IFM NE5004 - Sensor

NE5004 - Sensor IFM - Free user manual and instructions

Find the device manual for free NE5004 IFM in PDF.

📄 31 pages English EN Download 💬 AI Question
Notice IFM NE5004 - page 12
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about NE5004 IFM

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Sensor in PDF format for free! Find your manual NE5004 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. NE5004 by IFM.

USER MANUAL NE5004 IFM

  1. According to the ATEX directive 94/9/EC (ATEX) the original operating instructions and a translation of these operating instructions into the language or languages of the EU user country must be provided when a unit or protective system is put into operation within the member countries of the European Union (EU).
  2. If no operating instructions or EC declaration of conformity is supplied with this product in the language of the EU user country, these can be requested from your dealer (see delivery note) or manufacturer (see cover sheet / back).
  3. Only qualified personnel is allowed to set up the product. Furthermore, we expressly point out that any liability is excluded resulting from putting the unit into operation without the corresponding operating instructions in the language of the EU user country.

ESEspañol

Function and features

- Use in hazardous areas according to the classification

II 2G (Group II, category 2G, apparatus for gas atmosphere).

The requirements of the EN50014, EN50020, EN60947-5-6 standards are met.

EC type test certificate

PTB 01 ATEX 2191

- Use in hazardous areas according to the classification

II 1D (Group II, category 1D, apparatus for dust atmosphere).

The requirements of the prEN 61241-0, IEC 61241-11 (31H/171/CDV), EN 60947-5-6 standards are met.

EC type test certificate

BVS 04 ATEX E153

Use in hazardous areas according to classification / table 1a:

HousingGroup CategoryType of protectionExplosion groupTemperature classTa in °C
NT****NE****NF****II 2GEEx ia IICT6 -20...+70
NT****NE****NF****II 2GEEx ia IICT5 -20...+80
NG****NI****NN****NS****II 2GEEx ia IICT6 -20...+70
NG****NI****NN****NS****II 2GEEx ia IICT5 -20...+80

table 1b:

HousingGroup CategoryType of protectionExplosion groupTemperature classTa in °C
NE****NF****NG****NN****NS****NT****II 1DEx iaD 90°C-20...+70
NE****NF****NG****NN****NS****NT****II 1DEx iaD 100°C-20...+80
  • Marking
IFM NE5004 - BVS 04 ATEX E153 - 1II 2GEEx ia IIC T6CE0158TypesNT****, NE****, NF****
IFM NE5004 - BVS 04 ATEX E153 - 2II 1DEx iaD 20 T90°C
IFM NE5004 - BVS 04 ATEX E153 - 3II 2GEEx ia IIC T5CE0158TypesNT****, NE****, NF****
IFM NE5004 - BVS 04 ATEX E153 - 4II 1DEx iaD 20 T100°C
IFM NE5004 - BVS 04 ATEX E153 - 5II 2GEEx ia IIC T6CE0158TypesNG****, NI****, NN****,NS****
IFM NE5004 - BVS 04 ATEX E153 - 6II 1DEx iaD 20 T90°C
IFM NE5004 - BVS 04 ATEX E153 - 7II 2GEEx ia IIC T5CE0158TypesNG****, NI****, NN****, NS****
IFM NE5004 - BVS 04 ATEX E153 - 8II 1DEx iaD 20 T100°C

Installation / Set-up

The units should only be mounted, connected and set up by qualified staff. The qualified staff must have knowledge of protection classes, regulations and provisions for apparatus in hazardous areas.

Check whether the classification (see "Marking" above and marking on the unit) is suitable for the application.

- Connection only to intrinsically safe circuits which are approved with the EC type test certificate and do not exceed the following maximum values:

$$ U _ {i} = 1 5 \mathrm{V}, I _ {i} = 5 0 \mathrm{mA}, P _ {i} = 1 2 0 \mathrm{mW} $$

- Permissible operating temperature of the application (referred to the maximum power which can be supplied):

see table 1a / 1b

Installation remarks / Mounting

  • Adhere to the respective national regulations and provisions.
  • Avoid electrostatic charging on plastic units and cables.
  • Protect unit and cable against destruction.
  • The unit is not suitable for installation in walls which separate zone 0 from zone 1.
  • The relevant installation regulations must be adhered to.
  • Metal housing parts must be connected to potential by suitable mounting.

Maintenance / Repair

The unit must not be modified nor can it be repaired. In case of a fault please contact the manufacturer.

If needed, you can obtain the data sheet or the type test certificate from the manufacturer (see cover sheet).

• Maximum effective internal inductance (Li) and capacitance (Ci):

TypeInternal inductance total (μH)Internal capacitance total (nF)
NE5001 70 80
NF5001 340140
NF5002 340140
NF5003 130140
NF5004 130140
NG5001 4545
NG5002 4545
NG5003 5055
NG5004 5055
NI5001 140145
NI5002 140145
NI5003 110145
NI5004 110145
NN5001 135110
NN5002 135110
NT5001 70 80
NS5002 11080

The values apply to potted cables which are 2 m long.