TOSHIBA MMK-AP0153H - Air-conditioner

MMK-AP0153H - Air-conditioner TOSHIBA - Free user manual and instructions

Find the device manual for free MMK-AP0153H TOSHIBA in PDF.

📄 67 pages English EN Download 💬 AI Question 13 questions ⚙️ Specs
Notice TOSHIBA MMK-AP0153H - page 3
View the manual : Français FR English EN
Pick your language and provide your email: we'll send you a specifically translated version.
Device TypeWall-mounted VRF multi-split indoor unit
Cooling Capacity4.5 kW
Heating Capacity5 kW
Recommended Area45 m2
RefrigerantR410A (HFC)
Indoor Unit Weight15 kg
TechnologyInverter
System CompatibilityVRF Toshiba SMMS / SMMSi
Remote ControlWireless included (range 7 m)
Piping Directions6 directions (right, left, rear right, rear left, bottom right, bottom left)
Minimum Installation Height2 m (top of the unit)
Air FilterAccessible via front grille, washable

Frequently Asked Questions - MMK-AP0153H TOSHIBA

Is the Toshiba MMK-AP0153H compatible with all outdoor units?
No. The MMK-AP0153H is a wall-mounted indoor unit designed for Toshiba VRF multi-split systems (SMMS and SMMSi ranges). It must be connected to a compatible Toshiba outdoor unit by a qualified installer. It is not intended to operate in a traditional single-split setup.
What is the cooling and heating capacity of this device?
The MMK-AP0153H delivers 4.5 kW in cooling and 5 kW in heating. These capacities make it suitable for rooms of about 40 to 45 m2 with standard ceiling height.
What refrigerant does the MMK-AP0153H use?
This device uses R410A, an HFC refrigerant with no impact on the ozone layer. The pressure of this fluid is about 1.6 times higher than that of R22: specific R410A tools are required during installation or maintenance.
At what height should the indoor unit be installed?
The top of the unit should be at least 2 m above the floor. You should also provide a clearance of 850 mm above the device and 170 mm on the sides to ensure air circulation and facilitate maintenance.
In how many directions can the piping be routed?
The piping can be routed in 6 directions: right, left, rear right, rear left, bottom right, bottom left. This flexibility greatly simplifies installation in various room configurations.
Is the wireless remote control included with the device?
Yes. The MMK-AP0153H comes with a wireless remote control, a wall mount for the remote, and two batteries (R03 / AAA). The reception range is about 7 m in axial. Avoid placing the remote near a fluorescent light source or heat.
Is the air filter easily accessible?
Yes. The filter is accessible through the front air intake grille that opens upward without tools. It is recommended to clean the filter regularly (every 2 weeks in intensive use) with warm water and let it dry before replacing it.
The remote control is not working, what should I do?
First, check the condition of the batteries (type R03/AAA) and replace them if necessary. Ensure there is no obstacle between the remote and the unit's IR receiver, and that you are not more than 7 m away. Inverter-type fluorescent lights and direct sunlight can interfere with reception.
Can this device be installed in a kitchen or an area highly exposed to oil?
Installation is not recommended in a restaurant kitchen or near industrial machines using a lot of oil. Greasy vapors can clog the heat exchanger, reduce performance, and damage resin parts. Prefer installation in a clean and well-ventilated space.
What does VRF mean and how is it different from a standard split system?
VRF (Variable Refrigerant Flow) refers to a technology where several indoor units like the MMK-AP0153H are connected to a single powerful outdoor unit, with a variable refrigerant flow. Unlike a simple split system, a VRF system allows air conditioning of multiple zones independently and offers better energy efficiency on a large scale.
What precautions should be taken in case of a refrigerant leak?
In the event of an R410A leak, immediately ventilate the area and keep away from any flame. Contact a certified technician: handling refrigerant is regulated and reserved for qualified professionals. Never attempt to refill the circuit yourself.
What is the maximum recommended area for this model?
The MMK-AP0153H is sized for an area of about 45 m2 under standard conditions (adequate insulation, ceiling height of approximately 2.5 m). For poorly insulated rooms or those with large glass surfaces, it is advisable to request a thermal assessment.

User questions about MMK-AP0153H TOSHIBA

1 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

What do the symbols displayed on the TOSHIBA MMK-AP0153H air conditioner mean?
Frequently Asked Questions - 02/03/2026
Response Notice-Facile

The symbols displayed on your TOSHIBA MMK-AP0153H air conditioner correspond to the various functions and settings available to optimize its use. Here are the most common symbols and their meanings:

  • Power Symbol: A circle with a vertical line at the top, indicating the device's power on or off.
  • Fan Speed: An icon in the shape of a fan that allows you to adjust the airflow speed (low, medium, high).
  • Temperature Control: A thermometer symbolizing the ability to increase or decrease the desired temperature.
  • Mode Selection:
    • Snowflake: cooling mode
    • Sun: heating mode
    • Water droplets: dehumidification mode
    • Wind: ventilation only mode
  • Timer: A clock that allows you to schedule automatic shut-off or power on at a set time.
  • Sleep Mode: A crescent moon indicating quiet and economical operation for the night.
  • Oscillation: Arrows or a fan with curved lines indicating that the adjustable louvers move to distribute air evenly.

