IFM DL0201 - Detector

DL0201 - Detector IFM - Free user manual and instructions

Find the device manual for free DL0201 IFM in PDF.

📄 22 pages English EN Download 💬 AI Question
Notice IFM DL0201 - page 1
View the manual : Français FR Deutsch DE English EN Magyar HU 中文 ZH
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about DL0201 IFM

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Detector in PDF format for free! Find your manual DL0201 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. DL0201 by IFM.

USER MANUAL DL0201 IFM

Operating instructions

Level control relay

DL0201

Contents

1 Preliminary note.... 3

1.1 Symbols used.... 3
1.2 Warnings.... 3
1.3 Safety symbol on the device 3

2 Safety instructions 4

2.1 Cybersecurity 4

3 Transport, handling and storage 5
4 Intended use 6
5 Function 7

5.1 Overflow protection.... 7

5.1.1 Switching diagram.... 8
5.2 Run-dry protection 9
5.2.1 Switching diagram.... 10

6 Installation.... 11

6.1 Removing the unit 12
6.2 Installation of the sensors 12

7 Electrical connection 13

7.1 Overview.... 13
7.2 General wiring information.... 13
7.3 Notes on wiring 14
7.4 Pluggable cage clamps 14
7.5 Voltage supply (power) 14

7.5.1 AC voltage supply 15
7.5.2 DC voltage supply 15
7.5.3 External DC power supply for inputs and transistor output.... 15

7.6 Inputs.... 15

7.6.1 Sensor for overflow protection.... 16
7.6.2 Sensor for run-dry protection.... 16
7.6.3 Enable input 16

7.7 Outputs.... 16

7.7.1 Relay output.... 16
7.7.2 Transistor output 17
7.7.3 Connection of the valve or pump 17

8 Operating and display elements.... 18

8.1 Potentiometer.... 18
8.2 LEDs 18

9 Settings.... 20

9.1 Input delay 20
9.2 Output delay 20

9.2.1 Output delay factor 20
9.2.2 Output delay time.... 20

10 Troubleshooting.... 21

11 Maintenance, repair and disposal 22

11.1 Maintenance 22
11.2 Cleaning the housing surface 22
11.3 Repair 22
11.4 Disposal 22

1 Preliminary note

You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at documentation.ifm.com.

1.1 Symbols used

√ Requirement
Instruction
Reaction, result

bold Designation of keys, buttons or indications

→ Cross-reference without link

→ Cross-reference with link

IFM DL0201 - Symbols used - 1

Important note

Non-compliance may result in malfunction or interference

IFM DL0201 - Symbols used - 2

Information

Supplementary note

1.2 Warnings

Warnings indicate the possibility of personal injury and damage to property. This enables safe product handling. Warnings are graded as follows:

IFM DL0201 - Warnings - 1

WARNING

Warning of serious personal injury

▷ If the warning is not observed, fatal and serious injuries are possible.

IFM DL0201 - Warnings - 2

CAUTION

Warning of minor to moderate personal injury

▷ If the warning is not observed, minor to moderate injuries are possible.

IFM DL0201 - Warnings - 3

ATTENTION

Warning of damage to property

▷ If the warning is not observed, damage to property is possible.

1.3 Safety symbol on the device

IFM DL0201 - Safety symbol on the device - 1

Safety symbol on the device:

▶ Adhere to the operating instructions for the safe operation of the unit.

2 Safety instructions

- The unit described is a subcomponent for integration into a system.

  • The system architect is responsible for the safety of the system.
  • The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the architect of the system.

  • Read this document before setting up the product and keep it during the entire service life.

  • The product must be suitable for the corresponding applications and environmental conditions without any restrictions.
  • Only use the product for its intended purpose (→ Intended use).
  • If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur.
  • The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator.
  • Installation, electrical connection, set-up, programming, configuration, operation and maintenance of the product must be carried out by personnel qualified and authorised for the respective activity.
  • Protect units and cables against damage.
  • Replace damaged units, otherwise the technical data and safety will be impaired.
  • Observe applicable documents.

