Grundfos UPS 15-35 SUC/TLC - Water pump

UPS 15-35 SUC/TLC - Water pump Grundfos - Free user manual and instructions

Find the device manual for free UPS 15-35 SUC/TLC Grundfos in PDF.

📄 74 pages English EN Download 💬 AI Question
Notice Grundfos UPS 15-35 SUC/TLC - page 3
View the manual : Français FR English EN Español ES
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about UPS 15-35 SUC/TLC Grundfos

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Water pump in PDF format for free! Find your manual UPS 15-35 SUC/TLC - Grundfos and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. UPS 15-35 SUC/TLC by Grundfos.

USER MANUAL UPS 15-35 SUC/TLC Grundfos

Installation and operating instructions

Grundfos UPS 15-35 SUC/TLC - 1

English (US)

Installation and operating instructions 3

(AR)

36

Français (CA)

Original installation and operating instructions

CONTENTS

Page

  1. Limited warranty 3
  2. Introduction 4
    2.1 Safety warning 4

3.Pre-installation checklist 4

3.1 Confirm you have the correct pump 4
3.2 Check the condition of the pump 4
3.3 Verify electrical requirements 4
3.4 Pumped liquid requirements 5

4.Installation procedures 6

4.1 Electrical preparation 6
4.2 Piping considerations 6
4.3 Connect the pump 7
4.4 Electrical connection 7

  1. Starting the pump 9
    5.1 Vent the piping system 9
    5.2 Check the direction of shaft rotation 9
    5.3 Speed selection 10

6.Troubleshooting 12

6.1 Fault finding chart 12
6.2 Preliminary checks 13
6.3 Current measurement 14
6.4 Insulation resistance (lead-to-ground) 14
6.5 Winding resistance (line-to-line) 14
6.6 Winding resistance chart 16

  1. Replacing components 18

7.1 Removing the pump head 18
7.2 Fitting the pump head 18
7.3 Replacing the terminal box or capacitor 19
8.Disposal 19

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.

This booklet should be left with the owner of the pump for future reference and information regarding its operation.

1. Limited warranty

Products manufactured by GRUNDFOS PUMPS CORPORATION (Grundfos) are warranted to the original user only to be free of defects in material and workmanship for a period of

18 months from date of installation, but not more than 24 months from date of manufacture.

Grundfos' liability under this warranty shall be limited to repairing or replacing at

Grundfos' option, without charge, F.O.B.

Grundfos' factory or authorized service station, any product of Grundfos' manufacture.

Grundfos will not be liable for any costs of removal, installation, transportation, or any other charges which may arise in connection with a warranty claim. Products which are sold but not manufactured by Grundfos are subject to the warranty provided by the manufacturer of said products and not by Grundfos' warranty. Grundfos will not be liable for damage or wear to products caused by abnormal operating conditions, accident, abuse, misuse, unauthorized alteration or repair, or if the product was not installed in accordance with Grundfos' printed installation and operating instructions.

To obtain service under this warranty, the defective product must be returned to the distributor or dealer of Grundfos' products from which it was purchased together with proof of purchase and installation date, failure date, and supporting installation data. Unless otherwise provided, the distributor or dealer will contact Grundfos or an authorized service station for instructions.

Any defective product to be returned to Grundfos or a service station must be sent freight prepaid; documentation supporting the warranty claim and/or a Return Material Authorization must be included if so instructed.

GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL

DAMAGES, LOSSES, OR EXPENSES ARISING FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE NO EXPRESS OR IMPLIED WARRANTYES, INCLUDING MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, WHICH EXTEND BEYOND THOSE WARRANTY DESCRIBED OR REFERRED TO ABOVE.

Some jurisdictions do not allow the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last. Therefore, the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from jurisdiction to jurisdiction.

2. Introduction

2.1 Safety warning

2.1.1 Read this booklet

This booklet is designed to help a certified installer install, begin operation of and troubleshoot the Grundfos UPS pumps. The booklet should be left with the owner of the pump for future reference and information regarding its operation. Should the owner experience any problems with the pump, a certified professional should be contacted.

2.1.2 Electrical work

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

All electrical work should be performed by a qualified electrician in accordance with the latest edition of the National Electrical Code, local codes and regulations.

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

A faulty motor or wiring can cause electrical shock that could be fatal, whether touched directly or conducted through standing water. For this reason, proper grounding of the pump to the power supply's grounding terminal is required for safe installation and operation.

In all installations, the above-ground metal plumbing should be connected to the power supply ground as described in Article 250-80 of the National Electrical Code.

3. Pre-installation checklist

3.1 Confirm you have the correct pump

  • Read the pump nameplate to make sure it is the one you ordered.
  • Compare the pump's nameplate data and its performance curve (for head, gpm, etc.) with the application in which you plan to install it.
  • Will the pump do what you expect it to do?

3.2 Check the condition of the pump

The shipping carton your pump came in is specially designed around your pump during production to prevent damage.

As a precaution, it should remain in the carton until you are ready to install it. At that point, look at the pump and examine it for any damage that may have occurred during shipping.

Examine any other parts of the shipment as well for any visible damage.

3.3 Verify electrical requirements

Verification of the electrical supply should be made to be certain the voltage, phase and frequency match that of the pump motor.

The proper operating voltage and other electrical information can be found on the pump nameplate.

These motors are designed to run on + / - 10% of the nameplate-rated voltage.

Wiring connection diagrams can be found inside the terminal box cover and later in these Installation and Operating Instructions. If voltage variations are larger than + / - 10% do not operate the pump.

3.4 Pumped liquid requirements

Caution

The UPS pump is intended for use with water only.

The pump can be used to circulate:

  • Potable hot water
    Water for hydronic heating
    Water/glycol mixtures up to 50/50
    Cooling water

In domestic hot-water systems it is advisable to use bronze pumps (UPS model) only for water with a degree of hardness lower than 14 grains per gallon of hardness. For water with a higher degree of hardness, a direct-coupled Grundfos TP pump is recommended.

