FERROLI Atlas D Eco Cond Unit - Boiler

Atlas D Eco Cond Unit - Boiler FERROLI - Free user manual and instructions

Find the device manual for free Atlas D Eco Cond Unit FERROLI in PDF.

📄 112 pages English EN Download 💬 AI Question
Notice FERROLI Atlas D Eco Cond Unit - page 34
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about Atlas D Eco Cond Unit FERROLI

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Boiler in PDF format for free! Find your manual Atlas D Eco Cond Unit - FERROLI and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Atlas D Eco Cond Unit by FERROLI.

USER MANUAL Atlas D Eco Cond Unit FERROLI

  • Read the warnings in this instruction booklet carefully since they provide important information on safe installation, use and maintenance.
  • This instruction booklet is an integral and essential part of the product and must be kept with care by the user for future reference.
  • If the unit is sold or transferred to another owner or if it is to be moved, always make sure the booklet stays with the boiler so that it can be consulted by the new owner and/or installer.
  • Installation and maintenance must be carried out by professionally qualified personnel, according to current regulations and the manufacturer's instructions.
  • Incorrect installation or inadequate maintenance can result in damage or injury. The manufacturer declines any liability for damage caused by errors in installation and use or by failure to follow the instructions provided.
  • Before carrying out any cleaning or maintenance operation, disconnect the unit from the power supply using the system switch and/or the special cut-off devices.
  • In case of a fault and/or poor operation, deactivate the unit and do not try to repair it or directly intervene. Contact professionally qualified personnel. Any repair/replacement of the products must only be carried out by qualified personnel using genuine parts. Failure to comply with the above can compromise the safety of the unit.

  • Periodic maintenance performed by qualified personnel is essential in order to ensure proper operation of the unit.

  • This unit must only be used for its intended purpose. Any other use is deemed improper and therefore hazardous.
  • After unpacking, check the good condition of the contents. The packing materials are potentially hazardous and must not be left within the reach of children.
  • The unit can be used by children aged at least 8 years and by persons with reduced physical, sensory or mental capabilities, or lacking experience or the necessary knowledge, only if under supervision or they have received instructions on its safe use and the related risks. Children must not play with the unit. Cleaning and maintenance intended to be done by the user can be carried out by children aged at least 8 years only if under supervision.
  • In case of doubt, do not use the unit. Contact the supplier.
  • The unit and its accessories must be appropriately disposed of in compliance with current regulations.
  • The images given in this manual are a simplified representation of the product. In this representation there may be slight and insignificant differences with respect to the product supplied.
This symbol indicates “CAUTION” and is placed next to all safety warnings. Strictly follow these instructions in order to avoid danger and damage to persons, animals and things
This symbols calls attention to a note or important notice.
This symbol, which is used on the product, packaging or documents, means that at the end of its useful life, this product must not be collected, recycled or disposed of together with domestic waste. Improper management of electric or electronic waste can lead to the leakage of hazardous substances contained in the product. For the purpose of preventing damage to health or the environment, users are kindly asked to separate this equipment from other types of waste and to ask for it to be dealt with by the municipal waste service or dealer under the conditions and according to the methods set down in national and international laws transposing the Directive 2012/19/EU. Separate waste collection and recycling of unused equipment helps to save natural resources and to guarantee that this waste is processed in a manner that is safe for health and the environment. For more information about how to collect electric and electronic equipment and appliances, please contact your local Council or Public Authority competent to issue the relevant permits.

FERROLI Atlas D Eco Cond Unit - 1

The CE marking certifies that the products meet the essential requirements of the relevant directives in force.

The declaration of conformity may be requested from the manufacturer.

COUNTRIES OF DESTINATION: IT ES NL PL GR

1. OPERATING INSTRUCTIONS

1.1 Introduction

Dear Customer,

Thank you for choosing a FERROLI boiler featuring advanced design, cutting-edge technology, high reliability and quality construction. Please read this manual carefully since it provides important information on safe installation, use and maintenance.

ATLAS DECO COND UNIT is a high-efficiency condensing heat generator for heating and domestic hot water production (optional), equipped with a blown oil burner, wet fume chamber and fume heat recuperator in ceramic material. The boiler shell consists of castiron elements, assembled with double cones and steel stays. The control system is with microprocessor and digital interface with advanced temperature control functions.

FERROLI Atlas D Eco Cond Unit - Introduction - 1

The boller is arranged for connection to an external hot water storage tank (optional). In this manual all the functions relevant to domestic hot water production are only active with the optional hot water tank connected as indicated in sec. 2.3

1.2 Control panel

FERROLI Atlas D Eco Cond Unit - Control panel - 1
Panel
fig.1 - Control panel

Panel key

1 = DHW temperature setting decrease button
2 = DHW temperature setting increase button
3 = Heating system temperature setting decrease button
4 = Heating system temperature setting increase button
5 = Display
6 = Summer / Winter mode selection button
7 = Economy / Comfort mode selection button
8 = Reset button
9 = Unit On / Off button
10 = "Sliding Temperature" menu button
11 = Set DHW temperature reached
12 = DHW symbol
13 = DHW mode
14 = DHW outlet temperature / setting
15 = Eco (Economy) or Comfort mode
16 = External sensor temperature (with optional external probe)
17 = Appears on connecting the external Probe or the Remote Timer Control (optionals)
18 = Room temperature (with optional Remote Timer Control)
19 = Burner On
20 = Antifreeze operation
21 = Heating system pressure
22 = Fault
23 = Heating delivery temperature/setting
24 = Heating symbol
25=Heatingmode
26 = Set heating delivery temperature reached
27 = Summer mode

Indication during operation

Heating

A heating demand (generated by the Room Thermostat or Remote Timer Control) is indicated by flashing of the hot air above the radiator (details 24 and 25 - fig. 1).

The heating graduation marks (detail 26 - fig. 1) light up as the heating sensor temperature reaches the set value.

FERROLI Atlas D Eco Cond Unit - Heating - 1
fig.2

DHW (Comfort)

A DHW demand (generated by drawing domestic hot water) is indicated by flashing of the hot water under the tap (details 12 and 13 - fig. 1). Make sure the Comfort function (detail 15 - fig. 1) is activated

The DHW graduation marks (detail 11 - fig. 1) light up as the DHW sensor temperature reaches the set value.

FERROLI Atlas D Eco Cond Unit - DHW (Comfort) - 1
fig. 3

Exclude hot water tank (economy)

Hot water tank temperature maintaining/heating can be excluded by the user. If excluded, domestic hot water will not be delivered.

When hot water tank heating is activated (default setting), the COMFORT symbol (detail 15 - fig. 1) is activated on the display, and when off, the ECO symbol (detail 15 - fig. 1) is activated on the display

The hot water tank can be deactivated by the user (ECO mode) by pressing the eco/comfortfig. 1 button (detail 7 -). To activate the COMFORT mode, press the eco/comfort button (detail 7 -) fig. 1again.

1.3 Lighting and turning off

Boiler not electrically powered

FERROLI Atlas D Eco Cond Unit - Lighting and turning off - 1
fig. 4 - Boiler not electrically powered

The antifreeze system does not work when the power and/or gas to the unit are turned off. To avoid damage caused by freezing during long idle periods in winter, it is advisable to drain all water from the boiler, DHW circuit and system; or drain just the DHW circuit and add a suitable antifreeze to the heating system, complying with that prescribed in sec. 2.3.

Boiler lighting

  • Open the fuel on-off valves.
  • Switch on the power to the unit.

FERROLI Atlas D Eco Cond Unit - Boiler lighting - 1
fig.5-Boiler lighting

For the next 120 seconds "FH" will be displayed in the upper part of the display, which identifies the heating system air venting cycle.
During the first 5 seconds the software version of the card will also be shown in the lower part of the display.
- When the message FH disappears, the boiler is ready to operate automatically whenever domestic hot water is drawn or in case of a room thermostat demand.

Turning the boiler off

Press the on/off button (detail 9 - fig. 1) for 1 second.

FERROLI Atlas D Eco Cond Unit - Turning the boiler off - 1
fig. 6 - Turning the boiler off

When the boiler is turned off, the PCB is still powered.

Domestic hot water and heating are disabled. The antifreeze system remains activated. To relight the boiler, press the on/off button (detail 9 fig. 1) again for 1 second.

FERROLI Atlas D Eco Cond Unit - Turning the boiler off - 2
fig. 7

The boiler will be immediately ready to operate whenever domestic hot water is drawn or in case of a room thermostat demand.

