HSBC 300 L cool - Boiler STIEBEL ELTRON - Free user manual and instructions
Find the device manual for free HSBC 300 L cool STIEBEL ELTRON in PDF.
User questions about HSBC 300 L cool STIEBEL ELTRON
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Boiler in PDF format for free! Find your manual HSBC 300 L cool - STIEBEL ELTRON and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. HSBC 300 L cool by STIEBEL ELTRON.
USER MANUAL HSBC 300 L cool STIEBEL ELTRON
T (Puer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT20
T (Puffer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT13 BT20
SPECIAL INFORMATION - The appliance may be used by children over 8 years of age and persons with reduced physi- cal, sensory or mental capabilities or a lack of experience and expertise, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Children must never clean the appliance or perform user maintenance unless they are supervised. - The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power supply by an isolator that discon- nects all poles with at least 3mm contact separation. - Observe all applicable national and regional regulations and instructions. - Observe minimum distances (see chapter "In- stallation/ Preparations/ Installation site"). - Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance. DHW cylinders - Drain the appliance as described in chapter "Installation/ Maintenance/ Draining the DHW cylinder". - Observe the maximum permissible pressure (see chapter "Installation/ Specification/ Data table"). SPECIAL INFORMATIONOPERATION
1.5 Units of measurement 37
2.2 General safety instructions 38
5. Cleaning, care and maintenance 39
7.1 General safety instructions 40
7.2 Instructions, standards and regulations 40
9.2 Transport and handling 41
10.2 Heating water connection and safety valve 46
10.3 DHW connection and safety assembly 52
10.4 Filling the system 53
11.3 Power supply for auxiliary heating element 56
15.1 Dimensions and connections 60
15.4 Energy consumption data 65
The chapters "Special information" and "Operation" are intended for both users and qualified contractors. The chapter "Installation" is intended for qualified contractors. Note Read these instructions carefully before using the appli- ance and retain them for future reference. Pass on the instructions to a new user if required.
1.1 Relevant documents
Operating and installation instructions for the connected heat pump Operating and installation instructions for all other sys- tem components
1.2 Safety instructions
1.2.1 Structure of safety instructions
KEYWORD Type of risk Here, possible consequences are listed that may result from failure to observe the safety instructions. Steps to prevent the risk are listed.
1.2.2 Symbols, type of risk
KEYWORD Meaning DANGER Failure to observe this information will result in serious injury or death. WARNING Failure to observe this information may result in serious injury or death.CAUTION Failure to observe this information may result in non-seri-ous or minor injury.
1.3 Other symbols in this documentation
Note General information is identified by the adjacent symbol. Read these texts carefully. Symbol Meaning
Material losses(appliance damage, consequential losses and environmen-tal pollution)
Appliance disposal This symbol indicates that you have to do something. The ac- tion you need to take is described step by step.
1.4 Information on the appliance
Connections Symbol Meaning
1.5 Units of measurement
Note All measurements are given in mm unless stated oth- erwise.OPERATION Safety 38 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
This appliance is intended to be used for seasonal heating and cooling of interiors (7°C/ 12°C) and for DHW heating.The appliance is intended for domestic use. It can be used safely by untrained persons. The appliance can also be used in non-do-mestic environments, e.g. in small businesses, as long as it is used in the same way.Any other use beyond that described shall be deemed inappro-priate. Observation of these instructions and of the instructions for any accessories used is also part of the correct use of this appliance.
2.2 General safety instructions
WARNING BurnsThere is a risk of scalding at outlet temperatures in ex-cess of 43°C.
WARNING InjuryThe appliance may be used by children over 8 years of age and persons with reduced physical, sensory or men-tal capabilities or a lack of experience and expertise, provided that they are supervised or they have been instructed on how to use the appliance safely and have understood the potential risks. Children must never play with the appliance. Children must never clean the ap-pliance or perform user maintenance unless they are supervised.
WARNING InjuryFor safety reasons, only operate the appliance with the front casing closed. Note The DHW cylinder is under supply pressure. During the heat-up process, expansion water will drip from the safe-ty valve. If water continues to drip when heating is complet-ed, please inform your qualified contractor.
Material lossesThe system's active frost protection is not guaranteed if the power supply is interrupted. Never interrupt the power supply even outside the heating season.
See type plate on the appliance.