2.1 Cybersecurity

Installation

The device is suitable for operation in a secure environment according to IEC 62443-1-1.

▶ Carry out a risk assessment of the system according to IEC 62443-1-1.
▶ Take measures to ensure physical security. The device has no built-in protection against unauthorised access.

3 Transport, handling and storage

▶ Store the device in its original packaging.
▶ When the device is to be stored again, use the original packaging or pack the device in suitable packaging.
▶ Observe the permissible ambient conditions for the device during storage (→ Technical data).

IFM DL0201 - Transport, handling and storage - 1

WARNING

Storage without sufficient protection for pollution degree 2

▷ Risk of electric shock when connecting the device
▶ Store the device in its original packaging.
▶ Otherwise, ensure pollution degree 2 for the device during storage.

4 Intended use

The device is used to protect a tank against overflow or running dry.

The device receives signals from an external sensor and switches its outputs according to the adjustable input and output delays.

  • The input delay protects against unintended switching caused by waves on a medium surface.
  • The output delay protects the controlled actuator (e.g. pump or valve) against excessive wear.

Sensor supply and transistor output are equipped with an independent overload/short circuit protection.

IFM DL0201 - Intended use - 1

The device is not suited for environments with particular requirements on mechanical stability (e.g. shock/vibration).

▶ Observe the operating conditions (→ Technical data at www.ifm.com).

5 Function

5.1 Overflow protection

IFM DL0201 - Overflow protection - 1

Fig. 1: Overflow protection

1: Tank with liquid or dry bulk material
2: Valve or pump (inlet)
3: Sensor with normally closed output
4: relay output
5: Transistor output
6: PLC or signalling device

Processrelay
After switching on the devicede-energised
After activation of the device via the enable signalde-energised
Level is below the sensorenergised
Level is above the sensorde-energised
Level decreases below the sensor and output delay time is startedde-energised
After output delay timeenergised

Relay energised = switched (transistor output switched)

5.1.1 Switching diagram

IFM DL0201 - Switching diagram - 1

1: Level of the medium

2: Sensor with normally closed output

3: Enable signal

4: Power supply

5: Output

SP: Switch point

X: Input delay → 20

Y: Output delay ➞ 20

Relay energised, i.e. switched (transistor output switched)

IFM DL0201 - Switching diagram - 2

Output delay (Y) is not active:

- after switching on the device

- when the sensor signal is "High" and simultaneously the enable signal changes from "Low" to "High".

5.2 Run-dry protection

IFM DL0201 - Run-dry protection - 1

Fig. 2: Run-dry protection

1: Tank with liquid or dry bulk material
2: Valve or pump (inlet)
3: Sensor with normally open output
4: relay output
5: Transistor output
6: PLC or signalling device

Processrelay
After switching on the devicede-energised
After activation of the device via the enable signalde-energised
Level is above the sensorenergised
Level is below the sensorde-energised
Level increases above the sensor and output delay time is startedde-energised
After output delay timeenergised

Relay energised = switched (transistor output switched)

5.2.1 Switching diagram

IFM DL0201 - Switching diagram - 1

1: Level of the medium

2: Sensor with normally open output

3: Enable signal

4: Power supply

5: Output

SP: Switch point

X: Input delay 20

Y: Output delay ➞ 20

Relay energised, i.e. switched (transistor output switched)

IFM DL0201 - Switching diagram - 2

Output delay (Y) is not active:

- after switching on the device

- when the sensor signal is "High" and simultaneously the enable signal changes from "Low" to "High".

6 Installation

▶ Disconnect power.

To ensure correct operation, install the device in a housing that can only be opened using a tool or in a locked control cabinet (both protection rating IP 54 or higher) as an enclosure in accordance with EN61010-1.

IFM DL0201 - Installation - 1

Always comply with pollution degree 2 for the device.

