA: Min. circuit Amps (A)

MFA: Max. Fuse Amps (A)

DAIKIN FXSQ15A2VEB - Electrical characteristics - 1

For details, refer to "Electrical data" in the technical data book.

Specifications for field supplied fuses and wire

Power supply wiring Model Field fuses Wire Size
15~125 16 A H05VV-U3G Local codes
Model Wire Size
15~125 Sheathed wire (2)0.75-1.25 mm²

NOTE

For details, refer to "Wiring example" on page 7.

DAIKIN FXSQ15A2VEB - Specifications for field supplied fuses and wire - 1

Allowable length of transmission wiring between indoor and outdoor units, and between the indoor unit and the remote controller is as follows:

  1. Outdoor unit - indoor unit: max. 1000 m (total wiring length: 2000 m)
  2. Indoor unit - remote controller: max 500 m

Wiring example and how to set the remote controller

How to connect wiring

Remove the switch box cover as shown in figure 12, and make the connections.

1 Switch box cover
2 Switch box low voltage wiring inlet
3 Switch box high voltage wiring inlet
4 Wiring diagram
5 Switch box

Precautions

  1. Observe the notes mentioned below when wiring to the power supply terminal board.

  2. Use a round crimp-style terminal for insulation sleeve for connection to the terminal block for wiring the units. When none are available, follow the instructions below.

DAIKIN FXSQ15A2VEB - Precautions - 1

1 Round crimp-style terminal
2 Attach insulation sleeve
3 Wiring

  • Do not connect wires of different gauge to the same power supply terminal. (Looseness in the connection may cause overheating.)
  • When connecting wires of the same gauge, connect them according to the figure.

DAIKIN FXSQ15A2VEB - Precautions - 2

DAIKIN FXSQ15A2VEB - Precautions - 3

DAIKIN FXSQ15A2VEB - Precautions - 4

Use the specified electric wire. Connect the wire securely to the terminal. Lock the wire down without applying excessive force to the terminal. Use torques according to the table below.

Tightening torque (N· m)

Terminal block for remote controller0.79~0.97
Terminal block for power supply1.18~1.44
  • When attaching the control box lid, make sure not to pinch any wires.
  • After all wiring connections are done, fill in any gaps in the casing wiring holes with putty or insulation material (field supply) thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box.

  • Do not connect wires of different gauge to the same grounding terminal. Looseness in the connection may deteriorate the protection.

  • Remote controller cords and wires connecting the units should be located at least 50 mm away from power supply wiring. Not following this guideline may result in malfunction due to electrical noise.
  • For the remote controller wiring, refer to the "Installation manual of the remote controller" supplied with the remote controller.

NOTE

DAIKIN FXSQ15A2VEB - Precautions - 5

The customer has the ability to select the remote controller thermistor.

  1. Never connect the power supply wiring to the terminal board for transmission wiring. This mistake could damage the entire system.
  2. Use only specified wires and tightly connect wires to the terminals. Be careful that wires do not place external stress on the terminals. Keep wiring in neat order so that they do not obstruct other equipment such as popping open the switch box cover. Make sure the cover closes tight. Incomplete connections could result in overheating, and in the worse case, electric shock or fire.

Keep total current of crossover wiring between indoor units less than 12 A. Branch the line outside the terminal block of the unit in accordance with the electrical equipment standards, when using two power wiring of a gauge greater than 2mm2 (Ø1.6).

The branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself.

Wiring example

Fit the power supply wiring of each unit with a switch and fuse as shown in figure 16.

1 Power supply
2 Main switch
3 Power supply wiring
4 Transmission wiring

5 Switc
6 Fuse
7 BS unit REYQ only
8 Indoor unit
9 Remote controller

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit (Normal operation) (See figure 15)

For group control or use with 2 remote controllers (See figure 17)

When including BS unit (See figure 13)

1 Outdoor unit
2 Indoor unit
3 Remote controller (optional accessories)
4 Most downstream indoor unit
5 For use with 2 remote controllers
6 BS unit

DAIKIN FXSQ15A2VEB - Complete system example (3 systems) - 1

It is not necessary to designate an indoor unit address when using group control. The address is automatically set when the power is activated.

Precautions

  1. A single switch can be used to supply power to units on the same system. However, branch switches and branch circuit breakers must be selected carefully.
  2. For a group control remote controller, choose the remote controller that suits the indoor unit which has the most functions.
  3. All transmission wiring except for the remote controller wiring is polarized and must match the terminal symbol.
  4. In case of group control, perform the remote controller wiring to the master unit when connecting to the simultaneous operation system (wiring to the slave unit is unnecessary).
  5. When controlling the simultaneous operation system with 2 remote controllers, connect it to the master unit (wiring to the slave unit is unnecessary).
  6. Be sure to connect the wiring to the master unit when combining with a simultaneous operating multi-type in group control.
  7. Do not ground the equipment on gas pipes, water pipes, lightning rods or crossground with telephones. Improper grounding could result in electric shock.

Field setting

Field setting must be made on the remote controller in function of the installation condition.

Setting can be made by changing the "Mode number", "First code No." and "Second code No".
For setting and operation, refer to the "Field settings" in the installation manual of the remote controller.

Summary of field settings

Mode No.(Note 1)First code No.Description of settingSecond code No. (Note 2)
01 02 03
10(20)0Filter contamination - Heavy/Light = Setting to define time between 2 filter cleaning display indications. (When contamination is high, setting can be changed to half the time inbetween 2 filter cleaning display indications.)Ultra-long-life filterLight±10,000 hrs.±5,000 hrs.
Long-life filter±2,500 hrs.±250 hrs.
Standard filter±200 hrs. ±100 hrs.
2Thermostat sensor selectionUse both the unit sensor (or remote sensor if installed) AND the remote controller sensor. (See note 5+6)Use unit sensor only (or remote sensor if installed). (See note 5+6)Use remote controller sensor only. (See note 5+6)
3Setting for display of time between 2 filter cleaning display indicationsDisplay Do not ddysplay — —
6Thermostat sensor in group controlUse unit sensor only (or remote sensor if installed). (See note 6)Use both the unit senor (or remote sensor if installed) AND the remote controller sensor. (See note 4+5+6)
12(22)0Output signal X1-X2 of the optional KRP1B PCB kitThermostat-on + compressor run— OperationMal-function
1ON/OFF input from outside (T1/T2 input) = Setting when forced ON/OFF is to be operated from outside.Forced OFFON/OFF operation
3Fan setting during thermostat OFF at heating operationLL Sat speedOFF (See note 3)
4Differential automatic changeover0°C 1°C 2°C3°C (See note 7)
5Auto_restart after power failureDisabled Enabled— —
9Fixed cool/heat masterDisabledEnabled
15(25)3Drain pump operation + humidifier interlockEquippedNot equipped

Note 1: Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, indoor units can also be set individually.
Note 2: Factory settings of the Second code No. are marked in grey backgrounds.
Note 3: Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4: If group control is selected and remote control sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5: If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 10-2-02 or 10-2-03 have priority.
Note 6: If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have priority.
Note 7: More settings for Differential automatic change over temperatures are:
Second code No. 05 4°C
06 5°C
07 6°C
08 7°C

External static pressure settings

Settings for external static pressure can be achieved in 2 ways:

Using the airflow automatic adjustment function

Airflow automatic adjustment is the volume of blow-off air that has been automatically adjusted to the rated quantity.

1 Make sure the test run is done with a dry coil.

If the coil is not dry, run the unit for 2 hours with fan only to dry the coil.

2 Check if the power supply wiring to the air conditioning unit is completed along with the duct installation.

If a closing damper is installed in the air conditioning unit, make sure that it is open.

Also check if the air filter is properly attached into the air passage on the air suction side of the air conditioning unit.

3 If there is more than one air inlet and outlet, adjust the dampers so that the airflow rate of each air inlet and outlet is conform with the designed airflow rate.

Make sure the air conditioning unit is in fan operation mode. Press and set the airflow adjustment button on the remote controller to change the airflow rate to H or L.

4 Setting the airflow automatic adjustment settings.

When the air conditioning unit is running in fan operation mode perform the next steps:

  • stop the air conditioning unit,
  • go to field setting mode,
  • select mode No. 21 (or 11 in case of group setting),
  • set the first code No. to "7",
  • set the second code No. to "03".

Return to normal operating mode after setting these settings and press the ON/OFF operation button. The operation lamp will light up and the air conditioning unit will start the fan operation for airflow automatic adjustment.

DAIKIN FXSQ15A2VEB - Using the airflow automatic adjustment function - 1

Do not adjust the dampers during fan operation for airflow automatic adjustment.

After 1 to 8 minutes, the air conditioning unit stops operating automatically when the fan operation for airflow automatic adjustment has been carried out, the operation lamp will be off.

Mode No.First code No.Second code No.Setting content
11 (21) 701 Airflow adjustment is OFF
02 Completion of airflow adjustment
03 Start of airflow adjustment

5 When the air conditioning unit has stopped, check on an indoor unit if the second code No. of mode No. 21 is set to "02".

If the air conditioning unit does not stop operating or the second code No. is not "02", repeat step 4.

If the outdoor unit is not turned on, the display on the remote controller will show "UH" or "UH" (refer to "Test operation" on page 10). However, you can continue setting this function because these messages are only applicable to outdoor units.

After setting this function, be sure to turn on the outdoor unit before performing the test operation on the outdoor unit.

If any other error display occurs on the display of the remote controller, refer to "Test operation" on page 10 and the operation manual of the outdoor unit. Check the defective point.

DAIKIN FXSQ15A2VEB - Using the airflow automatic adjustment function - 2

If the external static pressure higher than 100Pa do not use airflow automatic adjustment function.
If there is no change after airflow adjustment in the ventilation paths, be sure to perform setting the airflow automatic adjustment again.
- Contact your dealer if there is no change after performing airflow adjustment in the ventilation paths, after performing the test operation of the outdoor unit or when the air conditioning unit is moved to another location.
If booster fans, an outdoor air processing unit or HRV via duct are used, do not use airflow automatic adjustment control with a remote controller.
If the ventilation paths have been changed, perform the setting of the airflow automatic adjustment again as described above from step 3 onwards.

Using the remote controller

Check on an indoor unit if the second code of mode No. 21 is set to "01" (= factory setting). Change the second code according to the external static pressure of the duct to be connected as shown in table 2.

DAIKIN FXSQ15A2VEB - Using the remote controller - 1

The second code No. is set to "01" by default.

