HONEYWELL BA295 - Faucets

BA295 - Faucets HONEYWELL - Free user manual and instructions

Find the device manual for free BA295 HONEYWELL in PDF.

📄 30 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice HONEYWELL BA295 - page 6
View the manual : Français FR Deutsch DE English EN Italiano IT
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Backflow Preventer (Type BA)
Brand Honeywell
Model BA295
Connection Sizes 1/2" (DN15), 3/4" (DN20), 1" (DN25), 1-1/4" (DN32), 1-1/2" (DN40), 2" (DN50)
Maximum Inlet Pressure 10.0 bar
Minimum Inlet Pressure 1.5 bar
Maximum Operating Temperature 65°C
Installation Position Horizontal with discharge valve downwards
Medium Water
Scope of Delivery Housing with integral strainer (0.6 mm mesh), valve cartridge with integral check valve and discharge valve, outlet check valve, three ball valves for differential pressure gauge, connection fittings, discharge connection
Options BA295-…A (threaded connections 1/2", 3/4", 1-1/2", 2"), BA295-…B (threaded connections 1", 1-1/4")
Maintenance Frequency Inspection every 6 months; maintenance every 1-3 years
Discharge Pipe Size DN50 for 1/2" to 1" connections; DN70 for 1-1/4" to 2" connections
Accessories D06F Pressure Reducing Valve, TK295 Test Kit (digital), TKA295 Test Kit (analogue), F76S Fine Filter
Spare Parts Cartridge insert, check valve complete, lip seal, O-rings
Materials Red bronze housing, high-quality synthetic valve cartridge, brass ball valves, elastomer sealing elements
Standards DIN EN 1717

Frequently Asked Questions - BA295 HONEYWELL

What is the purpose of the Honeywell BA295 backflow preventer?
The BA295 is a backflow preventer that protects drinking water networks by preventing back pressure or back siphonage. It divides into three pressure zones and opens a discharge valve when differential pressure falls below 0.14 bar.
What are the recommended installation conditions?
Install the device horizontally with the discharge valve pointing downwards. Ensure good access, protect from frost, and ventilate well. A straight pipe section of at least five times the nominal valve size is required after the backflow preventer.
How do I test the discharge valve?
Use a test control unit like TK295 or TKA295. For a quick test, lower the inlet pressure: if the discharge valve opens (drops), it functions correctly. Detailed procedure is in the test unit instructions.
How often should maintenance be performed?
Inspection is recommended every 6 months, and maintenance every 1-3 years, depending on local operating conditions. Always use authorized personnel.
Can I clean the cartridge insert myself?
Yes, the operator can clean the cartridge insert. Do not use cleaning agents with solvents or alcohol. Close shut-off valves, release pressure, remove cover, clean or replace the cartridge and lip seal, then reassemble.
What should I do if the discharge valve opens without reason?
Possible causes include pressure strokes or fluctuating inlet pressure. Install a pressure reducing valve (e.g., D06F) upstream. If the cartridge is contaminated, replace it.
What spare parts are available for the BA295?
Spare parts include cartridge insert (part numbers 0903733 for 1/2"-1", 0903745 for 1-1/4"-2"), check valve complete, and lip seals. Refer to the spare parts list in the manual.
What is the maximum operating temperature?
The maximum operating temperature is 65°C.
Do I need a strainer before the backflow preventer?
The BA295 has an integral strainer (0.6 mm mesh). For highly polluted water, install a fine filter (e.g., F76S) upstream to ensure proper function.
How do I dispose of the BA295?
The housing is red bronze, valve cartridge is synthetic, check valves are synthetic or red bronze, and ball valves are brass. Follow local recycling/disposal regulations. Do not let detergents enter the environment.

User questions about BA295 HONEYWELL

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Faucets in PDF format for free! Find your manual BA295 - HONEYWELL and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. BA295 by HONEYWELL.

USER MANUAL BA295 HONEYWELL

Keep instructions for later use!

DN15, DN20, DN25 RV295-1/2E

DN32, DN40, DN40 RV295-11/4E

HONEYWELL BA295 - 1
12. Zubehör

D06F Druckminderer

  1. Follow the installation instructions.

HONEYWELL BA295 - D06F Druckminderer - 1

The factory-set position of the ball valves may not be altered. Non-compliance with this instruction will make any warranty claims null and void.

  1. Use the appliance

according to its intended use
- in good condition
with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the applications detailed in these installation instructions. Any other use will not be considered to comply with requirements and would invalidate the warranty.
4. Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
5. Immediately rectify any malfunctions which may influence safety.