3. Appliance compatibility
The appliance can be operated in conjunction with the following air | water heat pumps:HSBC 300 cool: - WPL 10 AC - WPL 15/20/25 AC(S) - WPL 19/24 IHSBC 300 L cool: - WPL 09/17 ICS/IKCS classic - WPL 19/24 IK - WPF 04/05/07/10 (cool)
4. Appliance description
The buffer cylinder and DHW cylinder with indirect coil are ar-ranged one above the other and can be separated for easier han-dling.The appliance has a plastic jacket with foam insulation and is equipped with a removable front casing. The appliance is connect-ed hydraulically and electrically to the heat pump. All hydraulic connections are made at the top (heating) and rear (DHW).In addition to the DHW cylinder and the buffer cylinder, further system components are integrated: - Highly efficient circulation pump for a heating circuit without mixer - 3/2-way diverter valve - Cylinder charging pump (only in HSBC300cool)DHW cylindersThe steel cylinder is coated on the inside with special direct enam-el and is equipped with a signal anode. The anode with consump-tion indicator protects the cylinder interior from corrosion.The heating water heated by the heat pump is pumped through an indirect coil inside the DHW cylinder. The heat channelled through the indirect coil is thus transferred to the domestic hot water.Buffer cylinderThe steel cylinder provides hydraulic separation between the flow rates of heat pump and heating circuit. The heating water heat-ed by the heat pump is transferred to the buffer cylinder by the cylinder charging pump (only in HSBC 300 cool). When a demand is issued, the integral heating circuit pump delivers the heating water to the heating circuit.OPERATION Cleaning, care and maintenance www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 39 ENGLISH
5. Cleaning, care and maintenance
Have the electrical safety of the appliance and the function of the safety assembly regularly checked by a qualified contractor. Never use abrasive or corrosive cleaning agents. A damp cloth is sufficient for cleaning the appliance. Signal anode with consumption indicator
Material losses If the consumption indicator changes colour from white to red, have the signal anode checked by a qualified con- tractor and if necessary replaced. D0000080281
1 White = Anode OK 2 Red = Requires checking by qualified contractor Scaling Almost every type of water will deposit limescale at high temper- atures. This settles inside the appliance and affects both perfor- mance and service life. A qualified contractor who knows the local water quality will tell you when the next service is due. Check the taps regularly. Limescale deposits at the tap out- lets can be removed using commercially available descaling agents. Regularly activate the safety valve to prevent it from becom- ing blocked, e.g. by limescale deposits.
Problem Cause Remedy The water does not heat up. The heating does not work. There is no power. Check the fuses/MCBs in your fuse box/distribu- tion board. If you cannot remedy the fault, contact your qualified contractor. To facilitate and speed up your enquiry, please provide the serial number from the type plate (000000-0000-000000). No.:000000-0000-000000Made in GermanyD0000080280INSTALLATION Safety 40 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com INSTALLATION
Only a qualified contractor should carry out installation, commis-sioning, maintenance and repair of the appliance.
7.1 General safety instructions
We guarantee trouble-free function and operational reliability only if original accessories and spare parts intended for the appliance are used.
7.2 Instructions, standards and regulations
Note Observe all applicable national and regional regulations and instructions.
8. Appliance description
The following are delivered with the appliance: - 4 adjustable feetOnly HSBC 300 L cool: - 2 copper adaptors (28/28/28mm, for joining flow and return) - 4 copper reducers (28/22mm)
8.2.1 Required accessoriesSafety assemblies and pressure reducing valves are available to suit the prevailing supply pressure. These type-tested safety assemblies protect the appliance against impermissible excess pressure.8.2.2 Additional accessories - Pump assembly for a heating circuit with mixer HSBC3-HKM - Pipe assembly RBS-SBC - Auxiliary heating element HSBC3-HE - Pressure hoses - Water softening fitting HZEA - Temperature sensor for coolingPipe assembly RBS-SBCThe hydraulic connections can be routed upwards at the rear of the DHW cylinder using the RBS-SBC pipe assembly available as an accessory.
