Kübler Codix 130 - Measuring equipment

Codix 130 - Measuring equipment Kübler - Free user manual and instructions

Find the device manual for free Codix 130 Kübler in PDF.

📄 36 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Kübler Codix 130 - page 7
View the manual : Français FR Deutsch DE English EN Español ES Italiano IT
Pick your language and provide your email: we'll send you a specifically translated version.
BrandKübler
ModelCodix 130
Product typeLithium battery powered LCD counter
Dimensions (L×H×D)48 × 24 × 48 mm (housing)
Cut-out22.2 × 45 mm (tolerance +0.3 / +0.6 mm)
WeightApproximately 50 g
Power supplyNon-replaceable lithium battery (service life ~8 years at 20°C)
Backlight power supply (option)24 V DC ±20%, 50 mA, SELV, fuse T0.08 A
DisplayLCD, 8 digits, height 8 mm
Display range-9,999,999 to 99,999,999 (with leading zero suppression)
Maximum counting frequencyUp to 12 kHz (depending on model and input type)
Input typesNPN (0…0.7 V DC / 3…30 V DC) or PNP (0…0.7 V DC / 4…30 V DC); AC/DC (10…260 V AC/DC)
Operating modesCount, Cnt.Dir, Up.Dn, Quad, Quad2
FunctionsPulse, time, frequency counting; totalizing, piece counting, position detection, differential counting
Protection rating (front panel)IP65
ConnectionsScrew terminals, 8 terminals, max. cross-section 1 × 1.5 mm² or 2 × 0.75 mm²
Working temperature-10 to +55 °C (relative humidity <85% non-condensing)
Storage temperature-20 to +70 °C
Maximum altitude2000 m
Electromagnetic compatibilityEmissions EN 55011 Class B, immunity EN 61000-6-2
SafetyComplies with EN 61010-1, overvoltage category II, pollution degree 2, protection class 2 (front panel)
MaintenanceClean the front panel with a soft damp cloth; no special maintenance
BatteryLithium, do not open, do not dispose of in fire, recycling mandatory

Frequently Asked Questions - Codix 130 Kübler

How to reset the Codix 130 counter?
Use the reset input (screw terminal 3 for DC models, or terminal 5 for AC). Apply a low signal (0 V DC) for at least 50 ms. The reset button can be locked via the Reset Enable input (terminal 4).
What type of battery does the Codix 130 use and what is its service life?
The device uses a non-replaceable lithium battery. Its service life is approximately 8 years at 20 °C. At the end of life, the device must be returned for recycling.
How to change the operating mode (Count, Up/Down, Quadrature)?
The mode is selected by wiring the Mode input (terminal 5 for DC models). Connect this terminal to GND (terminal 6) to switch to Up.Dn or Quad2 mode depending on the model. Refer to Table 2 in the manual for exact assignments.
What to do if the counter does not count?
Check the connection of the counting input (terminals 1 and 2), the NPN/PNP polarity, the ground connection (GND) between the pulse generator and the counter, and the signal frequency (do not exceed the specified max. frequency). Ensure that signal levels reach the switching thresholds.
How to connect an NPN or PNP sensor?
For an NPN sensor, connect the sensor output to the input terminal (INP A or INP B) and the sensor common to GND (terminal 6). The counter is active on negative edge. For a PNP sensor, connect the output to GND via the input resistor; the counter is active on positive edge. Respect the specified voltage levels (NPN: low 0-0.7 V, high 3-30 V; PNP: low 0-0.7 V, high 4-30 V).
Which fuses to use to protect the device?
Use an external slow-blow fuse T0.08 A for the backlight power supply (24 V DC). For signal inputs, if the source does not have protective impedance, use a slow-blow fuse T0.01 A. Fuses must be approved and suitable for the voltage.
How to clean the Codix 130?
Clean only the front panel with a soft damp cloth. Do not use abrasive products or solvents. The recessed rear face does not require cleaning; it is the responsibility of maintenance personnel.
Can I open the device to repair it?
No, it is forbidden to open the device. Any opening or repair by the user voids the warranty and may compromise safety. Contact the manufacturer's after-sales service or your supplier.
What is the meaning of the triangle symbol with exclamation mark on the device?
This symbol indicates the presence of significant risks described in the user manual, such as dangerous voltages or safety instructions that must be strictly followed.
How to install the Codix 130 in a panel?
Cut an opening of 22.2 × 45 mm (tolerance +0.3 / +0.6 mm). Remove the mounting frame, insert the device from the front ensuring the gasket is in place, then slide the mounting frame from the back until it clicks. Leave a 10 mm gap around for ventilation.

