Product type Pressure regulator (reducing valve)
Authorized fluids Water, oil-free compressed air, nitrogen
Maximum upstream pressure 25 bar
Downstream pressure (model A) 1.5 - 6 bar (preset to 3 bar)
Downstream pressure (models E / EF) 1.5 - 5.5 bar (preset to 3 bar)
Max. operating temperature 70 °C
Minimum pressure drop 1 bar
Connection sizes 1/2" - 2"
Delivery contents Housing with G 1/4" pressure gauge connection, threaded and female connections, valve trim with diaphragm and seat, spring cap with adjusting knob, adjustment spring
Housing material Dezincification-resistant brass
Diaphragm material Textile-reinforced NBR
Seal material NBR
Pressure gauge connection G 1/4"
Installation Horizontal, spring cap upward
Maintenance Filter cleaning, annual downstream pressure check, professional maintenance every 1 to 3 years
Spare parts Complete assembly, valve core, filter element, plug, pressure gauge, hexagonal key, connection sets
Standards DIN EN 1567 (models E/EF), PED directive

Frequently Asked Questions - D05FS HONEYWELL

What is the default downstream pressure?
The downstream pressure is preset to 3 bar for all models.
How to adjust the outlet pressure?
Close the inlet isolation valve, depressurize the outlet, close the outlet valve, loosen the slotted screw, turn the adjusting knob to the left until stop, slowly open the inlet valve, then turn the knob to the desired value. Retighten the screw and slowly open the outlet valve.
What is the maximum upstream pressure?
The maximum upstream pressure is 25 bar.
Which fluids can be used?
Water, oil-free compressed air, and nitrogen, in accordance with applicable standards.
How to clean the filter?
Close the inlet valve, depressurize the outlet, close the outlet valve, release the spring tension, unscrew the cap, remove the ring, take out the valve trim assembly, remove the filter, clean it, then reassemble in reverse order.
How often should maintenance be performed?
Check the downstream pressure once a year. A complete maintenance should be performed every 1 to 3 years by a professional.
What to do if water comes out through the spring cap?
This indicates a defective diaphragm. The valve trim assembly must be replaced.
How to calibrate the adjustment scale after disassembly?
Install a pressure gauge, close the inlet valve, depressurize, close the outlet valve, loosen the slotted screw, slowly open the inlet valve, set the pressure (e.g. 4 bar), align the scale with the mark, retighten the screw, open the outlet valve.
What is the maximum operating temperature?
The maximum operating temperature is 70 °C.
What materials are used?
Housing in dezincification-resistant brass, diaphragm in textile-reinforced NBR, seals in NBR, spring in spring steel, cap and knob in high-quality plastic.

User questions about D05FS HONEYWELL

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Pressure regulator in PDF format for free! Find your manual D05FS - HONEYWELL and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. D05FS by HONEYWELL.

USER MANUAL D05FS HONEYWELL

Keep instructions for later use!

Pressure reducing valve

Disconnecteur

Drukreduceerklep

  1. Follow the installation instructions.
  2. Use the appliance
    according to its intended use
  3. in good condition
    with due regard to safety and risk of danger.
  4. Note that the appliance is exclusively for use in the applications detailed in these installation instructions. Any other use will not be considered to comply with requirements and would invalidate the warranty.
  5. Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
  6. Immediately rectify any malfunctions which may influence safety.

2. Application

MediumWater, compressed air* and nitrogen* in consideration of valid standards (e.g. DIN EN 12502)
Inlet pressuremax. 25 bar
Outlet pressure
D05FS-... A1,5-6 bar (preset to 3 bar)
D05FS-... E
D05FS-...EF1,5-5,5 bar (proven to NF EN 1567 and preset to 3 bar)

*As part of an installation being approved according to PED requirements, this product must also be certified.

3. Technical data

Operating temperaturemax. 70°C
Minimum pressure drop1 bar
Connection size1/2" - 2"

4. Scope of delivery

The pressure reducing valve comprises:

  • Housing with pressure gauge connection G1/4"
  • With internal and external threads 12 " - 1"
  • With external threads 1 1/4" - 2"
  • Valve insert complete with diaphragm and valve seat
  • Spring bonnet with adjustment knob and setting scale
  • Adjustment spring
  • Pressure gauge not included (see accessories)

5. Assembly

5.1 Installations Guidelines

It is necessary during installation to follow the installation instructions, to comply with local requirements and to follow the codes of good practice.

Install in horizontal pipework with spring bonnet directed upwards
Installshutoffvalves
- The installation location should be protected against frost and be easily accessible - Pressure gauge can be read off easily - Simplified maintenance and cleaning
- For residential applications where maximum protection against dirt is required, install a fine filter upstream of the pressure reducing valve
- Provide a straight section of pipework of at least five times the nominal valve size after the pressure reducing valve (in accordance with DIN 1988, Part 5)

5.2 Assembly instructions

HONEYWELL D05FS - Assembly instructions - 1

When using soldering connections, do not solder the connections together with the pressure reducing valve! High temperature will irreparably damage important internal working components!

  1. Thoroughly flush pipework
  2. Install pressure reducing valve

o Note flow direction

o Install without tension or bending stresses

  1. Set outlet pressure

6. Commissioning

6.1 Setting outlet pressure

HONEYWELL D05FS - Setting outlet pressure - 1

Set outlet pressure min. 1 bar under inlet pressure.