Material lossesNever install the appliance in wet rooms.Install the appliance near the draw-off point in a dry room free from the risk of frost. To reduce line losses, keep the distance short between the appliance and the heat pump.Ensure the floor has sufficient load bearing capacity and evenness (for weight, see chapter "Specification/ Data table").The room must not be subject to a risk of explosions arising from dust, gases or vapours.If you are installing the appliance in a boiler room together with other heating equipment, ensure that the operation of the other heating equipment will not be impaired.Minimum clearances ≥250 ≥250 ≥800 ≥100 ≥500 ≥100 ≥500 D0000080273The minimum side clearances can be swapped between left and right.INSTALLATION Preparation www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 41 ENGLISH
9.2 Transport and handling
Material losses Store and transport the appliance at temperatures be- tween -20°C and +60°C. Handling Undo the 4screws from the non-returnable pallet. D0000055519 Tilt the appliance and screw the 4adjustable feet into the appliance. Lift the appliance off the pallet. If narrow doors or hallways hinder handling, you can separate the upper and lower sections of the appliance as described in the following chapters.
9.2.1 Removing/ fitting the front casing
D0000080283 Remove the 2locking screws on the top of the front casing. Unhook the front casing towards the top. Remove the earth cable from the front casing. Fit the front casing in reverse order.INSTALLATION Preparation 42 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
9.2.2 Overview of insulation segments
9.2.3 Separating/ joining the appliance sections
Separating the appliance sections Material losses Unscrewing the fastening screws destroys the threads in the insulation segment. To open the 3 fixing tabs, loosen the fastening screws slightly but do not unscrew them completely. D0000083254 Note To make removal simpler, the insulation segments have labelled recessed grips on the left and right. D0000080284 Remove insulation segment1. Remove insulation segment2. D0000080287 Pull the "heating sensor" out of the buffer cylinder. D0000080288 Release the sensor lead from the guide groove. D0000080289 Disconnect the push-fit connectors of the 4hydraulic con- nections. To do this, pull the spring clips fully out with a screwdriver. Pull the hydraulic connectors as indicated.INSTALLATION Preparation 44 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com D0000080293 Remove the 4hydraulic hoses. Remove the 2insulation material screws. Remove insulation segment3. D0000080299 Undo the 2 locking screws on the side profile strips. Lift up and unhook the side profile strips. D0000080343 Release the 4screws on the tabs at the front of the appliance. D0000074613 Pull the upper section of the appliance towards the front. D0000080345
1 Handle Tip the upper section of the appliance backwards. Use the handle for improved grip. D0000080347 Place the upper section of the appliance on a base to prevent damage.INSTALLATION Preparation www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 45 ENGLISH Joining appliance sections Material losses To prevent condensation forming, the insulation seg- ments must fit closely against the lower section with no gaps. When inserting the insulation segments, ensure that the joint grooves are kept clear Tap the insulation segments down with your hand. Rejoin the appliance sections in reverse order. The positioning aids and the dotted line marking provide assis- tance when positioning and inserting the upper appliance section into the guide groove on the lower section: D0000080346
1 Dotted line (perforation in the panel) Place the upper appliance section onto the lower appliance section along the dotted line. D0000074614 Slide the upper appliance section to the back until it is flush with the lower appliance section. If the appliance sections are joined correctly, the final position is determined by the guide groove and guide pin. Secure the tabs on the appliance front. Fit the side profile strips. Fit insulation segment 3 and the 4 hydraulic hoses. Connect the push-fit connectors of the 4hydraulic connec- tions. Ensure that the spring clips click into place. Insert the "heating sensor" into the buffer cylinder. Lay the sensor lead in the guide groove provided for this purpose. Fit insulation segment2. Fit insulation segment1. Fit the front casing.INSTALLATION Installation 46 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
When positioning the appliance, observe minimum clearanc- es (see chapter "Preparations/ Installation site"). Use the adjustable feet to compensate for any unevenness in the floor.
10.2 Heating water connection and safety valve
Material losses The heating system to which the appliance is connected must be installed by a qualified contractor in accord- ance with the water installation drawings in the technical guides.
Material losses When fitting additional shut-off valves, install a further safety valve in an accessible location on the heat gen- erator itself or in the flow line in close proximity to the heat generator. There must be no shut-off valve between the heat gen- erator and the safety valve. Oxygen diffusion
Material losses Avoid open vented heating systems and underfloor heating systems with plastic pipes that are permeable to oxygen. In underfloor heating systems with plastic pipes that are per- meable to oxygen and in open vented heating systems, oxygen diffusion may lead to corrosion on the steel components of the heating system (e.g. on the indirect coil of the DHW cylinder, on buffer cylinders, steel radiators or steel pipes).