1.4 Adjustments

Summer/Winter Swithover

Press the summer/winter button (detail 6 - fig. 1) for 1 second.

FERROLI Atlas D Eco Cond Unit - Summer/Winter Swithover - 1
fig. 8

The display activates the Summer symbol (detail 27 - fig. 1): the boiler will only deliver domestic hot water. The antifreeze system remains activated.

To deactivate the Summer mode, press the summer/winter button (part. 6 - fig. 1) again for 1 second.

Heating temperature setting

Use the heating buttons (details 3 and 4 - fig. 1) to adjust the temperature from a min. of 30^ to a max. of 80^ .

In any case it is advisable not to operate the boiler below 45^

FERROLI Atlas D Eco Cond Unit - Heating temperature setting - 1
fig.9

DHW temperature adjustment

Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of 10^ to a max. of 65^ .

FERROLI Atlas D Eco Cond Unit - DHW temperature adjustment - 1
fig. 10

Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the temperature desired in the rooms. If the room thermostat is not installed the boiler will keep the heating system at its setpoint temperature.

Room temperature adjustment (with optional remote timer control)

Using the remote timer control, set the temperature desired in the rooms. The boiler unit will set the system water according to the required room temperature. For information on the remote timer control, please refer to its user's manual.

Sliding temperature

When the optional external probe is installed the control panel display (detail 5 - fig. 1) shows the actual outside temperature read by the probe. The boiler control system operates with "Sliding Temperature". In this mode, the temperature of the heating system is adjusted according the outside weather conditions, in order to ensure high comfort and energy saving throughout the year. In particular, as the outside temperature increases, the system delivery temperature is decreased according to a specific "compensation curve".

With Sliding Temperature adjustment, the temperature set with the heating buttons (details 3 and 4 - fig. 1) becomes the maximum system delivery temperature. It is advisable to set a maximum value to allow system adjustment throughout its useful operating range.

The boiler must be adjusted at the time of installation by qualified personnel. Possible adjustments can in any case be made by the user to improve comfort.

Compensation curve and curve offset

Press the mode button (detail 10 - fig. 1) once to display the actual compensation curve (fig. 11), which can be modified with the DHW buttons (details 1 and 2 - fig. 1).

Adjust the required curve from 1 to 10 according to the characteristic (fig. 13).

By setting the curve to 0, sliding temperature adjustment is disabled.

FERROLI Atlas D Eco Cond Unit - Compensation curve and curve offset - 1
fig. 11 - Compensation curve

Press the heating buttons (details 3 and 4 - fig. 1) to access parallel curve offset (fig. 14), modifiable with the DHW buttons (details 1 and 2 - fig. 1).

FERROLI Atlas D Eco Cond Unit - Compensation curve and curve offset - 2
fig. 12 - Curve parallel offset

Press the mode button (detail 10 - fig. 1) again to exit parallel curve adjustment mode. If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the room.

FERROLI Atlas D Eco Cond Unit - Compensation curve and curve offset - 3
fig. 13 - Compensation curves

FERROLI Atlas D Eco Cond Unit - Compensation curve and curve offset - 4

FERROLI Atlas D Eco Cond Unit - Compensation curve and curve offset - 5
fig. 14 - Example of compensation parallel curve offset

Adjustments from Remote Timer Control

FERROLI Atlas D Eco Cond Unit - Adjustments from Remote Timer Control - 1

If the Remote Timer Control (optional) is connected to the boiler, the above adjustments are managed according to that given in table 1. Also, the control panel display (detail 5 - fig. 1) shows the actual room temperature detected by the Remote Timer Control.

Table.1

Heating temperature settingAdjustment can be made from the Remote Timer Control menu and the boiler control panel.
DHW temperature adjustmentAdjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer/Winter SwithoverSummer mode has priority over a possible Remote Timer Control heating demand.
Eco/Comfort selectionOn disabling DHW from the Remote Timer Control menu, the boiler selects the Economy mode. In this condition, the button 7 - fig. 1 on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the boiler selects the Comfort mode. In this condition it is possible select one of the two modes with the button 7 - fig. 1 on the boiler panel.
Sliding TemperatureBoth the Remote Timer Control and the boiler card manage Sliding Temperature adjustment: of the two, the Sliding Temperature of the boiler card has priority.

Water system pressure adjustment

The filling pressure with system cold, read on the display, must be approx. 1.0 bar. If the system pressure falls to values below minimum, the boiler card will activate fault F37 (fig. 15).

FERROLI Atlas D Eco Cond Unit - Water system pressure adjustment - 1
fig. 15 - Low system pressure fault

FERROLI Atlas D Eco Cond Unit - Water system pressure adjustment - 2

Once the system pressure is restored, the boiler will activate the 120-second air venting cycle indicated on the display by FH.

2. INSTALLATION

2.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.

2.2 Place of installation

The boiler unit must be installed in a specific room with ventilation openings to the outside as prescribed by current regulations. If there are several burners or suction units that can work together in the same room, the ventilation openings must be sized for simultaneous operation of all the units. The place of installation must be free of flammable materials or objects, corrosive gases, powders or volatile substances that, conveyed by the burner fan, can obstruct the internal lines of the burner or the combustion head. The room must be dry and not exposed to rain, snow or frost.

FERROLI Atlas D Eco Cond Unit - Place of installation - 1

If the unit is enclosed in a cabinet or mounted alongside, a space must be provided for removing the casing and for normal maintenance operations.

2.3 Plumbing connections

Important

The heating capacity of the unit must be previously established by calculating the building's heat requirement according to the current regulations. The system must be provided with all the components for correct and regular operation. It is advisable to install shutoff valves between the boiler and heating system allowing the boiler to be isolated from the system if necessary.

FERROLI Atlas D Eco Cond Unit - Important - 1

The safety valve outlet must be connected to a funnel or collection pipe to prevent water spurting onto the floor in case of overpressure in the heating circuit. Otherwise, if the discharge valve cuts in and floods the room, the boiler manufacturer cannot be held liable.

Do not use the water system pipes to earth electrical appliances.

Before installation, flush all the pipes of the system thoroughly to remove any residuals or impurities that could affect proper operation of the unit.

Carry out the relevant connections according to the diagram in cap. 4 and the symbols given on the unit.

High efficiency circulating pump

Circulating pump adjustment with boiler connected to an external hot water storage tank

For proper operation of the boiler ATLAS D ECO COND UNIT with it connected to an external hot water storage tank, the speed selector (see fig. 16) must be set to position III.

FERROLI Atlas D Eco Cond Unit - High efficiency circulating pump - 1
fig. 16

Circulating pump adjustment without a connection to an external hot water storage tank

The factory setting is suitable for all installations; however a different operation strategy can be set, depending on the characteristics of the system.

FERROLI Atlas D Eco Cond Unit - High efficiency circulating pump - 2

FERROLI Atlas D Eco Cond Unit - High efficiency circulating pump - 3

  • Setting Dp-v Proportional head (fig. 17)

The circulating pump head will be automatically reduced with the decrease in flow rate required by the system. This setting is optimum for systems with radiators (2 pipes or single pipe) and/or thermostatic valves.

The strong points are the reduction in power consumption with the decrease in system demand and reduction of noise in radiators and/or thermostatic valves. The operating range is from min. (1) to max. (7).

  • Setting Fixed speed (fig. 18)

The circulating pump does not modulate its power. The operating principle is that of conventional 3-speed circulating pumps (with a reduction in power consumption compared to them). The operating range goes from speed 1 (I) to speed 3 (III).

High-efficiency circulating pump (model PARA)

Control buttons and signaling LEDs

FERROLI Atlas D Eco Cond Unit - High-efficiency circulating pump (model PARA) - 1
fig. 19

FERROLI Atlas D Eco Cond Unit - High-efficiency circulating pump (model PARA) - 2

FERROLI Atlas D Eco Cond Unit - High-efficiency circulating pump (model PARA) - 3

For a correct result of the "Thermal quantity balance" calculation (see section 11 THERMAL QUANTITY BALANCE (METERIN), the circulating pump must be set to "Constant speed" and to the position. To set this adjustment, press button "A" several times until the LEDs shown in the figure below light up.

FERROLI Atlas D Eco Cond Unit - High-efficiency circulating pump (model PARA) - 4

However, a different operating strategy can be set, depending on the characteristics of the system.

  • Setting A-v Proportional Head

The circulating pump head will be automatically reduced with the decrease in flow rate required by the system.

The strengths are reduced power consumption as the system demand decreases, and reduced noise. The operating range is from minimum to maximum.

