| Product type | Time counter (digital display) with 6 decades and SET/RESET preset function |
| Brand | Kübler |
| Model | Codix 523 |
| Housing dimensions | 48 x 24 mm (according to DIN 43700) |
| Panel cut-out | 22.2+0.3 x 45+0.6 mm or 25 x 50 mm depending on frame used |
| Weight | Approx. 50 g |
| Power supply | 10...30 V DC, max. 55 mA, with reverse polarity protection |
| Display | Red LEDs, 6 decades 7 segments, height 8 mm |
| Display range | 0 to 999,999 (seconds, minutes or hours) or 00:00:01 to 99:59:59 |
| Programmable time units | Seconds, minutes, hours, or HH:MM:SS format |
| Time measurement modes | Gate low/high, start/stop by INP B, start by INP A and stop by INP B |
| Preset function | Manual (SET/RESET button) and/or electrical (SET/RESET input) |
| Optional output | NPN optocoupler (open collector/emitter, max. 30 V DC / 10 mA) – flashes at 1 Hz when counter is active |
| Programming | Via two front panel buttons, guided by display messages |
| Data storage | EEPROM |
| Ambient temperature | -20... +65 °C (10...26 V DC) / -20... +55 °C (26...30 V DC) |
| Storage temperature | -25... +70 °C |
| Protection rating | IP 65 (front panel) |
| Maintenance and cleaning | Clean the front panel with a soft damp cloth only |
| Safety | Use only in perfect condition; disconnect power before maintenance; do not use in explosive areas; comply with EN 61010 |
| Delivery contents | Display unit, mounting bracket, clamp frame (50 x 25 mm), screw frame (50 x 25 mm), gasket, multilingual manual |
Frequently Asked Questions - Codix 523 Kübler
User questions about Codix 523 Kübler
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Measuring equipment in PDF format for free! Find your manual Codix 523 - Kübler and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. Codix 523 by Kübler.
USER MANUAL Codix 523 Kübler
SET-Wert -19 9999 ...
1.1 Safety instructions and warnings
Only use this display

– in a way according to its intended purpose
- if its technical condition is perfect
– adhering to the operating instructions and the general safety instructions.
1.2 General safety instructions
- Before carrying out any installation or maintenance work, make sure that the power supply of the digital display is switched off.
- Only use this digital display in a way according to its intended purpose:
If its technical condition is perfect.
Adhering to the operating instructions and the general safety instructions. - Adhere to country or user specific regulations.
- The digital display is not intended for use in areas with risks of explosion and in the branches excluded by the standard EN 61010 Part 1.
- The digital display shall only operate if it has been correctly mounted in a panel, in accordance with the chapter "Technical features".
1.3 Use according to the intended purpose
The digital display may be used only as a panel-mounted device. Applications of this product may be found in industrial processes and controls, in manufacturing lines for the metal, wood, plastics, paper, glass, textile and other processing industries. Over-voltages at the terminals of the digital display must be kept within the limits in Category II.
If the digital display is used to monitor machines or processes in which, in case of a failure of the device or an error made by the operator, there might be risks of damaging the machine or causing accidents to the operators, it is your responsibility to take appropriate safety measures.
1.4 Description
CODIX 521
Please note: Read first chapter 2 of CODIX 524 and go on on page 2.
CODIX 522
Please note: Read first chapter 2 of CODIX 524 and go on on page 4.
CODIX 523
Please note: Read first chapter 2 of CODIX 524 and go on on page 6.
CODIX 524
CODIX 524 is a multipurpose device. Depending on the programmed basic function, the device operates like
- the pulse counter CODIX 521 (see page2) or
• the frequency meter CODIX 522 (see page 4) or
• the time meter CODIX 523 (see page 6)
2. Setting of the operating pa ra me ters
a. Press both front side keys keys and switch on the supply voltage or, if the supply voltage is already on, press both keys simultaneously during 5 s.
b. The display shows
$$ \boxed {P r o f} $$
c. After releasing the keys, the display shows
$$ \boxed {0 0} $$
c1. Hold the left key pressed and press the right key to leave the programming operation.
c2. Press the right key to switch to
$$ \boxed {Y E S} $$
d. Hold the left key pressed and press the right key to switch to the first parameter.
e. After releasing the keys, the display alternates between the menu title and the current menu item setting. After pressing any key, only the menu item setting is displayed.
f. Pressing the right key, the menu item setting will be switched to the next value. If figures are to be input (e.g. when setting the scaling factor), select first the decade using the left key, and then set the value using the right key.
g. Hold the left key pressed and press the right key to switch to the next menu item.
h. The last menu title "EndPro" allows, when selecting "Yes", to exit the programming menu and to take over (store) the new values. If "no" is selected, the programming routine is repeated, the latest values set remaining active. They can now be checked again or modified.
3. Programming routine
The first menu item is the selection of the basic operating mode, which determines the functions of the device.
PNode