Table2

Mode No.1st code No.2nd code No.External static pressure (Pa)
FXSQ
15 2025 3240506380100125
13(23)6013030303030404050
02---------
033030303030---
0440404040404040-
0550505050505050
066060606060606050
077070707070707070
088080808080808080
099090909090909090
10100100100100100100100100100100
11110110110110110110110110110110
12120120120120120120120120120120
13130130130130130130130130130130
14140140140140140140140140140140
15150150150150150150150150150150

Control by 2 Remote Controllers (Controlling 1 indoor unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".

MAIN/SUB CHANGEOVER

Insert a wedge-head screwdriver into the recess between the upper and lower part of the remote controller and, working from the 2 positions, pry off the upper part. (See figure 18) (The remote controller PC board is attached to the upper part of the remote controller.)
Turn the main/sub changeover switch on one of the two remote controller PC boards to "S". (See figure 19) (Leave the switch of the other remote controller set to "M".)

1 Remote controller PC board
2 Factory setting
3 Only one remote controller needs to be changed

Computerised control (forced off and on/off operation)

1 Wire specifications and how to perform wiring

  • Connect input from outside to terminals T1 and T2 of the terminal board (remote controller to transmission wiring).
Wire specification Sheathed vinyl cord or cable (2 wire)
Gauge0.75-1.25 mm²
Length Max. 100 m
External terminal Contact that can ensure the minimum applicable load of 15 V DC, 10 mA

DAIKIN FXSQ15A2VEB - Computerised control (forced off and on/off operation) - 1

2 Actuation

  • The following table explains "forced off" and "on/off operations" in response to input A.
Forced off on/off operation
Input "on" stops operationinput off → on: turns on the unit (impossible by remote controllers)
Input "off" enables controlinput on → off: turns off the unit by remote controller

3 How to select forced off and on/off operation

  • Turn the power on and then use the remote controller to select operation.
  • Set the remote controller to the field set mode. For details, refer to the chapter "How to set in the field", in the remote controller manual.
  • When in the field set mode, select mode No. 12, then set the first code No. to "1". Then set second code (position) No. to "01" for forced off and to "02" for on/off operation. (forced off at factory set.) (See figure 20)

1 Second code No.
2 Mode No.
3 First code No.
4 Field set mode

Centralized control

For centralized control, it is necessary to designate the group No. For details, refer to the manual of each optional controller for centralized control.

Installation of the decoration panel

Refer to the installation manual attached to the decoration panel.

After installing the decoration panel, ensure that there is no space between the unit body and decoration panel.

Test operation

Refer to the installation manual of the outdoor unit.

The operation lamp of the remote controller will flash when an error occurs. Check the error code on the liquid crystal display to identify the trouble.

Error code Meaning
R8Error inpower supply to indoor unit
C1Transmission error between fan driver PCB and controller PCB of the indoor unit
C6Improper combination of fan driver PCB of the indoor unit or setting failure in control PCB type
U3Test operation of the indoor unit has not been finished

If any of the items in following table are displayed on the remote controller, there may be a problem with the wiring or power, so check the wiring again.

Error code Meaning
AThere is a short circuit at the forced off terminals (T1, T2)
UH or UH- The power on the outdoor unit is off - The outdoor unit has not been wired for power supply - Incorrect transmission of forced off wiring
no display- The power on the indoor unit is off - The indoor unit has not been wired for power supply - Incorrect transmission wiring, forced off wiring or remote controller wiring

Maintenance

DAIKIN FXSQ15A2VEB - Maintenance - 1

Caution

Only a qualified service person is allowed to perform maintenance.
Before obtaining access to terminal devices, all power supply circuits must be interrupted.
Do not use water or air of 50°C or higher for cleaning air filters and outside panels.
When cleaning the heat exchanger, be sure to remove the switchbox, fan motor, auxiliary electric heater and drain pump. Water or detergent may deteriorate the insulation of electronic components and result in burnout of these components.
If the main power supply is turned off during operation, operation will restart automatically after the power turns back on again.

How to clean the air filter

Clean the air filter when the display shows "TIME TO CLEAN AIR FILTER).

Increase the frequency of cleaning if the unit is installed in a room where the air is extremely contaminated.

If the dirt becomes impossible to clean, change the air filter. (Air filter for exchange is optional.)

1 Open the suction grille. (Only for bottom suction.)

Slide both knobs simultaneously as shown and then pull them downward.

DAIKIN FXSQ15A2VEB - How to clean the air filter - 1

If chains are present, unhook the chains.

DAIKIN FXSQ15A2VEB - How to clean the air filter - 2

2 Remove the air filters.

Remove the air filters by pulling their cloth upward (rear suction) or backward (bottom suction).

DAIKIN FXSQ15A2VEB - How to clean the air filter - 3

DAIKIN FXSQ15A2VEB - How to clean the air filter - 4

3 Clean the air filter.

Use vacuum cleaner (A) or wash the air filter with water (B).

(A) Using a vacuum cleaner

(B) Washing with water

DAIKIN FXSQ15A2VEB - How to clean the air filter - 5

DAIKIN FXSQ15A2VEB - How to clean the air filter - 6

When the air filter is very dirty, use soft brush and neutral detergent.

Remove water and dry in the shade.

4 Fix the air filter.

DAIKIN FXSQ15A2VEB - How to clean the air filter - 7

DAIKIN FXSQ15A2VEB - How to clean the air filter - 8

Align the two hanger brackets and push the two clips in their place (pull the cloth if necessary).

Confirm that four hangers are fixed.

5 Shut the air inlet grille. (Only for bottom suction.)

Refer to item no. 1.

6 After turning on the power, press FILTER SIGN RESET button.

The "TIME TO CLEAN AIR FILTER" display is turned off.

How to clean air outlet and outside panels

Clean with soft cloth.
When it is difficult to remove stains, use water of neutral detergent.
Clean the air inlet grille when it is shut.

NOTE

Do not use gasoline, benzene, thinner, polishing powder, liquid insecticide. It may cause discolouring or warping.

Do not let the indoor unit get wet. It may cause an electric shock or a fire.

Start up after a long stop

Confirm the following:

Check that the air inlet and outlet are not blocked. Remove any obstacle.
Check if the earth is connected.

Clean the air filter and outside panels.

After cleaning the air filter, make sure to attach it.

Turn on the main power supply switch.

The control panel display lights when the power is turned on.
To protect the unit, turn on the main power switch at least 6 hours before operation.

What to do when stopping the system for a long period

Turn on FAN OPERATION for half a day and dry the unit.

Refer to the operation manual of the outdoor unit.

Cut off the power supply.

When the main power switch is turned on, some wattage is being consumed even if the system is not operating.
The remote controller display is turned off when the main power switch is turned off.

Disposal requirements

Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with relevant local and national legislation.

Wiring diagram

:FIELD WIRING BLK:BLACK PNK:PINK

:CONNECTORBLU:BLUERED:RED
:SCREW TERMINAL BRN:BROWN WHT:WHITE

GRN:GREENYLW:YELLOW

ORG:ORANGE

A1P.. PRINTED CIRCUIT BOARD

A2P... PRINTED CIRCUIT BOARD (FAN)

C1............CAPACITOR

C105...CAPACITOR

HAP .INDICATION LAMPS

K1R. MAGNETIC RELAY

L1R. REACTOR

M1F .MOTOR (INDOOR FAN)

M1P .MOTOR (DRAIN PUMP)

PS. SWITCHING POWER SUPPLY

R1...RESISTOR (CURRENT SENSOR)

R2...RESISTOR (CURRENT SENSOR)

R1T.THERMISTOR (SUCTION)

R2T.THERMISTOR (LIQUID)
R3T.THERMISTOR (COIL)
S1L .........FLOAT SWITCH
V1R........DIODEBRIDGE
V2R.....POwER MOLURe
X1M TERMINAL STRIP (POWER SUPPLY)
X2M TERMINAL BLOCK (CONTROL)
Y1E.....ELECTRONIC EXPANSION VALVE COIL
Z1C....FERRITE CORE
Z2C FERRITE CORE
Z1F .NOISE FILTER

CONNECTOR (OPTIONAL ACCESSORY)

X28A.....CONNECTOR (POWER SUPPLY FOR WIRING)

X33A.........CONNECTOR (FOR WIRING)

X35A.........CONNECTOR (POWER SUPPLY FOR WIRING)

X38A.....CONNECTOR (FOR WIRING)

Wired REMOTE CONTROLLER: Wired remote controller

(OPTIONAL ACCESSORY) : (Optional accessory)

SWITCH BOX (INDOOR) Switch box (indoor)

TRANSMISSION WIRING : Transmission wiring

CENTRAL REMOTE CONTROLLER : Central remote controller

INPUT FROM OUTSIDE Input from outside

COMMON POWER SUPPLY : Common power supply

NOTE 1. USE COPPER CONDUCTORS ONLY.

DAIKIN FXSQ15A2VEB - CONNECTOR (OPTIONAL ACCESSORY) - 1

  1. WHEN USING THE CENTRAL REMOTE CONTROLLER, SEE MANUAL FOR CONNECTION TO THE UNIT.
  2. WHEN CONNECTING THE INPUT WIRES FROM OUTSIDE, FORCED "OFF" OR "ON/OFF" CONTROL OPERATION CAN BE SELECTED BY THE REMOTE CONTROLLER. SEE INSTALLATION MANUAL FOR MORE DETAILS.
  3. REFER TO INSTALLATION MANUAL.