User questions about Codix 130 Kübler

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Measuring equipment in PDF format for free! Find your manual Codix 130 - Kübler and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Codix 130 by Kübler.

USER MANUAL Codix 130 Kübler

(24 V DC ±20%, 50 mA)

SELV,CLASS II (Limited Power Source)

High-Pegel: 3...30 V DC

High-Pegel: 4...30 V DC

Schraubklemme 3:

Low-Pegel: 0...0.7 V DC

High-Pegel: 3...30 V DC

High-Pegel: 3...5 V DC

High-Pegel: 3...5 V DC

Low-Pegel: 0...2 V AC/V DC

High-Pegel: 10...260 V AC/V DC

Low-Pegel: 0...0.7 V DC

High-Pegel: 3...5 V DC

High-Pegel: 3...5 V DC

The Codix 13X display counters are battery-powered. They are controlled by contact or voltage pulses. They may be used in various applications, like e. g. totalising, parts counting, position acquisition, differential counting, etc. In addition, the various models with specific input types may be extended using control inputs to select operatin modes and set for almost any application thanks to adjustable operating modes.

1.1 Preface

Kübler Codix 130 - Preface - 1

Please read this instruction manual entirely and carefully before installation and start-up. Please observe all warnings and advice, both for your own safety and for general plant safety. If the device is not used in accordance with this instruction manual, then the intended protection can be impaired.

1.2 Safety Instructions andWarnings

Kübler Codix 130 - Safety Instructions andWarnings - 1

Please use the device only if its technical condition is perfect. It should be used only for its intended purpose. Please bear in mind safety aspects and potential dangers and adhere to the operating instructions at all times.

Defective or damaged devices should be disconnected from the mains immediately and taken out of operation.

The device shall not be opened. Use the repair service of the manufacturer.

Only connect the device to the electricity networks provided to that purpose.

The safety of the system in which the device is integrated is the responsibility of the installer.

Disconnect all electricity networks prior to any installation or maintenance work.

Use exclusively cables approved in your country and designed for your temperature and power ranges.

Installation and service work shall be carried out exclusively by qualified personnel.

The device must compulsorily be protected with approved external fuses. The value of these fuses can be found in the technical information.

Kübler Codix 130 - Safety Instructions andWarnings - 2

This symbol is used on the device to remind of the existence of dangers, which are referred to in this manual.

1.3 Use according to the intended purpose

The display counter detects and measures pulses, times and frequencies up to max. 12kHz and offers a wide variety of different operating modes. Use for any purpose over and beyond this will be deemed as not in accordance with its intended purpose and thus not complying with the requirements.

The application area for this device lies in industrial processes and controls, in the fields of manufacturing lines for the metal, wood, plastics, paper, glass, textile and other like industries. Over-voltages at the terminals of the device must be kept within the limits of Over-voltage Category II.

The device must only be operated when mounted in a panel in the correct way and in accordance with the section "Technical Data".

The device is not suitable for use in hazardous areas and for areas excluded in EN 61010 Part 1. If the device is used to monitor machines or processes in which, in the event of a failure of the device or an error made by the operator, there might be the risk of damaging the machine or causing an accident to the operators, it is your responsibility to take the appropriate safety measures.

The device has been designed for indoor operation. It may nevertheless be used outdoors, provided the technical data is adhered to. In this case, take care to provide suitable UV protection.

1.4 Mounting in a control panel

Kübler Codix 130 - Mounting in a control panel - 1
CAUTION

Mount the device away from heat sources and avoid direct contact with corrosive liquids, hot steam or similar.

Provide a free space of 10mm all around the device for its ventilation.

The device should be mounted so that the terminals are out of the reach of the operator and cannot be touched by him. When mounting the device, consider the fact that only the front side is classified as accessible for the operator.

1.5 Mounting instructions

  1. Remove the mounting clip from the device.
  2. Insert the device from the front into the panel cut-out, ensuring the front-panel gasket is correctly seated.
  3. Slide the fixing clip from the rear onto the housing, until the spring clamps are under tension and the upper and lower latching lugs have snapped into place.

Note: In case of proper installation, IP65 can be reached on the front side.

1.6 Electrical Installation

Kübler Codix 130 - Electrical Installation - 1

The device must be disconnected from any power supply prior to any installation or maintenance work. Make sure that no more voltages LIABLE TO CAUSE AN ELECTRO-CUTION are present.