If the pump is installed in a heating system, the water should meet the requirements of accepted standards on water quality in heating systems.

In water/glycol mixtures, in order to prevent the glycol from degrading, temperatures above those for which the fluid is rated should be avoided and time spent at high temperatures minimized.

It is also important that the system is cleaned and flushed prior to the installation of the glycol mixture.

In order to avoid problems with corrosion or precipitation, the glycol fluids should be checked and maintained regularly. If further dilution of the supplied glycol is required, follow the requirements of the supplier of the glycol.

Grundfos UPS 15-35 SUC/TLC - Pumped liquid requirements - 1

WARNING

Glycol with the trade name DEXCOOL can harm the pump.

DEXCOOL® is a registered trademark of General Motors Corporation, used under license by Texaco Lubricants NA.

The pump is lubricated and cooled by the liquid being pumped. Therefore, the pumped liquid must always be allowed to circulate through the pump. Extended periods without circulation will cause premature wear to the bearings and excessive motor heat. The pumped liquid must also meet the following requirements:

Minimum pump inlet pressure (during operation)

UPS modelAt these liquid temperatures
167 °F/75 °C 194 °F/90 °C 230 °F/110 °C
[psi] hf [psi] hf [psi] hf
32-40/4 0.7 1.6 2.2 5.1 21.0 48.5
32-80/2 0.7 1.6 5.1 11.8 23.9 55.2
32-160/2 11.6 26.8 16.0 37.0 34.1 78.8
40-40/4 0.7 1.6 4.4 10.2 23.2 53.6
40-80/4 0.7 1.6 1.5 3.5 18.1 41.8
40-80/2 6.5 15.0 10.9 25.2 29.0 67.0
40-160/2 5.1 11.8 9.4 21.7 27.6 63.8
40-240/2 11.6 26.8 16.0 37.0 34.1 78.8
50-40/4 0.7 1.6 2.9 6.7 21.8 50.4
50-80/4 0.7 1.6 4.4 10.2 23.2 53.6
50-80/2 4.4 10.2 8.7 20.1 26.8 61.9
50-160/2 11.6 26.8 16.0 37.0 34.1 78.8
50-240/2 10.2 23.6 14.5 33.5 32.6 75.3
53-55/57 4.4 10.2 8.7 20.1 26.8 61.9
75-6911.6 26.8 1637 34.1 78.8
80-40/4 11.6 26.8 16.0 37.0 34.1 78.8
80-80/4 14.5 33.5 18.9 43.7 37.0 85.5
80-160/2 21.8 50.4 26.1 60.3 43.5100.5
100-40/427.6 63.8 31.9 73.7 50.0115.5

Liquid temperature range

Continuously:

14^ (-10^) up to 230^ (110^) .

Intermittent:

< 284 °F (140 °C) for short periods of time.

Domestic hot water:

< 140 °F (60 °C).

4. Installation procedures

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

Never make any connections in the pump terminal box unless the electrical supply has been switched off.

4.1 Electrical preparation

Terminal box position

At the bottom of the stator, closest to the pump housing, there are eight drain holes to allow condensed water to escape. The drain holes shall not be blocked. The drain holes must point downwards. The terminal box must therefore point upwards in one of the positions shown in fig. 1. The following terminal box positions apply whether the piping is mounted vertically or horizontally.

Grundfos UPS 15-35 SUC/TLC - Terminal box position - 1

Grundfos UPS 15-35 SUC/TLC - Terminal box position - 2

Grundfos UPS 15-35 SUC/TLC - Terminal box position - 3
TM03 7296 4706
Fig. 1 Possible terminal box positions

Rotating the terminal box

To change the position of the terminal box, follow these steps:

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

If the pump is already installed in the system, the system must be drained or the isolation valves on both sides of the pump must be closed before the allen-head screws are removed as the pumped liquid may be scalding hot and/or under pressure.

Do not start the pump until the system has been filled with liquid and vented.

  1. Remove the four allen-head screws holding the pump head onto the pump housing.
  2. Carefully lift the pump head and rotate it so the terminal box is in the desired position. DO NOT locate the terminal box beneath the pump. Make sure the O-ring is properly seated in the pump housing.
  3. Replace the pump head onto the pump housing.
  4. Tighten the allen-head screws evenly. Torque:

8 mm: 15 ft lbs

10 mm: 25 ft lbs.

  1. Check to make sure the rotor turns freely. Do this by removing the vent plug in the middle of the pump nameplate. Insert a medium size flat-blade screwdriver into the slot at the exposed end of the shaft. Gently turn the shaft. If it does not turn easily, repeat steps 1 to 4 above.
  2. The position of the nameplate can be changed by easing the outer edge of the plate at the cutout with a screwdriver. Turn the nameplate to the required position and push into place.
  3. Refer to page 18 and page 19 for additional instructions.

4.2 Piping considerations

Thoroughly clean and flush all dirt and sediment from the system before attempting to install the pump.

Location in the piping line

The pump should never be located at the lowest point of the piping system, where dirt and sediment collect. Nor should it be located at the highest point of the piping system, where air accumulates.

Mounting positions

The arrows on the flanges of the pump indicate the direction of water flow. Although the UPS may be installed in either vertical or horizontal piping, the motor shaft must always remain horizontal, as shown in fig. 1 and fig. 2.

Grundfos UPS 15-35 SUC/TLC - Mounting positions - 1
TM03 7290 4706
Fig. 2 Direction of water flow through the pump

Grundfos UPS 15-35 SUC/TLC - Mounting positions - 2

Pumps installed outdoors must be protected by a ventilated, watertight cover to keep out moisture and dirt.

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

The pump must be positioned so that someone cannot accidentally come into contact with the hot surfaces of the pump.

4.3 Connect the pump

Install the pump into the piping system.

Grundfos recommends that pressure gauges be installed in the inlet and discharge flanges or pipes to check pump and system performance.