These symbols facilitate a quick understanding of the active functions on your air conditioner and help you adjust the settings according to your needs.

Respond (be the first)

Download the instructions for your Air-conditioner in PDF format for free! Find your manual MMK-AP0153H - TOSHIBA and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. MMK-AP0153H by TOSHIBA.

USER MANUAL MMK-AP0153H TOSHIBA

Leading Innovation >>

SUPER MODULAR MULTI SYSTEM AIR CONDITIONER

Installation Manual

HFC

R410A

SUPER

SUPER MODULAR MULTI

Indoor Unit

Model name:

High-Wall Type

MMK-AP0073H, MMK-AP0073H-C
MMK-AP0093H, MMK-AP0093H-C
MMK-AP0123H, MMK-AP0123H-C
MMK-AP0153H, MMK-AP0153H-C
MMK-AP0183H, MMK-AP0183H-C
MMK-AP0243H, MMK-AP0243H-C

TOSHIBA MMK-AP0153H - Indoor Unit - 1

For commercial use

Pour usage commercial

Please read this Installation Manual carefully before installing the Air Conditioner.

  • This Manual describes the installation method of the indoor unit.
  • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.

ADOPTION OF NEW REFRIGERANT

This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.

Contents

1 ACCESSORY PARTS 2
2 PRECAUTIONS FOR SAFETY 3
3 SELECTION OF INSTALLATION PLACE 5
4 INSTALLATION OF INDOOR UNIT 7
5 CUTTING A HOLE AND MOUNTING INSTALLATION PLATE 8
6 Piping and Drain Hose Installation 9
7INDOOR UNIT FIXING 12
8 DRAINAGE 12
9 REFRIGERANT PILING 13
10 ELECTRIC WORK 15
11 APPLICABLE CONTROLS 21
12 TEST RUN 24
13 TROUBLE SHOOTING 26

1 ACCESSORY PARTS

Accessory parts

Part nameQ'tyShape
Installation plate1
Wireless remote controller1
Battery2
Remote control holder1
Mounting screw Ø4 × 25l6
Pan head wood screw Ø3.1 × 16l2×
Screw Ø4 × 10l2
Heat insulator1

Name
Owner's manual
Installation manual

2 PRECAUTIONS FOR SAFETY

  • Ensure that all Local, National and International regulations are satisfied.
  • Read this "PRECAUTIONS FOR SAFETY" carefully before Installation.
  • The precautions described below include the important items regarding safety. Observe them without fail.
  • After the installation work, perform a trial operation (test run) to check for any problem. Follow the Owner's Manual to explain how to use and maintain the unit to the customer.
  • Turn off the main power supply switch (or breaker) before the unit maintenance.
  • Ask the customer to keep the Installation Manual together with the Owner's Manual.

TOSHIBA MMK-AP0153H - PRECAUTIONS FOR SAFETY - 1

WARNING

  • Ask an authorized dealer or qualified installation professional to install (including moving)/ maintain the air conditioner.

Inappropriate installation may result in water leakage, electric shock or fire.

  • Be sure to connect earth wire. (grounding work)

Incomplete grounding cause an electric shock.

Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.

  • Turn off the main power supply switch or breaker before attempting any electrical work.

Make sure all power switches are off. Failure to do so may cause electric shock.

  • Install the refrigerant pipe securely during the installation work before operating the air conditioner.

If the air conditioner is operated with the valve open and without the refrigerant pipe, the compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.

  • When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.

If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons.

  • Perform installation work properly according to the Installation Manual.

Inappropriate installation may result in water leakage, electric shock or fire.

  • When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level.

  • Install the air conditioner securely in a location where the base can sustain the weight adequately.

  • Perform the specified installation work to guard against an earthquake.

If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.

  • If refrigerant gas has leaked during the installation work, ventilate the room immediately.

If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.

  • After the installation work, confirm that refrigerant gas does not leak.

If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.

  • Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive power supply.

An insufficient power supply capacity or inappropriate installation may cause fire.

  • Use the specified wires for wiring connect the terminals securely fix.

To prevent external forces applied to the terminals from affecting the terminals.

  • Conform to the regulations of the local electric company when wiring the power supply.

Inappropriate grounding may cause electric shock.

  • For the refrigerant recovery work (collection of refrigerant from the pipe to the compressor), stop the compressor before disconnecting the refrigerant pipe.

If the refrigerant pipe is disconnected while the compressor is working with the valve open, the compressor sucks air and the refrigeration cycle is over pressurized, which may cause a burst or injury.

TOSHIBA MMK-AP0153H - WARNING - 1

CAUTION

New Refrigerant Air Conditioner Installation

  • THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
  • The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
  • To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
  • Accordingly the exclusive tools are required for the new refrigerant (R410A).
  • For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.

To Disconnect the Appliance from Main Power Supply.

  • This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3mm .
  • The installation fuse must be used for the power supply line of this conditioner.
  • Tighten the flare nut with a torque wrench in the specified manner.

Excessive tightening of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.

  • Wear heavy gloves and a long sleeve shirt during the installation work to avoid injury.

3 SELECTION OF INSTALLATION PLACE

TOSHIBA MMK-AP0153H - SELECTION OF INSTALLATION PLACE - 1

WARNING

  • Install the air conditioner at enough strong place to withstand the weight of the unit.