  • Setting A-c Constant Head

The circulating pump head is constant as the flow rate required by the system varies.

  • Setting Fixed speed

The circulating pump does not modulate its power. The operating principle is that of conventional 3-speed circulating pumps (with a reduction in power consumption compared to them). The operating range is from speed 1 (to speed 3 ( ).

Water system characteristics

In the presence of water harder than 25^ Fr (1^ = 10ppm CaCO3), use suitably treated water in order to avoid possible scaling in the boiler. Treatment must not reduce the hardness to values below 15^ (Decree 236/88 for uses of water intended for human consumption). Treatment of the water used is indispensable in case of very large systems or with frequent introduction of replenishing water in the system.

If water softeners are installed at the boiler cold water inlet, make sure not to reduce the water hardness too much, as this could cause early deterioration of the magnesium anode in the hot water tank.

Antifreeze system, antifreeze fluids, additives and inhibitors

The boiler is equipped with an antifreeze system that turns on the boiler in heating mode when the system delivery water temperature falls under 6^ . The device will not come on if the electricity and/or gas supply to the unit are cut off. If it becomes necessary, it is permissible to use antifreeze fluid, additives and inhibitors only if the manufacturer of these fluids or additives guarantees they are suitable for this use and cause no damage to the heat exchanger or other components and/or materials of the boiler unit and system. It is prohibited to use generic antifreeze fluid, additives or inhibitors that are not expressly suited for use in heating systems and compatible with the materials of the boiler unit and system.

Connection to a storage tank for domestic hot water production

The unit's electronic board is arranged for managing an external storage tank for domestic hot water production. Make the plumbing connections according to the diagram fig. 21. Carry out: electrical connections as shown in the wiring diagram in cap. 4.5. A probe FERROL must be used.

Carry out the access procedure described below.

"Service Menu"

The card Service Menu is accessed by pressing the Reset button for 10 seconds.

Press the Heating buttons to select "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" Information Menu, "Hi" History Menu, and "rE" History Menu Reset. Select "tS" and press the Reset button.

The card has 20 transparent parameters also modifiable from Remote Control (Service Menu).

Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to modify the value of a parameter: the change will be automatically saved.

Change parameter P02 of the "Transparent Parameters Menu" to 6.

Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit to the card Service Menu.

FERROLI Atlas D Eco Cond Unit - Connection to a storage tank for domestic hot water production - 1
Fig. 21 - Diagram of connection to external hot water tank

Key

8 Domestic hot water outlet
9 Domestic cold water inlet
10 System delivery
11 System return
95 3-way valve - 2 wires with spring return (not provided)

2.4 Burner connection

The burner is equipped with flexible pipes and a filter for connection to the oil feed line. Run the flexible pipes out of the back and install the filter as indicated in fig. 22.

FERROLI Atlas D Eco Cond Unit - Burner connection - 1
fig.22-Fuel filter installation

The oil feed circuit must be made according to one of the following diagrams, without exceeding the pipe lengths (LMAX) given in the table.

FERROLI Atlas D Eco Cond Unit - Burner connection - 2
fig. 23 - Gravity feed

FERROLI Atlas D Eco Cond Unit - Burner connection - 3
fig.24 - Suction feed

FERROLI Atlas D Eco Cond Unit - Burner connection - 4
fig.25 - Siphon feed

FERROLI Atlas D Eco Cond Unit - Burner connection - 5
fig.26-Ring feed

2.5 Electrical connections

Connection to the electrical grid

The unit's electrical safety is only guaranteed when correctly connected to an efficient earthing system executed according to current safety standards. Have the efficiency and suitability of the earthing system checked by professionally qualified personnel. The manufacturer is not responsible for any damage caused by failure to earth the system. Also make sure that the electrical system is adequate for the maximum power absorbed by the unit, as specified on the boiler data-plate.

The boiler is prewired and provided with a Y-cable and plug for connection to the electricity line. The connections to the grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum opening of at least 3 mm, interposing fuses of max. 3A between the boiler and the line. It is important to respect the polarities (LINE: brown wire / NEUTRAL: blue wire / EARTH: yellow-green wire) in making connections to the electrical line. During installation or when changing the power cable, the earth wire must be left 2 cm longer than the others.

The user must never change the unit's power cable. If the cable gets damaged, switch off the unit and have it changed solely by professionally qualified personnel. If changing the electric power cable, use solely "HAR H05 VV-F" 3x0.75 mm2 cable with a maximum outside diameter of 8 mm.

Room thermostat (optional)

IMPORTANT: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE CONTACTS. CONNECTING 230 V TO THE ROOM THERMOSTAT TERMINALS WILL PERMANENTLY DAMAGE THE ELECTRONIC BOARD.

When connecting time controls or a timer, do not take the power supply for these devices from their breaking contacts Their power supply must be by means of direct connection from the mains or with batteries, depending on the kind of device.

Accessing the electrical terminal block

Undo the two screws "A" located on the top part of the control panel and remove the cover.

FERROLI Atlas D Eco Cond Unit - Accessing the electrical terminal block - 1
fig. 27 - Accessing the terminal block

2.6 Connection to the flue

The unit must be connected to a flue designed and built in compliance with the current regulations. The pipe between the boiler and flue must be made from material suitable for the purpose, i.e. heat and corrosion resistant. Ensure the seal at the joints.

2.7 Condensate drain connection

The unit's condensate drain must be connected to a suitable disposal system. Comply with the specific local and national regulations on discharging condensate water into the waste water disposal system. For boilers not using exclusively low-sulphur gas oil (S content < 50 ppm) make sure to provide for a suitable condensate neutralisation device. Connect the condensate drain pipe located at the back of the boiler (ref. A - fig. 28) to the neutralisation device connected to the waste water system. The condensate discharge pipes must be acidproof and installed sloping at least 3^ towards the drain, without any constrictions and obstructions.

IMPORTANT. Fill the trap with water before starting the unit.

ATTENTION: The unit must never be operated with the trap empty!

Periodically check the water in the trap.

FERROLI Atlas D Eco Cond Unit - Condensate drain connection - 1
fig.28-Condensate drain

2.8 Conversion of boiler with burner to sealed chamber (only version ATLAS DECO 34 COND UNIT)

ATTENTION: The connection with separate pipes indicated here can be done only and exclusively with the sealed chamber kit.

A kit is available on request for converting the boiler with burner to sealed chamber. This conversion allows the air necessary for combustion to be sucked directly from the outside.

For installation, refer to the instructions contained in the kit.

FERROLI Atlas D Eco Cond Unit - Conversion of boiler with burner to sealed chamber (only version ATLAS DECO 34 COND UNIT) - 1
fig. 29 - Sealed chamber conversion kit

After installation, the unit becomes a "C type" with sealed chamber and forced draught. The air inlet and fume outlet must be connected to one of the extraction/suction systems specified below. The unit is approved to operate with all the Cxy flue configurations given in these instructions. Some configurations may be expressly limited or not permitted by law, standards or local regulations. Before proceeding with installation, check and carefully observe the above instructions. Also, comply with the provisions on the positioning of wall and/or roof terminals and the minimum distances from windows, walls, ventilation openings, etc.

FERROLI Atlas D Eco Cond Unit - Conversion of boiler with burner to sealed chamber (only version ATLAS DECO 34 COND UNIT) - 2

Only use ducts in stainless steel, suitable for use with oil-fired condensing heat generators.

Connection with separate pipes

FERROLI Atlas D Eco Cond Unit - Connection with separate pipes - 1
fig. 30 - Examples of connection with separate pipes (Air / Fumes)

Before installation, make sure the maximum permissible length has not been exceeded, by means of a simple calculation:

  1. Completely establish the layout of the system of split flues, including accessories and outlet terminals.
  2. Consult the table 3 and identify the losses in m eq (equivalent metres) of every component, according to the installation position.
  3. Check that the sum total of losses is less than or equal to the maximum permissible length in table 2.