4.4 Electrical connection

The electrical connection and protection should be carried out in accordance with the latest edition of the National Electrical Code, local codes and regulations by a qualified electrician.

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

Never make any connections in the pump terminal box unless the electrical supply has been switched off.

The pump must be grounded.

The pump must be connected to an external main power switch.

The operating voltage and frequency are marked on the pump nameplate. Make sure that the motor is suitable for the electrical supply it is being installed to.

The pump should be grounded to protect against indirect contact and a ground fault interrupter can be used as extra protection.

Multi-speed pump (single-phase)

All single-phase pumps are equipped with built-in, automatic resetting, thermal overload protection. The pump is protected at all three speeds.

Multi-speed pump (three-phase)

The pump must be connected to the electrical supply via an external contactor. The contactor must be connected to the built-in thermal overload switch terminals T1 and T2 (3 x 208-230 V) or P1 and P2 (3 x 460 V and 575 V) to protect the pump against overloading at all three speeds.

OR: If the pump is protected by means of a motor starter, the starter must be set to the current consumption of the pump at the selected speed. The motor starter setting must be changed every time the pump speed is changed. The current consumption at the individual speeds is stated on the pump nameplate.

Figures 4, 6, 7, 9, and 10 on the next pages show the possible connections.

4.4.1 UPS 1 x 115 V and 1 x 230 V terminal box

Grundfos UPS 15-35 SUC/TLC - UPS 1 x 115 V and 1 x 230 V terminal box - 1
TM03 7744 4806TM03 7743 4806
Fig. 3 UPS 1 × 115V and 1 × 230V terminal box

All UPS single-phase pumps come with a protection module and a speed switch as shown in fig. 3. All pumps are equipped with built-in, automatic resetting, thermal overload protection. The pump is protected at all three speeds.

Wiring diagrams

Figure 4 shows the electrical connections for a single-phase pump with protection module.

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 1

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 2
Fig. 4 1 x 115 V and 1 x 230 V supply

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 3

Provide electrical disconnect and current protection as per local electrical codes.

K = External contactor sized to FL and LR pump current.

4.4.2 UPS 3 x 208-230 V terminal box

Grundfos UPS 15-35 SUC/TLC - UPS 3 x 208-230 V terminal box - 1
Fig. 5 UPS 3 × 208 - 230V terminal box

All UPS pumps with three-phase x 208-230 V come with a standard module and a speed switch as shown in fig. 5. All pumps are equipped with an internal thermal overload switch (terminals T1 and T2, to be connected to an external contactor) to protect the pump at all three speeds.

Wiring diagrams

Figure 6 shows the electrical connections when using an external changeover contact (safety circuit) for start/stop push button station.

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 1
TM03 7892 5106
Fig. 6 External changeover contact

Auxiliary contacts rated for supply voltage.

Figure 7 shows the electrical connections when using external impulse contacts (momentary contacts) for start/stop push button station.

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 2
TM03 7740 4806
Fig. 7 External impulse contacts

4.4.3 UPS 3 x 460 V and 575 V terminal box

Grundfos UPS 15-35 SUC/TLC - UPS 3 x 460 V and 575 V terminal box - 1
Fig. 8 UPS 3 x 460 V and 575 V terminal box

All UPS pumps with three-phase x 460 V and 575 V terminal boxes (fig. 8) come with a special two-speed terminal box. The speed is changed by the orientation of the jumpers as shown on page 11. All pumps are equipped with an internal thermal overload switch (terminals P1 and P2) to be connected to external contactor.

Wiring diagrams

Figure 9 shows the electrical connections when using an external changeover contact (safety circuit) for start/stop push button station.

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 1
TM03 7738 5106
Fig. 9 External changeover contact

Auxiliary contacts rated for supply voltage.

Grundfos UPS 15-35 SUC/TLC - Wiring diagrams - 2
Figure 10 shows the electrical connections when using external impulse contacts (momentary contacts) for start/stop push button station.
Fig. 10 External impulse contacts

TM03 7737 4806

5. Starting the pump

5.1 Vent the piping system

After the pump has been installed and the electrical connections made, the piping system must be vented.

Caut

Never operate the pump dry - the system must first be filled with liquid and vented.

Not

Do not vent the piping system through the pump.

Instead, follow these steps:

  1. Fill and pressurize the system with liquid, and vent all trapped air from the piping by suitable means.
  2. If any isolation valves are used, make sure they are OPEN.

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

If the vent screw is to be loosened, care should be taken to ensure that the escaping scalding hot liquid does not cause personal injury or damage to components (see fig. 12).

5.2 Check the direction of shaft rotation

Applies to 460 V and 575 V two-speed models only

(The direction of rotation of three-speed pumps is checked by means of the fault finding chart, page 12 and page 13).

  1. Make sure that the power is OFF.
  2. Unscrew and remove the vent plug located at the center of the nameplate.
  3. Insert a small, flat-blade screwdriver into the slot in the end of the motor shaft (see fig. 12). Rotate the shaft with the screwdriver to make sure it does so freely.
  4. Bump the pump and watch to see which direction the shaft rotates. The shaft must rotate in the counterclockwise direction as shown on the nameplate (see fig. 11).
  5. If the pump shaft is rotating incorrectly, disconnect the power and interchange any two power leads in the terminal box.
  6. Check once again for proper counterclockwise rotation. When it is rotating correctly, replace the vent plug.

Grundfos UPS 15-35 SUC/TLC - Applies to 460 V and 575 V two-speed models only - 1
Fig. 11 Vent plug and direction of rotation

Grundfos UPS 15-35 SUC/TLC - Applies to 460 V and 575 V two-speed models only - 2
Fig. 12 Removing the vent plug

5.3 Speed selection

5.3.1 Three-speed pumps, all models except 3 × 460 ~V and 575 ~V

The speed switch in the terminal box can be turned to three positions. The speed in the three positions appears in the table below (also see fig. 13).