Material losses The products of corrosion (e.g. rusty sludge) can set- tle in the heating system components, which may re- sult in a lower output or fault shutdowns due to reduced cross-sections. Supply lines The maximum permissible line length between the appli- ance and the heat pump will vary, depending on the version of the heating system (pressure drop). As a standard value, assume a maximum line length of 10m and a pipe diameter of 22-28mm. Insulate the flow and return lines in accordance with regional regulations. Connect the hydraulic connections with flat gaskets. Pressure hoses against structure-borne sound transmission: The appliance and the heat pump are connected to each other hydraulically via pipes carrying heating water. To reduce the trans- mission of structure-borne sound on the water side, connect the appliance to the heat pump with pressure hoses if these are not already installed in the heat pump. Pressure differential: If the available external pressure difference is exceeded, the pres- sure drop in the heating system could result in a reduced heating output. When sizing the pipes, ensure that the available external pressure differential is not exceeded (see chapter "Specifica- tion/ Data table"). When calculating the pressure drop, take account of the flow and return lines and the pressure drop of the heat pump. The pressure drop must be covered by the available pressure differential.INSTALLATION Installation www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 47 ENGLISH
10.2.2 Fitting the pump assembly (accessory) if required
WARNING Electrocution Before starting work on the appliance, disconnect all poles from the power supply and drain the heating circuit via the drain valve on the buffer cylinder. To extend the appliance with a heating circuit with mixer, you can install pump assembly HSBC 3-HKM (available as an accessory). Standard delivery HSBC 3-HKM D0000080357
1 Pipe insulation 2 Connection pipes (*) 3 Temperature sensor 4 Heating circuit pump (*) 5 3-way mixer (*) 6 Insulation mat for 3-way mixer 7 Flat gaskets 8 Servomotor for 3-way mixer (*) 9 Insulation mat for 3-way mixer and heating circuit pump (*) Pipe assembly Preparation for installation of HSBC3-HKM Remove the front casing and insulation segment1 (see chap- ter "Installation/ Preparations/ Transport and handling"). The following components are prefitted on the HSBC side at the pump assembly installation site: D0000080375
10 Insulation plugs 11 Profiles for 3-way mixer 12 Insulation mat, closed 13 Adaptor with dummy cap screwed on Remove the insulation plugs. Remove the closed insulation mat and profiles for the 3-way mixer and the heating circuit pump. Counterhold and unscrew the dummy caps from the adaptors.INSTALLATION Installation 48 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com HSBC3-HKM installation 1-2 Nm D0000081576 Check the position of the 3-way mixer shaft. Adjust the posi- tion if necessary. D0000080376
(*) Pipe assembly inserted 6 Insulation mat for 3-way mixer 8 Servomotor for 3-way mixer 11 Profiles for 3-way mixer Insert the pipe assembly. Insert the flat gaskets into the union nuts for the connection pipes. Counterhold and secure the union nuts to the adaptors. Check the alignment of the pipes and functional elements of the pump assembly. Retighten all fittings. Install the profiles for the 3-way mixer over the mixing valve body and above the pump. Place the insulation mat for the 3-way mixer on the valve body. Install the servomotor for the 3-way mixer D0000085474
Material losses To prevent condensation from forming, do not lay any cables in the joint grooves of the EPP parts. Route the pump assembly connecting cable to the control panel as shown. Slide the pipe insulation over the connection pipe connectors from above.INSTALLATION Installation www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 49 ENGLISH D0000085473
(*) Pipe assembly inserted 9 Insulation mat for 3-way mixer and heating circuit pump 11 Profiles for 3-way mixer Insert the insulation mat on the HKM side for the 3-way mixer and the heating circuit pump. Electrical connection HSBC3-HKM MA19
D0000081761 Wire up the heating circuit pump and 3-way mixer (see chap- ter "Installation/ Electrical connection/ Control voltage").INSTALLATION Installation 50 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com10.2.3 If necessary, install an HSBC3-HE auxiliary heating element as an accessory WARNING ElectrocutionBefore starting work on the appliance, disconnect all poles from the power supply and drain the DHW cylinder.D0000080386211 Blank flange2 Insulation segment Remove the insulation segment in front of the flange plate. Remove the blank flange.