If the strength is not enough, the unit may fall down resulting in injury.

TOSHIBA MMK-AP0153H - WARNING - 1

CAUTION

  • Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.

If a combustible gas leaks and stays around the unit, a fire may occur.

Upon approval of the customer, install the air conditioner in a place that satisfies the following conditions.

  • Place where the unit can be installed horizontally.
  • Place where a sufficient servicing space can be ensured for safety maintenance and check.
  • Place where drained water will not cause any problem.

Avoid installing in the following places.

  • Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring).
    (Should the unit be used in these places, special protective measures are needed.)
  • A restaurant kitchen where a lot of oil is used or place near machines in a factory (Oil adhering to the heat exchanger and resin part (cross flow fan) in the indoor unit may reduce the performance, generate mist or dew drop, or deform or damage resin parts.)
  • Place where organic solvent is used nearby.
  • Place close to a machine generating high frequency.
  • Place where the discharged air blows directly into the window of the neighbour house. (Outdoor unit)
  • Place where noise of the outdoor unit is easily transmitted. (When install the outdoor unit on the boundary with the neighbour, pay due attention to the level of noise.)
  • Place with poor ventilation.
  • Do not use the air conditioner for special purposes such as preserving food, precision instruments, or art objects, or where breeding animals or growing plants are kept. (This may degrade the quality of preserved materials.)
  • Place where any of high-frequency appliances (including inverter devices, private power generators, medical equipment, and communication equipment) and inverter-type fluorescent light is installed. (A malfunction of the air conditioner, abnormal control, or problems due to noise to such appliances/ equipment may occur.)
  • When the wireless remote controller is used in a room equipped with an inverter-type fluorescent light or at a place exposed to direct sunlight, signals from the remote controller may not be received correctly.
  • Place where organic solvent is used.
  • Place near a door or window exposed to humid outside air (Dew dropping may form.).
  • Place where special spray is used frequently.

Installation diagram of Indoor and outdoor units

TOSHIBA MMK-AP0153H - Installation diagram of Indoor and outdoor units - 1

Installation space

The indoor unit shall be installed so that its top surface comes at a height of 2m or more.

Also it must be avoided to put anything on top of the indoor unit.

1 Reserve space required to install the indoor unit and for service work.
Keep 110mm or more for clearance between top plate of the indoor unit and the ceiling surface.
2 Provide a space as shown for service clearance for the cross flow fan.

Installation place

  • A place which provides the spaces around the indoor unit as shown in the above diagram.
  • A place where there is no obstacle near the air inlet and outlet.
  • A place that allows easy installation of the piping to the outdoor unit.
  • A place which allows the front panel to be opened.

TOSHIBA MMK-AP0153H - Installation place - 1

CAUTION

  • Direct sunlight to the indoor unit's wireless receiver should be avoided.
  • The microprocessor in the indoor unit should not be too close to RF noise sources. (For details, see the owner's manual.)

■ Wireless remote controller

  • A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
  • Do not install the remote controller in a place exposed to direct sunlight or close to a heating source, such as a stove.
  • Keep the remote controller at least 1m apart from the nearest TV set or stereo equipment.

(This is necessary to prevent image disturb-bounces or noise interference.)

  • The location of the remote controller should be determined as shown below.

TOSHIBA MMK-AP0153H - ■ Wireless remote controller - 1
*: Axial distance

4 INSTALLATION OF INDOOR UNIT

TOSHIBA MMK-AP0153H - INSTALLATION OF INDOOR UNIT - 1

WARNING

Install the air conditioner certainly to sufficiently withstand the weight.

If the strength is insufficient, the unit may fall down resulting in human injury.

Perform a specified installation work to guard against strong wind or earthquake.

An incomplete installation can cause accidents by the units falling and dropping.

REQUIREMENT

Strictly comply with the following rules to prevent damage of the indoor units and human injury.

  • Do not put a heavy article on the indoor unit. (Even units are packaged)
  • Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be sure to use buffering cloth, etc. to not damage the unit.
  • To move the indoor unit, do not apply force to the refrigerant pipe, drain pan, foamed parts, or resin parts, etc.
  • Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.

Be careful to the following items when installing the unit.

  • Considering air discharge direction, select an installation place where discharge air can circulate evenly in a room. Avoid to install the unit at place with "NO GOOD" mark in the right figure.

OK

Good installation place Cooled well all over.

TOSHIBA MMK-AP0153H - OK - 1

NO GOOD

Bad installation place

Not cooled well.

TOSHIBA MMK-AP0153H - NO GOOD - 1

TOSHIBA MMK-AP0153H - NO GOOD - 2

5 CUTTING A HOLE AND MOUNTING INSTALLATION PLATE

Cutting a hole

In case of installing the refrigerant pipes from the rear:

  1. Decide the hole position for piping at 180mm from the arrow mark () on the installation plate and drill a hole at a slight downward slant toward outdoor side. Pipe hole; dia.65mm: AP007-AP018 type Pipe hole; dia.80mm: AP024 type

TOSHIBA MMK-AP0153H - Cutting a hole - 1

NOTE

  • When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.

Mounting the installation plate

Be sure that the installation plate is fix to the wall with screws to make the indoor unit fit to the wall.

TOSHIBA MMK-AP0153H - Mounting the installation plate - 1

When the installation plate is directly mounted on the wall

  1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
  2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
  3. Install the installation plate horizontally in the wall.