Switch positionSpeed in % of maximum speed
Single-phase pumpsThree-phase pumps
1 approx. 60 % approx. 70 %
2 approx. 80 % approx. 85 %
3 100 % 100 %

Changing to lower speeds offers considerable reduction in energy consumption and less noise in the system.

Grundfos UPS 15-35 SUC/TLC - Three-speed pumps, all models except 3 × 460 ~V and 575 ~V - 1
Fig. 13 Pump performance at speed settings

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

Never make any connections in the pump terminal box unless the electrical supply has been switched off.

Change the pump performance as follows:

  1. Switch off the electrical supply to the pump at the main circuit breaker.
    The green indicator light in the terminal box must be off.
  2. Remove the terminal box cover by loosening the four screws in the cover.
  3. Pull out the speed switch module and re-insert it so that the desired speed is visible through the window in the terminal box (see fig. 14).

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 1
SPEED

SPEED

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 2
1

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 3
2

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 4
SPEED
3
TMM 77354806
Fig. 14 Speed switch module

When changing to and from speed 1, the cover of the speed switch module must be removed and fitted on the other side of the switch.

  1. Fit the terminal box cover back onto the terminal box and tighten the four screws in the cover.
  2. Switch on the electrical supply. Check that the green indicator light is permanently on or flashing.

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 5

The speed switch module must never be used as an on/off switch.

5.3.2 Two-speed pumps, 3 × 460V and 575V

The speed setting in the terminal box can be changed to two positions. The speed in the two positions appears in the table below (also see fig. 13 on page 10).

Speed step Speed in % of max. speed
1 approx. 75 %
2 100 %

Grundfos UPS 15-35 SUC/TLC - Two-speed pumps, 3 × 460V and 575V - 1

WARNING

Never make any connections in the pump terminal box unless the electrical supply has been switched off.

Change the pump performance as follows:

The speed is changed by the position of the jumpers in the terminals. The jumpers are fitted according to:

  • figure 15 for speed 1 - low speed
  • figure 16 for speed 2 - high speed.

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 1

TM03 7734 4806

Fig. 15 Speed 1 (low speed)

Grundfos UPS 15-35 SUC/TLC - Change the pump performance as follows: - 2
Fig. 16 Speed 2 (high speed)

TM03 7733 4806

6. Troubleshooting

6.1 Fault finding chart

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

Before removing the terminal box cover, make sure that the electrical supply has been switched off and that it cannot be accidentally switched on.

The pumped liquid may be scalding hot and under high pressure. Before any removal or dismantling of the pump, the system must be drained or the isolation valves on both sides of the pump must be closed.

Fault Cause Remedy

1. The pump does not run. None of the indicator lights are on.a) One fuse in the installation is blown.Replace the fuse.
b) External circuit breaker is switched off.Switch the circuit breaker on.
c) Current-/voltage-operated ground fault interrupter has tripped.Repair the insulation defects and reset the interrupter.
d) The pump's internal thermal overload switch has cut out (standard module only).Check that the liquid temperature falls within the specified range. With external on/off changeover contact: The pump will restart automatically when it has cooled to normal temperature. With external on/off impulse contacts: The pump can be restarted when it has cooled to normal temperature.
2. The pump does not run. The green indicator light is on.a) Rotor blocked, but the pump hasn't been cut out by the thermal overload switch.Switch off the electrical supply and clean/repair the pump.
b) The speed switch module has not been fitted.Switch off the electrical supply at the external circuit breaker and fit the speed switch module into position.
3. Three-phase pumps only: The pump is running. The red and green indicator lights are on.a) The pump is running with the wrong direction of rotation.Switch off the electrical supply at the external circuit breaker and interchange any two phases (leads) in the pump terminal box.
4. Noise in the system. The green indicator light is on.a) Air in the system. Vent the system.
b) The pump flow is too high. Reduce the pump performance.
c) The pressure is too high. Reduce the pump performance.
5. Noise in the pump. The green indicator light is on.a) Air in the pump. Vent the pump.
b) The inlet pressure is too low.Increase the inlet pressure and/or check the air volume in the expansion tank (if installed).
6. Insufficient heat in some places in the heating system.a) The pump performance is too low.Increase the pump performance, if possible, or replace the pump with a pump with higher flow.
Fault Cause Remedy
7. Single-phase pumps with protection module (only). The pump does not run. The red indicator light is on. The green indicator light is off.a) The pump has been cut out by the thermal overload switch due to high liquid temperature or blocked rotor.Check that the liquid temperature falls within the specified range. The pump will restart automatically when it has cooled to normal temperature. NOTE: If the thermal overload switch has cut out the pump three times within a short period, the pump must be restarted manually by switching off the electrical supply.
b) The speed switch module has not been fitted.Switch off the electrical supply by means of the external mains switch and fit the speed switch module.

6.2 Preliminary checks

Supply voltage

To check the voltage being supplied to the motor, use a voltmeter.

WARNING

Grundfos UPS 15-35 SUC/TLC - WARNING - 1

Be careful, since power is still being supplied to the pump. Do not touch the voltmeter leads together while they are in contact with the power lines.

Evaluation

When the motor is under load, the voltage should be within 10% (+ or -) of the nameplate voltage. Any variation larger than this may indicate a poor electrical supply and can cause damage to the motor windings. The motor should not be operated under these conditions. Contact your power supplier to correct the problem or change the motor to one requiring the voltage you are receiving.

Single-phase motors Three-phase motors

Touch one voltmeter lead to each of the lines supplying power to the pump: • L and N for 115 V circuits • L1 and L2 for 230 V circuits.Touch a voltmeter lead to: • Power leads L1 and L2 • Power leads L2 and L3 • Power leads L3 and L1. These tests should give a reading of full line voltage.

Grundfos UPS 15-35 SUC/TLC - Evaluation - 1
Fig. 17 Checking single-phase power

6.3 Current measurement

To check the current, use an ammeter.

To do so, follow these steps:

  1. Make sure the pump is operating.
  2. Set the ammeter to the proper scale.
  3. Place the tongs of the ammeter around the leg to be measured.
  4. Compare the results with the amp draw information on the motor nameplate.
  5. Repeat for the other legs.