Table. 2 - Separate ducts

Separate ducts
Model ATLAS D ECO 34 COND UNIT
Max. permissible length25 m_eq

Table. 3 - Accessories

Losses in \( m_{eq} \)
Air adjustmentFume exhaust
Vertical Horizontal
Ø 80 PIPEBEND0.5 m M/F 0.5
1 m M/F 1.0
2 m M/F 2.0
45° F/F 1.2
45° M/F 1.2
90° F/F 2.0
90° M/F 1.5
90° M/F + Test point 1.5
PIPE SECTIONwith test point 0.2
for condensate drain-
TEEfor condensate drain-
TERMINALair, wall 2.0
fumes, wall with antiwind-
FLUESplit air/fumes 80/80-
Fume outlet only Ø80-
Ø 100REDUCTIONfrom Ø80 to Ø1000.0
from Ø100 to Ø801.5
PIPE1 m M/F 0.4 0.40.8
BEND45° M/F 0.6 1.0
90° M/F 0.8 1.3
TERMINALair, wall 1.5-
fumes, wall with antiwind-3.0

3. SERVICE AND MAINTENANCE

All adjustment, conversion, commissioning and maintenance operations described below must only be carried out by Qualified Personnel (meeting the professional technical requirements of current regulations) such as the personnel of the Local After-Sales Technical Service.

FERROLI declines any liability for damage and/or injury caused by unqualified and unauthorized persons tampering with the unit.

3.1 Adjustments

TEST mode activation

Press the heating buttons (details 3 and 4 - fig. 1) together for 5 seconds to activate the

TEST mode. The boiler switches on irrespective of the system or DHW request

The heating symbol (detail 24 - fig. 1) and DHW symbol (detail 12 - fig. 1) flash on the display.

FERROLI Atlas D Eco Cond Unit - TEST mode activation - 1
fig. 31 - TEST mode

To deactivate the Test mode, repeat the activation sequence.

The TEST mode is automatically disabled in any case after 15 minutes.

Burner adjustment

The burner is factory-set. The burner can be set to a different output by acting on the pump pressure, nozzle, head adjustment, and air adjustment as per the following paragraphs. In any case, the new adjusted output must fall within the boiler's nominal operating range. After making any adjustments, using a combustion analyser check that the CO_2 content in the fumes is between 11% and 12% .

Nozzle flow rate table for oil

table 4 gives the oil flow rates (in kg/h) according to the change in pump pressure and nozzles.

N.B. - The values given below are only approximate, since nozzle flow rates can vary by ± 5% . Also, with burners having a preheater, the fuel flow rate decreases by about 10% .

Table.4

Pump pressure (bar)
NOZZLE GPH.891011121314
0.401.321.401.471.541.611.681.75
15.6616.6017.4318.2619.0919.9220.75
0.501.571.651.731.811.891.972.05
18.6219.5720.5121.5022.4223.3624.31
0.601.932.012.232.322.422.522.64
22.8923.8326.4427.5128.7029.8831.31
Pump pressure (bar)
0.652.122.252.402.632.742.802.91
25.1426.6828.4631.1932.4933.2134.51
0.752.502.652.802.953.073.203.33
29.6531.4333.2134.9936.4137.9539.49
0.852.923.103.273.453.603.753.90
34.6336.7638.7840.9242.6944.4746.25
1.003.303.503.673.854.024.20
39.1341.5143.5245.6647.6748.7251.95
Flow rate at nozzle outlet in kg/h

Pump pressure adjustment

The pump is factory-set to 12 bar. Use an oil bath gauge to check the pressure. The pressure can be adjusted between 11 and 14 bar.

FERROLI Atlas D Eco Cond Unit - Pump pressure adjustment - 1
fig. 32-Pump ITALPUMP

FERROLI Atlas D Eco Cond Unit - Pump pressure adjustment - 2
fig. 33-Pump DANFOSS

  1. Suction 01/4"
  2. Return 01/4
  3. Oil delivery 01/8"
  4. Pressure adjustment
  5. Pressure gauge connection 1 / 8^
  6. Vacuum gauge connection 1 / 8^

Combustion head adjustment

The head is adjusted by means of the screw 1, according to the indications of the pointer 2.

FERROLI Atlas D Eco Cond Unit - Combustion head adjustment - 1
fig. 34

Air damper adjustment

After loosening the screw 3, operating the screw 1, the combustion air is adjusted according to the indications of the pointer 2. After adjustment, lock the screw 3.

FERROLI Atlas D Eco Cond Unit - Air damper adjustment - 1
fig. 35

Position of electrodes - baffle

After fitting the nozzle, check correct positioning of the electrodes and baffle, according to the dimensions given below. It is advisable to check the dimensions after each operation on the head.

FERROLI Atlas D Eco Cond Unit - Position of electrodes - baffle - 1
fig. 36- Position of electrodes - baffle

3.2 Commissioning

Checks to be made at first lighting, and after all maintenance operations involving disconnection from the systems or an operation on safety devices or parts of the boiler:

Before lighting the boiler

  • Open any on-off valves between the boiler and the systems.
  • Check the tightness of the fuel system.
  • Check the pre-filling of the expansion tank
  • Fill the water system and make sure that all air contained in the boiler and the system has been vented by opening the air vent valve on the boiler and any vent valves on the system.
  • Make sure there are no water leaks in the system, hot water circuits, connections or boiler.
  • Make sure the electrical system is properly connected and the earth system works properly.
  • Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler.
  • Fit the pressure gauge and the vacuum gauge on the pump (remove after starting) of the burner.
    open the gate valves along the diesel pipe

FERROLI Atlas D Eco Cond Unit - Before lighting the boiler - 1
Start-up
fig. 37 - Starting

A

When the thermostalic line closes, the burner motor starts turning together with the pump: all the oil sucked is sent to the return. The burner blower and the ignition transformer are also working, therefore the following stages are carried out:

  • firebox prevention.
  • prewash of a part of the oil circuit.
    preignition, with discharge between electrode tips.

B

At the end of prewash, the unit opens the electromagnetic valve: the oil reaches the nozzle, where it is finely sprayed.

Its contact with the discharge between the electrode tips creates the flame.

The safety time begins simultaneously.

Unit cycle

FERROLI Atlas D Eco Cond Unit - B - 1
fig. 38 - Unit cycle

R-SB-W Thermostats/Pressure switches

OH Oil pre-heater
OW Operation enabling contact
M Burner motor
Z Ignition transformer
BV Electromagnetic valve
FR Photoresistance
A' Starting with pre-h
A Starting without pre-heater
B Flame present
C Normal operation
D Adjustment stop (TA-TC)
t1 Pre-ventilation time
TSA Safety time
t3 Pre-ignition time
t3n Post-ignition time
tw Pre-heating time

Output signals from the unit

Necessary input signals

Checks during operation

  • Ignite the appliance as described in sec. 1.3.
  • Check that the fuel circuit and water systems are airtight.
  • Check the efficiency of the flue and air-fume ducts while the boiler is working.
  • Check that the water is circulating properly between the boiler and the systems.
  • Check the proper ignition of the boiler by performing various tests, turning it on and off with the room thermostat or remote control.
  • Check that the burner door and fume chamber are tight.
  • Check that the burner works properly
  • Analyse the combustion (with the boiler unit stable) and check that the content of CO_x in the fumes is between 11% and 12% .
  • Check the parameters are programmed correctly and perform any required customization (compensation curve, power, temperatures, etc.).

3.3 Maintenance

Periodical check

To ensure correct operation of the unit over time, have qualified personnel carry out a yearly check, providing for the following:

The control and safety devices must function correctly.
The fume exhaust circuit must be perfectly efficient.
- Check there are no obstructions or dents in the fuel supply and return pipes.
- Clean the filter of the fuel suction line.
Measure the correct fuel consumption
- Clean the combustion head in the fuel outlet zone, on the swirl disc.
- Leave the burner running at full rate for approximately ten minutes, then analyse the combustion, checking:

  • All the elements specified in this manual are set correctly
  • Temperatures of the fumes at the flue
  • CO2 percentage content

The air-fume end piece and ducts must be free of obstructions and leaks
- The burner and exchanger must be clean and free of deposits. For possible cleaning do not use chemical products or wire brushes.

The gas and water systems must be airtight.
- The water pressure in the cold water system must be approx. 1 bar; otherwise, bring it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
- Check the magnesium anode and replace it if necessary.

FERROLI Atlas D Eco Cond Unit - Periodical check - 1

The boiler casing, control panel and aesthetic parts can be cleaned with a soft and damp cloth, if necessary soaked in soapy water. Do not use any abrasive detergents and solvents.

Accessing the electrode and nozzle

  • Disconnect the transformer electrode cables and remove the photoresistance 1, and the union 2 connecting the oil pipe to line 3 of the nozzle. Loosen the screws 4 and pull out the nozzle-baffle-electrode flange assembly.

FERROLI Atlas D Eco Cond Unit - Accessing the electrode and nozzle - 1
fig. 39

  • Undo the screw 5 to remove the baffle and screw 6 to remove the electrodes. Proper cleaning of the nozzle is obtained by removing the filter and cleaning the slots and spraying hole with petrol, rinsing it with fuel oil. When reassembling everything, pay attention to the correct positioning of the electrodes-baffle.