CAUTION

When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.

TOSHIBA MMK-AP0153H - CAUTION - 1

CAUTION

Failure to firmly install the unit may result in personal injury and property damage if the unit falls.

  • In case of block, brick, concrete or similar type walls, make 5mm dia. holes in the wall.
  • Insert clip anchors for appropriate mounting screws.

NOTE

  • Secure four corners and lower parts of the installation plate with 6 mounting screws to install it.

6 Piping and Drain Hose Installation

Piping and drain hose forming

  • Apply heat-insulation for both refrigerant pipe and drain hose surely so that no dew generates inside of the equipment. (Use polyethylene foam for insulating material.)

TOSHIBA MMK-AP0153H - Piping and drain hose forming - 1

1. Remove the front panel

The front panel must be removed for piping connections in the left, bottom left, and rear left directions.

  • Open the air inlet grille upward.
  • Remove the four screws securing the front panel.
  • Slightly open the lower part of the front panel, and then pull the upper part of the front panel toward you to remove it from the rear plate.

TOSHIBA MMK-AP0153H - Remove the front panel - 1

2. Die-cutting front panel slit

Cut out the slit on the leftward or right side of the front panel for the left or right connection and the slit on the bottom left or right side of the front panel for the bottom left or right connection with a pair of nippers.

3. Changing drain hose

For leftward connection, bottom-leftward connection and rear leftward connection's piping, it is necessary to change the drain hose and drain cap.

Without changing the drain hose position, the indoor unit will not fit to the wall.

How to remove the drain hose

  • The drain hose can be removed by removing the screw securing the drain hose and then pulling out the drain hose.
  • When removing the drain hose, be careful of any sharp edges of steel plate. The edges can injuries.
  • To install the drain hose, insert the drain hose firmly until the connection part contacts with heat insulator, and the secure it with original screw.

TOSHIBA MMK-AP0153H - How to remove the drain hose - 1
Heat insulator

How to remove the drains cap

Clip the drain cap by needle-nose pliers and pull out.

TOSHIBA MMK-AP0153H - How to remove the drains cap - 1

How to fix the drains cap

1) Insert hexagonal wrench (dia. 4mm) in a centre head.

TOSHIBA MMK-AP0153H - How to fix the drains cap - 1

2) Firmly insert drains cap.

TOSHIBA MMK-AP0153H - How to fix the drains cap - 2

TOSHIBA MMK-AP0153H - How to fix the drains cap - 3

CAUTION

Firmly insert the drain hose and drain cap; otherwise, water may leak.

How to remove the drain hose

1) Remove the front panel.
2) Remove the screws of drain hose.
3) Pull out the drain hose.

How to fix the drain hose

1) Put the drain hose.
2) Screw the drain hose to the indoor unit.
3) Install the front panel.

In case of right or left piping

After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool.

TOSHIBA MMK-AP0153H - In case of right or left piping - 1

In case of bottom right or bottom left piping

  • After scribing slits of the front panel with a knife or a marking-off pin, cut them with a pair of nippers or an equivalent tool.

TOSHIBA MMK-AP0153H - In case of bottom right or bottom left piping - 1

Left-hand connection with piping

Bend the connecting pipe so that it is laid within 43mm above the wall surface. If the connecting pipe is laid exceeding 43mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.

Bend the connection pipe within a radius of 30~mm

To connect the pipe after installation of the unit (figure)

TOSHIBA MMK-AP0153H - Bend the connection pipe within a radius of 30~mm - 1

TOSHIBA MMK-AP0153H - Bend the connection pipe within a radius of 30~mm - 2

NOTE

If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.

After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.

TOSHIBA MMK-AP0153H - NOTE - 1

CAUTION

  • Bind the auxiliary pipes (two) and power supply wiring and control wiring with facing tape tightly. In case of leftward piping and rear leftward piping, bind the auxiliary pipes (two) only with facing tape.

TOSHIBA MMK-AP0153H - CAUTION - 1

  • Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
  • Carefully connect the auxiliary pipes and connecting pipes to one another and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
  • Since dew results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
  • When bending a pipe, carefully do it, not to crush it.

7 INDOOR UNIT FIXING

  1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
  2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
  3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.

TOSHIBA MMK-AP0153H - INDOOR UNIT FIXING - 1

  • For detaching the indoor unit from the installation plate, pull the indoor unit toward you while pushing its bottom up at the specified parts.

TOSHIBA MMK-AP0153H - INDOOR UNIT FIXING - 2

REQUIREMENT

The lower part of indoor unit may float, due to the condition of piping and you cannot fix it to the installation plate. In that case, use the screws provided to fix the unit and the installation plate. Especially when the pipes are pulled out from the left side, the unit must be screwed to the installation plate.

TOSHIBA MMK-AP0153H - REQUIREMENT - 1

8 DRAINAGE

  1. Run the drain hose sloped downwards.

NOTE

  • Hole should be made at a slight downward slant on the outdoor side.

  • Put water in the drain pan and make sure that the water is drained out of doors.

  • When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.

TOSHIBA MMK-AP0153H - NOTE - 1

TOSHIBA MMK-AP0153H - NOTE - 2

TOSHIBA MMK-AP0153H - NOTE - 3

CAUTION

Arrange the drain pipe for proper drainage from the unit.

