IF5792 - Inductive sensor IFM - Free user manual and instructions
Find the device manual for free IF5792 IFM in PDF.
Questions des utilisateurs sur IF5792 IFM
0 question sur cet appareil. Repondez a celles que vous connaissez ou posez la votre.
Poser une nouvelle question sur cet appareil
Download the instructions for your Inductive sensor in PDF format for free! Find your manual IF5792 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. IF5792 by IFM.
USER MANUAL IF5792 IFM
DC2 Function and features This sensor detects metals without contact and indicates their presence by providing a switched signal. Nominal sensing range (Sn) see type label; (value based on standard measurement with mild steel; a shorter sensing range for other metals). Installation
- Flush or non-flush installation (see type label: Sn = Xmm f or Xmm nf) (→ fig. 1)
- Open space around the sensing face when mounted in metal (→ fig. 2).
- Minimum distance when several sensors of the same type are mounted (→ fig. 3, 4). Sn = x mm f Sn = x mm nf
Electrical connection ► Disconnect power before connecting the proximity switch; connection:
- For cables longer than 30 m and wires greater than 0.5 mm² the cable should be laid separately from sources of interference (at a distance of about 50 cm) or a screened cable should be used.
- Connect the load before applying the operating voltage.
- Observe the values for current rating and minimum load current.
- If capacitive loads are used, ensure that the peak current rating is not exceeded.4 ► Do not connect loads of low resistance (e.g. lamps) directly to the sensor. Switch these loads via a relay (→ fig. 6):
► For inductive loads a RC circuit should be connected in parallel to the load (→ fig. 7).
► A load which is too low for 2-wire sensors may lead to malfunction. In such a case a resistor should be connected in parallel to the load (→ fig. 8).
- For series connection consider the voltage drop of each unit.5
► As a rule avoid connecting 2-wire units in parallel (only in exceptional cases, check the safe function, → fig. 9):
► The supply voltage must correspond to the values indicated on the label. If it is not stabilised, a capacitor should be connected (at 24 V and 1 A for example a capacitor of 1000 μF, 50 WV → fig. 10):
EasyManual