FERROLI Atlas D Eco Cond Unit - Accessing the electrode and nozzle - 2
fig. 40

Boiler cleaning

  1. Disconnect the power supply to the boiler.
  2. Remove the burner as described above.
  3. Remove the panels "E" and "F" undoing the respective nuts
  4. Clean the inside of the boiler and the entire path of exhaust fumes, using a tube brush or compressed air.
  5. Close the panels.

FERROLI Atlas D Eco Cond Unit - Boiler cleaning - 1
fig.41

Cleaning the fume recuperator

To clean the fume recuperator:

  • Remove the cover B.
  • Remove the fume recuperator closing covers C
  • Carefully clean the inside of the recuperator using an aspirator.
  • If particularly dirty, a suitable device for spraying water inside can be used. In this case, make sure large amounts of water do not come into contact with the cast iron elements in the smoke chamber. Run the water through the condensate drain D after disconnecting the trap.

FERROLI Atlas D Eco Cond Unit - Cleaning the fume recuperator - 1
fig. 42 - Cleaning the recuperator

Positioning of combs

After cleaning the recovery unit make sure the combs are positioned correctly, as shown in fig. 43. Tighten the nuts on the compressor disk "A" respecting the torque setting of 0.6Nm . If a torque wrench is unavailable, check that there is a fume passage of 1mm between the coils.

FERROLI Atlas D Eco Cond Unit - Positioning of combs - 1

FERROLI Atlas D Eco Cond Unit - Positioning of combs - 2
fig. 43 - Positioning of combs

3.4 Troubleshooting

Diagnostics

The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault code.

There are faults the cause permanent shutdowns (marked with the letter "A"): to restore operation, just press the RESET button (detail 8 - fig. 1) for 1 second or use the RESET on the remote timer control (optional) if installed; if the boiler does not restart, it is necessary to eliminate the fault indicated in the operation LEDs.

Other faults cause temporary shutdowns (marked with the letter "F") which are automatically reset as soon as the value returns within the boiler's normal working range.

ATTENTION

From software version 23, an additional feature has been introduced to facilitate burner calibration, i.e. flame flashing on the display to indicate that the burner is on but with indication of non-optimal flame.

For the various software versions, the meanings of the symbols shown on the display can be found in the table 1.

Table. 5- Flame symbol indications

Indication on the display and meaning
Software VersionFlame Off Flame On SteadyFlame Flashing
≤22Burner off Burner on-
≥23Burner offBurner on and indication of stable flameBurner on with indication of NOT optimal flame

Table. 6 - List of faults

Fault codeFault Possible causeuse Cure
A01 Burner blockPump blocked Replace
Faulty electric motor Replace
Faulty oil valve Replace
No fuel in tank, or water on bot- tomRefill with fuel or suck the water
Oil line feed valves closed Open
Dirty filters (line-pump-nozzle) Clean
Pump unprimed Prime and find the cause of unpriming
Ignition electrodes not properly adjusted, or dirtyAdjust or clean them
Nozzle clogged, dirty or deformedReplace
Unsuitable head and shutter adjustmentsAdjust
Faulty electrodes or earthed Replace
Faulty ignition transformer Replace
Faulty electrode wires or earthed Replace
Electrode wires deformed by high temperatureReplace and protect
Faulty valve or transformer elec- trical connectionsCheck
Broken pump-motor joint Replace
Pump inlet connected to return pipeCorrect the connection
Faulty photoresistanceReplace
Dirty photoresistanceClean the photoresistance
A02Flame present signal with burner offPhotoresistance short circuitReplace the photoresist- ance
Extraneous light strikes the pho- toresistanceEliminate the light source
A03Overtemperature protection activa- tionHeating sensor damagedCheck the correct position- ing and operation of the heating sensor
No water circulation in the sys- temCheck the circulating pump (See table 7)
Air in the systemVent the system
A04Card parameter faultWrong card parameter settingCheck the card parameter and modify it if necessary
F07Preheater fault (the contact does not close in 120 seconds)Preheater faultCheck the preheater
Wiring disconnected Check the wiring
F09Card parameter faultWrong card parameter settingCheck the card parameter and modify it if necessary
F10Delivery sensor 1 faultSensor damagedCheck the wiring or replace the sensor
Wiring shorted
Wiring disconnected
Fault codeFault Possible causeUse Cure
F11DHW sensor faultSensor damagedCheck the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F12Card parameter faultWrong card parameter settingCheck the card parameter and modify it if necessary
F14Delivery sensor 2 faultSensor damagedCheck the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F16Card parameter faultWrong card parameter settingCheck the card parameter and modify it if necessary
F34Supply voltage under 170V.Electric mains troubleCheck the electrical system
F35Faulty mains frequencyElectric mains troubleCheck the electrical system
F37Incorrect system water pressurePressure too lowFill the system
Sensor damagedCheck the sensor
F39External probe faultProbe damaged or wiring shortedCheck the wiring or replace the sensor
Probe disconnected after activat-ing the sliding temperatureReconnect the external sen-sor or disable the sliding temperature
F40Incorrect system water pressurePressure too highCheck the system
Check the safety valve
Check the expansion tank
A41Sensor position-ingDelivery sensor not inserted in boiler shellCheck the correct position-ing and operation of the heating sensor
F42Heating sensor faultSensor damagedReplace the sensor
F47System water pressure sensor faultWiring disconnectedCheck the wiring

Circulating pump diagnostics

Some faults linked to the circulating pump are signalled by the LED located around the speed selector (fig. 44 - fig. 45).

FERROLI Atlas D Eco Cond Unit - Circulating pump diagnostics - 1
fig. 44

Table. 7 - Circulating pump LED indications

4 1 7 6Off Circulating pump on STANDBY
Green ON Circulating pump Working
Green Flashing Air venting cycle
Green/Red alternating Circulating pump blocked due to external causes: - Overvoltage (>270V) - Insufficient voltage (<160V) - Motor overload
Red Flashing Circulating pump blocked due to internal causes: - Motor blocked - Damaged electronics

Circulating pump diagnostics (model PARA)

Some faults linked to the circulating pump are signaled by the LED (fig. 45).

FERROLI Atlas D Eco Cond Unit - Circulating pump diagnostics (model PARA) - 1
fig. 45

LED Fault Cause Cure
On with red lightFault Blacked rotorActivate manual restart or contact Customer Service
Contact/winding Faulty winding
Flashing with red lightUnder/overvoltage Supply side voltage too low/highCheck the mains voltage and conditions of use. Request Customer Service
Excessive module temperatureInside of module too hot
Short circuit Motor current too high
Flashing with red/green lightTurbine operationThe hydraulic system of pumps is fed but the pump does not have mains voltageCheck the mains voltage, the water flow/pressure as well as the environmental conditions
Dry running Air in pump
OverloadThe motor turns with difficulty. Pump operation not in accordance with specifications (e.g. high module temperature). The speed is lower than in normal operation.

4. TECHNICAL DATA AND CHARACTERISTICS

4.1 Main components, dimensions and connections

FERROLI Atlas D Eco Cond Unit - TECHNICAL DATA AND CHARACTERISTICS - 1
fig.46-Frontview

FERROLI Atlas D Eco Cond Unit - TECHNICAL DATA AND CHARACTERISTICS - 2
fig. 47- Side view

L
ATLAS D ECO 34 COND UNIT930
ATLAS D ECO 45 COND UNIT1030

FERROLI Atlas D Eco Cond Unit - TECHNICAL DATA AND CHARACTERISTICS - 3
fig.48 - Rear view

a4 Flue 0100

10 System delivery - 0 3/4"

11 System return - 0 3/4

14 Heating safety valve

32 Heating circulating pump

36 Automatic air vent

56 Expansion tank

193 Trap

246 Pressure transducer

275 Drain - 0 1/2

278 Double sensor (Safety + heating)

295 Burner

338 Fumes recuperator

FERROLI Atlas D Eco Cond Unit - TECHNICAL DATA AND CHARACTERISTICS - 4
4.2 Water circuit
fig.49-Water circuit

4.3 Diagrams

Circulating pumps Head/Pressure loss
- Circulating pump with "fixed speed" setting.

FERROLI Atlas D Eco Cond Unit - Diagrams - 1

FERROLI Atlas D Eco Cond Unit - Diagrams - 2
H [m H2O]

A Boiler pressure losses
1-2-3 Circulating pump speed
- Circulating pump with "proportional head" setting.