2. Functional description

BA type backflow preventers are divided into three pressure zones. The pressure in zone ① is higher than in zone ②, which in turn is higher than in zone ③. A discharge valve is connected to zone ② which opens at the latest when the differential pressure between zones ① and ② falls to 0.14 bar. The water from zone ② discharges to atmosphere. In this way the danger of back pressure or back syphonage into the supply network is prevented. The pipework connection is interrupted and the drinking water network is protected.

3. Application

MediumWater
Maximum inlet pressure10.0 bar
Minimum inlet pressure1.5 bar

4. Technical data

Installation position Horizontal with discharge valve downwards

Max. operating temperature 65°C

Discharge pipe DN50 for connection sizes 1 / 2^ - 1^ connection DN70 for connection sizes 1 / 4'' - 2'' Connection size 1 / 2^ - 2^

5. Scope of delivery

The backflow preventer consists of:

Housing
- Integral strainer, mesh size approx. 0.6 mm
- Valve cartridge with integral check valve and discharge valve
- Outlet check valve
- Three ball valves for the connection of a differential pressure gauge
- Connection fittings
- Discharge connection

6. Options

BA295-… A =Standard version with threaded
connections1/2", 3/4", 11/2" und 2"
BA295-… B =Standard version with threaded
connections
1" and 11/4"
Connection size

7. Assembly

7.1 Installations Guidelines

  • Install shutoff valves before and after backflow preventer
    Install in horizontal pipework with the discharge valve downwards
  • Ensure good access
  • Simplifies maintenance and inspection
  • Backflow preventers of this type have an integral strainer which protects the device from the ingress of dirt. With highly polluted water a fine filter should be installed upstream to ensure the correct function of the device.
  • Do not install in places where flooding can occur
  • The installation environment should be protected against frost and ventilated well
  • Install discharge pipework which has adequate capacity

Use and type of installation according to DIN EN 1717

7.2 Assembly instructions

  1. Thoroughly flush pipework
  2. Install backflow preventer

Install in horizontal pipework with discharge connection directed downwards
Note flow direction (indicated by arrow) o Install without tension or bending stresses
- Provide a straight section of pipework of at least five times the nominal valve size after the backflow preventer

  1. Attach drain pipe to discharge connection (plastic pipe HT 50, HT70)
  2. The appliance is ready for use

8. Maintenance

HONEYWELL BA295 - Maintenance - 1

We recommend a planned maintenance contract with an installation company

HONEYWELL BA295 - Maintenance - 2

Maintenance of backflow preventer must be carried out by authorized personnel!

8.1 Inspection

HONEYWELL BA295 - Inspection - 1

  • Frequency: every 6 month (depending on local operating conditions)
  • To be carried out by an installation company
    Inspection with a test control unit and maintenance-set (see accessories)

8.1.1 Testing discharge valve

HONEYWELL BA295 - Testing discharge valve - 1

Take note of the instructions of the test control unit TKA295 or TK295

  1. Procedure according to instruction of the test control unit TKA295 resp. TK295

HONEYWELL BA295 - Testing discharge valve - 2

Quick test for the discharge valve:

  • Lower the inlet pressure o if the discharge valve opens (it drops), the function is o.k.

8.1.2 Testing outlet check valve

HONEYWELL BA295 - Testing outlet check valve - 1

Take note of the instructions of the test control unit TKA295 or TK295

  1. Procedure according to instruction of the test control unit TKA295 resp. TK295

8.2 Maintenance

HONEYWELL BA295 - Maintenance - 1

We recommend a planned maintenance contract with an installation company

In accordance with DIN EN 1717 a regular maintenance must be taken.

HONEYWELL BA295 - Maintenance - 2

Frequency: every 1-3 years (depending on local operating conditions)

To be carried out by an installation company

8.2.1 Cartridge insert

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut off valve on outlet
  4. Remove cover
  5. Replace cartridge insert and lip seal

HONEYWELL BA295 - Cartridge insert - 1

  • Don't disassemble cartridge insert to individual parts!

  • Reassemble in reverse order o push down the cartridge insert till it snaps in

  • Test function (see chapter inspection)

8.2.2 Check valve

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut off valve on outlet
  4. Remove cover
  5. Exchange check valve
  6. Test function (see chapter inspection)

8.3 Cleaning

HONEYWELL BA295 - Cleaning - 1

  • To be carried out by an installation company
    To be carried out by the operator

If necessary, the cartridge insert can be cleaned.

HONEYWELL BA295 - Cleaning - 2

Do not use any cleaning agents containing solvents and/or alcohol to clean the plastic parts!

HONEYWELL BA295 - Cleaning - 3

Detergents must not be allowed to enter the environment or the sewerage system!