Signal lines carrying voltages exceeding 30V AC or 70V DC must be operated with a device allowing disconnecting them from the voltage source. This device must be located close to the equipment and marked as its disconnecting device - excepted when it can be excluded that a defect presents a danger.

Installation or maintenance work must only be carried out by qualified personnel and in compliance with the applicable national and international standards.

Take care to separate all extra-low voltages entering or exiting the device from hazardous electrical conductors by means of a double or reinforced insulation (SELV circuits).

Kübler Codix 130 - Electrical Installation - 2

The device must be protected externally for its proper operation. Information about the prescribed fuses can be found in the technical information.

  • During installation, make sure that the signal inputs are fed from the same mains phase, in order not to exceed the maximum permitted voltage of 250V .
  • The cables must be designed for the planned temperature and voltage ranges. Regarding the type of the cables, adhere to the applicable standards of the country and of the plant. The cross sections allowed for the screw terminals can be found in the technical data.
  • Before starting the device, check the cables for proper wiring and tightening. The screws of unused screw terminals must be screwed to the stop, so that they cannot loosen and get lost.

  • The device has been designed for overvoltage category II. If higher transient voltages cannot be excluded, additional protection measures must be taken in order to limit the overvoltage to the values of CAT II.

1.7 Advice on noise immunity

All connections are protected against external sources of interference. The installation location should be chosen so that inductive or capacitive interference does not affect the device or its connecting lines! Interference (e.g. from switch-mode power supplies, motors, clocked controllers or contactors) can be reduced by means of appropriate cable routing and wiring.

1.8 Measures to be taken

  • Use only shielded cable and control lines. Connect shield at both ends. The conductor cross-section of the cables should be a minimum of 0.14mm^2
  • The shield connection to the equipotential bonding should be as short as possible and with a contact area as large as possible (low-impedance).
  • Only connect the shields to the control panel, if the latter is also earthed.
  • Install the device as far away as possible from noise-containing cables.
  • Avoid routing signal or control cables parallel to power lines

DC versions

Use shielded wires for the counting and control inputs so as to obtain the maximum EMC resistance or connect not used count inputs to ground (0 V).

AC versions

Use shielded wires for the counting and control inputs so as to obtain the maximum EMC resistance.

1.9 Cleaning and maintenance

The front side of the unit should only be cleaned using a soft damp (water!) cloth. Cleaning of the embedded rear side is not planned and is the responsibility of the service personnel or of the installer.

In normal operation, this device is maintenance-free. Should the device nevertheless not operate properly, it must be sent back to the manufacturer or to the supplier. Opening and repairing the device by the user is not allowed and can adversely affect the original protection level.

1.10 Operation

Is the device set and programmed correctly (function; for counters, max. counting frequency)?

1.11 Failure possibilities and causes

Impossible to use the keys:

Key lock input activated
Counter does not count:
- Wrong or reversed wiring of the counting input
- Setting of an input signal not matching the pulse generator
- Polarity (NPN/PNP) reversed
- No ground connection between the pulse generator and the counter

Maximum counting frequency exceeded
- Signal levels do not reach the switching threshold of the counter

If, despite all, your device still does not operate, contact your local representative or call us directly for technical support.

When sending your device back, please attach a short description of the failure, of the programming and of the connection diagram, in order to allow us to reproduce a possibly existing defect and to repair your device as quickly as possible.

Overview
Table 1

Model Operating mode Counting inputs
INP A INP B
6.130.012.8x0 Count 0...0,7 V DCNPN7 kHz 0...0,7 V DCNPN
6.130.012.8x24...30 V DCPNP12 kHz0...0,7 V DCPNP
6.130.012.8x310...260 V AC/DCAC/DC30 Hz10...260 V AC/DCAC/DC
6.131.012.8x0 Cnt.Dir/Up.Dn0...0,7 V DCNPN7 kHz 0...0,7 V DCNPN
6.131.012.8x14...30 V DCPNP12 kHz4...30 V DCPNP
6.131.012.8x3 Up.Dn10......260 V AC/DCAC/DC30 Hz10...260 V AC/DCAC/DC
6.132.012.8x3 Cnt.Dir10......260 V AC/DCAC/DC30 Hz10...260 V AC/DCAC/DC
6.133.012.8x0 Quad/Quad20...0,7 V DCNPN3 kHz 0...0,7 V DCNPN
6.133.012.8x14...30 V DCNPN6 kHz 4...30 V DCNPN
Options:x = 5: no backlight
x = 6: with backlight

DC input modes:

Count: Fast and slow counting inputs

INP A: Fast counting input

INP B: Slow counting input

Cnt.Dir: Counting and counting direction input

INP A: Counting input

INP B: Counting direction input

Up.Dn: Differential counting input

INP A: Adding counting input

INP B: Subtracting counting input

Quad: Phase discriminator input

INP A: 0^ counting input

INP B: 90^ counting input

Quad2: Phase discriminator input with pulse doubling

INP A: 0^ counting input

INP B: 90^ counting input

Each edge of INP A is counted.