Inhalt Seite

M1F .MOTOR (INNENLÜFTER)

M1P .MOTOR (KONDENSATPUMPE)

R3T.THERMISTOR (SPULE)

S1L .SCHWIMMERSCHALTER

V1R........DIODENBRUCKE

V2R.........STROMVERSORGUNGSMODUL

(OPTIONAL ACCESSORY)

: (Optionales zubehor)

SWITCHBOX(INDOOR)

Avant installation 1

(Voir figure 1 et figure 2)

R1T THERMISTANCE (ASPIRATION)

R2T THERMISTANCE (LIQUIDE)

R3T. THERMISTANCE (BOBINE)
S1L.....INTERRUPTEUR A FLOTTEUR
V1R .PONT DE DIODE
V2R.........MODULE D'ALIMENTATION
X1M. BARRETTE DE RACCORDEMENT (ALIMENTATION)
X2M............BORNIER (COMMANDE)
Y1E... BOBINE DE LA VANNE DE DÉTENTE ÉLECTRONIQUE
Z1C. TORE MAGNETIQUE
Z2C. TORE MAGNETIQUE
Z1F. FiltRE ANTIPARASITE

CONNECTEUR (ACCESSION EN OPTION)

X28A... CONNECTEUR (ALIMENTATION POUR CABLAGE)
X33A... CONNECTEUR (POUR CÁBLAGE)
X35A... CONNECTEUR (ALIMENTATION POUR CABLAGE)
X38A. CONNECTEUR (POUR CÁBLAGE)

WIRED REMOTE CONTROLLER : Telecommande cable
(OPTIONAL ACCESSORY) : (Accessaire en option)
SWITCH BOX (INDOOR) : Coffret electrique (interne)
TRANSMISSION WIRING Cablage de transmission
CENTRAL REMOTE CONTROLLER : Telecommande centrale
INPUT FROM OUTSIDE Entree de I'exterieur
COMMON POWER SUPPLY : Alimentation electrique commune

SCHROEF KLEM BRN:BRUIN WHT:WIT

GRN:GROEN YLW:GEEL

ORG:ORANJE

A1P PRINTPLAAT

A2P PRINTPLAAT (VENTILATOR)

C1............CONDENSATOR

C105............CONDENSATOR

DS1 KEUZESCHAKELAAR

F1U ZEKERING (T, 3,15 A, 250 V)

F2U ZEKERING (T, 5 A, 250 V)

F3U ZEKERING (T, 6,3 A, 250 V)

HAP. INDICATIONLAMPJES

K1R . MAGNETISCH RELAIS

L1R. REACTOR

M1F . MOTOR (BINNENVENTILATOR)

M1P.........MOTOR (AFVOERPOMP)

PS. SCHAKELENDE VOEDING

Q1DI. AARDLEKSCHAKELAAR

R1. WEERSTAND (STROOMSENSOR)

R2. WERSTAND (STROOMSENSOR)

R1T THERMISTOR (AANZUIGING)

R2T. THERMISTOR (VLOEISTOF)

R3T. THERMISTOR (SPOEL)

S1L. VLOTTERSCHAKELAAR

V1R DIODEBRUG

CONNECTOR (OPTIONEEL ACCESSOIRE)

X28A......... CONNECTOR (VOEDING VOOR BEDRADING)

X33A... CONNECTOR (VOOR BEDRADING)

X35A... CONNECTOR (VOEDING VOOR BEDRADING)

X38A... CONNECTOR (VOOR BEDRADING)

WIED REMOTE CONTROLLER Bedrade afstandsbediening

(OPTIONAL ACCESSORY) : (Optioneel accessoire)

Z2C....NUCLEO DE FERRITA

(OPTIONAL ACCESSORY)

Tia aeTTIOpeIEc, avatpEte Otny EvOTnTa "HAEKPTiKa oToiExia" OTO EYEXIPIO TExVIKuv DeoEvuv.

PpOsiaypaqes yia TApExoEvEc aQaAeies kai Kaawdiou eTropiou

M1P... MOTEP (ANTIA AIOSTPATIIGH

PS .AIKONTH TPOOODOEIAZ

Q1DI...AIAKONTHFIEI0H

R1. ANTIETAZH (AIΘΘHTPA Σ ENTΛΗΣ)

R2. ANTIAZH (AIΘHTPAE ENTAEH)

R1T ......AI ΘHTHPA Σ (ANAPPOΦHΞH)

R2T. AI∑ΘHTHPA∑ (YΓPOY)

R3T. AIGOTHPA2 (MONAAGFANCOIL)

S1L. DIAKONTHME IAIOTHPA

V1R .FEOYPA ME DIODO

V2R MONADA IXYZOZ

X1M. .AKETA AKPOAETON (TPOOOSIA)

X2M... MIAOKAKPOAETONXEIPIMO

Y1E. HANIO HAEKTPONIKH2 BANA EKTONOHS

Z1C. ..NYPHNAΦEPPITH

Z2C. IYPHNA ΦEPPITH

Z1F. .ΦIATPO ΘOPYBOY

AKPOADEKTH∑ (IPOAIPETIKO IAPAEKOMENO)

X28A. AKPOAEKTHZ (TPOO0O0IA IATH N KAANJIOH)

X33A. AKPOADEKTH∑IKAANΩIΩ∑H

X35A. AKPOAEKTHZ (TPOΦOΔOεIA ΓIA THN KAΛΩΔIΩΣH)

MFA: Amperesolestadosfusivel (A)

NOTA

DAIKIN FXSQ15A2VEB - AKPOADEKTH∑ (IPOAIPETIKO IAPAEKOMENO) - 1

PnroTOBka K MoHTaKy 3

MOnTax BHyTpEnHero arperata. 4

MOnTak Bo3dyxOBoDa 4

PekomeHdaunnoMTaKy TpybOpOBoB XnaDaareHa 5

PekomeHdaunnoMOHTaKydpEhaXhoroTpybOpObOa 6

Pa6oTa c 3eKeTpueeckoi npoBokoi. 7

PpMep npoBokn HacToa NyIbTa Y 8

Iprime npoBdoKn 9

HacpoKa no MeCy 3Knnyatau.. 9

UcTaHOBka DeKopatNBHOI naHeJI 12

Ipo6HbI 3anyck 12

Texnueckoe obcnykubahne 12

ytninaaia 13

3neKtpuecka cxema 14

DAIKIN FXSQ15A2VEB - AKPOADEKTH∑ (IPOAIPETIKO IAPAEKOMENO) - 2

IPEMMOHTAXOM CNTEMBI BHIMATEJIbHO O3HAKOMbTECb C HACTOJIeEN IHCTPYKLIeN. XPAHITE INCHTPYKLNIIO B DOCTYINHOM MECTE, YTO5bl B BYDUYEM EE MOXHO BblNO IcNoJIb3OBATb B KAUCHTBCEPABOCHOROMATEPNAJIA.

HEBEPHbIM MOHTAX CNTEMbl, HEPNABINbHOE NOKIOUOEHNE YCTPOICTB N OBOPYDOBAHnM OMYT PNPBECTNI K NOPAXEHNO3JIEKTPYCHECKIM TOKOM, KOPOTKOM3AMbIKAHIO, IPOTEYKAM, POXAPY IN DpyROMY UyCEP6Y. NCIOJIb3yITE TOJbKO TOI0NJHHTENbHOE OOBPyDOBAHNE, KOTOPOE1N3TOTOBGEHO KOMPAHNEI DAIKIN INIPEDHA3HAeHO DII JDAHHOI CNTEMbl KOHNIOHINPOBAHn. DOBEPaTb MOHTAXOBOPyDOBAHnCNEyET TOJbKO KBALNFUNPOBAHHbIM CNEUANINTAM.

ECJN BO3HNIKHHT COMHEHNAI NO NOBOOY MOHTAKA NIN 3KCNPIYATAUIN CNCTEMbl, OBPATNTECb 3A COBETOM I DONOJIHHTJIbHOI INHΦOPMALUEIK DNIEPY KOMNAHN DAIKIN.

OpunHaON pyKOBoCTBa YBnEeTc TaKT Ha aHnnckom 3bIke. TeKT Ha npyRux 3bIkaX YBnEeTc nepeBOOM c opunHaHa.

DAIKIN FXSQ15A2VEB - AKPOADEKTH∑ (IPOAIPETIKO IAPAEKOMENO) - 3

MOnTax DoJxKeH BbINOJIHrTb KBaIIuΦnIpuBaHHbI cNeuaJIInCT.

Bb6op MaTepnana N MoTax DonxKbI COOTBeCTBOBaTb npImeHmblm rOcydapCTBeHHbIM mEKKdyHapoHbIM HopMaM.

Ipepe yctaHOBko

Ioka arperat He 6ydet Doctablen Ha MeCTO yCTaHOBKn, OH DoJKeH OCTaBaTbCBy YnakOBKe. Ecn63 pacnakOBKn He 0oBtncb, NcNoJIb3yIe npn NoDbemE CToPbN 3 MmKOrO MaTePnAJa IIN 3aUThBle NaHeN BMeCe C KaHaTOM, YTO6bl He NOBpeDntb H He noCuapanaTb arperat.

Pn pacnakobke arperata n npn nepemesehenn ero noce pacnakobkn arperat cneyet NOHMaTb TOnbko 3a NOBecHOKPOHTH. He OKa3bBaIte DaBHeHne Ha Dpyme YacTN, BOC6eHHocTN Ha TpybI C XnaAareHToM, DpeHaxhNt TpybonpoBoD n dpyrne nonmepHBie deTann.

IpeweHn BOpocOB, He paccMOptpeHHbIX B DaHHOM pyKOBOdCTBe, 06paTNTecb K pyKOBOdCTBy NO MOHTaKy HApXKHO 6noka.

Mepb obecneeyn 6e3oNaChocT npn o6paueHm cXlaaareHTOM R410A:

IIOcOeHnHReMbIe HApxHbIe 6NOKn DOnKhbl 6bItb paCCHTaHbHa IcNoJIb3oBaHHe NCKIQUHTeJIbHO xJaAareHrTa R410A.

He pa3meuaine B HENOCpeDCTBeHHoB 6nHc0Tn OT HApyKHO6 6noka pa3nHbIe npedMebl n He donyckaTe cKONneHnBOKpyr Hero JInCTbeB IN pyrTO Mycopa.

IInctbI - nntaTeIbHa cpeDa IINr MeJIkIX JxNBOThbIX, KOTOpBle MOrTy npOHnKHyTB B 6nok. OkazabWncB B 6noke, TaKe opraHn3Mb1 MOrTy Bb3BaTb C6oB I Ero pa6ote, 3aDbIMHeHne INN BO3ropaHne npBCTyPnEHN B KOHTAKT C 3eNEKTPNueCKMm DetanAaMn.

MepbI npedocTopoKHOCTN

He yctaHaBnBaIte n He 3KcPnyatnpyTe 6NOK B NOMEeHnX, yka3aHHbIX HnKe.