Improper drainage can result in dew-dropping.

This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan.

Therefore, do not store the power cord and other parts at a height above the drain guide.

TOSHIBA MMK-AP0153H - CAUTION - 1

9 REFRIGERANT PIPING

Refrigerant Piping

  1. Use copper pipe with 0.8 ~mm or more thickness. (In case pipe size is dia. 15.9, with 1.0 ~mm or more.)
  2. Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut attached to the main unit of the air conditioner, and use it.

REQUIREMENT

When the refrigerant pipe is long, provide support brackets at intervals of 2.5 to 3m to clamp the refrigerant pipe. Otherwise, abnormal sound may be generated.

TOSHIBA MMK-AP0153H - REQUIREMENT - 1

CAUTION

IMPORTANT 4 POINTS FOR PIPING WORK

  1. Remove dust and moisture from the inside of the connecting pipes.
  2. Tight connection (between pipes and unit)
  3. Evacuate the air in the connecting pipes using VACUUM PUMP.
  4. Check the gas leakage. (Connected points)

Pipe size

(dia.: mm)

MMK-AP007 to AP012 typeAP015 to AP018 typeAP024 type
Gas side9.512.715.9
Liquid side6.46.49.5

■ Permissible Piping Length and Height Difference

They vary according to the outdoor unit.

For details, refer to the Installation Manual attached to the outdoor unit.

Flaring

  • Cut the pipe with a pipe cutter.

Remove burrs completely.

Remaining burrs may cause gas leakage.

  • Insert a flare nut into the pipe, and flare the pipe. As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.

However, the conventional tools can be used by adjusting projection margin of the copper pipe.

TOSHIBA MMK-AP0153H - Flaring - 1

Projection margin in flaring: B (Unit: mm)

Rigid (Clutch type)

Outer dia. of copper pipeR410A tool usedConventional tool used
R410AR410A
6.4, 9.50 to 0.51.0 to 1.5
12.7, 15.9

Flaring dia. meter size: A (Unit: mm)

Outer dia. of copper pipeA+0.4
R410A
6.49.1
9.513.2
12.716.6
15.919.7
  • In case of flaring for R410A with the conventional flare tool, pull it out approx.

0.5 mm more than that for R22 to adjust to the specified flare size.

The copper pipe gauge is useful for adjusting projection margin size.

TOSHIBA MMK-AP0153H - Flaring dia. meter size: A (Unit: mm) - 1

Tightening connection

TOSHIBA MMK-AP0153H - Tightening connection - 1

CAUTION

  • Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

(Unit:N·m)

Outer dia. of copper pipeTightening torque
6.4 mm (dia.)14 to 18 (1.4 to 1.8 kgf*m)
9.5 mm (dia.)33 to 42 (3.3 to 4.2 kgf*m)
12.7 mm (dia.)50 to 62 (5.0 to 6.2 kgf*m)
15.9 mm (dia.)68 to 82 (6.8 to 8.2 kgf*m)

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.

(Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

TOSHIBA MMK-AP0153H - Tightening torque of flare pipe connections - 1
Work using double spanner

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

Piping with outdoor unit

  • Shape of valve differs according to the outdoor unit.

For details of installation, refer to the Installation Manual of the outdoor unit.

Heat insulation

Heat insulation for the pipes should be done separately for the liquid side and gas side. Because both of the liquid and gas side pipes become a low temperature during cooling operation, sufficient heat insulation should be done to prevent condensation.

  • Heat insulator with a heat resistance of 120^ or more must be used for the gas side pipe.
  • The pipe connection section of the indoor unit must be heat insulated securely and compactly with the attached heat insulator.

TOSHIBA MMK-AP0153H - Heat insulation - 1

Airtight test/Air purge, etc.

For airtight test, air purge, addition of refrigerant, and gas leak check, follow the Installation Manual attached to the outdoor unit.

- Open fully valves of the outdoor unit

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively HFC refrigerant (R410A, R134a, etc.).

10 ELECTRIC WORK

TOSHIBA MMK-AP0153H - ELECTRIC WORK - 1

WARNING

  1. Using the specified wires, ensure to connect the wires, and fix wires securely so that the external tension to the wires do not affect the connecting part of the terminals. Incomplete connection or fixation may cause a fire, etc.
  2. Be sure to connect earth wire. (grounding work) Incomplete grounding cause an electric shock. Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone wires.
  3. Appliance shall be installed in accordance with national wiring regulations.

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.

TOSHIBA MMK-AP0153H - WARNING - 1

CAUTION

  • If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke.
  • Be sure to install an earth leakage breaker that is not tripped by shock waves. If an earth leakage breaker is not installed, an electric shock may be caused.
  • Be sure to use the cord clamps attached to the product.
  • Do not damage or scratch the conductive core and inner insulator of power and interconnecting wires when peeling them.
  • Use the power cord and Inter-connecting wire of specified thickness, type, and protective devices required.
  • Never connect 220–240V power to the terminal blocks (U1, U2, A, B, etc.) for control wiring.

(Otherwise, the system will fail.)

REQUIREMENT

  • For power supply wiring, strictly conform to the Local Regulation in each country.
  • For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.
  • Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.

The coating may melt resulting in an accident.