▶ Install the device vertically on a 35 mm DIN rail.

IFM DL0201 - Installation - 2

IFM DL0201 - Installation - 3

Leave enough space ( ≥ 50 mm) between the device and the top and bottom of the control cabinet to enable air circulation and to avoid excessive heating.

IFM DL0201 - Installation - 4

ATTENTION

If units are mounted side by side, inadmissible heating may occur between the units.

▷ Malfunction / damage is possible.
▶ Take into account the internal heating of all devices when mounting different devices side by side and observe the environmental conditions for each device.

6.1 Removing the unit

IFM DL0201 - Removing the unit - 1

6.2 Installation of the sensors

▶ Follow the manufacturer's installation instructions.

7 Electrical connection

7.1 Overview

IFM DL0201 - Overview - 1

Fig. 3: Wiring

IFM DL0201 - Overview - 2

Fig. 4: Terminal overview

IFM DL0201 - Overview - 3

All GND connections are internally connected with each other.

IFM DL0201 - Overview - 4

The terminals 1 and 2 are internally interconnected. The terminals 3 and 4 are internally interconnected. The terminals 21 and 22 are internally interconnected. The terminals 23 and 24 are internally interconnected.

7.2 General wiring information

IFM DL0201 - General wiring information - 1

The unit must be connected by a qualified electrician.

▶ Observe the national and international regulations for the installation of electrical equipment.

IFM DL0201 - General wiring information - 2

WARNING

Use of unconnected terminals

▷ Electric shock possible.
▶ Do not use unconnected terminals (n.c.) which are not shown in the drawing as support point terminals.
▷ Protection guaranteed.

Accessible surfaces of the device are insulated from the circuits with basic insulation according to IEC 61010-1 (mains circuit of overvoltage category II up to 300 V nominal mains voltage).

This does not apply to connection areas and cooling openings (IP20).

The AC voltage supply and relay circuit are insulated from the DC voltage supply and from each other with reinforced insulation according to IEC 61010-1 (mains circuit of overvoltage category II up to 300 V nominal mains voltage).

The external wiring has to be carried out in a way that ensures the required separation from other circuits.

7.3 Notes on wiring

Maximum length of the connection cables:

• 30 m at each terminal

IFM DL0201 - Notes on wiring - 1

It is recommended to lay all cables in the control cabinet in cable ducts.

Alternatively:

Provide all outgoing cables with suitable strain relief after a maximum of 400 mm. Observe the minimum bending radius of the cables (information from the cable manufacturer).

7.4 Pluggable cage clamps

IFM DL0201 - Pluggable cage clamps - 1

ATTENTION

No IP 20 protection without connector.

▶ Cover unused connectors with terminals.
▷ Observe IP 20.

IFM DL0201 - Pluggable cage clamps - 2

Stripping length for the supplied cage clamps: 9...10 mm

Connections that may carry mains voltage are colour-coded red on the pluggable cage clamps. This prevents them from being accidentally plugged on the SELV terminals.

Network terminals:

  • AC supply (21...24)
  • Out relay (17...20)

SELV terminals:

  • DC supply (1...4)
  • Input / Enable (5...8)
    • Out transistor (13...16)

IFM DL0201 - Pluggable cage clamps - 3

WARNING

Use of non-coded cage clamps for AC supply (21...24) and out relay (17...20)

▷ Cage clamps carrying mains voltage may be accidentally plugged onto SELV-terminals of the device.
▷ Electric shock possible.
▶ Only use the supplied coded cage clamps for network terminals.
▷ Protection guaranteed.

7.5 Voltage supply (power)

▶ Voltage supply see type label.
▶ Connect the device only to one of the possible voltage connections, either to terminals 21-22 and 23-24 (AC) or to terminals 1-2 and 3-4 (24 V DC).
▶ Lay all supply and signal cables separately. Use a screened cable if required in the application.