BnomeueHx,coepkauxMnHepaIbHbeMacna,napbimaceNIMmacJnHbTymah,HanpImepBnomeueHnxInpriroTOBneHHn(Bo3moXHOpa3pyuHnePiactMACCOBbIXKOMNOHeHTOB.)
B NomeeHnX C HnUHmE Koppo3nHbIX Ra3OB, HnPnMep cepHnCToRrTa3. (Bo3MoJxHa KoppO3nMeHbIX Tpy6 n MeCT naKIn TBepDbIM npnNoem.)
B nomeeHnX cncnoJIb3ObaHnem neTynx BOCnIaMeHnIOuXcraTaO,B,HaNPmEpOTpactBopntTnNn 6eH3nHa.
B nomeeHnax, coepkaux MaunHbI, rehepyuOuue 3neKtpomarHHThie noJa. (Bo3moXHo HapyuHeHpe pa6oTbI cnCTem ynpaBneHna.)
B MecTax c NObIeHHbIM coepKaHHeM coJe B aTMOcpepe, HApnMpE Ha MOpckOM 6epey, n Tam, rDe BO3MOXbI 3HaHTeJIbHbIe KoneBaHnHa npJxHnB CetN IITaHn (HaNPmEe, B6NI3 3aBOoB N fapnk).Kpome TORO, B aBTOMoBnIax INI HA cydax.

He yctaHaBnBaIte npHaIaNExKHOCTn HEnocpeIcTBeHHO KaKoxy. IpcOBepIeHHbIe B KoxyXe OTBepCTmMOrY T NOBpeIb3NeKTpueckne npBODa N BbI3BaTb BO3ropaHne.
DahHoe yCTpoiCTBO He npedHa3HaueHo DnIg 3KcNpyaTaNINaAMN (BKIOUOyA DeTe) C ORpAHuYeHHbIMN Pn3NUeCKMn, CEHCOPHBIMN INY YMCTBEHNbIMN BO3MOXHOCTAMN, a PABHO NTEM, y KORo HET COOTBeTCTBYIOJIero ONbTA n 3HaHNN. TaKne INa DOynyCAHOTCK 3KcNPyaTaN YcTOPOCTBA ToJbKO NOHApNDHeHMe INN pyKOBOdCTBOM INIa, HecyUeOTBTCTBEHHOCb 3a INx 6e3OnaCHOb.
3a DeTbMn Heo6xOdMM npncMoTp Bo n36eKaHne nRp C yCTpOHTBOM.
DahHoe yCTPOINCTBO MOKET NcNOLb3OBaTbCnCEuNAHCTAMNI OByeHHbIMN NOnB3OBaTEJIaMn B Mara3INax,Ha npednpnraTnx NERKO pPOMblIeHHoCTn,Ha fepmax,JIINO HeCNEuNAInCTAmn DnA KOMMepecknx HykD.
YpOBeHb 3ByKOBOrO DaBHeHn. MeHee 70 dE(A).

PnHaJnEeXHocTn

Y6eINTecb, yTO B 6NIOK BKJIOUHeHb CNeDyUOJIne PnHaJdJIeXHOCTN.

Metallnueckni 3axkIM 1 wt.ClnBnoi shanr 1 wt.Shai6a dny noDBeCHOrO KPOHsTeYHa 8 wt.1 2 Срedingу yIINOTHInbHa noDyUka 2 wt.
Большая yIINOTHIneJIbHa noDyUka 1 wt.ИЗOLЯЦЯ дny apMaTуры ДлгЖДКОCTHо Пини 1 wt. Длг razOBо Пини 1 wt.ДлнHоe yIINOTHeHne 2 wt.Инструksи no MONTaKу и Экплuyataси
ВИNTы дlya phanucesв Bo3dYxOBoDA 1 komPleKt 40 wt.4 ka6elNbIx СТЯЖИ

BnHTbI Jn KpEnJHnnaHeNe npKpEnJIOTcK naHEnn BO3dyxo3a6OpHnka.

DOnonHnTeIbHbIe npHaIaIeXHOCTN

IpeDycmOTpeHbnytBdNCTaHcUOnHOrOynpaBHeHnBdyx TnOB: npoBODhie n 6ecnpoBODhie. BblpaTne nybT DnCTaHcUOnHOrOynpaBHeHnB COOTBeTcBmC 3anpocAMn 3aka3vnKa n yctaHaBnBaJte erO B HndNeJaem MeCte. HΦopMaJn O bblope NdoXoJzero nybTa DnCTaHcUOnHOrOynpaBHeHn pnbBeHa B kataIorax n TexHHueckon DokymeHTaCIN.
Pn yctaHOBKe BO3dyxo3a6opa C HIXHHe CTOpOHb: naHEnb BO3dyxo3a6OpHNka Hn6Ka BCTaBA DnA Hee.

No cIeDyUOUM N03NmR Tpe6yeTc OOCoe BHNMaHneB npocce MoTaxa N KOHTpOJB NO eRO OKOHuaHH

(1)ΓΓΓ = notehuian rno6aibho ro notenneHn

B COOTBETCTBn C 06UeEBPoneNCKM NIN MeCTHBIM 3aKoHOaTeBcTBOM MOKET 6bITb Heo6XoDima nepoOnueckar npOBepKa Ha HAnuHye yTeek XnaJaareHTa. 3a 6Oone NoPpOboHnHΦopMaune ObaaainTecb K CBOeMy MecTHOMy dInepy.

BbI6op MeCTa yCTaHOBKn

(CM.pnc.1 npnc.2)

1 BbIbepeTe MeCTO yCTaHOBKn, OTBeUaHOuEe CNeDyUOIM Tpe6oBaHnM nYTBepKdEHnE 3aKa3uKOM.

B Mectax, Tne MoKHO oBeCneHTb ONTmAbHoe pacnPpeDeneHe B03dyxa.
C OTCyTCTBnEM PnpenrTcTbN npoxokDeHIO Bo3dyxa.
B MecTx, rIe BOHbI KOHdeHcat CInBaetc DOxKHbIM 06pa3OM.
B MeCTaX, Ie NOBecHOI NToTIOK yTaHOBJIeH 6e HaKnOHa.
B Mectax, Ie DoctaToUHO MeCTa IINI pOBeHnIg 06cnykubAHnI.
B Mectax, rIe OTCyTCTByeT pIck yTeKIN BOCIIaMeHReMOrO ra3a.
- He donyckaetc3kcnnyataunia o6opydoBaHnB B3pbIBoOnaHoi cpe.
C BO3MOXHOCTbIO CO6HIODEHNA DOYNCKOB HA IpOKnAky Tpy6 MeXy BHYTpEHHM HApYKHBM arperaTaMn. (CM. INCHTPyKUIO NO MOHTAXy HApYKHORO arperata.)
BHyTpHnH arperat, HApyKnHb arperat, npOBoJka 3NeKtpoNTaHnHa N CoeHNHTeNbHnA npOBoJka DOJXHb HaxoDHTcRa Ha ydaJeHnHe MeHee 1 MeTpa OT TeBeu3HOHn Ra daNoaAnpapaTypb. 3To no3BOHT n36KaTaN cKaKeHn N3o6paKeHn nn WymOB B DaHHbIX 3NeKtpueCeKn Xnp6opax. (DaXe npN ydaJeHn Ha 1 MeTp Wym MoKET IMTeB MecTO B 3aBNCIMOCtN OT YcNOBn BO3HKnHOBeHn 3NeKtpOMaHnTHbIX BOJIH.)
Ipy yctahOBke kOMnneKTA dny 6ecnpoBnHoro nybTa DY pacCTOHRMExNyTOM Dy IN BHYtpEHNM arperaTOM DOxNHO 6bTB MehLIM, ECIN B NOMeueHN NcNOB3yOTc FnyopeCHTBHe JAMBI C 3NeKTpueckM NyckaTeMe. BHyTPEHNI arperat Heo6XoDMO yTaHaBnBaTb KaK MOxHO daNbWe OT FnyopeCHTBix NaMn.
- He pa3MeaIe BoCnpnMmNBbIe K Bnare npEdMeTbI HEnOcpeDCTBeHNO IOD BHyTpEHHNIM NIN HApyXhblM arperaTOM. PpOn npEdeNeHHbY cNoBnAix KOHeHcaun Ha oCHOBHOM 6bnKe INI TpyBaX C XJaadAreHTOM, 3aqr3HeHHbl BO3dyuHbI MylbTp INI 3acopeHHbl DpeHax MoryT Bb3BAtb KaHaHne, YTO pRBeTeK 3 aqr3HeHHIO INI BbIXoYd N3 CTPOyKa3aHHbIX npEdMeTob.

2 Y6eINTecb B TOM, yTO Ha CTOPoHax BnYcKa N Bblnycka Bo3dyxa yCTaHOBHeH 3aUHThIe peuETKn, yTO6bI npEOTbpaNTb cOpNKOCHOBeHne C IONACTaMn BEHTNIArTopa NIN TENNOO6MeHHKOM.

3aunTa DoJxHa 6bItb BbINHeHa B COOTBeTCTBmC o6ueeBpOeNCKMn IMecTHbIMn HopMaTbAMn.

3ДЯ MOHTaKa IcIOnb3yIte NIOBecHbIe 6OITbI. Y6eIITecb, YTO NOTONOK DOCTaTOHNO pOCHbI IN BbIDepKINBaET BEC BHYTpEHrero arperata.EcIN NOTONOK HeoCTaTOHNo pOHeH, yKpeNITe erO nepeD MOHTaxOM arperata.

1 30ha 6cbnykmbaHn
2 Dpehaxnna Tpy6ka
3 OTBepTne dny npoBOda 3nEeKtpOnTuHa
4 OTBepCTne InpOBoKn ynpaBHeHn
5 DpehaXHoe OTBepCTme IJIaTe XeHHueckoro 06cnyKbAHHa
6 Ra3oBaA rpybKa
7 KndKocTha NHHH

IOnrToOBKa KMOHTaKy

1 CoOTBeTCTBnE OTBepCTn B NtOJIke NIOJKeHnArperata nNoDBecbIX 6oITOB. (CM.pucyHOK5)

МоселA (MM)В (MM)
15~32550588
40~50700738
63~8010001038
100~12514001438

1 BnytpenHH arperat
2 Tpy6a
3 POnBeCHOH KPOHHTeH (4 wT.)
4 PacToHHe MeKJy NDoBeChbIM6oTTAMn

Bb6epuTe OIMN N3 PpeCtABnEHbIX HNXe BapnaHTOB MOHTaKa.