After connecting wires to the terminal blocks, provide a trap and fix wires with the cord clamp.

  • Run the refrigerant piping line and control wiring line in the same line.
  • Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.

Power supply wire and communication wires specifications

Power supply wire and communication wires are procured locally.

For the power supply specifications, follow the table below. Power supply wiring and communication wiring are to be procured locally.

For specifications of the power capacity of the outdoor unit and the power supply wires, refer to the

Installation Manual supplied with the outdoor unit.

Indoor unit power supply

  • Prepare an exclusive power supply for the indoor unit independently of the outdoor unit.
  • Arrange the power supplies to the indoor and outdoor units, so that a common earth leakage breaker and main switch can be used.
  • Power supply wire specification: Cable 3-core 2.5mm^2 , in conformity with Design H07 RN-F or 60245 IEC 57.

Power supply

Power supply220–240V ~ 50Hz 220V ~ 60Hz
Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for indoor units should be selected by the accumulated total current values of the indoor units.
Power supply wiringBelow 50m2.5 mm²

Control wiring, Central controller wiring

  • Use a 2 core non polarity wire.
  • To prevent any possible noise issues, use a shielded 2 core wire.
  • The total stated length of communication wiring is determined by the interconnecting length of indoor to outdoor wire plus the length of the central control communication wire.

Communication line

Control wiring between indoor units, and outdoor unit (2-core shield wire)Wire size(Up to 1000m) 1.25 mm² (Up to 2000m) 2.0 mm²
Central control line wiring (2-core shield wire)Wire size(Up to 1000m) 1.25 mm² (Up to 2000m) 2.0 mm²

Wired remote controller wiring

This wiring is not required when using the supplied wireless remote controller.

  • For wiring remote controllers a 2 core non polarity wire must be used.
Wired remote controller wiring, remote controller inter-unit wiringWire size: 0.5mm² to 2.0mm²
Total wire length of wired remote controller wiring and remote controller inter-unit wiring = L + L1 + L2 + ... LnIn case of wired type onlyUp to 500m
In case of wireless type includedUp to 400m
Total wire length of wired remote controller inter-unit wiring = L1 + L2 + ... LnUp to 200m

TOSHIBA MMK-AP0153H - Wired remote controller wiring - 1

CAUTION

The remote controller wire (Communication line) and AC220-240V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise, etc.

TOSHIBA MMK-AP0153H - CAUTION - 1

Control wiring between indoor and outdoor units

NOTE

An outdoor unit that is interconnected to the indoor units automatically becomes the header unit.

Wiring example

TOSHIBA MMK-AP0153H - Wiring example - 1

Address setup

Set up the addresses as per the Installation Manual supplied with the outdoor unit.

■ Wired remote controller wiring

  • As the wired remote controller wire has non-polarity, there is no problem if connections to indoor unit terminal blocks A and B are reversed.

Wiring diagram

TOSHIBA MMK-AP0153H - Wiring diagram - 1

Wiring Connection

How to connect the power supply wiring and control wiring

The power supply wire and the control wire can be connected without removing the front panel.

REQUIREMENT

Connect the power supply wire after connecting the control wire for this model.

  1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
  2. Remove the terminal cover and the clamp base.
  3. Insert the power supply wire and control wire (according to the local rule) into the pipe hole on the wall.
  4. Take the power supply wire out of the cable slot on the rear panel so that it protrudes about 150mm from the front.
  5. Insert the control wire fully into the control/ wired remote controller terminal block _1 _2 A, B and secure it tightly with screws.
  6. Clamp the control wire with the cord clamp.
  7. Install the clamp base with a screw.
  8. Insert the power supply wire fully into the terminal block and secure it tightly with screws. Tightening torque: 1.2 N·m (0.12 kgf·m) Secure the earth line with the earth screw.
  9. Clamp the power supply wire with the cord clamp.
  10. Attach the terminal cover and the air inlet grille to the indoor unit.

TOSHIBA MMK-AP0153H - REQUIREMENT - 1

CAUTION

  • Be sure to refer to the wiring diagram attached inside the front panel.
  • Check local electrical cords and also any specific wiring instructions and limitations.
  • Do not catch the control wire when installing the clamp base.

TOSHIBA MMK-AP0153H - CAUTION - 1

TOSHIBA MMK-AP0153H - CAUTION - 2

TOSHIBA MMK-AP0153H - CAUTION - 3

TOSHIBA MMK-AP0153H - CAUTION - 4

Wiring connection for flow selector unit

How to connect the wiring of flow selector unit

Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor unit.

  1. Remove the air inlet grille.
    Open the air inlet grille upward and pull it toward you.
  2. Remove the four screws securing the front panel.
  3. Slightly open the lower part of the front panel, and then pull the upper part of the front panel toward you to remove it from the rear plate.
  4. Remove the terminal cover and the clamp base.
  5. Insert the control wire fully into the control/wired remote controller terminal block and secure it tightly with screws.
  6. Connect the control wire connector of the flow selector unit to the lead with a connector to the left of the control/wired remote controller terminal block.
  7. Clamp the control wire and the control wire of the flow selector unit with the cord clamp.
  8. Install the clamp base with a screw.
  9. Insert the power supply wire fully into the terminal block and secure it tightly with screws.

Tightening torque: 1.2N· m (0.12 kgf·m)

Secure the earth line with the earth screw.

