USER MANUAL NE5004 IFM
- According to the ATEX directive 94/9/EC (ATEX) the original operating instructions and a translation of these operating instructions into the language or languages of the EU user country must be provided when a unit or protective system is put into operation within the member countries of the European Union (EU).
- If no operating instructions or EC declaration of conformity is supplied with this product in the language of the EU user country, these can be requested from your dealer (see delivery note) or manufacturer (see cover sheet / back).
- Only qualified personnel is allowed to set up the product. Furthermore, we expressly point out that any liability is excluded resulting from putting the unit into operation without the corresponding operating instructions in the language of the EU user country.
ESEspañol
Operating instructions (safety-related part ATEX) Information on the safe use in hazardous areas
Function and features
- Use in hazardous areas according to the classification
II 2G (Group II, category 2G, apparatus for gas atmosphere).
The requirements of the EN50014, EN50020, EN60947-5-6 standards are met.
EC type test certificate
PTB 01 ATEX 2191
- Use in hazardous areas according to the classification
II 1D (Group II, category 1D, apparatus for dust atmosphere).
The requirements of the prEN 61241-0, IEC 61241-11 (31H/171/CDV), EN 60947-5-6 standards are met.
EC type test certificate
BVS 04 ATEX E153
Use in hazardous areas according to classification / table 1a:
| Housing | Group Category | Type of protection | Explosion group | Temperature class | Ta in °C | |
| NT****NE****NF**** | II 2G | EEx ia IIC | T6 -20...+70 | |||
| NT****NE****NF**** | II 2G | EEx ia IIC | T5 -20...+80 | |||
| NG****NI****NN****NS**** | II 2G | EEx ia IIC | T6 -20...+70 | |||
| NG****NI****NN****NS**** | II 2G | EEx ia IIC | T5 -20...+80 | |||
table 1b:
| Housing | Group Category | Type of protection | Explosion group | Temperature class | Ta in °C | |
| NE****NF****NG****NN****NS****NT**** | II 1D | Ex iaD 90°C | -20...+70 | |||
| NE****NF****NG****NN****NS****NT**** | II 1D | Ex iaD 100°C | -20...+80 | |||
- Marking
![]() | II 2G | EEx ia IIC T6 | CE0158 | TypesNT****, NE****, NF**** |
![]() | II 1D | Ex iaD 20 T | 90°C | |
![]() | II 2G | EEx ia IIC T5 | CE0158 | TypesNT****, NE****, NF**** |
![]() | II 1D | Ex iaD 20 T | 100°C | |
![]() | II 2G | EEx ia IIC T6 | CE0158 | TypesNG****, NI****, NN****,NS**** |
![]() | II 1D | Ex iaD 20 T | 90°C | |
![]() | II 2G | EEx ia IIC T5 | CE0158 | TypesNG****, NI****, NN****, NS**** |
![]() | II 1D | Ex iaD 20 T | 100°C |
Installation / Set-up
The units should only be mounted, connected and set up by qualified staff. The qualified staff must have knowledge of protection classes, regulations and provisions for apparatus in hazardous areas.
Check whether the classification (see "Marking" above and marking on the unit) is suitable for the application.
- Connection only to intrinsically safe circuits which are approved with the EC type test certificate and do not exceed the following maximum values:
$$ U _ {i} = 1 5 \mathrm{V}, I _ {i} = 5 0 \mathrm{mA}, P _ {i} = 1 2 0 \mathrm{mW} $$
- Permissible operating temperature of the application (referred to the maximum power which can be supplied):
see table 1a / 1b
Installation remarks / Mounting
- Adhere to the respective national regulations and provisions.
- Avoid electrostatic charging on plastic units and cables.
- Protect unit and cable against destruction.
- The unit is not suitable for installation in walls which separate zone 0 from zone 1.
- The relevant installation regulations must be adhered to.
- Metal housing parts must be connected to potential by suitable mounting.
Maintenance / Repair
The unit must not be modified nor can it be repaired. In case of a fault please contact the manufacturer.
If needed, you can obtain the data sheet or the type test certificate from the manufacturer (see cover sheet).
• Maximum effective internal inductance (Li) and capacitance (Ci):
| Type | Internal inductance total (μH) | Internal capacitance total (nF) |
| NE5001 70 80 | ||
| NF5001 340 | 140 | |
| NF5002 340 | 140 | |
| NF5003 130 | 140 | |
| NF5004 130 | 140 | |
| NG5001 45 | 45 | |
| NG5002 45 | 45 | |
| NG5003 50 | 55 | |
| NG5004 50 | 55 | |
| NI5001 140 | 145 | |
| NI5002 140 | 145 | |
| NI5003 110 | 145 | |
| NI5004 110 | 145 | |
| NN5001 135 | 110 | |
| NN5002 135 | 110 | |
| NT5001 70 80 | ||
| NS5002 110 | 80 |
The values apply to potted cables which are 2 m long.
Cable unit versions:
The following values are added for cable unit versions NE****, NF****, NG****, NI****, NN****, NT****, NS**** with potted cable > 2 m: 0.9 μH (Li) / 140 pF (Ci) per metre of potted cable.