FERROLI Atlas D Eco Cond Unit - Diagrams - 3

FERROLI Atlas D Eco Cond Unit - Diagrams - 4
H [m H2O]
A Boiler pressure losses

4.4 Technical data table

DataUnitATLAS DECO 34 COND UNITATLAS DECO 45 COND UNIT
Number of elements no. 3 4
Max. heating capacity kW 33.0 43.5 (Q)
Min. heating capacity kW 16.3 30.9 (Q)
Max. heat output in heating (80/60)kW3242(P)
Min. heat output in heating (80/60)kW1630(P)
Max. heat output in heating (50/30) kW 33.8 44.5 (P)
Min. heat output in heating (50/30)kW17.031.7(P)
Efficiency Pmax (80-60°C)%97.2 96.6
Efficiency Pmin (80-60°C)%97.8 97.3
Efficiency Pmax (50-30°C)%102.6102.3
Efficiency Pmin (50-30°C)%103.7102.8
Efficiency 30%%103.5102.8
Max. working pressure in heatingbar3 (PMS)
Min. working pressure in heatingbar0.80.8
Max. heating temperature°C100100(tmax)
Heating water contentliters2126
Heating expansion vessel capacityliters1010
Heating expansion vessel precharge pressurebar1
Protection ratingIPXOD XOD
Power supply voltageV/Hz230/50230/50
Electrical power input W 224 228
Empty weightkg177216
Combustion chamber lengthmm350450
Combustion chamber diametermm300300
Pressure loss on fume sidembar0.12 0.18

ErP product fiche

MODEL:ATLASDECO34CONDUNIT-(0JHW3YWA) MODEL:ATLASDECO45CONDUNIT-(0JHW4YWA)

Trademark: FERROLI
Condensing boiler: YES
Low-temperature boiler (**) : YES
B1 Boiler: NO
Combination heater: NO
Cogeneration space heater: NO0JHW3YWA - 0JHW4YWA
ItemSymbolUnitValueValue
Seasonal space heating energy efficiency class (from A+++ to D)AA
Rated heat outputPnkW3242
Seasonal space heating energy efficiencyηs%9190
Useful heat out put
Useful heat output at rated heat output and high-temperature regime (*)P4kW32,142,0
Useful heat output at 30% of rated heat output and low-temperature regime (**)P1kW9,612,6
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*)η4%91,390,7
Useful efficiency at 30% of rated heat output and low-temperature regime (**)η1%97,296,5
Auxiliary electricity consumption
At full loadelmaxkW0,2000,230
At part loadelminkW0,1050,118
In standby modePSBkW0,0030,003
Other items
Standby heat lossPstbykW0,1050,120
Ignition burner power consumptionPignkW0,0000,000
Annual energy consumptionQHEGJ102133
Sound power levelLWAdB6263
Emissions of nitrogen oxidesNOxmg/kWh9189

(^) High-temperature regime means 60^ return temperature at heater inlet and 80^ feed temperature at heater outlet.
(^
*) Low temperature means for condensing boilers 30^ for low-temperature boilers 37^ and for other heaters 50^ return temperature [at heater inlet].

4.5 Wiring diagram

FERROLI Atlas D Eco Cond Unit - Wiring diagram - 1
fig. 52 - Wiring diagram

32 Heating circulating pump
42 DHW temperature probe (optional)
72 Room thermostat (optional)
95 Diverter valve (optional)
- Powered (230 Vac) = Heating position
Not powered = DHW position
138 External probe (optional)
139 Remote Timer Control (optional)
246 Pressure transducer
278 Double sensor (Safety + Heating)
TR Ignition transformer
PR Preheater
FR Photoresistance
MB Burner motor
VE Electromagnetic valve

FERROLI Atlas D Eco Cond Unit - Wiring diagram - 2

FERROLI Atlas D Eco Cond Unit - Wiring diagram - 3
fig.28-Evacuation condensation

Tableau 7 - Indications led circulator

1.2 Bedleningspaneel

Paneel<

FERROLI Atlas D Eco Cond Unit - Bedleningspaneel - 1
fig.1 - Controlepaneel

Legenda paneel

Sanitair water (Comfort)

Uitschakeling boiler (economy)

Egapiepn mroiaep (economy)

O xipntnc mtopei va diakoei tn thepuavan/diatnpn on nts eepokpaaic tou mioiep. Tnv tpiwn autn dev utapxeyi npaywyn cetou vepou xpns.

Oav n 6epaovon Tou mIoep elvai evpyn (Tpoetnioyn), oTIV oOvyn elvai evpyo to oUBOLO COMFORT (AeTTIOU. 15 - EK. 1), eVvOtavai aTeVEpyoToInJeuN, oTIV oOvyn evpyoToeiTA to OuBPO ECO (AETTI. 15 - EK. 1)

To tiolepe npoei ve atteevytoinoei to xpnnt (eitoupyia ECO) natovac to koujti eco/comfort (eTT. 7 -Eik. 1). Ia nve evytoinon TcI eantoupyiac COMFORT TATOTET EK VOU TO KOUJIeco/comfort (eTT. 7 -Eik. 1).

1.3 Evepytooinn kalteevpoytoinon

AeBntasXwpiis nEkrptiKt troofooio

FERROLI Atlas D Eco Cond Unit - Evepytooinn kalteevpoytoinon - 1

FERROLI Atlas D Eco Cond Unit - Evepytooinn kalteevpoytoinon - 2
EIK.4-AeBntaXwipnnaektpknTpoopooia

AiaKoTTovTac TnV TpoOoOia nAekTPIKOU peuatoC n/Kai aepiou Tns OuaKEuNC,TO ouoTma TPOoTAoIAC aTo TO PAYeTO DEV LEIToupyei. Ia va aTPOeUxOouv BALAEc Tous OpeiIoAVtai OTOV PAETO e Eeyalec TEPIOOUs biakOtnc xPnOg To xeiuWva, Ouviotatai n EKKevwOn oAou Tou Vepou aTo TO AEBnta, too Tou Vepou oIKiAKNc xPnOng 000 KAI TOU VEPou TNS EYkATAOtaOns. DIApOpETiKa, Ouviotatai n EKKEVWOn MVO Tou Vepou oIKiAKNc XPnOng Kai n TPOoTHKn EIDIKOU AVTIuKTIOU OTNV EYkATAOtaOn Thepavonc OUMFWVA ME TIG ODNyIEc OTN SEZ.2.3.

EvpyoToInOnn Aebnta

AvolTe Tg BaBldes biakOnns Taopxns KaouJou.
SUVDEOTIoukeun OTNVnAekpiKnpoobogia.

FERROLI Atlas D Eco Cond Unit - EvpyoToInOnn Aebnta - 1

FERROLI Atlas D Eco Cond Unit - EvpyoToInOnn Aebnta - 2
EIK.5-EepyoToiOnnAeBnta

Sigma ETEUVEA 120 DEUTEPOLETTA, OTO TAVW MEPOCS aOVOV cEAPAVCEaI eEvdeiE FH TOU UTODEIKVUEI TNY KKTAEON TOU KUKLAOU EEAePwON TC Nc EYKAATAOANC 8epauvAnS.
Sta 5 Pwota deutepoAeTTA, eupavicTai EIncS OTo KAtu Tnua Tns OboVnc n Ekoon loyioikou nTn NkAeTas.
Otaatapnai evaepavicetai nEvbeiH F, oEbetaac evai Etouc yiautoaetaeupyia kabe pao TnXPnoiotoeiTceto Vepo iokianxpnans divetaievtol an toeepoataxwpu.

ATEVEpyOToina

PntnoTe To Koupti on/off (AETT. 9-EIK.1) yia 1 EutepeoAETTO

FERROLI Atlas D Eco Cond Unit - ATEVEpyOToina - 1
EIK.6-AntevepyoTOnn Aebnta

Otav aTepepyoToiOnBei o AebnTac, n naektpik npopooia Tns naektpovikns taaketac ouvexicai.

ATVEpyoTIOeIa n aeioupvia vepou oikiaKs xipnks kai bepuvans. Napapeve I Epeytoiuevo to ouatma npoataiaac ato tv naet.

Tia va evepytoietae 5aVa to aeBnTa, TATnate kai taI To Koupi on/off (AETTT.9 EIK.1) ia 1 eutepeoAeTo.

FERROLI Atlas D Eco Cond Unit - ATEVEpyOToina - 2
EK.7

O Aéβηtrac éivai eioiouc yia ayean aeitoupyia kαθe φρa triu xρnoiμtonoiitai ζeotovp oikänkx pniangn idivatnEvtoan to Bepoostatn xwpou.