CTaHdapTHbI Bo3dyxo3a6op C 3aHei CTopoHbI (CM. pucyHok 6a)

1 NoBepxHocThb Notonka
2 OTBepCTHe B NtOJIke
3 CepBnCHaCbemHnHaHnB(DOnONHnTeHbHa npHaNekHOCTb)
4 Bo3nyuHbIΦnIbTp
5 Bo3yxoBn noaHn B03yxa
6 CepBnCHoe OTBepCTne B 03dyxOBoDe
7 CbemHa nahenb

MOHTAX C yCTaHOBHeHHbIM C 3aHHe CTOpHO b BO3dyXoBOOM I cepBnCHbIM OTBepCTnEM B BO3dyXoBOe (CM. pncyHok 6b)

MOHTAX C yCTaHOBHeHHbIM C 3aDHei CTopoHbI BO3dyXOBOOM, 6e3 cepBnCHOrO OTBepCTnB BO3dyXoBOe (CM. pncyHOK 6c)

ПИМЕЧАНО

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 1

Ipeed MOHTaxkom 6noka (B cnuyae MoHTaxa CBO3dyxOBOOM, HO 6e3 cepBnCHOROTBepCTN B BO3dyxOBODe): N3MeHInTe NIOJKeHne BO3dyuHbIX qinlbTPOB.

1 CHIMMITE BO3DyHbI ΦnBtp (ΦnBTrp) C hApYKHOI CTOPOHb 6noka
2 CHIMITE cbeMHyIO naHEnb
3 YctaHOBNTe BO3dyuHbI bHytp (fNlbTpbl) C BHTpHeHcTOpOb6noka
4 YcTaHOBnTe CbEMHyIO NaHeIb

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 2

ПИМЕЧАНО

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 1

YTo6bl npDoTbpaNTb NOBpeKdHHe BO3DyUHOro
fNtbpa Bo Bpem TExnueckoro 06CnykBaHn, npn
MOHTaxe BO3DyXOBoJa NDaun BO3Dyxa BB6epnte
KpeJnxHbE BnHTb, KOTpbIe BbCTynaTc CBHyTpene
CTopoHbI PhaNca He 6Onee Yem Ha 5 MM.

1 Bo3nyxOBoN noaHn Bo3dyxa
2 BHTpeHHraCTOpHaФnHa
3 KpenexhblnHT

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 2

MOnTaX nAHeNn BO3DyXo3a6OpHnKa C rIbKoBCTaBko (Cm. pncyHok 7a)

HenocpeCTBeHHbMOHTaK NaHeJIIN BO3dYxo3a6OpHnka (CM.pncyHOK7b)

1 NobepxHoctb notonka
2 OTBepCTHe B NOTOnJIke
3 PanaHb Bo3dyxo3a6Opnka (DOnONHTeJIbHa npHaIaNexHoCTb)
4 BnytpenHHn arperat (3aHnra ctopoHa)
5 I6KAB BCTaBA Dnna NaHEn Bo3dyXo3a6OpHnKa (DOnONHTeBHa PnHaAeKHOCTb)

Мо德尔A (MM)
15~32610
40~50760
63~801060
100~1251460

Bo3dyxo3a6op c HnKHei CToPOHb (CM. pncyHok 7c)

DIPMEYAHNE

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 3

YTO6bl NcNoIb3ObaTb 6nOK C HIXHIM BO3dyxo3a6Opom, NOMeHJTe MeCTamn CbeMHyIO naHeB I KpeEnxHyIO pIacTHNy BO3dyuHOro fNltpa.

1 Kpeenexnna nactina B03dyuHoro fnnbtpa c fnnbtpom (fnnbtpamn)
2 Cbemnna naheB

ПРМЕЧАНО

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 4

3a KOHCyIbTaUnei No MoTHaKy, OTNuAioUeMyc O TcAndapThoro, 6paauTecb K 6bnxKaUeMy Dnepy KOMnAHn Daikin.

2 ⅡIЯ 3TORO BHyTpEHHero arperata npedBapntelho 3aHaHcKOpocTb BEHTnIraTopa, T06bl ObecneuHt CtaHdapTHoe BHeUHHe CTaTNUeCKOE DaBHeHne.
3 YcTaHOBInTe noDBecHbIe 6oNTbl.

(NcnoIb3yIte noDBeChbIe 6oJIbI M10.) DnY yKpenneHnnoTOKOB, KOtOpBle DOJXHbI BblDepKbBaTb Bec arperaTa,NCNoIb3yIte aHKepeBb IIN NMeIOUxCRe NOToNkOB n Bpe3HbE BTyKN, Bpe3HbI e AHepeBbl INN DpyRNe npNo6peTaEMbIe Ha MeCe DeTaN DnHOBBIX NOTOKOB.

Ppumep MoHmka

(CM.pucyHOK 3)

1 AHKepe
2 TOTONOCHAR nIHTA
3 DnHHaMyoTaHn BNHTOBaCTXKa
4 POnBecHO60JT
5 BHytpenHn arperaT

DPMEYAHNE

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 5

Bce yonomaytbe Bblte deTann npno6petaotc HAMeCTe.
3a KOHCyIbTaUneH NO yCTaHOBKe,OTNnHaIOUeICr OT CTaHdApTHoH,OBpaUaNTecb K 6nJkaMWeMy dInepy.

MoHTax BHyTpeHHero arperata

Pn yctahOBke DOnONHHTeNBbIX npHaADNEXKHOCTe (3a NCKIOHcHEm naHei BO3dYxo3abOpHnKa) TaKKe IcNoIb3yTe pyKOBOCTBO nO MOHTaky DOnONHHTeNBbIX npHaADNEXKHOCTe. B 3aBNCIMOCtO arperata.

1 BpemeHHoYcTaHOBnTe BHyTpeHHn arperaT.

PekomeHdaunnoMOHTaKy Tpy6oNpOBoDxJaDaReHt a

CbeHnO npoknaKe TpybonpoBOna XlaDareHTa Do HapyKHOarperata coepkataC B pykoBOCTBe NO MOHTaKy, KOtOpoe BXoNTB KOMNNEKT NocTabKn HapyKHOarperata.

Ipeep MOHTaxKom Tpy6 npoBepbTe, KaKoT Tn XnaaareHtA nCnoNb3yETc.

DAIKIN FXSQ15A2VEB - PekomeHdaunnoMOHTaKy Tpy6oNpOBoDxJaDaReHt a - 1

YcTaHOBka DOnKHa npOn3BODHTbC aTTECTOBaHHbIMn CneuaHInCTAMn. MaepnaIb I NopraDOK MOHTaKa DOnKHb NONHOCTbIO COOTBETCTBOBaTb CyueCTByOuIM HAOnOHaJIbHbIM MekdyHapOnHbIM HopMaM. B Ebpone DoJxeh NCOnBJ30BaTbC DeIeCTByUoi CTaHdapt EN378.

NcnoNb3yIe Tpy6ope3 n pactpy6, COOTBETCTBYIOUne NcNoJIb3yEMOMY XnaIaIareHTy.
Bo n36eXaHne nonadHnB Tpy6y nbIn, BnAin nnDpynX noCTOpOHnX BeueCTB 06KmMaTe KOHeu Tpy6bI Nn6o 06MaTbBaIte erO JeHTOn.
Ncnoj3yIte 6ecwOBBhe Tpy6bln MeHoro cnnaba (ISO 1337).
HapyKbI 6nok 3arpykaeTcXnaDareHTOM.
TTO6bl PpeoTbpaTb yTeKy BObl, BblONHITe TENNO3OJIaIOHOHbIpe 80BoBmOBbEMcObeHXCTOPOHra3OBORINIKDIOKTHOrTOpyoPBOBOOB.PnNCNtOB3OBAHIN TENNOBORHO HACOCa TEMNepaTypaBra3OIPBOBDoMOKETDOCTnRa120°C, NO3OMy NcNoB3yIte N3OJIaUHO, OblaDaIoUyIO DOCTaTOHOUYcToHIVBOCTbKO TaKoi TemPeatype.
Pn noCoeHHeHH MeHbIX Tpy6 K 6NOKy Hnn npn nx OTcoeHHeHH NcNoJIb3yIOrCa OHOBpeMeHHo Dba raeHbIX KIIHOa-ObIHyHn INHaHOMEtprueckn.

1 DnHAMOMeTpueckn Klnou
2 Taeyhny KIOU
3 CoeHHeHHe Tpy6
4 HauHra

DAIKIN FXSQ15A2VEB - PekomeHdaunnoMOHTaKy Tpy6oNpOBoDxJaDaReHt a - 2

CneIte 3a TEM, YTO6bB KOHTyp XnaJaReHtA He nonaAnn NOCTOPOHHe Cpebl, HApIMep BO3dyx.
NcnoB3yIe oToXKeHHbIM MaepnAn TOnbKO dIra CoeHHeHNC HAKNDbIMrKaKAM.
Pa3MepbI HakuHbIX raeK 3HaueHn MOpHTOB 3aTJkN npBedeHb I Ta5nua 1. (EcnraKn nepetHyb,TO moXHO NOBpeDntb pa3BaIbCuOBAHHy Uactb Tpy6bl,TO npBedeT K TeUKe XnaDarEHTa.)

Tabnla 1

Y6eNTecb HnAdnEkaueHnOJauH BCEx Tpy5 Ha BcEM INN pOToTaeHnD O CoeHNHTebhix 3NeMeHToB BHyTp n arperata.

B Tpy6ax 6e3 n30nauu BO3MOxHo o6pa3oBaHne KOHehCata. TaKKe BO3MOxHbI OXOrn Pn KoHTaKTe CTaKmM Tpy6amn.

Mepbl npedoctopoxhoctn npn naKe

063aTeBbHO BbIOnHITe npOdyBky a3OTOM npn naKe.

PaiKa 6e3 npoBeHn npOyBKn a3OTOM nIN NOaHn a3Oa B Tpy6oPiBOJnpiBOJNT K o6pa3oBaHnIO OKcIuPoBaHHo NIIeHKn Ha BHyTpHeHn NobepxHocTNpy6,OKa3bBAra HeRaTHBHOE Bo3deIcTBne Ha KJIanaHbI N KOMnPecccOpbl B CnCTeme OXnaKeHn IN ppeTCTByr HopMaIbHomy FyHKUHOHPOBaHHIO.

C nomoBpo peDyKIOHHO KnaHa yCTaHOBt EaBHeHne a30a B Tpy6oPbOBe 0,02 MPa (=To eCTb JnMb OuyTmBIM, ecnn HapabNTb Ha KOxy).