Evaluation

If the current draw exceeds the listed nameplate amps, or if the current imbalance is greater than 5% between each leg on three-phase units, then check the following:

The voltage supplied to the pump may be too high or too low.
The contacts on the motor starter may be burned.
The terminals in the starter or terminal box may be loose.
- There may be a winding defect. Check the winding and insulation resistance.
- The motor windings may be shorted or grounded.
The pump may be damaged in some way and may be causing a motor overload.
- A voltage supply or balance problem may exist.

Grundfos UPS 15-35 SUC/TLC - Evaluation - 1
Fig. 18 Current measurement

6.4 Insulation resistance (lead-to-ground)

To check the insulation resistance (lead-to-ground) of the motor and leads, a megohmmeter is required.

To do so, follow these steps:

  1. Turn the POWER OFF.
  2. Disconnect all electrical leads to the motor.
  3. Set the scale selector on the megohmmeter to R x 100K, touch its leads together, and adjust the indicator to zero.
  4. Touch the leads of the megohmmeter individually to each of the motor leads and to ground (i.e. L1 to ground; L2 to ground, etc.).

Grundfos UPS 15-35 SUC/TLC - Insulation resistance (lead-to-ground) - 1
Fig. 19 Insulation resistance measurement

Evaluation

The resistance values for new motors must exceed 1,000,000 ohms. If they do not, replace the motor.

6.5 Winding resistance (line-to-line)

To check the winding resistance of the motor windings, a megohmmeter is required.

To do so, follow these steps:

  1. Turn the POWER OFF.
  2. Disconnect all electrical leads to the motor.
  3. Set the scale selector on the megohmmeter to R × 1 , touch its leads together, and adjust the indicator to zero.
  4. Using the charts below for reference, touch the leads of the megohmmeter to the appropriate pair of connectors. Check all pairs that are present and write down and label (RA, RS1, RS2, R) all readings.
  5. Compare your readings to the matching model, phase and voltage on the chart on page 16 and page 17.

Evaluation

The resistance values must fall within the tolerances listed on page 16 or page 17. If they do not, replace the motor.

Internal wiring UPS

Terminal plug in stator

Grundfos UPS 15-35 SUC/TLC - Internal wiring UPS - 1

Single-phase Three-phase 208-230 V
Grundfos UPS 15-35 SUC/TLC - Internal wiring UPS - 2
RA:6-1 or 6-1,7-2
RS1: 12-8 or 12-8, 14-9
RS2:4-10 or 4-10,5-11

RA: Main winding

RS_1 : Auxiliary winding

RS2: Auxiliary winding

Grundfos UPS 15-35 SUC/TLC - Internal wiring UPS - 3
R: 5-9 or 5-9, 7-14
R: 11-12 or 11-12, 1-10
R: 4-6 or 4-6, 8-2

Internal wiring UPS

Terminal plug in stator

Grundfos UPS 15-35 SUC/TLC - Internal wiring UPS - 1

Three-phase 460/575 V

Grundfos UPS 15-35 SUC/TLC - Internal wiring UPS - 2

Pump type Voltage[Ω] 68 °F - 122 °F (20 °C - 50 °C)
RRA 1RRS2
UPS 32-40/41 x 115 V 17.8 - 23.2 3.95 - 5.20 9.40 - 12.4
1 x 230 V 70.0 - 91.5 17.0 - 22.2 39.5 - 52.0
3 x 208-230 V 180 - 236
3 x 460 V 360 - 470
3 x 575 V 575 - 750
UPS 32-80/21 x 115 V 9.55 - 12.6 3.05 - 4.00 6.70 - 8.80
1 x 230 V 19.4 - 25.5 5.45 - 7.10 12.6 - 16.4
3 x 208-230 V 44.0 - 57.5
3 x 460 V 83.5 - 110
3 x 575 V 132 - 174
UPS 32-160/21 x 115 V 4.15 - 5.45 1.20 - 1.56 2.65 - 3.50
1 x 230 V 8.30 - 10.8 2.20 - 2.90 5.05 - 6.65
3 x 208-230 V 26.0 - 34.0
3 x 460 V 53.5 - 70.0
3 x 575 V 84.5 - 110
UPS 40-40/41 x 115 V 11.4 - 15.0 2.95 - 3.85 5.60 - 7.35
1 x 230 V 50.5 - 66.5 14.0 - 18.4 25.5 - 34.0
3 x 208-230 V 118 - 154
3 x 460 V 234 - 310
3 x 575 V 360 - 475
UPS 40-80/21 x 115 V 5.60 - 7.35 1.84 - 2.42 4.50 - 5.90
1 x 230 V 11.0 - 14.4 3.95 - 5.20 8.55 - 11.2
3 x 208-230 V 32.0 - 42.0
3 x 460 V 64.0 - 84.0
3 x 575 V 102 - 132
UPS 40-80/41 x 115 V 4.15 - 5.45 1.94 - 2.55 3.30 - 4.35
1 x 230 V 8.10 - 10.6 3.05 - 4.00 4.60 - 6.05
3 x 208-230 V 46.5 - 61.0
3 x 460 V 90.5 - 118
3 x 575 V 164 - 216
UPS 40-160/21 x 115 V 2.85 - 3.75 1.10 - 1.44 1.94 - 2.55
1 x 230 V 5.60 - 7.35 2.02 - 2.66 3.75 - 4.95
3 x 208-230 V 22.8 - 30.0
3 x 460 V 45.5 - 59.5
3 x 575 V 72.0 - 95.0
UPS 40-240/21 x 230 V 6.80 - 8.95 2.02 - 2.65 3.70 - 4.85
3 x 208-230 V 11.0 - 14.4
3 x 460 V 22.0 - 29.0
3 x 575 V 35.0 - 45.5