Operating mode pulse counter. Continued in point 4. of CODIX 521 on page 2

Operating mode frequency meter. Continued in point 4. of CODIX 522 on page 4

Operating mode time meter. Continued in point 4. of CODIX 523 on page 6
Pulse counter/Po si ti on indicator CODIX 521
(CODIX 524: Operating mode pulse counter)
1. Description
- 6-digit display counter with SET/RESET-function
- Red LED display, character height 8 mm
• Display range from -199 999 to 999 999 - Leading zeros suppression
- Programming via two setting keys on the front side
- During programming, the display guides the user with text prompts
- Counter operating modes:
Count input INP A + count direction input INP B (Cnt.Dir)
Differential count INP A - INP B (up.dn)
Totalising INP A + INP B (up.up)
Count Up/Down INP A 90° INP B x 1 (quAd)
Count Up/Down INP A 90° INP B x 2 (quAd2)
Count Up/Down INP A 90° INP B x 4 (quAd4)
• Optional optocoupler output
2. Inputs
INP A
Dynamic count input.
INP B
Dynamic count input.
SET/RESET
Dynamic SET/RESET input. Linked in parallel to the red SET/RESET key. Resets the counter to the predefined setting value.
3. Optocoupler output (optional)
Active if count value < 0. Simple preset counter can be realized, when using subtract mode.
4. Programming routine
The programmable parameters of the device are described below, in the order in which they can be set. The device is fully programmed after one pass of the routine.
The first values stated correspond to the factor settings
4.1 Polarity of the inputs


npn: switching for 0 V

pnp: switching for +U_B
4.2 Switching on the 30 Hz filter (INP A, INP B)

The filter provides input damping*

30 Hz filter off ( f_max )

30 Hz filter on
4.3 Input mode


Count input and count direction input
INP A: Count input
INP B: Count direction input

Differential input
INP A: count input adding
INP B: count input subtracting

Totalising
INP A: count input adding
INP B: count input adding

Quadrature input
INP A: count input 0°
INP B: count input 90°
9u8d 2
Quadrature input with pulse doubling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A will be counted
9u8d 4
Quadrature input with pulse quadrupling
INP A: count input 0°
INP B: count input 90°
Each pulse edge of INP A and INP B will be counted.
4.4 Multiplying factor
Factor
010000
It can be set from 00.0001 up to 99.9999.
The decimal point is set to 4 decimal places.
„0“ is not accepted!
4.5 Dividing factor
d:0:50
010000
It can be set from 00.0001 up to 99.9999.
999999
The decimal point is set to 4 decimal places.
„0“ is not accepted!
4.6 Decimal point
dP
The decimal point defines the way of displaying the count values. It does not affect counting.
8
0 no decimal place
0.0 one decimal place
0.00 two decimal places
0.000 three decimal places
4.7 SET/RESET Mode
rESn7d
PTRnEL
manual reset via the red SET/RESET key and electrical reset via the SET/RESET input
no rES
no reset (red SET/RESET key and SET/RESET input locked)
EL rES
only electrical reset via the SET/RESET input
P18orE
only manual reset via the red SET/RESET key
4.8 SET value
SEtPt
000000
The device will be set to the set point by pressing the red
999999
SET/RESET key or activating the SET/RESET input.
SET value -199999... 999999 (number of decimal places depends on the decimal point option)
For programming the decimal point see 4.6
4.9 End of programming
EndPro
no
The programming routine is repeated once more. The values set until now can be checked and modified.
YES
The programming routine will be left and all values set will be stored as new parameters.
Afterwards the device is ready for operation.
Tachometer/Frequency meter CODIX 522
(CODIX 524: Operating mode frequency meter)
1. Description
• 6 digit frequency meter
• Red LED display, character height 8 mm
• Display range from 0 to 999 999
- Leading zeros suppression.
- Programming via two setting keys on the front side
- During programming, the display guides the user with text prompts
- Value conversion and display in 1/s or 1/min
- Optional optocoupler output
2. Inputs
INP A
Dynamic count input.
3. Optocoupler output (optional)
Active at f=0. Can be used e.g. to activate a „No operation“ lamp.
4. Programming routine
The programmable parameters of the device are described below, in the order in which they can be set. The device is fully programmed after one pass of the routine.
The first values stated correspond to the factor settings
4.1 Polarity of the inputs


npn: switching for 0 V

pnp: switching for +U_B
4.2 Switching on the 30 Hz filter

The filter provides input damping*

30 Hz filter off ( f_max )

30 Hzfilter on
4.3 Multiplying factor


It can be set from 00.0001 up to 99.9999.
The decimal point is set to 4 decimal places.