DAIKIN FXSQ15A2VEB - Mepbl npedoctopoxhoctn npn naKe - 1

1 TpybopobOdbxnaaareHtA
2 PpnaBaeMaJ DaTalb
3 O6MOTKaJeHTOn
4 Puyho Knaan
5 PedykuHnBknAan
6 A30T

PekomeHdaunnoMOHTaxy dpehaXHoro Tpy6o npOboda

YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa

YcTaHOBnTe DpeHaxHbI Tpy6oPBOD, KaN oKa3aHo Ha pCycHke, N BblONHnTE BCE Heo6xOIMMbIe Oepaun No npDeOpTbpaueHIO 06pa3oBaHnKoHdEhCATA. HEnpaBUNbHO ycTaHOBNeHHbI Tpy6oPBOD MoKET cTAtb PpUHNOyTeek, YTO MOKET pINBeCTN K HamokAHIO Me6eIN n dpyrX PpeDMetOB.

DAIKIN FXSQ15A2VEB - YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa - 1
1 PnDBeChra nAnKa

DAIKIN FXSQ15A2VEB - YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa - 2

YcTaHOBtEpeHaxHbIe Tpy6bl.

Tpy6oip0BdI DoKHb 6bIb KaM OKOHO CkyHOHOM Bn3 He MeHee 1/100, T05bBo3dyx He yepKmbaCnB Tpy6.
Pa3Mep Tpy6doJONKeH 6bITb paBEN pa3Mepy coeHNHTenBHOI Tpy6bI HIN PpeBbIaTb erO (BHNIOBAra Tpy6a c HOMHaJIbHBM DnAmETPOM 25 MM HapyKbIM DnAmETPOM 32 MM).
BCTaBbTe npnnaeMbI cINBHOH UHaHr KaK MoXHo rny6Ke B DpeHaXKnbl pa3beM.

DAIKIN FXSQ15A2VEB - YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa - 3

1 DpehaxHb pa3bem (3akpenneHa arperate)
2 CnBHOJUHaH (noCTaBnEraTC BMeTe c aRperaTOM)

3aTaNHTeMeTALNueckn 3axm TAK, yTO6bI rONOBKa BnHTa 6bIHa Ha pacCToHn MeHee 4 MM OT DeTaN MeTALNueckOro 3axmHa, KAK NOKa3aHo Ho pncyHke.

DAIKIN FXSQ15A2VEB - YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa - 4

1 Dpehaxhbl pa3bem (3akpenneHa arperate)
2 CnBHOJ WJAHr (NOCTABNRETC BMECTe C aperatOM)
3 MetanJnueckm 3axkM (noCTabnEeTcBMeCTe C arperatOM)
4 Bonya ynnotenbna noyuka (noctabnaetc a rperatom)
5 DpehaKbI Tpy6oPBOOd (pno6pTaetcHa MeTe)

IIN30JnO6epHnTe 6oBsyU yNIOHTnBHyIO NOyky (NoCTaBnRETC) BOKpy MetaIIHueCKOrO 3axmAm N CnBHORO WNaHra N 3akpenITe ee c NOMoubHO 3axmMOB.
Becb dpenhaekhny Tpy6oNpOBoD B 3daHm Heo6xOIMO nOIOPOBaTb (Ha MeCTe).
- Pn HEBO3MOXHOCTN yCTAHOBINT CINBHOI NNAH NOI DOCTAOTOHBM YKIOHOM 3AKPeINTE erC NOMOUIBO DpeHAXHORO NOBemHOro Tpy60npoBODa (Pnno6peTaetcHa MecTe).

Kakpa6oTaBcpeHaxHbIMtpy6oPBODOM

(CM.PUCYHOK10)

1 NotonoynarnnTa
2 POnDbecHOH KPOHHTeHH
3 Hana30H perynipOBKn
4 DpeHxHnnoBemHaTpyBa
5 CnBHOH uHaHR (noCTABnrrerCB MeCte C arperatOM)
6 MeTaanHueckn 3axmN (noCTaBnRETCBMeCe C6IokOM)

1 POncoeHNHte CnHBHOI WNaHr K DpeHaXHbIM NOpBeMHbIM Tpy6am 3a30nnpyTe WNaHr C Tpy6am.

2 POncoeHNHTe CnBHOI WNaHr K DpeHaxHOMy OTBepCTIO Ha BHyTpEHHeM arperate n 3akpenITE erO C NmOuBIO 3aKIma.

He n3BnkeKaIte npO6Ky dpEHaXHoN Tpy6bl. Bo3MoXHO BbITeKaHHe BObl.

Dpehaxhoe OTBepCTne NcNoIb3yETcN IaBnYcKa B0bl, TOnbKO ecHn He npMHeTcN DpeHaXhBn Hacoc nn nepeed TexHnecKIM 6cbnykBaHnEM. OctopoxHo BCTabJIte N3BNeKaIe TcINBHyO np6Ky. Ype3MePHOe ycIIne MOKeT pNBecTn K DeOpMaun DpeHaXhORo pa3bema DpeHaXHOro nOdoHa.

13BHeHne np6kn

DAIKIN FXSQ15A2VEB - YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa - 5

1 CnBna np6ka

He kaayte npo6ky Bbepx-BnH3

YCTaHOBka npo6kn

DAIKIN FXSQ15A2VEB - YcTaHOBka DpeHaxKHoro Tpy6onpoBoDa - 6

YCTAHOBITE np06ky HnKaKMITE Ha Hee Kpectoo6pa3HOn OTBeptKoI

Cnauana BbINOHNTE MoNTax 3NEKtpoPBOQKn coNtacHo pa3deNy "PaOTo c 3NEKtpuYeCKo npoBOKo" Ha cTp. 7. YcTaHObKa nyIbTa DnCTaHNoHHoro ynpaBHeHna ONCaHa B pa3dene "PpIMep npoBOKn HAcTPOkN pNbTa Da" Ha cTp. 8.

Tocnie 3abepene npoTc anektpnpoDko

PpOBeBte NoTOK CnBa BO BpemXOJIOHOI paOToI;ObjrcHeHne npBHeHO B"PpObHb 3aYcK"Ha cTp.12.

Ecn pa60tbc 3nKtpnpoBOKn He 3aBepueHbI

CHIMITE KpbIky pacnPdeHNTeNBHOKOPO6KNIOODCOEHNHTOHOHpa3bH NTOUHHNITAHNA HYNB TINCTAHNOHOROynpABNEHnK KNEMMAM.(YcTAHOBA/CHTne pacPdeHNTeNBHOKOPO6Kn ONICAHA B pa3dene "Pa6ota c 3JIeKTPuYeCKoN pnoBOkO"Ha CTp.7.) (CM.pnc.12 n pnc.14)

1 Kpbuika pacnpedeHnteHoh KOPO6Kn
2 OTBepctne Inpobodkn ynpabnene
3 OTBepCTne nnpoBoDa 3NeKtponTuHa
4 3neKtpnueckar cxema
5 Pacnpenentbna Kopo6ka
6 nactmaccoBb 3axm
7 PpOBoKa nYbTa Dv
8 KneMMHAR KOONKa dnn npoBOOB ynpabHeHn 6noka
9 PpOBoD 3eNkTpOnnTaHn
10 Neuathar nata 1 BHTpeHero arperata
11 KneMMHaKoJOnKa 3eKeTpOHTaHnI
12 PpOBoKa ynpaBHeHmExy 6nokam
13 Neuathra nata 2 BHTpeHero arperata
14 DnHHoe yIINOTHeHne
15 PpOboKa

Ha nyIbte Dv HaxMMTe KONky KOHTpOra/npo6Horo 3anycka TEST

BLOK nepeienet B pexnM npo6Horo 3ayncKa. HaxmMaTe KhoNky Bb6opa peXnMa pa60tbl noka He 6yDet Bb6paH peXnM

BHTNlraTopa HaxMITE KONKY BKNIOUeHn/BBkNIOUeHn 3anyckaetc BHTNlraTOp n dpehakHbI Haococ BHTpeHHero arperata.

Y6eIITcB TOM, YTO BOa CnITA N3 BHyTpeHHeRo aPerata. HaKMNTe KHOJky TEST, YTObblBepHyTbcK nepBOMy peKIMy.

Pa6ota c 3JIeKTpnuYeCKo npOBoDko

06une yka3aHn

MoHTaK 3eKtpoPbOdkn IN DpyrNk 3eKtpuecknx KOMIOHeHTOB CNTEmbl DOJKeH BblONJIHrTbCg TOIbKO ATTECTOBaHHbIM 3eKtpNKOM B CTPorom COOTBeTcBm C O6UeEBponeckMn IN HAIOHOJIbHbIM CTaHdApTaMn IN paBUNaMn.
IcnoNb3ynteToNbKOMeHbIe npoB0da.
I pykoBcByteb 3eKtpuecko cxemoi, 3aKpenneHno Ha Kopnyce 6noka. DOnonHntbHbIe CBeHnO pa3MeueHnn nybTa DY npnbEbeB b pykoBcTBE no yctahOBke nybTa DY.
BbIOnHeHne IIO6bIX pa60T no 3JIeKtpnueckOMy MOHTaKy CNeDyET DoBeprToTbKO 3JIeKTPnky C COOTBeTcTBYIOUM Donyckom.
I OdkHIOUHTe K JINHH NITaHn yCTPOHCTBO 3aUNTHORO OTKIOUHeHn INpeDOxpaHNTenb.
B cTaIOHApHyIO npOBOky Heo6xOIMMo BKNHOHTb rAaHBbl BbIKIOUaTeIb nIN dpYrNE cpeCTBa pa3beDUNHeHNr NO BCEM nonHOCAM B COOTBeTCTBnC DeiCTByIOUIMM MecTHbIMN n 06ueroCyapcTBeHHbIMn HopMaTINbAMN.

OBpatnte BHIMAHNE, YTO 3Ta Oepaunr npBBOHT K aBTOMaTmHeCKOMy nepe3anycky npn OTKIOHcHIN N NOBTOPHM BKIOHcHmOCHOBHOrN ICTOHHnKa NITAHN.