s

Pump type Voltage[Ω] 68 °F - 122 °F (20 °C - 50 °C)
RRA 1RRS2
UPS 50-40/41 x 115 V 6.55 - 8.55 2.12 - 2.80 4.30 - 5.65
1 x 230 V 25.0 - 33.0 8.30 - 10.8 15.0 - 19.8
3 x 208-230 V 57.5 - 75.0
3 x 460 V 114 - 148
3 x 575 V 184 - 242
UPS 50-80/21 x 115 V 4.15 - 5.45 1.20 - 1.56 2.65 - 3.50
1 x 230 V 8.30 - 10.80 2.20 - 2.90 5.05 - 6.65
3 x 208-230 V 26.0 - 34.0
3 x 460 V 33.5 - 70.0
3 x 575 V 84.5 - 110
UPS 50-80/41 x 115 V 2.75 - 3.60 1.74 - 2.30 2.85 - 3.75
1 x 230 V 5.50 - 7.25 2.65 - 3.50 4.95 - 6.50
3 x 208-230 V 37.0 - 49.0
3 x 460 V 79.0 - 104
3 x 575 V 120 - 156
UPS 50-160/21 x 230 V 6.80 - 8.95 2.02 - 2.65 3.70 - 4.85
3 x 208-230 V 12.4 - 16.2
3 x 460 V 24.2 - 31.5
3 x 575 V 37.5 - 49.5
UPS 50-240/23 x 208-230 V 7.80 - 10.2
3 x 460 V 15.6 - 20.6
3 x 575 V 25.0 - 33.0
UPS 53-55/571 x 115 V 4.15 - 5.45 1.20 - 1.56 2.65 - 3.50
1 x 230 V 8.30 - 10.80 2.20 - 2.90 5.05 - 6.65
3 × 208-230 V 26.0 - 34.0
3 x 460 V 33.5 - 70.0
3 x 575 V 84.5 - 110
UPS 75-691 x 230 V 6.80 - 8.95 2.02 - 2.65 3.70 - 4.85
3 x 208-230 V 12.4 - 16.2
3 x 460 V 24.2 - 31.5
3 x 575 V 37.5 - 49.5
UPS 80-40/43 x 208-230 V 46.5 - 61.0
3 x 460 V 90.5 - 118
3 x 575 V 164 - 216
UPS 80-80/4 3 x 208-230 V 23.6 - 31.0
UPS 80 -160/23 x 208-230 V 7.80 - 10.2
3 x 460 V 15.6 - 20.6
3 x 575 V 25.0 - 33.0
UPS 100-40/43 x 208-230 V 27.5 - 36.0
3 x 460 V 54.5 - 71.5
3 x 575 V 86.0 - 114

7. Replacing components

7.1 Removing the pump head

  1. Disconnect or TURN OFF the power supply.
  2. Close any isolation valves on either side of the pump to avoid draining the system of liquid.
  3. Disconnect the electrical leads from the terminal box.
  4. Disconnect and remove the conduit from the terminal box.
  5. Loosen and remove the four allen-head screws (8 or 10mm ) which connect the pump head housing to the pump housing.
  6. Remove the pump head from the pump housing.
  7. Clean the machined surfaces in the pump housing of any foreign material.

Grundfos UPS 15-35 SUC/TLC - Removing the pump head - 1
Fig. 20 Removing and fitting the pump head

7.2 Fitting the pump head

  1. Carefully remove the new pump head assembly from its packaging. Separate the impeller/rotor assembly from the new pump head.
  2. While holding the thrust bearing, carefully place the impeller/rotor assembly into the pump housing. The bearing plate should fit snugly into the lowest machined surface in the pump housing.
  3. Make sure that the impeller/rotor assembly can rotate freely.
  4. Place the O-ring over the rotor and locate it into the inner diameter of the pump housing.
  5. Carefully place the pump head housing over the rotor and rotate it so the terminal box is in the position you wish, see section 4.1 under Terminal box position.

  6. Make sure the pump head housing is properly seated on the pump housing. Do not force the two together - if there is binding, disassemble them and repeat steps 2 to 6. Tighten the allen-head screws evenly to secure the pump head. Torque: 8 mm: 15 ft lb 10 mm: 25 ft lb.

  7. Check to make sure the motor shaft turns freely, as explained in section 4.1 under Rotating the terminal box.

7.3 Replacing the terminal box or capacitor

If the terminal box is replaced, make certain the electrical information listed on the new box matches the information listed on the old box, and that it is compatible with the pump and incoming electrical supply.

For all terminal boxes, it is very important to tightly secure the frame grounding screw through the terminal box, so that a proper connection between the terminal box and motor is made.

Grundfos UPS 15-35 SUC/TLC - Replacing the terminal box or capacitor - 1
Fig. 21 Terminal box

All1. Before replacing the terminal box or capacitor, make sure the power is OFF.
2. Remove the terminal box cover by completely loosening all four torx/standard screws.
3. Remove the speed switch (noting its position) by pulling firmly and evenly on both sides of it. (Not for 460/575 V).
Capacitora.4. Capacitor replacement, single-phase pumps only: Disconnect the two connector clips from the capacitor and unscrew the complete plastic strain relief nut. Remove capacitor wire and strain relief.
a.5. Screw in new complete strain relief nut and connect new clip connectors. Pull excess sheathed cable out of terminal box, being sure to leave at least 1/8" of sheath inside of terminal box.
Terminal boxb.4. Terminal box replacement: Disconnect all wiring, remove the three phillips-head screws holding the terminal box in place and remove the terminal box by pulling firmly and evenly on both sides.
b.5. Check that the clear rubber gasket is in place around the terminal box connector stem, carefully press the terminal box into the stator socket, replace the three phillips-head terminal box screws and replace wiring.
All6. Replace the speed switch to its proper position, making sure to push it all the way in. (Not for 460/575 V).
7. Replace the terminal box cover and tighten all four torx/standard screws.
8. Switch on electrical power supply. The pump is now ready for operation.