10.Clamp the power supply wire with the cord clamp.

11.Insert the power supply wire fasten terminal of the flow selector unit into the power supply terminal.

Secure the earth line with the earth screw.

12.Clamp the power supply wire of the flow selector unit tight with the cord clamp.
13. Attach the terminal cover, the front panel and the air inlet grille to the indoor unit.

TOSHIBA MMK-AP0153H - How to connect the wiring of flow selector unit - 1

TOSHIBA MMK-AP0153H - How to connect the wiring of flow selector unit - 2

CAUTION

Confirm that every wires are stored in the electric parts box without getting caught before attaching the terminal cover.

11 APPLICABLE CONTROLS

A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller.

REQUIREMENT

  • When you use this air conditioner for the first time, it takes approx. 5 minutes until the remote controller becomes available after power-on. This is normal.

It takes approx. 5 minutes until the remote controller becomes available.

TOSHIBA MMK-AP0153H - REQUIREMENT - 1

It takes approx. 1 minute until the remote controller becomes available.

TOSHIBA MMK-AP0153H - REQUIREMENT - 2

  • Normal settings were made when the indoor unit was shipped from factory. Change the indoor unit settings as required.
  • Use the wired remote controller to change the settings.

  • The settings cannot be changed using the wireless remote controller, sub remote controller, or remote-controller less system (for central remote controller only). Therefore, install the wired remote controller to change the settings.

Changing of settings of for applicable controls

Basic procedure for changing settings

Change the settings while the air conditioner is not working.

(Be sure to stop the air conditioner before making settings.)

The display content for setting differs from that on the former types of remote controller (RBC-

AMT21E/AMT31E). (The number of CODE No. has increased.)

TOSHIBA MMK-AP0153H - Basic procedure for changing settings - 1

Procedure 1

Push TEST button and "TEMP." button simultaneously for at least 4 seconds.

After a while, the display flashes as shown in the figure.

Confirm that the CODE No. is [10].

  • If the CODE No. is not [10], push TEST button to erase the display content, and repeat the procedure from the beginning. (No operation of the remote controller is accepted for a while after TEST button is pushed.) (While air conditioners are operated under the group control, "ALL" is displayed first. When UNIT LOUVER is pushed, the indoor unit number displayed following "ALL" is the header unit.)

TOSHIBA MMK-AP0153H - Procedure 1 - 1
(*Display content varies with the indoor unit model.)

Procedure 2

Each time you push UNIT LOUVER button, indoor unit numbers in the control group change cyclically. Select the indoor unit you want to change settings for.

The fan of the selected unit runs and the louvers start swinging. You can confirm the indoor unit for which you want to change settings.

TOSHIBA MMK-AP0153H - Procedure 2 - 1

Procedure 3

Using "TEMP." / buttons, specify CODE No.[**].

Procedure 4

Using timer "TIME" 一 / 一 buttons, select SET DATA [ ****].

Procedure 5

Push SET button. When the display changes from flashing to lit, the setup is completed.

  • To change settings of another indoor unit, repeat from Procedure 2.
  • To change other settings of the selected indoor unit, repeat from Procedure 3.

Use SET button to clear the settings.

To make settings after button was pushed, repeat from Procedure 2.

Procedure 6

When settings have been completed, push TEST button to determine the settings.

When TEST button is pushed, "SETTING" flashes and then the display content disappears and the air conditioner enters the normal stop mode.

While "SETTING" is flashing, no operation of the remote controller is accepted.

TOSHIBA MMK-AP0153H - Procedure 6 - 1

Change of lighting time of filter sign

According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed.

Follow to the basic operation procedure

$$ (\mathbf {1} \rightarrow \mathbf {2} \rightarrow \mathbf {3} \rightarrow \mathbf {4} \rightarrow \mathbf {5} \rightarrow \mathbf {6}). $$

  • For the CODE No.. in Procedure 3, specify [01].
  • For the [SET DATA] in Procedure 4, select the SET DATA of filter sign lighting time from the following table.
SET DATAFilter sign lighting time
0000None
0001150H (Factory setting)
00022500H
00035000H
000410000H

To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling.

Follow to the basic operation procedure

$$ (\mathbf {1} \rightarrow \mathbf {2} \rightarrow \mathbf {3} \rightarrow \mathbf {4} \rightarrow \mathbf {5} \rightarrow \mathbf {6}). $$

  • For the CODE No.. in Procedure 3, specify [06].
  • For the SET DATA in Procedure 4, select the SET DATA of shift value of detection temperature to be set up from the table below.
SET DATADetection temp shift value
0000No shift
0001+1°C
0002+2°C
0003+3°C (Factory setting)
0004+4°C
0005+5°C
0006+6°C

■ Adjustment of air direction

  1. Using the remote controller switch, change the up/down air direction by moving the horizontal louver.
  2. Adjust the right/left air direction by bending the vertical grille inside of the air outlet port with hands.

REQUIREMENT

Do not touch the horizontal louver directly with hands; otherwise a trouble may be caused.

For handling of the horizontal louver, refer to

"Owner's Manual" attached to the outdoor unit.

Group control

In a group control, a remote controller can control up to maximum 8 units.