Ceyehne 3NeKtpuecknx npoBODOB nCTOCHNkA nHTAHn, noKnIOyaeMbIX K HApYXHOMy arperaTy,napaMeTpbl ycTpoIcTBa 3auNTHOro OTKnIOUeHHeN N ppeDOxpaHHTeN, a TaKKe INHCTpyKuIN No 3NeKtpueckomy MOHTaxy PpNBedeHb B pyKOBoIcTBe NO MOHTaxy, pnpilaraemom K HApYXHOMy arperaTy.
KoHdNIOHeP Heo6XoJIMO 3a3eMJIaTb.
He noDcoeINHnTe npoBOd 3a3emnHnK cJeNyUOuM KOMNoHEHTAM:

ra30bIe Tpy6bl: BO3MOxH B3pbIB ININ NOXap B Cnyae yTeKn ra3a;
TeNEoHbIe IPOBOa 3a3eMnHnN NIM MOHHeOTBObI: BO3MOXHO HAKONJIeHne BbICOKOTo 3JIeKTPuYeCKOro NOTEHuaA Na K KOHType 3a3eMnHnB Cnyae nonaHaHn MOHNi
KaHaJIIN3aIIOHIIbe Tpy6b: B Cnyae IcNoJIb3OBAHnI Tpy6 n3 JecTKoro BUNHnIa 3ΦΦeKt 3a3EmHeHnO tcyTCTByET.

Y6eINTEcB B TOM, YTO npoBOd 3a3emNHeHmEXKdy 3axnMOM DnA Ocna6bHeHn HaTaeKeHn IN KIeMMO nnHHee octaJIbHbIX npoBOOB.
Ipeed BBOOM npoBOOB a arperaT y6eHntecb, 7TO fopMa Ka6eJn NTaHnN n Dpyrnx npoBOOB COOTBETCTByET NOKa3aHHo HapncyHke.
Bce 3aBODnMbIe B 6nok Ka6enN DoJXHbI KpeNTbcra Ka6enbHbIMn CTJKKAMN (npHaadneKHOCTn).
Ncnonb3yIte DnHHoe yIIOTHHeHne, YTO6bl 3aKpbItB BXoB BpacnpedeJIteJbHyIO Kopo6Ky, KaN oKa3aHO Ha pnc.12.

DAIKIN FXSQ15A2VEB - 06une yka3aHn - 1

3neKtpueckne xapaKtepncnK

Мо德尔ГцВДианазон Изmenения напрахеньяЗлес耗费патни MCAMFA
1550/60220-240/220±10%0,416 A
200,4
250,4
320,4
400,8
500,8
630,9
801,0
1001,5
1252,0

MCA:MHHMMaJIbHbI TOK B CEEN (A) MFA:MAKc.TOK npedoxpaHnten(A)

DIPMUEYAHNE

DAIKIN FXSQ15A2VEB - 06une yka3aHn - 2

Iopobhna HnΦopMaun npBedeHa B pa3deNe "3neKtpnueckne xapakTepcNTkN" 6yKneta cTexHnueckmXapaKTepcNTkAmn.

Texnueckne xapaKTepeNtKN npdeoxpAHnteNe I npoBOIOB, yCTaHaBnBaEMbIX no MeCTy 3KcnJyatauIN

Cnocob noDCoeHHeHH npoBOKn

Chmnte KpbuKy pacnpedentbHoi Kopo6Kn, KaK noka3aHo Ha pnc. 12, N BbIOJNHTe coeINHeHn.

1 Kpbuika paacnpedeJIeNTbHoiKopo6Kn
2 Bxod paonpeIeHtIbHoH Kopo6Kn IJI npoBOkN H3KOrO HanpJKeHH
3 Bxod paacnpedeHntelbHOKopo6Kn dIpy npoBOKn Bicokoro HapraKeHHa
4 3neKtpnueckar cxema
5 PacnpedenntbHaKop06ka

Mepbl npedocTopoKHOCTN

  1. PnnoKIOHcyEHIN pOBOOB K KneMMHO KoIIOKe HcTOHHKa nITaHn ObpaauTe BHMaHHe Ha npBedeHHbe Hxke 3ameuHn.

IcnoB3yTe KpyTbI OTOHytbI pa3bEmnI3OJauoHHO BTyNKn Pn NODKIOHeHN K KneMMHOKOJNOKe Dn npOBOnArperata.Ecn pa3bEmbHeNoCTynb, BbINONHTe CnDeIyUcme DeiCTBna.

DAIKIN FXSQ15A2VEB - Mepbl npedocTopoKHOCTN - 1

1 Kpyrtnb otOrhytb pa3bem
2 YcTaHOBnTe N3OJIaUNOHHyBOTyNkY
3 PpOboKa

He npncoeinHnTe K OndHn Toi Je KneMm NcToHHa nTahnnpoBoda, pa3nnuauuuece no copTaMeHTy. (Ppocna6nHn CoeHNHeHn MoKet npOn30Tu nepepeB.)
- Ppi noKluOeHn npoBOOB OINaKOBOrO ceHnnpicoeHNrTe nx cornaCHO pcyHky.

DAIKIN FXSQ15A2VEB - Mepbl npedocTopoKHOCTN - 2

DAIKIN FXSQ15A2VEB - Mepbl npedocTopoKHOCTN - 3

DAIKIN FXSQ15A2VEB - Mepbl npedocTopoKHOCTN - 4

Icnonb3yte yka3aHnbl 3neKtpueckn npoBO. IpOuyho nOdoeHNHTe npoBO K KJEMME. 3aФNKcpyte npoBO, He npunara qpe3mepHo cnbl K KJEMME. MoMeHTbl 3aTAAKKyka3aHb B cIeDyIOuSe T6nue.

EcnKoHnIeHep He npekpaaaet pa6Oy, HnHOMep BTOPOKoJa He paBEN "02", NOBtOpNTe DeNCTBne 4.

EcHn HApxHbI arperaT He BkIOueH,Ha DnCnIeepyNtTa
DnCTaHnOHHoro ynpabEnHn OTo6paKaaetc KaD"UH"nn "UH"
cm. pa3dEe "PpO6HbI 3anyck" Ha cTp.12).OHaKo MoXHo
npoOnJHTb HAcTpoKy 3ToI FyHKuIN, NocKoNkY 3TN
coo6uHHe nPpmeHmbl ToBko dner HApxHbIX arperatOB.

Iocne HAcTpoKn 3ToN cyHKuIN BkHIOHTe HApYKbH arpera Tpeep np6bHm 3aNyckOM daHHoro arperata.

Ecni Ha dncnnee nybta nctaHcHNOHHoro ynpabneHna oTo6paKaetca npraa Oun6ka, cm. pa3den "PpObHbI 3anyck" Ha cTp.12 i pyKoBOcTBo no 3KcNlyatauHn HApXHoro arperata.YcTpaHnte HeNCnpaBHOCTb.

DAIKIN FXSQ15A2VEB - Mepbl npedocTopoKHOCTN - 5

EcnBHeHHe cTaNueckoe DaBnHeNe npeBbIaet 100 Pa, He nCIOB3yIte FyHKUIO ABOtOMaTnecko peYINPOBKN BO3DyUHORO NOTOKA.
Ecn nocne perynipOBKn BO3dyuHoro noTOKA OTCyTCTBYOT N3MeHeHn B BEHTNIAUHOHBIX KaHaIax, BbINOHNTE HAcTpOky ABOTMaTuYeCKoI peynipOBKn BO3dyuHoro NOToKa NOBtOpHo.
O6paTntecb K CBOeMy DnIepy, ecnn nocpepyInpOBKn BO3DyUHoro NOTOKa OTCYCTBYOTn3MeHeHn B BEHTnIaUIOHHbIX KaHaJnx nocneBblONHeHn npo6Horo 3anycka HapyXHoro arperata nnI nepeMeueHn KOHNIOHOhepa.
Ecn npmeHOTc BCNOMORAeBbHbe BHTnTOpbl, Hapyxhbl arperat nIg opa60Kn BO3yxa nn 6nK HRV, noCoeHNHeHHb ype3 BO3yXoBOd, He nCnoJb3yTe nyIbT Dy nn ynpaBneHna aBTOMATUeckO peYnIpOBKO B03dyuHoro nOToka.
Iocne n3MeHeHn BcHTnLzIOHHbIX KaHaIOB NOBTOPOB BbINONHITe HAcTPOy ABTOMaTHUeCKO perynipOBKn BO3DyUHoro NOTOKa, HauHna C DeiCTBn 3,Kak ONCaHO Bblie.

Icnonb3oBaHne npbTa dncTaHnOHHoro ynpaBneHna

Y6eINTeB TOM, YTO BO BHYTpEHem arperate DnB TOpORO KoJa pexkma 21 3aHaHO 3NaHeHne 01 (3aBOdCKa HacTPOka). N3MeHNTe BTOPO KOD B COOTBeCTBm C BHeUHM CTaTHueckm DaBNeHEm NOcEOHNHeHNOB3dyXoBOda, KaK Noka3aHO B Ta6nue 2.

PnncnoB3oBAHm2nybTOB DYcneyET nepeBeCTn OINH nHxB OCHOBHON peKIM, a pyroB peKIM CY6BJIOK.

NEPEKNIIOUeyHEOCHOBHO/CYEBJOK

Bctabte OTBepkcy C nIOCKMM WJINcEM B NOIOCTb MeKdy BepxHn HIXHHe Yy, Bo3eJeCTByc 2 CTopoOH, OCTOPOKHO CHIMITE BepXHIOU Yactb. (CM. pucyHok 18) (NeuTHa nnata NybTa DY npCoeDHHReTc K BepHe qactn nyIbTa Dv.)
IpepeBeHnTe nepeKIOuHaTeNb CMeHbI peKIMa OCHOBHO/ CY55JOK Ha oHOB n3 nIaT PC nyIbTa Iy B noOnKeHne S. (CM.pncyHok 19)

(ПepeknoyateNBpyrOTo nIbTa DnCTaHOnHO rypabHeNn octabTe B noJoxeHm M.)

1 NeuHnna nynbTa D
2 3aOdkaHaCTpoKa
3 Heo6xOIMO n3MeHnB HAcTPOkY ToIbKO dIa OJHO rNJIbTa D

KOMnbIbTepeHoe ynpaBHeHne (npuHynteHbHoe BbIKIOueHne H Oepaunn BKIOUeyHra/BbIKIOUeyHna)

1 CneuPnkaun npoBOOB u kaaHn no 3eKtpueckomy MoTAty

IIOKIOUHTeBXOcHApyKHOCTOPOHKKNMeMMAMT1NT2 KEMMHOKOJOKn(npoBOKapeepaDAnHHbxCnybTaDY)

UHCTKa BO3dUwHbIXΦHbTpOB

OuHuaTb BO3DyHbIe FnIbTpbl Heo6xOIMo TOrda, KOrda Ha dncnnee NOBUTc CmBOBn" (NOPA YNCTNTb FInlbpT).

Ecnn KOHdNIOHeP 3KcNpyATnpyETcB MecTax, rIe BO3dyxCnIbHO 3aqrpa3HeH, YnCTky FmNbTPOB Heo6xOJIMO npOn3BOJtB Haue.