7.5.1 AC voltage supply

The device features an internal power supply that powers both the device and the connected sensors. There are two terminals each for L and N. The 2. terminal can be used to supply other devices with AC voltage. These terminals are bridged in the device, so unplugging will interrupt the supply to other devices.

IFM DL0201 - AC voltage supply - 1

The maximum current rating of the bridged terminals 21-22, 23-24 is 8 A.

IFM DL0201 - AC voltage supply - 2

WARNING

No internal protection of the bridged terminals 21-22, 23-24

▷ Risk of fire / electric shock due to overload / short circuit
▶ The system architect must provide external protection/limitation to 8 A in accordance with the applicable regulations
▷ Protection guaranteed

If the device is operated on an AC supply, the extra-low voltage provided for the sensor supply meets the SELV criteria according to IEC 61010-2-201.

7.5.2 DC voltage supply

▶ Comply with the SELV criteria for a DC power supply.
▶ The DC supply cable + (terminals 1/2) must be protected externally with a 315 mA time-lag fuse (5 x 20 mm or similar).
▶ The supply of the subsequent devices is not intended.

The DC supply terminals are directly connected to the sensor supply terminals.

7.5.3 External DC power supply for inputs and transistor output

The inputs and the transistor output can optionally be operated via an external +24 V DC power supply.

IFM DL0201 - External DC power supply for inputs and transistor output - 1

WARNING

No internal protection of inputs and transistor output

▷ Potential fire hazard
▶ The system architect must provide external protection/limitation to 315 mA in accordance with the applicable regulations
A common fuse for inputs and outputs is permitted.
▷ Protection guaranteed

▶ Connect the reference point (GND) of the external power supply with terminal 15 or 3/4 of the device. Otherwise no switching operation is possible.
▶ The SELV criteria must be observed for external voltage supply.

7.6 Inputs

IFM DL0201 - Inputs - 1

The connection of mechanical switch contacts is not recommended since they tend to bounce and produce faulty pulses.

Terminals 5 and 7 can be used for the sensor supply.

7.6.1 Sensor for overflow protection

IFM DL0201 - Sensor for overflow protection - 1

Use a sensor with normally closed output for overflow protection (Overflow protection → 7).

3-wire DC PNP
2-wire DC quadronorm
2-wire AC/DC
Mechanical switch
IFM DL0201 - Sensor for overflow protection - 2

IFM DL0201 - Sensor for overflow protection - 3

IFM DL0201 - Sensor for overflow protection - 4

IFM DL0201 - Sensor for overflow protection - 5

BN: brown

BU: blue

BK: black

WH: white

7.6.2 Sensor for run-dry protection

IFM DL0201 - Sensor for run-dry protection - 1

For proper operation, use a sensor with normally open output (Run-dry protection → 9).

3-wire DC PNP
2-wire DC quadronorm
2-wire AC/DC
Mechanical switch
IFM DL0201 - Sensor for run-dry protection - 2

IFM DL0201 - Sensor for run-dry protection - 3

IFM DL0201 - Sensor for run-dry protection - 4

IFM DL0201 - Sensor for run-dry protection - 5

BN: brown

BU: blue

BK: black

WH: white

7.6.3 Enable input

The enable signal is required to activate the device. It can be supplied directly from 24 V DC or from terminal 5 or controlled by another sensor (for example leakage sensor).

When + 24 V DC is applied, the device is active.

7.7 Outputs

The relay and transistor output have the same switching status.

7.7.1 Relay output

Relay for general use according to IEC 61010-2-201.

IFM DL0201 - Relay output - 1

WARNING

No internal protection of the relay output

▷ Risk of fire / electric shock due to overload / short circuit
▶ The system architect must provide external protection/limitation to 6 A in accordance with the applicable regulations
▷ Protection guaranteed

▶ To prevent excessive wear and to comply with the EMC standards, interference suppression of the contacts is required for switching inductive loads.