D000008053911 Earthing contact PE Move the auxiliary heating element into the correct instal-lation position. Use the position of the earthing contact as a guide.D0000080387 Place the insulation mat (included in the standard delivery for the auxiliary heating element) on the thermostat. Insert the insulation mat between the flange plate and cable. Install the auxiliary heating element. Observe the tight-ening torque (see chapter "Installation/ Specification/ Accessories").Electrical connection HSBC3-HEIn the delivered condition, the 3 wires for connecting the auxil-iary heating element are connected to a prefitted terminal and earthing tab.D00000805411 21 Terminal2 Earthing tab Disconnect the 3wires from the terminal and the earthing tab. Remove the terminal and earthing tab.INSTALLATION Installation www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 51 ENGLISH D0000080544 Connect the 3 wires to the auxiliary heating element as shown. A BK/BN B BU PE GNYE Note The auxiliary heating element standard delivery in- cludes two identical wiring diagram labels for covering "HSBC3-HE(accessory X2.11)" on the wiring diagram: - On the back of the front casing - In these instructions (see chapter "Installation/ Specification/ Wiring diagram") After installation of the auxiliary heating element, affix the wiring diagram labels in the corresponding places. Wire up the auxiliary heating element (see chapter "Installa- tion/ Electrical connection/ Auxiliary heating element"). Setting HSBC3-HE
1 Temperature selector for the auxiliary heating element Turn the temperature selector anti-clockwise as far as it will go to set the maximum temperature (65±5°C).INSTALLATION Installation 52 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
10.2.4 Hydraulic connection
Note Observe the details specified in the chapter "Installa- tion/ Specification/ Hydraulic diagrams". Thoroughly flush the pipes before connecting the heat pump. Foreign bodies (e.g. welding pearls, rust, sand, sealant, etc.) can impair the operational reliability of the heat pump. Install the heating water pipes (see chapter "Specification/ Dimensions and connections").
10.3 DHW connection and safety assembly
Material losses The maximum permissible pressure must not be exceed- ed (see chapter "Specification/ Data table").
Material losses Operate the appliance only with pressure-tested taps. Cold water line Galvanised steel, stainless steel, copper and plastic are approved materials.
Material losses A safety valve is required. DHW line, DHW circulation line Stainless steel, copper and plastic are approved materials.
10.3.2 Installing the pipe assembly (accessory) if required
WARNING Electrocution Before starting work on the appliance, disconnect all poles from the power supply and drain the DHW cylinder. Note The following diagrams show pipe assembly RBS-SBC (see chapter "Specification/ Dimensions and connec- tions"). Ø=3mm D0000080428 Hook the retainer for the connection pipes into the top centre of the appliance. Use the retainer as a drilling template and pre-drill the fixing holes. Secure the retainer with the screws.INSTALLATION Installation www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 53 ENGLISH D0000080429
1 Retainer 2 Insulated connection pipes Install the connection pipes in sequence, starting on the left or right depending on the positioning of the appliance. Insert the connection pipes through the retainer from below. Secure the connections to the appliance using the union nuts. Connect the pipes of the pipe assembly to the domestic pipe- work system.
10.3.3 Installing the DHW circulation line, if applicable
A DHW circulation line with external DHW circulation pump can be fitted to the DHW circulation connection (see chapter "Specifi- cation/ Dimensions and connections"). Remove the sealing cap from the DHW circulation connection (see chapter "Specification/ Dimensions and connections"). Connect the DHW circulation line.
10.3.4 DHW connection and safety assembly
Flush the pipes thoroughly. Install the DHW outlet line and the cold water inlet line (see chapter "Specification/ Dimensions and connections"). Con- nect the hydraulic connections with flat gaskets. Install a type-tested safety valve in the cold water inlet line. Please note that, depending on the supply pressure, you may also need a pressure reducing valve. Size the drain pipe so that water can drain off unimpeded when the safety valve is fully opened. The safety valve drain aperture must remain open to atmosphere. Install the safety valve drain pipe with a constant fall to the drain.