EcnnnHbTp HeBO3MOxHO OCHNTb OT rpa3n, 3aMeHHTe ero. (Cmehhbln HbTp nocTaNrEcTn oTdEnbHomy 3aka3y.)

1 OtkpoTe Bo3dyxo3a6opHyo peWetky (TOnbKO dNra Bo3dyxo3a6opa C HnKHe CTopoHbI).

OndOBpeMeHHo CdbHbTe o6e pyK, KaK Noka3aHo, IN NOTAHNTe INX BHN3.

DAIKIN FXSQ15A2VEB - UHCTKa BO3dUwHbIXΦHbTpOB - 1

Ecn npedycmToHbI cHmnte nx C KpkoOB.

DAIKIN FXSQ15A2VEB - UHCTKa BO3dUwHbIXΦHbTpOB - 2

2 CHMMTe BO3DyUHbIe fNJIbTpbl.

CHIMITE BO3DyUHbIe CnBtpbl,NOTAHy IN XTKaHB BBepx (BO3DyXo3a6Op c 3aHHei CTopoHbI) HIN BHIN3 (BO3DyXo3a6Op c HIXKHei CTopoHbI).

DAIKIN FXSQ15A2VEB - UHCTKa BO3dUwHbIXΦHbTpOB - 3

B03dyx03a6op c HIXKHei CTOPHOI

DAIKIN FXSQ15A2VEB - UHCTKa BO3dUwHbIXΦHbTpOB - 4

3 OuHCTHTE BO3dyHbI htp.

BocnoIb3yIteCb nbIeCOCOM (A) nIN npoMoTe BO3dyHbI ΦnIbTp BDOI (B).

YnCTka HapyKhbix nHaHei

HcTky cIeDyET npOn3BOuNTb C nOMOuM MAnKoTKaHn.
IyraJeHn TpyHOBBIOBIMBX NATEH HcNoJIb3yTe BOy IIN HeITpaJIbHOe MOIOue CpeCTBO.
OuHCTnTe 3aKpblTyU peWlEly Ko3dyXo3a6OpHNka.

TIPIMMEYAHNE

DAIKIN FXSQ15A2VEB - YnCTka HapyKhbix nHaHei - 1

He npimHeHnTe nIy NCTKn 6eH3nH, KePOcIH, pactBOpHTeIN, abpa3nHBhle MaTePmaJIb IN HNCEKTHUINDbI. 3To MoKet Bb3BaTb ObecuBeHNBaHne INI DeΦopMaHIO KOpTyCa KOHNHOHaepa.

He donyckaIte nonadaHna Bnarn Ha Koprnyc BHyTpeHHero 6noka.3To MoKet npBecTu KnopajehnIO 3JKeTPOTOKOM Nn BO3ropaHNO.

BkHoueHne nocJe dntTeNbHoro npocToA

Ponu3BeDnTe CneDuOuHne Oeepaunm:

PpOBepbTe, HETIINIOCTOPOHHHN PpeMToB, ppenTCTByIOxN BxOdy N BbIXOy BO3Dyxa. Ecnn ectb, y6epnte ux.
PpoBepbTe HaedKHOCTb 3a3eMJIeHnI.

OuCTTE BO3dyHbI ΦnIbTp n HapyKhIe NaHeI N KOHNIOHOpe.
No 3aBepeHnOChcKHe 3a6yDbTe NoCTaBnTp HmecTo.

BknHouHTe pa3MbkaTeN bEN NITaHn.

Pn noahe nTaHna 3arOpntc DaCnneynyBta ynpabHeHna.
Дя 3auntb6noka yctahabnBaTe OCHOBH BbIKHOATEJIb nHTAHIBpa6oyee noJoxKeHHe XOTb3a6YacOBdoHaayana pa60tbl.

Peped BbIKIOeHHeM KOHNIOHepa Ha dNITeIbHbI cpoK

IpepeBeDte KOHNIOHOEP B pexm TOJbKO BEHTNJLIAHn DaTe emy nondno npabOToB b 3TOM pexmme, yTO6bl npocuHTb 6nok.

CMOTPNTe HNCTpyKUHNO no 3KcnnyatauHn HApyXHoro arperata.
OTKIOHHTe NITAHNE.
Ecn nntaHHe OTKNoeHo, HekotopbIe cenn CnCTembl HaxoJrTcNd HapnKHeM, daKe ecn OHa He pa60Taet.
Iucnne nynbta nctaHcnoHHoro ynpabNeHna BbIKIOaetc npn nepemuehen rnaBHORO BbIKIOaTeB BBIKIOeHHoe nonoxKeHne.

yTnna

EmoHTax arperata, ydaIeHne XOJOnbHoro areHTa, Macna n dpyrnx Yactei DoJXHb IPOBOINTBcB B COOTBeCTBm C MeCTHbIM n 6ozerocdyapctBeHHbIM 3aKHOJaTeJIbCTBOM.

3JIeKTpUeCKa cxema

MECTHARIPOBOKAKAPA3bEMKINEMMA C BINTOBbIM KPEJIENHEM

BLK : YEPHbI PNK : PO3OBbl BLU : CINHn RED : KPACHbl BRN : KOPNUHEBbl WHT : BELbl GRN : 3EJIeHbI YLW : XENTbl ORG : OPAHKeBBbl

A1P. .NEUATHAJIATA
A2P. .NEUATHAJIATA (BEHTNIJTOP)
C1. KOHDEHCATOP
C105. KOHDEHCATOP
DS1. CEJIKTOPHBI IPEEKLIQUATEJB
F1U. .IPEOxPAHITIEL (T,3,15 A,250 B)
F2U. .IPEOxPAHITIEL (T,5 A,250 B)
F3U. .IPEOxPAHITIEL (T,6,3 A,250 B)
HAP. JAMbl INDINKAUM
K1R. .MAGHTHOE PEIE
L1R. .PEAKTOP
M1F. .IBNATIEL (BHTPEHHN BEHTNIJTOP)
M1P. .IBNATIEL (IPEHAXHBI HACOC)
PS. .IMNUbCHbI NCTOCHNK NTATAHIA
Q1DI. .YCTPOICTBO 3AUITHORO OTKIOUCHENRA
R1. .PE3NCTOP (DATUK TOKA)
R2. .PE3NCTOP (DATUK TOKA)
R1T. .TEPMNCTOP (BCACsIBAHNE)
R2T. .TEPMNCTOP (KNDKOCTb)

R3T. TEPMICTOP (3MEEBNK)
S1L. .IIOJIABKOBOE PEIE YPOBHA
V1R. .IIOJHbIMOCT
V2R. .BLOK NITAHNIA
X1M. .KIEMMHAR KOJODKA (3JEKTPONHTAHNE)
X2M. .KIEMMHAR KOJODKA (YIPABJIENHE)
Y1E. .OBMOTKA 3JEKTPOHHO
TEPMOPEYINPYUQERO BEHTINRA
Z1C. .ΦEPPITOBBI CEPDEHNIK
Z2C. .ΦEPPITOBBI CEPDEHNIK
Z1F. .ФИЛБТР ПОДАВLEHNI POMEX

PA3bEM(DONONHHTeJIbHbIe PnIHADJIeKHOCTN)
X28A...PA3bEM(ДЯ ПОВODКИ NCTOCHNKA
PITAHNY)
X33A...PA3bEM(ДЯ ПОВODKN)
X35A...PA3bEM(ДЯ ПОВODKN NCTOCHNKA
PITAHNY)
X38A...PA3bEM(ДЯ ПОВODKN)

WIEDR REMOTECONTROLLER IpoBDOHnIyIbI DnCTaHIOHOYnpabHeHHA (OPTIONAL ACCESSORY) (DOnoJIHITeHbHa npHaIaNEXHoCTb) SWITCH BOX (INDOOR) PaCppeJeHtEhBaKop06ka(BHyTpEHnRA TRANSMISSION WIRING IpoBOKa ceHnpeJaH CENTRAL REMOTE CONTROLLER LcHTpaHbHnIpyIbI dy INPUT FROM OUTSIDE Bxod chapyKn COMMON POWER SUPPLY O6uH NCTOHNIK PHTAHNA

ПИМЕЧАНО

DAIKIN FXSQ15A2VEB - ПИМЕЧАНО - 1

  1. INTOINb3yIe TOJIbKO MEHbIE NPOBODA.
  2. ECINI NCIIOJIb3yETCRAIHTPAJIbHbI IYbLT Dc, CM.PYKOBODCTBO IIO NOIKIIQUEHIO K BLOKY.
  3. ECLI NOCDOENHEBBI BHEHNE IPOBODA, C NOMOUIIO NylbTA DMY MOXHO BBISPATPBATOBY PEXIME INPHYNTIELHO BbIKIOUeyHNAI ONEPAUHIO YNPABJEHNAI BKIOUeHEM/BbIKIOUeHEM. IONOHHTIELHBIE CBEDEHNA CM. B PYKOBODCTBE NOMOHTAXY.
  4. CM.PYKOBODCTBO NMOHTAXY.

Icindekiler Sayfa

Montaj oncesi. 1

Boruyalitimproseduru

DAIKIN FXSQ15A2VEB - Boruyalitimproseduru - 1

DAIKIN FXSQ15A2VEB - Boruyalitimproseduru - 2

1 Boru yalitim malzemesi (sahada temin edilir)
2 Konik somun baglantisi
3 Baglanti yalitimi (uniteyle birlikte verllir)
4 Boru yalitim malzemesi (ana unite)
5 Ana unite
6 Kablo bagi (sahada ledarik edilir)
7 Gaz borulari icin ortam 1 szidirmazlik pedi (uniteyle birlakte verilir) Siv borulari icin ortam 2 szidirmazlik pedi (uniteyle birlakte verilir)
A Dikisler yukar gelir
B Tabana sabitleyin
C Boru yaltim malzemesi disindaki parcayi sikin.
D Üntenin tabanindan konik somun baglantisin nüerine kadar sarin.

DAIKIN FXSQ15A2VEB - Boruyalitimproseduru - 3

MCA: Min. devre Amp (A)

MFA: Maks. Sigorta Amp (A)

NOT

Ayrintili bilgi icin, teknik veri kitabindaki "Elektrik

DAIKIN FXSQ15A2VEB - Boruyalitimproseduru - 4

verileri'bolumenebakin.

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAIKIN

Model : FXSQ15A2VEB

Category : Air Conditioning