„0“ is not accepted!
4.4 Dividing factor


It can be set from 00.0001 up to 99.9999.
The decimal point is set to 4 decimal places.

„0“ is not accepted!
4.5 Decimal point

The decimal point defines the resolution in the selected measuring range 1/min or 1/sec

0 no decimal place
0.0 one decimal place
0.00 two decimal places

0.000 three decimal places
4.6 Display mode


Value conversion and display in 1/s

Value conversion and display in 1/min
4.7 Max. time to wait until „0“ is displayed
This parameter indicates, how long it takes, when measuring is active, until „0“ is displayed.


Max. time to wait 00.1 s (min. value)

Max. time to wait 99.9 s
4.8 End of programming


The programming routine is repeated once more. The values set until now can be checked and modified.

The programming routine will be left and all values set will be stored as new parameters. Afterwards the device is ready for operation.
Time meter CODIX 523
(CODIX 524: Operating mode time meter)
1. Description
- 6 digit time meter with SET/RESET function
• Red LED display, character height 8 mm
• Display range from 0 to 999 999 - Leading zeros suppression.
• Operation indicator: the decimal point of the lowest digit blinks while the count is active. - Programming via two setting keys on the front side
- During programming, the display guides the user with text prompts
• Time meter operating modes - Counting while INP B is inactive (GAtE.Lo)
- Counting while INP B is active (GatE.hi)
- Count Start/Stop with INP B edge (Inb.Inb)
- Count Start with INP A edge, count Stop with
INP B edge (InA.Inb)
- Counting ranges h; min; s; h.min.s
- Optional optocoupler output
2. Inputs
INP A
Start input (depending on the input mode chosen)
INP B
Start/Stop or gate input (depending on the input mode chosen)
SET/RESET input
Dynamic SET/RESET input. Linked in parallel to the red RESET key. Resets the counter to the predefined setting value.
3. Optocoupler output (optional)
On active counting the output alternates at a frequency of 1 Hz between active and inactive.
4. Programming routine
The programmable parameters of the device are described below, in the order in which they can be set. The device is fully programmed after one pass of the routine.
The first values stated correspond to the factor settings
4.1 Polarity of the inputs


npn: switching for 0 V

pnp: switching for +U_B
4.2 Switching on the 30 Hz filter
(INP A, INP B)


30 Hz filter off
Start/Stop inputs not damped

30 Hz filter on
Start/Stop inputs damped for use with me cha nical switches.
4.3 Input mode


Start/Stop via Inp B. counting while Inp B (Gate) not active or open

Start/Stop via Inp B. counting while Inp B (Gate) active (High level with pnp; Low level with npn)

Count Start/Stop via INP B (LOW-HIGH edge with pnp; HIGH-LOW edge with npn). Every active edge changes the counter status.

Count start via INP A, stop via INP B. (LOW-HIGH edge with pnp; HIGH-LOW edge with npn)
4.4 Operating mode


Time unit: seconds (accuracy depending on position of the decimal point*)

Time unit: minutes (accuracy depending on position of the decimal point*)

Time unit: hours (accuracy depending on position of the decimal point*)

Time units: Hours:Minutes:Seconds (decimal point setting is ignored)
*0, 0.1, 0.01, 0.001 means: time measurement in 0, 0.1, 0.01, 0.001 time units
4.5 Decimal point

The decimal point defines the resolution of the program med time unit.