10.4 Filling the system
Heating circuit water quality Carry out a fill water analysis before filling the system. This analy- sis may, for example, be requested from the relevant water supply utility. To avoid damage as a result of scaling, it may be necessary to soften or desalinate the fill water. The fill water limits specified in chapter "Specification/ Data table" must always be observed. Recheck these limits 8-12weeks after commissioning and during the annual system service. Note With a conductivity >1000μS/cm, desalination treatment is recommended in order to avoid corrosion. Note If you treat the fill water with inhibitors or additives, the same limits apply as for desalination. Note Suitable appliances for water softening, as well as for filling and flushing heating systems, can be obtained via trade suppliers.
Material losses Never switch on the power before filling the system.
10.4.1 Filling the heating system
D0000080425 Fill the heating system via the drain valve. Vent the pipework.
10.4.2 DHW cylinder filling
Filling the DHW cylinder via the "cold water inlet" connection. Open all downstream draw-off valves until the appliance is full and the pipework is free of air. Adjust the flow rate. For this, observe the maximum permis- sible flow rate with a fully opened tap (see chapter "Specifi- cation/ Data table"). If necessary reduce the flow rate at the butterfly valve of the safety assembly. Carry out a tightness check. Check the safety valve.INSTALLATION Electrical connection 54 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
10.5 Venting the appliance
1 Air vent valve 2 Vent hose 3 Hose attachment Detach the vent hose from the hose attachment. Hang the free end of the vent hose in a container. To ventilate, open the air vent valve. After ventilation, close the air vent valve. Secure the vent hose.
11. Electrical connection
WARNING Electrocution Carry out all electrical connection and installation work in accordance with relevant regulations. Before any work on the appliance, disconnect all poles from the power supply. WARNING Electrocution The connection to the power supply must be in the form of a permanent connection. Ensure the appliance can be separated from the power supply by an isolator that dis- connects all poles with at least 3mm contact separation. This requirement can be met by using contactors, circuit breakers, fuses/MCBs, etc.
Material losses Provide separate fuses for the two power circuits of the appliance and the control unit.
Material losses Observe the type plate. The specified voltage must match the mains voltage. Note Leakage currents of up to 5 mA may occur. Note You must have permission to connect the appliance from the relevant power supply utility. The terminal box of the appliance is located behind the front casing (see chapter "Preparations/ Transport and handling/ Removing/ Fitting the front casing").INSTALLATION Electrical connection www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 55 ENGLISH D0000080437 Route all power cables and sensor leads into the appliance through the cable entry. Connect the power cables and sensor leads as detailed below. Install cables with the following cross-sections in accordance with the respective fuse protection: Fuse protection Assignment Cable cross-sectionB 16 A Control 1.5mm²
Material losses Only connect energy efficient circulation pumps ap- proved by us to the pump connections. D0000080432 XD03.1 Control terminal XD03.2 Control terminal XD03.3 Control terminal XE03 Earth terminal, control unit XD03.1 Control terminal Power supply 220-240VMains buffer charging pump XD03.2 Control terminalHKP Heating circuit pumpMKP Mixer circuit pump, heating circuit 2 Note At terminals XD03.2HKP/MKP, you can install a tempera- ture limiter for the underfloor heating system by remov- ing the jumper between L and 2. XD03.3 Control terminalMixer Mixer, servomotor, heating circuit 2UV Diverter valve, heating/DHWINSTALLATION Electrical connection 56 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
11.2 Safety extra low voltage
D0000080433 XD04 Terminal, safety extra low voltage T(MK) Mixer circuit temperature sensor for HSBC3-HKM (optional) T(KUE) Temperature sensor for area cooling (optional) T(WW) DHW temperature sensor T(Puffer) Temperature sensor, buffer cylinder PWM Control by WPM Control by WPM via PWM signal Observe the information in the operating and installation in- structions of the WPM heat pump manager.
11.3 Power supply for auxiliary heating element
Note The "Heaterterminal" (XD06.1) can only be assigned when the optional HSBC3-HE auxiliary heating element is installed. D0000080434 XD06.1 Heater terminal (accessories HSBC 3-HE)
11.4 Sensor installation
Note The temperature sensor needs to be replaced on com- bined appliance system HSBC300Lcool with WPF/ WPFcool. Use the PTC temperature sensor that was included in the standard delivery of the heat pump. D0000082327D0000080287Kleinspannung
T (Puer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT20
11.4.1 Temperature sensor for cooling (accessory), if required
Cooling requires the fitting of a temperature sensor, available as an accessory. Remove the front casing (see chapter "Preparations/ Trans- port and handling/ Removing/ fitting the front casing"). D0000080426 Insert the temperature sensor into the sensor well "Sensor heat pump cooling, optional". D0000080288 Lay the sensor lead in the guide groove provided for this pur- pose in the insulation segment. Connect the temperature sensor to T(KUE) of terminalXD04 of the appliance.INSTALLATION Commissioning 58 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
Our customer support can assist with commissioning, which is a chargeable service. If the appliance is intended for commercial use, observe the rules of the relevant Health & Safety at Work Act during commissioning. For further details, check with your local authorising body (in Germany, for example, this is the TÜV).