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shutoff valve on outlet
  4. Loosen slotted screw

o Do not remove slotted screw

  1. Slacken tension in compression spring
    o Turn control handle to the left (-) until it does not move any more
  2. Slowly open shutoff valve on inlet
  3. Turn control handle until the setting scale shows the desired value
  4. Retighten slotted screw
  5. Slowly open shutoff valve on outlet

7. Maintenance

We recommend a planned maintenance contract with an installation company In accordance with DIN 1988, part 8, the following measures must be taken:

7.1 Inspection

7.1.1 Pressure reducing valve

HONEYWELL D05FS - Pressure reducing valve - 1

Interval: once a year

  1. Close shut off valve on outlet
  2. Check back pressure using a pressure meter when there is zero through-flow o If the pressure is increasing slowly, the valve may be dirty or defective. In this instance, carry out servicing and cleaning
  3. Slowly open shutoff valve on outlet

7.2 Maintenance

HONEYWELL D05FS - Maintenance - 1

Frequency: every 1-3 years (depending on local operating conditions)
To be carried out by an installation company

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shutoff valve on outlet
  4. Loosen slotted screw o Do not remove slotted screw
  5. Slacken tension in compression spring o Turn control handle to the left (-) until it does not move any more
  6. Unscrew spring bonnet o Use double ring wrench ZR06K
  7. Remove slip ring
  8. Remove valve insert with a pair of pliers
  9. Remove filter and clean
  10. Check that sealing ring, edge of nozzle and slotted ring are in good condition, and if necessary replace the entire valve insert
  11. Reassemble in reverse order
    Press in diaphragm with finger before inserting slip ring
  12. Adjust setting scale and set outlet pressure

7.3 Adjusting the setting scale

If the adjustment knob is removed, this setting is lost. A new setting can be achieved using a pressure gauge.

  1. Close shutoff valve on inlet

  2. Release pressure on outlet side (e.g. through water tap)

  3. Close shutoff valve on outlet
  4. Fit manometer
  5. Loosen slotted screw o Do not remove slotted screw
  6. Slowly open shutoff valve on inlet
  7. Set desired outlet pressure (e.g. 4 bar)
  8. Align scale (e.g. 4) in middle of viewing window
  9. Retighten slotted screw
  10. Slowly open shutoff valve on outlet

7.4 Cleaning

HONEYWELL D05FS - Cleaning - 1

Caution!

Do not use any cleaning agents containing solvents and/or alcohol to clean the plastic parts!

If nesseccary, the filter can be cleaned.

HONEYWELL D05FS - Cleaning - 2

To be carried out by an installation company or the operator.

HONEYWELL D05FS - Cleaning - 3

Detergents must not be allowed to enter the environment or the sewerage system!

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shutoff valve on outlet
  4. Slacken tension in compression spring o Turn control handle to the left (-) until it does not move any more
  5. Unscrew spring bonnet o Use double ring wrench ZR06K
  6. Remove slip ring
  7. Remove valve insert with a pair of pliers
  8. Remove filter, clean and reinsert
  9. Reassemble in reverse order

HONEYWELL D05FS - Cleaning - 4

Press in diaphragm with finger before inserting slip ring

  1. Adjust setting scale and set outlet pressure

8. Disposal

  • Dezincification resistant brass housing
  • High-quality synthetic material valve insert
  • High-quality synthetic material spring bonnet with adjustment knob and setting scale
    Spring steel adjustment spring
  • Fibre-reinforced NBR diaphragm
    NBR seals

HONEYWELL D05FS - Disposal - 1

Observe the local requirements regarding correct waste recycling/disposal!

  1. Troubleshooting

VST06-B Connection set

ProblemCauseRemedy
Beating soundsPressure reducing valve is too largeCall our Technical Customer Services
Water is escaping from the spring bonnetDiaphragm in valve insert is faultyReplace valve insert
Too little or no water pressure1109Shutoff valves up- or downstream of the pressure reducing valve are not fully openOpen the shutoff valves fully
Pressure reducing valve is not set to the desired outlet pressureSet outlet pressure
Filter in pressure reducing valve is contaminatedClean or replace filter
Pressure reducing valve is not fitted in flow directionFit pressure reducing valve in flow direction (note direction of arrow on housing)
The outlet pressure set does not remain constantFilter in pressure reducing valve is contaminated or wornClean or replace filter
Valve insert, sealing ring or edge of nozzle is contaminated or wornReplace valve insert
Rising pressure on outlet (e.g. in boiler)Check check valve, safety group etc.
  1. Spare Parts

Pressure Reducing Valve D05FS, from 2007 onwards

No.Description Dimension Part No.

1 Spring bonnet 1 / 2^ - 1^ 0901515 complete with 114'' - 2'' 0903890 setting scale
2 Valve insert 1/2" - 1" D05FA-1/2B complete (without 114'' - 2'' D05FA-11/4B filter)
3 Replacement filter 1 / 2^ - 2^ ESD05FS insert
4 Blanking plug with 1 / 2'' - 2'' S06K-1/4 O-ring R1/4" (5 pcs.)

  1. Accessories

M38K Pressure gauge Housing diameter 50~mm below connection thread G1/4". Ranges: 0 - 4, 0 - 10, 0 - 16 or 0 - 25 bar. Please indicate upper value of pressure range when ordering

ZR06K Double ring wrench

For removal of spring bonnet

VST06-A Connection set

Threaded connections

Solder connections

Automation and Control Solutions

Honeywell GmbH

Hardhofweg

D-74821 Mosbach

Phone: (49) 6261 810

Fax: (49) 6261 81309

http://europe.hbc.honeywell.com

www.honeywell.com

Manufactured for and on behalf of the

Environmental and Combustion Controls Division of

16, Switzerland by its Authorised Representative Honeywell GmbH

MU1H-1034GE23 R1109

Subject to change

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HONEYWELL

Model : D05FS

Category : Pressure regulator