AC input modes:

Count: Counting and reset inputs

INP A: AC/DC counting input

INP B: AC/DC reset input

Cnt.Dir: Counting and counting direction input

INP A: AC/DC counting direction input

INP B: AC/DC counting input

Up.Dn: Differential counting input

INP A: AC/DC subtracting counting input

INP B: AC/DC adding counting input

Main technical features:

Display: LCD, 8 decades, height of the figures 8mm

Display range:

-9999999...99999999

with leading zeros suppression.

Overflow: In case of a display range overflow, the counter starts again from 0, but without removing the leading zeros and activating all decimal points. In case of a display range underflow, the counter starts again from 0 and displays the minus sign, without removing the leading zeros and activating all decimal points.

Keys: Electrical locking of the reset key

Housing: Panel mounting, 48 × 24 ~mm according to DIN 43700, RAL 7021

Panel cut-out:

$$ 2 2, 2 + ^ {0, 3} \mathrm {m m} \times 4 5 + ^ {0, 6} \mathrm {m m} $$

Mounting depth: approximately 48 mm

Weight: approximately 50g

Protection level: IP65 on the front side

Connection:

Screw terminals, RM 5.00, 8 poles Rated cross-section: max.: 1 × 1.5 ~mm 2 2 × 0.75 ~mm

AWG 26-14

EMC:Interference emissions EN 55011 Class B Interference resistance EN 61000-6-2

Device safety (for the AC models):

Design to: EN 61010 Part 1

Protection Class: Protection Class 2 (front side)

Kübler Codix 130 - Main technical features: - 1

Only the front side is classified as accessible for the operator.

Application area: Pollution level 2 over-voltage Category II

Insulation:

Front: double insulation,

Rear side: basic insulation, Signal inputs and und sensor power supply: SELV

Power supply:

Non-replaceable lithium battery

(lifetime approximately, 8 years at 20^ )

Working temperature:

-10 +55^ relative humidity < 85%

without condensation

Operating temperature:

-10...+60°C

Storage temperature:

-20...+70°C

Altitude: to 2000 m

Backlighting:

external electrical source

(24 V DC ±20%, 50 mA)

SELV,CLASS II (Limited Power Source)

ext. fuse protection T0.08 A

Input specification, pin assignment and adjustable operating modes (DC versions) A control input (screw terminal 5) allows adjusting the operating mode.
Table 2

Screw terminalNo. 1No. 2No. 3No. 4No. 5No. 6No. 7No. 8
Designation ModelINP AINP BResetReset EnableControl inputs for operating mode (Mode)GNDBL-BL+
6.130.012.8x07 kHzNPN30 Hz NPNNPN reset inputNPN reset key locking input, Contact with GND, key free.not active = addingcontact with GND = subtractingGND = 0 V DCHintergrundbeleuchung (-)Hintergrundbeleuchung (+)
6.130.012.8x212 kHzPNPNPN
6.131.012.8x07 KHzNPN7 kHz NPNnot active = Cnt.Dr Modecontact with GND = Up.Dn Mode
6.131.012.8x112 kHzPNP12 kHzPNP
6.133.012.8x03 kHzNPN3 kHzNPNnot active = Quad Modecontact with GND = Quad2 Mode
6.133.012.8x16 kHzPNP6 kHzPNP

Screw terminals 1 and 2:

Function and max. frequencies

(Pulse/Pause 1:1) see Table 2

NPN: active for negative edge

Input resistance: approximately 1 MOhm

Low level: 0...0.7 V DC

High level: 3...30 V DC

PNP: active for positive edge

Input resistance: approximately 100 kOhm

Low level: 0...0.7 V DC

High level: 4...30 V DC

Screw terminal 3:

Reset input, active for negative edge

Contact input / Open Collector NPN

(switching at 0VDC

Low level: 0...0.7 V DC

High level: 3...30 V DC

Min. pulse duration: 50 ms

Input resistance: approximately 2.2 MOhm

Screw terminal 4:

Electrical locking of the reset key

Contact input / Open Collector NPN

(switching at 0VDC

Low level: 0...0.7 V DC

High level: 3...5 V DC

Input resistance: approximately. 2.2 MOhm

Input not active: Reset key locked

Input in contact

with GND: Reset key unlocked

Screw terminal 5:

Operating mode switch (Mode)

Contact input / Open Collector NPN

(switching at 0VDC

Low level: 0...0.7 V DC

High level: 3...5 V DC

Input resistance: approximately 2.2 MOhm

Function: see Table 2

Screw terminal 6:

GND connection common for all inputs

Screw terminal 7:

(-) external power supply for the LCD backlight option

Screw terminal 8:

(+) external power supply for the LCD backlight option

(24 V DC ±20%, 50 mA), Fuse T0.08 A, delayed action

Kübler Codix 130 - Screw terminal 8: - 1
DANGER

All low voltages, SELV, reinforced/double insulation. Signal inputs must be protected with an external delayed T0.01 A fuse when the source does not provide protective impedance (fuse/ current limitation).

Input specification and pin assignment (AC-version)
Table 3

Screw terminalNo. 1No. 2No. 3No. 4No. 5No. 6No. 7No. 8
Bezeichnung TypINP A AC/DCCommon AD/DCINP B AC/DCReset EnableResetGNDBL-BL+
6.130.012.8x3 countingCommon connection for INP A and INP BresetNPN reset key locking input, Contact with GND. Key free.not connectedGND = 0 V DCBacklighting (-)Backlighting (+)
6.131.012.8x3 subtractingaddingNPN reset input
6.132.012.8x3 counting directioncounting

Screw terminals 1 and 3:
Counting input and reset input
Optocoupler input 10...260 V AC/V DC
galvanic isolation, active for High signal
Min. pulse duration: 16 ms
Max frequency: approximately 30 Hz
Low level: 0...2 V AC/V DC
High level: 10...260 V AC/V DC
Input resistance: approximately 160 kOhm
AC mains frequency: 50/60Hz

Screw terminal 2: Common AC/DC, common connection for the optocoupler inputs (screw terminals 1 and 3).

Screw terminal 4:
Electrical locking of the reset key
Contact input / Open Collector NPN (switching at 0 V DC)
Low level: 0...0.7 V DC
High level: 3...5 V DC
Input resistance: approximately 2.2 MOhm
Input not active: Reset key locked
Input in contact with GND: Reset key unlocked

Screw terminal 5:
Function: see table 3, active for negative edge
Contact input/Open Collector NPN (switching at 0 V DC)
Low level: 0...0.7 V DC
High level: 3...5 V DC
Min. pulse duration: 50 ms
Input resistance: ca. 2.2 MOhm
Input High: ---
Input Low: Reset of the counter Dynamic resetting behaviour

Screw terminal 6: Common GND connection for screw terminal 4 (reset key locking input) and screw terminal 5 (reset input).

Screw terminal 7: (-) external power supply for the backlight option

Screw terminal 8: (+) external power supply for the backlight option (24V± 20% ,50mA) Fuse T0.08 A, delayed action

All low voltages, SELV, reinforced/double insulation. Signal inputs must be protected with an external delayed T0.01 A fuse when the source does not provide protective impedance (fuse/ current limitation).

Scope of delivery:
Digital dispay
Clamp
Front frame for screw mounting,
Panel cut-out 50 × 25 ~mm Front frame for clamp mounting,
Panel cut-out 50 × 25 ~mm Seal
Operating instructions

Note:

Kübler Codix 130 - Note: - 1

This product includes a lithium battery. Do not open it by force, do not throw it in the fire. Avoid temperatures below -20^ and above +70^ .

1.Description

Raccordement (executions AC)

La consegna include:

Contatore

Staffa di montaggio

This device contains a lithium battery. In compliance with the battery directive, we inform you that:

Batteries must not be discarded in the household waste, but the law obliges you to bring them to the collection point specifically provided for that purpose. You can send us back the complete devices after use. If you can remove the batteries according to the state of the art, you can also bring them to a local collection point or to a retailer collecting batteries.

Specific provisions for returning lithium batteries:

Avoid short-circuits! For that purpose, protect the poles with isolating tape. The poles of the lithium battery shall not come in contact with metallic objects, neither by accident nor intentionally!

Batteries containing pollutants are marked with a symbol representing a crossed-out garbage can and the chemical symbol of the heavy metal that determines their classification as containing pollutants. Thank you for your help!

F

Kübler Codix 130 - Specific provisions for returning lithium batteries: - 1

1 Countersinking Af3, DIN 74

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Kübler

Model : Codix 130

Category : Measuring equipment