IFM DL0201 - Relay output - 2

WARNING

Connection of different AC phase conductors to the AC power supply and relays

▷ Electric shock possible
▶ Connect the same phase conductor to the AC voltage supply and the relay.
▷ Protection guaranteed

IFM DL0201 - Relay output - 3

If the relay output is used to switch very small currents (e.g. PLC inputs), considerable contact resistance can arise. In this case use the transistor outputs for DC.

▶ Connect the changeover contact according to the valve or pump being used (Connection of the valve or pump ➞ 17).

7.7.2 Transistor output

The transistor output needs an external +24 V DC supply on terminal 13 (see External DC power supply for inputs and transistor output ➕ 15).

IFM DL0201 - Transistor output - 1

The transistor output is only intended for resistive loads. Do not connect any inductive loads.

7.7.3 Connection of the valve or pump

The principle of normally open operation must be adhered to for the connection of the valve or the pump. For example, connect the normally open output of the device (terminals 17/18) to a valve with normally closed operation.

IFM DL0201 - Connection of the valve or pump - 1

By adhering to the principle of normally open operation the inlet or outlet of the medium is blocked in the event of a wire break or a power failure.

8 Operating and display elements

IFM DL0201 - Operating and display elements - 1

1: LEDs
2: Potentiometer
3: panel for labelling

8.1 Potentiometer

PotentiometerSetting
Input DelayInput delay [s](Input delay → 20)
Output Delay (factor)Output delay factor [sec (x1), min (x1), sec (x2), min (x2)](Output delay factor → 20)
Output Delay (time)Output delay(Output delay time → 20)

8.2 LEDs

LEDColourStateDescription
PowerGreenOnOK voltage supply
FlashingPotentiometer Output Delay (factor) in invalid setting zone
InputYellowOnInput signal "High"
OutputGreenOnrelay energised
Transistor switched
FlashingOutput delay active
EnableYellowOnEnable input switched (+24 V DC is applied to the enable input). Device activated.

Error signals and diagnostics under Troubleshooting ➞ 21

9 Settings

▶ Set the continuously adjustable potentiometer using a suitable screwdriver.

9.1 Input delay

The input delay sets the minimum duration of the stable input signal to be evaluated. It protects against unintended switching caused by waves on a medium surface.

Value: 0...10 s

9.2 Output delay

The output delay sets the minimum duration of the output in de-energised state. It protects the controlled actuator (e.g. pump or valve) against excessive wear.

Value: 0...30 s / 0...60 s / 0...30 min / 0...60 min (depending on the output delay factor and the output delay time)

9.2.1 Output delay factor

IFM DL0201 - Output delay factor - 1

Fig. 5: "Output delay (factor)" potentiometer

□ Valid setting zone
■ Invalid setting zone
▶ Make sure that the setting of the potentiometer is within a valid zone.
▷ If the setting is outside a valid zone, the device is disabled and Power flashes.

Value: sec (x1), min (x1), sec (x2), min (x2)

9.2.2 Output delay time

Value: 0...30

10 Troubleshooting

LEDErrorTroubleshooting
PowerInputOutputEnable
Output delay time is activeWait till output delay time is expired
----Potentiometer "Output Delay (factor)" in invalid setting zoneCorrect the potentiometer position (Output delay factor ➔ 20)
Short circuit at sensor supplyRemove the short circuit.
----Short circuit at transistor outputRemove the short circuit.
--Internal device errorContact service

Legend:

○ Off

- On

Flashing

-- any

11 Maintenance, repair and disposal

11.1 Maintenance

The unit is maintenance-free.

11.2 Cleaning the housing surface

▶ Disconnect the device from the voltage supply.
▶ Clean the device from dirt using a soft, chemically untreated and dry micro-fibre cloth.

11.3 Repair

▶ The device must only be repaired by the manufacturer. Observe the safety instructions (→ Safety instructions).

11.4 Disposal

▶ After use, dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations.

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : IFM

Model : DL0201

Category : Detector