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut off valve on outlet
  4. Remove cover
  5. Clean or replace cartridge insert and lip seal

HONEYWELL BA295 - Cleaning - 4

  • Don't disassemble cartridge insert to individual parts!

  • Reassemble in reverse order o push down the cartridge insert till it snaps in

  • Test function (see chapter inspection)

9. Disposal

Red bronze housing
High-quality synthetic material valve cartridge
- High-quality synthetic material or red bronze check valves
- Brass ball valves
Sealing elements made of elastomer materials suitable for drinking water
- Discharge connection DN15-25 High quality synthetic material DN32-50 Red bronze

HONEYWELL BA295 - Disposal - 1

Observe the local requirements regarding correct waste recycling/disposal!

10. Troubleshooting

DisturbanceCauseRemedy
Discharge valve opens without apparent reasonPressure strokes in water supply systemInstall a pressure reducing valve upstream the backflow preventer
Fluctuating inlet pressureInstall a pressure reducing valve upstream the backflow preventer
Cartridge insert is contaminatedRemove cartridge insert and exchange it
Discharge valve don’t closeDeposits on valve seatRemove cartridge insert and clean or exchange it
Damaged ‘o’ringRemove cartridge insert and exchange it
Leaky discharge valveRemove cartridge insert and clean or exchange it
Flow is to lowInlet strainer is blockedRemove strainer and clean it

11. Spare Parts

HONEYWELL BA295 - Spare Parts - 1

No.Description

Part No.

1Cartridge insert1/2" - 1"0903733
complete1/4" - 2"0903745

2 Check valve complete with

Check valve cone and spring made of red bronze

DN15, DN20, DN25 up to 05/06 RV295-1/2

DN32, DN40, DN50 up to 05/06 RV295-11/4

Check valve cartridge with adapter ring

DN15 up to 02/09 RV295-1/2

DN20 up to 10/08 RV295-1/2

DN25 up to 12/08 RV295-1/2

DN32 up to 08/08 RV295-11/4

DN40, DN50 up to 05/09 RV295-11/4

Check valve cartridge without adapter ring

DN15, DN20, DN25 RV295-1/2E

DN32, DN40, DN40 RV295-11/4E

12. Accessories

HONEYWELL BA295 - Accessories - 1

D06F Pressure reducing valve

Noise protected pressure reducing valve with setting scale. Maximum inlet pressure 16 bar, with brass filter bowl 25 bar, outlet pressure range 1.5 - 6.0 bar

A = With clear filter bowl up to 40^ / 16 bar

B = With brass filter bowl up to 70^ / 25 bar

TK295 Test kit

Electronic pressure measuring device with digital indicator, battery-operated.

With case and accessories, ideal for inspection and maintenance of backflow preventer type BA.

TKA295 Test kit

Analogue pressure measuring device with differential pressure display.

With case and accessories, ideal for inspection and maintenance of backflow preventer type BA.

F76S Fine filter, reverse rinsable

AA= With clear filter bowl

AAM= With red bronze filter bowl

DN15, DN20, DN25 a 05/06 RV295-1/2

DN32, DN40, DN50 a 05/06 RV295-11/4

DN15, DN20, DN25 RV295-1/2E

DN32, DN40, DN40 RV295-11/4E

12. Accessori

HONEYWELL BA295 - Accessori - 1

DN15, DN20, DN25 05/06 asti RV295-1/2

DN32, DN40, DN50 05/06 asti RV295-11/4

DN15, DN20, DN25 RV295-1/2E

DN32, DN40, DN50 RV295-11/4E

HONEYWELL BA295 - Accessori - 2
12. Lisātarvikkeet

DN15, DN20, DN25 RV295-1/2E

DN32, DN40, DN40 RV295-11/4E

HONEYWELL BA295 - Accessori - 3
12. Tilbehør

D06F Trykreduktion

Automation and Control Solutions

Honeywell GmbH

Hardhofweg

D-74821 Mosbach

Phone: (49) 6261 810

Fax: (49) 6261 81309

http://europe.hbc.honeywell.com

www.honeywell.com

Manufactured for and on behalf of the

Environmental and Combustion Controls Division of

Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16,

Switzerland by its Authorised Representative Honeywell GmbH

ENOH-1220GE23 R0809

Subject to change

  1. Safety Guidelines 6
  2. Functional description 6
  3. Application 6
  4. Technical data 6
  5. Scope of delivery 6
  6. Options 6
  7. Assembly 6
  8. Maintenance 7
  9. Disposal 8
  10. Troubleshooting 8
  11. Spare Parts 9
  12. Accessories 9

F

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HONEYWELL

Model : BA295

Category : Faucets