Operation indicator: LED illuminates green in normal operation LED illuminates/flashes when there is a fault Display of selected control mode ∆p-v, ∆p-c and constant speed Display of selected curve (I, II, III) within the control mode
Combinations of LED displays for venting function, man-ual re-start and key lock Operating button
Press To select control mode To select curve (I, II, III) within the control mode Press and hold To activate venting function (press for 3seconds) For manual restart (press for 5seconds) To lock/unlock keys (press for 8seconds) Control modes and functions Variable differential pressure ∆p-v (I, II, III)
Recommended for two-pipe heating systems with radi-ators to reduce flow noise at thermostatic valves The pump reduces the delivery head by a half when flow rate drops in pipework. Saves energy by matching the delivery head to the flow rate demand and the lower flow velocities. Choice of three pre-defined curves (I, II, III). Constant pressure differential ∆p-c (I, II, III)
Recommended for underfloor heating systems or with large-diameter pipework and for all applications with a non-varying pipework curve (e.g. cylinder charging pumps) and single-pipe heating systems with radiators The control system keeps the set delivery head con-stant, irrespective of delivered flow rate. Choice of three pre-defined curves (I, II, III). Constant speed (I, II, III)
Recommended for systems with unchanging system resistance which require a constant throughput. The pump runs at three preset fixed speed levels (I, II, III). Note Factory setting: Constant speed, curve III Venting
Fill the system properly and ventilate it If the pump is not ventilated automatically: Activate the venting function via the operating button, press button for 3seconds, then release it. Venting function starts (duration 10minutes). The top and bottom rows of LEDs flash alternately every second. To cancel, press the operating button for 3seconds.
Note After venting, the LED indicator displays the previously set pump values. Setting control modes Selecting the control mode
The LEDs for the control modes and associated curves illuminate one after the other. Briefly press the operating button (for approx.1sec-ond). LEDs indicate the current selected control mode and curve (see following table).Operating buttonLED indicator Control mode Curve
Variable differential pressure ∆p-v III
Variable differential pressure ∆p-v
Variable differential pressure ∆p-v
Constant differential pressure ∆p-c III
Constant differential pressure ∆p-c
Constant differential pressure ∆p-c
III (*) Pressing the button for the 9thtime in succession returns the system to the factory setting (constant speed, curveIII).
Explain the appliance function to users and familiarise them with how it works. Make users aware of potential dangers. Hand over these instructions.
Material losses Observe the temperature application limits and the min- imum circulation volume on the heat consumer side (see chapter "Specification/ Data table").
Material losses Drain the system when there is a risk of frost and the heat pump is completely switched off (see chapter "Mainte- nance/ Draining the DHW cylinder"). If you take the system out of use, set the heat pump manager to standby so that the safety functions that protect the appli- ance (e.g. frost protection) remain active.