8. Disposal

This product or parts of it must be disposed of in an environmentally sound way:

  1. Use the public or private waste collection service.
  2. If this is not possible, contact the nearest Grundfos company or service workshop.

Subject to alterations.

aalal alal aalal aalal 1

2

a a 2 j 3

y

6.2

1
1
2
3

4
5
3.1 3.1

as iall Jy jia as iial 6j1.6

21 7

Grundfos UPS 15-35 SUC/TLC - 6.2 - 1

[Ω] 68 °F - 122 °F (20 °C - 50 °C)### ### ###
RS2RS1RAR
4,30 - 5,65 2,12 - 2,80 6,55 - 8,55 1 x 115 VUPS 50-40/4
15,0 - 19,8 8,30 - 10,8 25,0 - 33,0 1 x 230 V
57,5 - 75,0 3 x 208-230 V
114 - 148 3 x 460 V
184 - 242 3 x 575 V
2,65 - 3,50 1,20 - 1,56 4,15 - 5,45 1 x 115 VUPS 50-80/2
5,05 - 6,65 2,20 - 2,90 8,30 - 10,80 1 x 230 V
26,0 - 34,0 3 x 208-230 V
33,5 - 70,0 3 x 460 V
84,5 - 110 3 x 575 V
2,85 - 3,75 1,74 - 2,30 2,75 - 3,60 1 x 115 VUPS 50-80/4
4,95 - 6,50 2,65 - 3,50 5,50 - 7,25 1 x 230 V
37,0 - 49,0 3 x 208-230 V
79,0 - 104 3 x 460 V
120 - 156 3 x 575 V
3,70 - 4,85 2,02 - 2,65 6,80 - 8,95 1 x 230 VUPS 50-160/2
12,4 - 16,2 3 x 208-230 V
24,2 - 31,5 3 x 460 V
37,5 - 49,5 3 x 575 V
7,80 - 10,2 3 x 208-230 V
25,0 - 33,0 3 x 575 V
2,65 - 3,50 1,20 - 1,56 4,15 - 5,45 1 x 115 VUPS 53-55/57
5,05 - 6,65 2,20 - 2,90 8,30 - 10,80 1 x 230 V
26,0 - 34,0 3 x 208-230 V
33,5 - 70,0 3 x 46O V
84,5 - 110 3 x 575 V
3,70 - 4,85 2,02 - 2,65 6,80 - 8,95 1 x 230 VUPS 75-69
12,4 - 16,2 3 x 208-230 V
24,2 - 31,5 3 x 460 V
37,5 - 49,5 3 x 575 V
46,5 - 61,0 3 x 208-230 V
164 - 216 3 x 575 V
23,6 - 31,0 3 x 208-230 V UPS 80-80/4
7,80 - 10,2 3 x 208-230 V
UPS 80 -160/215,6 - 20
25,0 - 33,0 3 x 575 V
27,5 - 36,0 3 x 208-230 V
UPS 100-40/454,5 - 71
86,0 - 114 3 x 575 V
[Ω] 68°F - 122°F (20°C - 50°C)الجِدَهُّيْالجِدَهُّيْ
RS2 RS1 RA R
9,40 - 12,4 3,95 - 5,20 17,8 - 23,2 1 x 115 VUPS 32-40/4
39,5 - 52,0 17,0 - 22,2 70,0 - 91,5 1 x 230 V
180 - 236 3 x 208-230 V
360 - 4703 x 460 V
575 - 7503 x 575 V
6,70 - 8,80 3,05 - 4,00 9,55 - 12,6 1 x 115 VUPS 32-80/2
12,6 - 16,4 5,45 - 7,10 19,4 - 25,5 1 x 230 V
44,0 - 57,5 3 x 208-230 V
83,5 - 1103 x 460 V
132 - 1743 x 575 V
2,65 - 3,50 1,20 - 1,56 4,15 - 5,45 1 x 115 VUPS 32-160/2
5,05 - 6,65 2,20 - 2,90 8,30 - 10,8 1 x 230 V
26,0 - 34,0 3 x 208-230 V
53,5 - 70,03 x 460 V
84,5 - 1103 x 575 V
5,60 - 7,35 2,95 - 3,85 11,4 - 15,01 x 115 VUPS 40-40/4
25,5 - 34,0 14,0 - 18,4 50,5 - 66,5 1 x 230 V
118 - 154 3 x 208-230 V
234 - 3103 x 460 V
360 - 4753 x 575 V
4,50 - 5,90 1,84 - 2,42 5,60 - 7,35 1 x 115 VUPS 40-80/2
8,55 - 11,2 3,95 - 5,2011,0 - 14,4 1 x 230 V
32,0 - 42,0 3 x 208-230 V
64,0 - 84,03 x 460 V
102 - 1323 x 575 V
3,30 - 4,35 1,94 - 2,55 4,15 - 5,45 1 x 115 VUPS 40-80/4
4,60 - 6,05 3,05 - 4,00 8,10 - 10,6 1 x 230 V
46,5 - 61,0 3 x 208-230 V
90,5 - 1183 x 460 V
164 - 2163 x 575 V
1,94 - 2,55 1,10 - 1,44 2,85 - 3,75 1 x 115 VUPS 40-160/2
3,75 - 4,95 2,02 - 2,66 5,60 - 7,35 1 x 230 V
22,8 - 30,0 3 x 208-230 V
45,5 - 59,53 x 460 V
72,0 - 95,03 x 575 V
3,70 - 4,85 2,02 - 2,65 6,80 - 8,95 1 x 230 VUPS 40-240/2
11,0 - 14,4 3 x 208-230 V
22,0 - 29,03 x 460 V
35,0 - 45,53 x 575 V

Grundfos UPS 15-35 SUC/TLC - 6.2 - 2

Grundfos UPS 15-35 SUC/TLC - 6.2 - 3

(5.4

aolal (jai jai bail) jai a gao

S_ OBC = 12 · BO · CD = 12 × CD × 5

1,2,3 1,4,5 2,3,4

a ball 1

2

Rle jaoj 100

100Kx

( x,y) 0

J 4

L2:J L1

.