1.4 Pubuigeic

Emoyn 0epivns/xeiueepivns aeitoupyias

PnTnote To KOUPTI eepivic/xeiuepivics aeitoupyias (AETT.6-EK.1) yia 1 EeutepeLTTo.

FERROLI Atlas D Eco Cond Unit - Emoyn 0epivns/xeiueepivns aeitoupyias - 1
EIK.8

Awaioyko maovotepiko uoos p-v

Teaepo maovopetpkó uos p-c

Sigma

EvEeig Etnyuevns xaoaikmpoianKKaumuans 1 ,2 ,3

I vO S TOU pOToU pOToHnS

SuvouaTikcEvEeieuAUXwGLELDKATAIaENoupyiaEeaepoongtou Kukaoopopyn, TxepokivnETTROVEKKIVNpKai ToKaEoiWQAoumIO

Eevnnte to koumtl mptelte va pubaetote touk dappoocu ouvuaoupou poun

Eav to natoe via 3 deutepoAetia, evpytoioi ta n Aetoupiy
Eav to taoe fo 5 eepoAETTA, npayatotooiE xepoknTt eravekkyn
EAV TO TIOIHOETE YO 8 EUTEPOAEETRA, KAEISWVEIgKAEIDWVEI TO KOUPTI

Tia ootao tnteaejou tou uoloyiouu Ioouyu 0epukns pnootnac ( ) evotna 1I OZYIO OEPIMKHE NOSOTHTA2 (KATAOXPIH), o kukloopnptnc Tp va exei puoiote ot nteitoupyia Etaepoc apioos opoov Kai otn Bcn . Tia va ekeetaeate autyntu pueoiian, tnatotie PAAe, opeoc to koupti Aexpi v avayouv oi auviic LED TIO paivovtai OTnv Tnapakatw Eikova.

Xapaktnpiotka tou vepou tns eykatataoans

Eav n okknptnta Tou vepou tnc ykataotaanc utepbaivei touc 25° Fr (1°F = 10ppm CaCO3), uviotatai n xhon kataanae tceepyaevou vepou wote aantoepueyetai o tiavoc oxnatuaoc atawv toa eBnta. H tteepyaee a th penei va meuvei tn okknpnta oe tiec mikpotepe cto 15°F (π,Δ. 236/88 ia xphoe ievou piocs Katavaow an to tov dovpumoo. Se kae tpepiTuwn, n tteepyaia Tou xpanoiauoivevou evov el attapaintn ekyataaec ieyalanc ektaanc n e ouxve avatianpwaeis Tou vepou tnc ykataataanc.

O tivakac diathe 20 napapetpouv Tou ptoopoov va TpoTOnToHouv kai ato to nExeiptipio (Mevou epeBic).

TATWYAC ta KOUMTI BepaVAnC, MTPOEte va METAKINthe Tn IAta TAPaTePua Ue auoua nΦthoua oepia. Vp TaTOPTOInoAe Tm NIm ia TAPaETpu, TIPeTeVa TATHOte ta KOUMTI vepou iKIAKNS XphonC: nTOPTOInoAToTHKeUeTaAutaOpA.

AAaTe Tny TnapaETPO 02 TOU Mevou Tapaepwv 6

Tia va EITiTpEeTe OTo Mevou eepBic, TATnATE To KOUmTI EITavaopopa. Ia efo 0to MeVou eepBic TOU nIvaka, TpETeVA TATnOe To KOUmTI EITavaopopa. Yia 10 DEUTePOAETTA.

8

9

A

EIK.20

Otoo, mopeite va putheta e diapopetikto tpo taioupyiac avaoa ta xapaktipitka tsykatataans.

-PuOuian p-v aVauoyikou mavouetpiokou 0ouc

To yapovetpiok uosoc tou kukloopnnt tha eiwthetaautopata otav eiwtheta nnapoxnou atanatei ato tv evkataotaon.

Ta TIAEVOETJMAI EAVI N JELIOW TNC N KKTPIKNG KATAVALUANG OTAV MEIWEI N GNTN TNS EYKAATAOANs KA I EIWON TOU OTOBPOU. To EUPOCS LEITOUPYIAKUAIEVATAI ATN TY EAXAIXT WECN T MEOIIN TNI.

-PuOiO p-c Oaepou aavoetipkoU uyous

To avoetpiok uoc Tou kukopopnT npauevei oaepe otav eataaenei npox Tou aaiteirai ato tv Eykataotan.

OeOnnAeKtpoBiw-BiaqpaayatoS

Meta TNYTOTOBENIOTU μTKE, ELEYE TE OAWTNTOTOEETN TUV NAEKPOBIW KAI TOI 11aipaypatoc ouPwovA TE TAPAKATOWIc. Suviotata O AeyxosT W TIVW M TaO kabe ETIEBaON Tny KEpaH

FERROLI Atlas D Eco Cond Unit - OeOnnAeKtpoBiw-BiaqpaayatoS - 1

3.2 QeON OE Aetoupyia

'EAeyxoi TOU PPeTI VA EKTALOUVTAI KAa TIV TIPwTN EVpyoTIOJOn, KaWc KAI eTAtro EpyaOIEC OuvtnpOAnG YIA TIG OTIOE CATAIeITAI aTOOuVDeON TOW OuaTnmuTsw n ETEμBaON OTA opyava aOgAaleiac n OTA EGApTnpuTau LEBNTa:

Pivavoveto λeβητα

AvoIeTc Tc EvexoEvcs BaJIbEs dakottns metaU aeBnta kai EykaataoaeWv.
ELeyTe Tn OteyavotntaTc Tng EYkataoTaon Kaouou.
EeYTe Tn Owtn PpOPOTIOI TO DOxeiou DiaToA
F EJIaIe Tn U6paAunikvEYkataOaon Kai BepaWBeite yia Tny TAnp EaePwOn Tou aepa Tn TepiExei OlambdaTc Ka n EYkataOaon AoviovVtac n BaAlbda Biaqpyns aepa Tn ElambdaTc Ka Tc Evxoepeves Baalbdes Eaepuwns Tc NkEATaOaons.
Beaiwthei 10vI auXovuapooce vpu oTny evkataaon, ota kukawata vpu xphnc, otc suvdeoeic n oto Aebnta.
BaeiWthe iay niouwn ouveon nnc naekptikc Ekyataoans kai yni atoteaepatikotntn cyselwng.
Bbaowte otov npxouv eukkta uypa nukov ta oAeeta.
TOTOBETNTOA JAVOJPO KAI TO KEVOpTeo ATNv AVTLia Tou KAUATnPa (aapaipeTe Ta tegT In Theon Oe Aeioupyla).
Avoigt Tis Baveos OTouc oWAnveTou TETpeAiaou

Evauon

FERROLI Atlas D Eco Cond Unit - Evauon - 1
EIK.37-EvEpyoToin

A

OaV Kaei ngepooatnynpaun, o kivntnpac tou kauotnpa tibetai oe aeitoupyia paqi me tvavta: to ttepeiaio ncs avapopqnns onoynelai oao npoc nvy eitipopn. Aetioupyov EETION O avepiatnpac tou kauotnpa ka o paaanpatnc evauanc kai kata ouvetieia kctekouvtaoi o poaeic

TPOeEaepiooC ts Eaia
PpOuOgEvOgTuKkWpatOgTepaioU.
TPOaVapalegncEeKkewwn eTaTuWakpWtWnAektpoivw.

B

TeAos Tns TpOAnOs O IVaKaE Aevxou avolye TnV nAeKtpoayvnti KaBla: to TETpeAio QTaeI OTo MTek aTo TOtolo Yekacetai.

H eTnEe Tnv EKevwn PeaTu wv NektpodiWv POKaEI to oxnuaioo nC oovac.