0 1
0.0 1/10 (0,1)
0.00 1/100 (0,01)
0.000 1/1000 (0,001)

4.6 SET/RESET mode


manual reset via the red SET/RESET key and electrical reset via the SET/RESET input

no reset (red SET/RESET key and SET/RESET input locked)
EL rES
only electrical reset via the SET/RESET input
P180rE
only manual reset via the red SET/RESET key
4.8 SET value
SEPT
000000
The device will be set to the set point by pressing the red SET/RESET key or activating the SET/RESET input.
999999
SET value 0 ...999 999 or 99.59.59 (number of decimal places depends on the decimal point option)
4.8 End of programming
EndPro
oo
The programming routine is repeated once more. The values set until now can be checked and modified.
YES
The programming routine will be left and all values set will be stored as new parameters. Afterwards the device is ready for operation.
5. Technical data
Supply voltage
DC power supply: 10 ... 30 V DC/max. 55 mA with inverse-polarity protection
Display: 6 digits, red 7 segment LED display, height 8 mm
Data retention: EEPROM
Polarity of the inputs:
Programmable, npn or pnp for all inputs
Input resistance: appr. 5 kOhm
Count frequency CODIX 521:
| Power supply DC: | 24 V | 12 V | 10 ...30 V |
| Input level: | Standard | 5V | |
| typ. Low Level: | 2,5 V | 2,0 V | 1,0 V |
| typ. High Level: | 22,0 V | 10 V | 4,0 V |
| Fmax*: kHz | kHz | kHz | |
| CntDir | 60 20 | 8 | |
| UpDown | 25 15 | 8 | |
| Up.Up | 25 15 | 8 | |
| Quad1 | 25 15 | 8 | |
| Quad2 | 25 15 | 8 | |
| Quad4 | 15 15 | 8 | |
Count frequency CODIX 522:
Frequency measurement
Accuracy <0.1 %
Measuring principle:
< 38 Hz: period measurement
38 Hz: gating time measurement gating time 26,3 ms
| Power supply DC: | 24 V | 12 V | 10 ...30 V |
| Input level: | Standard 5V | ||
| typ. Low Level: | 2,5 V | 2,0 V | 1,0 V |
| typ. High Level: | 22,0 V | 10 V | 4,0 V |
| Fmax*: | kHz kHz | kHz | |
| Tacho | 6 | 20 | 8 |
Counting ranges CODIX 523:
Seconds 0.001 s ... 999999 s
Minutes 0.001 min ... 999999 min
Hours 0.001 h ... 999999 h
h.min.s 00 h 00 min 01 s
... 99 h 59 min 59 s
Accuracy <50 ppm
Minimum pulse length for the Reset input:
5 ms
Input sensitivity:
Standard sensitivity:
Low: 0 ... 0,2 x UB [V DC]
High: 0,6 x UB ... 30 V DC
4 ... 30 V DC level: Low: 0 ... 2 V DC
High: 4 ... 30 V DC
Pulse shape: any*, Schmitt-Trigger inputs
Optocoupler output (optional):
NPN optocoupler with open collector and open emitter; max. switching performance: 30 V DC/10 mA
Ambient temperature:
-20 ... +65 °C at 10 ... 26 V DC
-20 ... +55 °C at >26 ... 30 V DC
Storage temperature:
-25 ... +70 °C
Altitude: to 2000 m
EMC:
Noise emission EN 55 011 Class B
Noise immunity EN 61 000-6-2
Housing:
For front panel mounting: 48 x 24 mm
acc. to DIN 43700, RAL7021, dark grey
Weight: appr. 50 g
Protection: IP 65 (front)
Cleaning: The front of the units is to
be cleaned only with a soft wet (water!) cloth.
6. Terminal assignment
without optocoupler
1 10 ... 30 V DC
20V GND
3 INP A
4 INP B (Codix 522: n.c.)
5 SET/RESET (Codix 522: n.c.)
with optocoupler
1 10 ... 30 V DC
20V GND
3 INP A
4 INP B (Codix 522: n.c.)
7. Delivery includes:
1 Digital display
1 Panel mounting clip
1 Bezel for screw mounting, panel cut out 50 x 25 mm
1 Bezel for clip mounting, panel cut out 50x25 mm
1 Seal
1 Multilingual operating instructions
8. Ordering code:
6.521.01X.3X0
6.522.01X.3X0
6.523.01X.3X0
6.524.01X.3X0

Input sensitivity
0 = Standard sensitivity
A = 4 ... 30 V DC level
Output
1 = Optocoupler output
2 = No output
6.521.01X.3X0
6.522.01X.3X0
6.523.01X.3X0
6.524.01X.3X0

text_image
50 25 32±0.1 R31 Counter sinking Af3, DIN 74
6.521.01X.3X0
6.522.01X.3X0
6.523.01X.3X0
6.524.01X.3X0