WARNING Electrocution Carry out all electrical connection and installation work in accordance with relevant regulations. WARNING Electrocution Before any work on the appliance, disconnect all poles of the appliance from the power supply. Draining the buffer cylinder D0000080425 Drain the buffer cylinder via the drain valve. Draining the DHW cylinder CAUTION Burns Hot water may escape during draining. Close the shut-off valve in the cold water inlet line. Open the hot water taps on all draw-off points. Empty the DHW cylinder via the "cold water inlet" connection. Cleaning and descaling the DHW cylinder
Material losses Never use descaling pumps or descaling agents to clean the cylinder. Clean the appliance through the inspection port. For the torque of the flange screws, see chapter "Specification/ Dimensions and connections". Replacing the signal anode Replace the signal anode if it becomes depleted.INSTALLATION Specication 60 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
15.1 Dimensions and connections
T (Puffer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT13 BT20
BN GNYE D0000078314INSTALLATION Specication www.stiebel-eltron.com HSBC 300 cool | HSBC 300 L cool | 63 ENGLISH BT06 Temperature sensor, heat pump buffer cylinder BT20 Temperature sensor, DHW cylinder BT13 Temperature sensor HP flow HC2 (accessories HSBC3-HKM) MA10 Motor, pump, heating circuit MA11 Motor, pump, heating circuit 2 MA14 Motor, buffer charging pump (not for HSBC300Lcool and TSBC300Lplus) MA15 Motor, diverter valve, heating, DHW MA19 Motor, mixing valve heating circuit 2 XD04 LV terminal XD06.1 Heater terminal (accessories HSBC 3-HE) XD06.2 Heater terminal (accessories HSBC 3-HE) XD03.1 Control terminal (mains buffer charging pump) XD03.2 Control terminal (heating circuit pump, pump heating circuit 2) XD03.3 Control terminal (mixer heating circuit 2, diverter valve) KF17 Relay, diverter valve, heat source XE03 Earth terminal, control unitINSTALLATION Specication 64 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com
15.4 Energy consumption data
Hydraulic data Nominal capacity, DHW cylinder l 270 270 Nominal capacity, buffer cylinder l 100 100 Surface area, indirect coil m² 3.3 3.3 Capacity, indirect coil l 21 21 External available pressure differential, circulation pump/heat pump at 1.0m³/h hPa 656 External available pressure differential, circulation pump/heat pump at 1.5m³/h hPa 527 External available pressure differential, circulation pump/heat pump at 2.0m³/h hPa 210 External available pressure differential, circulation pump / heating circuit 1 at 1.0 m³/h hPa 725 725 External available pressure differential, circulation pump / heating circuit 1 at 1.5m³/h hPa 663 663 External available pressure differential, circulation pump / heating circuit 1 at 2.0m³/h hPa 444 444 External available pressure differential, circulation pump / heating circuit 2 (optional) at 1.0 m³/h hPa 665 665 External available pressure differential, circulation pump / heating circuit 2 (optional) at 1.5m³/h hPa 518 518 External available pressure differential, circulation pump / heating circuit 2 (optional) at 2.0m³/h hPa 189 189 Application limits Max. permissible pressure, DHW cylinder MPa 1.0 1.0 Test pressure, DHW cylinder MPa 1.5 1.5 Max. flow rate l/min 25 25 Max. permissible pressure, buffer cylinder MPa 0.3 0.3 Test pressure, buffer cylinder MPa 0.45 0.45 Max. permissible temperature °C 85 85 Max. permissible temperature, primary side °C 75 75 Heating water quality requirements Water hardness °dH ≤3 ≤3 pH value (with aluminium fittings) 8.0-8.5 8.0-8.5 pH value (without aluminium fittings) 8.0-10.0 8.0-10.0 Conductivity (softening) μS/cm <1000 <1000 Conductivity (desalination) μS/cm 20-100 20-100 Chloride mg/l <30 <30 Oxygen 8-12 weeks after filling (softening) mg/l < 0.02 < 0.02 Oxygen 8-12 weeks after filling (desalination) mg/l < 0.1 < 0.1 Power consumption Max. power consumption, charging pump W 60 Max. power consumption, circulation pump on the heating side W 60 60 Energy data Standby energy consumption/24 h at 65°C kWh 1.5 1.5 Energy efficiency class B B Electrical data Frequency Hz 50 50 Versions IP rating IP20 IP20 Dimensions Height mm 1918 1918 Width mm 680 680 Depth mm 910 910 Height when tilted mm 2123 2123 Weights Weight, full kg 641 639 Weight, empty kg 250 248INSTALLATION Specication 66 | HSBC 300 cool | HSBC 300 L cool www.stiebel-eltron.com Further details HSBC 300 cool HSBC 300 L cool
Connections Heating circuit connection mm 22 Auxiliary heating element HSBC3-HE HSBC 3-HE
1.1 Documentation applicable 69
1.1 Documentation applicable
Raccordements Symbole Signification
T (Puer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT20
T (Puffer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT13 BT20
T (Puer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT20
T (Puffer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT13 BT20
T (Puer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT20
T (Puffer)(X1.4)T (WW)(X1.8)T (KUE)(X1.11)T (MK)(X1.6) BT06 BT13 BT20
EasyManual