Tauroxpova, apxiEIO xpovos aepaaleas

Kuklos ouakeun

FERROLI Atlas D Eco Cond Unit - B - 1
EK.38-Kuklos ouokeuins

R-SB-W ΕεμοστάτεςΠεδοστάτες
OH Ppoepmuavnpa nTpeaaifou
OW Etnaipn eEyxou aeitoupyia
M Kivntnpac kauotnpa
Z Metaoxnpatiotnc evauonc
BV Hektpoayvntik i
FR
A' EvapgEvauonG ppoepmuvtnpa
A Evapg envaunx wpi npoepaavnpa
B Napouoiαλoγα
C OuaHn Aetoupyia
D Naouonpuθμiσns(TA-TC)
t1 Xpovoc TpoeEaepiou
TSA Xpovoc aopaaieas
t3 Xpovoc npoavapAeEns
t3n Xpovoc
tw Xpovoc ppoepmuavong
Σηματεξόδου αποτον πίνακα
∑nua aaykala stny eioo

EeYxo kata th diapkeia tns aeitoupyias

Avayte Tn ouakeun ouuowua e Tc obnye cTny sez.1.3.
BebaiwBeite yia n oteyavotnTa Tou kukkwpatoc kaoumuou kai twv eykataotaeewvepou.
EAEyTE TnV aTIOoON TNS KAIVADaC KAI TOW V ayWyyw aepa-kaUOaepiW ME To AEBNTa OE AIEIoupyia.
Beaiwtheire yia in oawtn kukloopopia tou vepou oto λeβnta kai otic eykataotaeic.
EAEYETn OWTNI AEIOUPVIA TOU AEBNTI PPAYATOTIOAVTAC OPIOVEC 0KIOEC evauoN KBI OINIATOC MEOW TOU BEPPOATN TEPBAALOVTO N TOU EIGTEPIKO XeipiTNIPIOU.
ELeyTe Tn Oteyavotnta TnTnpTaou KauoTpa KaI Tou Balaou Kauoaeplw.
Bεβαιωθείe οτο καυστήραςλειουργέι σωτά.
EKTAEOTIa avauon ts kaounO (e To λebnta staepooinuevo) kai βepaowtei 0TI TOIOOOTO CO, OTA KAUaaepia Kuaivetai ano 11% EwC 12%.
EAEYETO OAWOTIPOypaumiaoTOUVTAPaETPWKAI EKTEAEOTUXOVavaykaie TPOOWNIKEspuHIOIEG(KaUMNAnVNTATBIOIg,IOXUS,EPouOKpaoiesK.AT).

3.3 Evvtnponn

πepiδikos λεγxos

Tia va eEgapalicietai n owtn aeitoupyia tnc oukeuins me tvnpodou xpvou, ta TPTeirva aovabece de EeEieikkeuve Ptooowtko to Etioo epic no Ta PtoaPaeTeIO Touc AokolouBocEAEYXOC

Ta ouotnmuata xeiipaoou kai aopaaieac PpTei va aeitoupyoov owaTa.
To kukawga aattaywyng twv kauaepiw npetie va aeitoupye tEia
Bbaowte 01 o wlnves tropooboc kai eioptpohc kaouou dev evai Bouluevoi kai dev exouv xutnmuata.
Kaaiote to pIATPO TnS ypaunC avappnoTou kauipou.
Metphote tn owath katavawon kaouipou
Kaapate nV Keapn KaanC atn Zwn Eoo Tou Kaouou, oTo biako 0tpoiaou.

Aphote Tov kauotnpa va aleitoupyne ie t n meviot ioxy eti deka lettta tepinou KAI OTN OUVEXIA AVAUte ta kauoepia ia va ekyete:

Tis oowotc puoipieic oawv wv toxieiw Tou npiypapovtai oto npov Eeyxepio
Tic 0epuokpaoies tw kauoapeiw otny kaivaba
-To TnoooCo2

Oi ayyoai kai to Teppatiko aepa-kaauaepiw npetie va eivai euehepoia ato Emuia kai va mny napouotaoov diappots.
O KaUToIpaC KAI O evAAakTc TpTei VA EIVA KAbaoi KAI EAEUBepoi ATOAaTA. Ia To EvExoMeV KOaipoiO np XpnaiotIOeITE XnmuKia TPOIOvTA n ATAOIAVECS BOpTOE
Olyekataotadaeic kauooukai vepou Tpentei va eivai oteyavec.
H niocn Tou vepou e Tnv Ekyataoan Kpua npetra va evai npitou 1 bar. avtBttn nepittwn npetra va nv enavapepe ae auty tv tni.
O Kukaoopopnns 6ev TpeT eiv aiv aiaokapiaevoC.
To doxio diaoToAns npenv aivayeepato.
EAEyTe TnV avoOaaynoIou kEv avayknavtikataotneTnV.

FERROLI Atlas D Eco Cond Unit - πepiδikos λεγxos - 1

Tia tv TIAVIO KABAPIO TOI PEPBAAHATOC,TOU NIVAKA KAI TOW BIAKOJNTIKUVO ATOXIEUV TOA EJIHTa UTOPEITE VA XPOIOTIOEETE EVA MAKOK KAI UVPVTBIPEYEV OVEQYEWEO SE DIAUMA ME ATOPPUTAVIKO. PENTI VA ATOPEUYOVTAOA TDAIBPWTIAATOPPUTAVIKO KAI DIAULTEC.

Pp6oBaaon 0To nAekTpodio kai 0To pTtEK

Atoouvde ta kalwia tuv nektpoiwiu tou metaoynnatiotn kai apaipeote tn qutoavtioaon 1 kai to pakop 2 tou ouvseei to ownaTETPEAIou OTypaui 3 Tou uTK. Xaalapowte Tc BiEc 4 KAI apaipeote To ouoTnua qAvvtacmTEKdiappayatoc-naktpoiwiw.

FERROLI Atlas D Eco Cond Unit - Pp6oBaaon 0To nAekTpodio kai 0To pTtEK - 1
EIK.39

EbiowTe Tbi0a 5 ia va apaipeeteto diappayka kai tn bi6 yia va apaipeeteto naekpobia. KaacKaapaiocou Tou ttek EENTUYXavetau pe apaipeon Tou pfalpou, KaepapioTuw EKOTWv KNTc OTNtpsiKaaou je BeVcnk AETLua. Kata nTv EtavatoTOBENn OAWv Tu aOteiWv, antaeiTn PPOoxn otwn ToTtoBttnoTuv NkEkpodiWv-Tou diaqpayatoc.

FERROLI Atlas D Eco Cond Unit - Pp6oBaaon 0To nAekTpodio kai 0To pTtEK - 2
EIK.40

KaopioosAeBnta

  1. AnouvOeTo λεβηTa απo ην Λεκτρικ Tpopoδoσia.
  2. Apaipoe TOV Kauo npa oTWC Tepiypapetai TapaTavw
  3. ApaipoteTOUS IVAKES EKAI FF EBiowovTAsOxETIA
  4. KaBaplate To eouteipko Tou Aebeta Kai ooknpn Tbiapoun Twkauaepiw Xpnootowrtos Boptoc nTETeouevo aepa.
  5. KAEIOTE TOU TIVAKEC

FERROLI Atlas D Eco Cond Unit - KaopioosAeBnta - 1

Kaepiopocouoatmuosavaktnonkaaepiwv

Tia tov kaabapioo tou ouatniatoa avaktnnks kauaaepiw TpTei va:

Apaipate To Kattaki B

ApaipoeTe Ta kattakia kleiojatoc C Tou ouotmuoc avaktnnc kauoepiwv.
XpooiotoiovtacnAekpiKooutaKaBapite PPOeKTiKaTO eawtepko Tou auTmuatocavaktnang.
Eav utapxouv noaies akabapieis, mtopei va xpoiooitnoe tia kataan an oukeun yia ekaov oevp oTo eotwepikoi. Tny npiipttwn autn, attariteai ibaitepn npooyn wote va atopveuxei n etapn neyalnc troootntac vepu me ta otoixeia ato utooipno oTo dalaqau kawaeipvi. Apnrote to vepva tpeelieu wtnc eaywnsouittkuvmatoC d apov atouuvseetoe to opovi.

FERROLI Atlas D Eco Cond Unit - Apaipate To Kattaki B - 1
EK.42-KaBapiooosouotnatoacavaktnons

TOnToBcTeHnXTeVivv

Metavot katoo tou ouatnatoos avaktnons, pteie va bebaiote et on ta xevia exouv totoe tneoiota otwc atowc palvatai otyn Eik. 43. sice ta taoiaodia otepuwong odo kao soumtiet A) peoitn ouoigns 0,6 Nm. Eaov eexte duvaopetko kleiidi, beaiote on n diieueon twkauoeipwu metae uot oeipw eviai 1 mm.

FERROLI Atlas D Eco Cond Unit - TOnToBcTeHnXTeVivv - 1

FERROLI Atlas D Eco Cond Unit - TOnToBcTeHnXTeVivv - 2
EIK.43-TOTTOBETONXTEVIW

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : FERROLI

Model : Atlas D Eco Cond Unit

Category : Boiler