Grundfos UPS 15-35 SUC/TLC - 6.2 - 4

jzai aiaa

19

1 + u1 - 1 = ( 1 + u) u1 < 1 = u

1.000.000

(bi) (bi) 5.5

a 1

y

1,2,·s ,n

1

2

Rle jao le all 3

1x

aai 4

y

e 1

(RA,RS1,RS2,R)

5

32 1

.33

m = 311

Ssall jooill bi jia gai all

33 32

5.3

Jillu 1

1

S APQ = S AQP + S_ QPQ

aal 2

3

1

a 4

5

m = 311

( xt^2 + x) a + bt^2 = 5| 8y| x

%5

1

1

a

1 1

Ssina 0sill gss

Jj-llg 100

S APQ = S AQP + S_ QPQ

all 11 all sb

( xt^2 + x) ( xt^2 + y) = - ( xt^2 + yt^2 + z) ^2

Grundfos UPS 15-35 SUC/TLC - (bi) (bi) 5.5 - 1

J 1

18

الإستعمالالترجمةالترجمة
الإستعمال الحرفية حرفية ممن نزه و رشح بعس و صحي的女孩الإستعمال الحرفية بعس و صحي的女孩الإستعمال الحرفية .7
الإستعمال الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية EXCIDEالإستعمال الحرفية الحرفية الحرفية الحرفية الحرفية الحرفية EXCIDEالإستعمال EXCIDE (b.摘要)
3 ممن الحرفية الحرفية الحرفية الحرفية الحرفية EXCIDEالإستعمال EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLEالإستعمال EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLEEXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EXCILLE EX CIL EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILEالإستعمال EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBE EXCIBEالإستعمال EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCIBLE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILEEXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EX CIL EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILEEXCILEEXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EXCILE EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CILEX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EXCIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILL EX CILLEXCIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX CIL EX

5.2

21 + 2 = 4

1

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Grundfos UPS 15-35 SUC/TLC - 5.2 - 1

% (%)% (2015)% (2014)
allall
allallall
allallall
70%60%1
85%80%2
100%100%3

y

Grundfos UPS 15-35 SUC/TLC - 5.2 - 2

J !

4.2

UPS 575460x 42
y jll y jll y jll
jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll jll

a aal 1s y b c a a a a a a a a a a a a a a a a a a a a a

10,9,7,6,4 5

1

aai jie 1

  1. 1

h aeg aag a jilal a jall j 1 slaas

aaiall 15 aaiall 10 3

在 Rt ABD 中:

mm:158

mm:2510

5
1
1
1
1
1

  1. 4 1 1 1

a 35,34 1

3.2

1 1

y

aai 1 aai iie 1i aai nai y

1 2

90∠4062∠0W⊥

Grundfos UPS 15-35 SUC/TLC - y - 1

Grundfos UPS 15-35 SUC/TLC - y - 2

Grundfos UPS 15-35 SUC/TLC - y - 3

2J 1

j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j

0g216

2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Grundfos UPS 15-35 SUC/TLC - y - 1

3

y !

3.1

y

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

902962£OW

Grundfos UPS 15-35 SUC/TLC - y - 2

Grundfos UPS 15-35 SUC/TLC - y - 3

Grundfos UPS 15-35 SUC/TLC - y - 4

1 1

y

y

Grundfos UPS 15-35 SUC/TLC - y - 5

()

eallg plisi wu auaus UPS as nall

i 1

jlll

all jus sll e all

1 1

50/50

a 1221 yg cia a jll aal all aai

14 14

TTP 1

i 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

i j 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

J 1

J 1 1 1 1 1 1 1 1 1 1 1 1 1 1

1 1

j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j 1 j

sL 1 L sI 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Grundfos UPS 15-35 SUC/TLC - y - 1

DEXCOOL

General Motors Corporation. Texaco Lubricants NA

y

a a

y

J 1

i: i.

2

2.1

gpm 1

()

2.2

i 1

a aai j 1 1 1 1 1 1 1 1 1 1 1

1

1 1

2.3

5 5

1 2

J 1

边 CAD

% 10-1+2i jle jia klll aao 100 all o

e 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

51 51

10-/+

1.1

1.1.1

1.1.2

y

y 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0

Grundfos UPS 15-35 SUC/TLC - 1.1 - 1

Grundfos UPS 15-35 SUC/TLC - 1.1 - 2

36###1.1
36###2.2
35###2.1
35###2.2
35###2.3
35###2.4
34###3.3
34###3.1
33###3.2
33###3.3
33###3.4
31###4.4
31###4.1
30###4.2
30###4.3
28###5.5
28###5.1
27###5.2
26###5.3
26###5.4
26###5.5
24###5.6
22###6.6
22###6.2
21###6.3
21###6.7
20###7

1 1

a 1000

iill iie

Grundfos UPS 15-35 SUC/TLC - 四 - 1

a

a aal 1e buiu

1

17100 West 118th Terrace

Olathe, Kansas 66061

Phone: (913) 227-3400

Fax: (913) 227-3500

www.grundfos.us

GRUNDFOS Canada

2941 Brighton Road

Oakville, Ontario L6H 6C9 Canada

Phone: +1-905 829 9533

Telefax: +1-905 829 9512

www.grundfos.ca

GRUNDFOS México

Boulevard TLC No. 15

C.P. 66600 Apodaca, N.L. Mexico

Phone: 011-52-81-8144 4000

Fax: 011-52-81-8144 4010

www.grundfos.mx

United Arab Emirates

GRUNDFOS Gulf Distribution

P.O.Box 16768

Jebel Ali Free Zone

Dubai

Phone: +971-4-8815-166

Fax: +971-4-8815-136

www.grundfos.uae

L-UPS-TL-001

96459998 0419

ECM: 1260728

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Grundfos

Model : UPS 15-35 SUC/TLC

Category : Water pump