  • The wired remote controller only can control a group control. The wireless remote controller is unavailable for this control.
  • For cabling procedure and cables of the individual line (Identical refrigerant line) system, refer to "Electric work" in this Manual.
  • Cabling between indoor units in a group is performed in the following procedure. Connect the indoor units by connecting the remote controller inter-unit cables from the remote controller terminal blocks (A, B) of the indoor unit connected with a remote controller to the remote controller terminal blocks (A, B) of the other indoor unit. (Non-polarity)
  • For address setup, refer to the Installation Manual attached to the outdoor unit.

NOTE

Net work adapter (Model TCB-PCNT20E) can not connect to this High Wall type air conditioner.

12 TEST RUN

A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller.

Before test run

  • Before turning on the power supply, carry out the following procedure.
    1) Using 500V-megger, check that resistance of 1M or more exists between the terminal block of the power supply and the earth (grounding). If resistance of less than 1M is detected, do not run the unit.
    2) Check the valve of the outdoor unit being opened fully.
  • To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.

TOSHIBA MMK-AP0153H - Before test run - 1

WARNING

  • Never press the electromagnetic contactor to forcibly perform a test run. (This is very dangerous because the protective device does not work.)
  • Before starting a test run, be sure to set addresses following the installation manual supplied with the outdoor unit.

How to execute a test run

Using the wired remote controller, operate the unit as usual.

For the procedure of the operation, refer to the attached Owner's Manual.

A forced test run can be executed in the following procedure even if the operation stops by thermo.-OFF.

In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the usual operation.

TOSHIBA MMK-AP0153H - How to execute a test run - 1

CAUTION

  • Do not use the forced test run for cases other than the test run because it applies an excessive load to the devices.

In case of wired remote controller

TOSHIBA MMK-AP0153H - In case of wired remote controller - 1

Procedure 1

Keep TEST button pushed for 4 seconds or more. [TEST] is displayed on the display part and the selection of mode in the test mode is permitted.

TOSHIBA MMK-AP0153H - Procedure 1 - 1

Procedure 2

Push ON/OFF button.

Procedure 3

MODE button, select the operation mode, [COOL] or [HEAT].

  • Do not run the air conditioner in a mode other than [COOL] or [HEAT].
  • The temperature controlling function does not work during test run.
  • The detection of error is performed as usual.

TOSHIBA MMK-AP0153H - Procedure 3 - 1

Procedure 4

After the test run, push ON/OFF button to stop a test run.

(Display part is same as procedure 1.)

Procedure 5

Push TEST check button to cancel (release from) the test run mode.

([TEST] disappears on the display and the status returns to a normal.)

TOSHIBA MMK-AP0153H - Procedure 5 - 1

In case of wireless remote controller (Forced test operation is performed in a different way.)

REQUIREMENT

  • For the operation procedure, be sure to follow the Owner's Manual.
  • Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
  • A test operation of forced heating is unavailable. Perform a test operation by heating operation using the switches of the remote controller.

However heating operation may be not carried out according to the temperature conditions.

- Check wiring/piping of indoor and outdoor units

  1. When pushing ⑥ button for 10 seconds or more, "Pi!" sound is heard and the operation changes to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcibly. Check cool air starts blowing. If the operation does not start, check wiring again.
  2. To stop a test operation, push button once again (Approx. 1 second). The louver closes and the operation stops.

TOSHIBA MMK-AP0153H - - Check wiring/piping of indoor and outdoor units - 1

- Check transmission of remote controller

  1. Push "START/STOP" button of the remote controller to check an operation can also start by the remote controller.

  2. "Cooling" operation by the remote controller may be unavailable according to the temperature conditions.

Check wiring/piping of the indoor and outdoor units in forced cooling operation.

13 TROUBLE SHOOTING

A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller.

Confirmation and check

When a trouble occurred in the air conditioner, the check code and the indoor UNIT No. appear on the display part of the remote controller.

The check code is only displayed during the operation.

If the display disappears, operate the air conditioner according to the following "Confirmation of error history" for confirmation.

TOSHIBA MMK-AP0153H - Confirmation and check - 1

Confirmation of error history

When a trouble occurred on the air conditioner, the trouble history can be confirmed with the following procedure. (The trouble history is stored in memory up to 4 troubles.)

The history can be confirmed from both operating status and stop status.

TOSHIBA MMK-AP0153H - Confirmation of error history - 1

Procedure 1

When pushing SET and TEST buttons at the same time for 4 seconds or more, the following display appears.

If [Service check] is displayed, the mode enters in the trouble history mode.

  • [01: Order of trouble history] is displayed in CODE No. window.
  • [Check code] is displayed in CHECK window.
  • [Indoor unit address in which an error occurred] is displayed in UNIT No.

TOSHIBA MMK-AP0153H - Procedure 1 - 1

Procedure 2

Every pushing of "TEMP." button used to set temperature, the trouble history stored in memory is displayed in order.

The numbers in CODE No. indicate CODE No. [01] (latest) [04] (oldest).

REQUIREMENT

Do not push button because all the trouble history of the indoor unit will be deleted.

Procedure 3

After confirmation, push TEST button to return to the usual display.

Check method

On the remote controller (Wired remote controller, Central control remote controller) and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.

  • In case of check from indoor remote controller: See "Wired remote controller display" in the list.
  • In case of check from outdoor unit: See "Outdoor 7-segment display" in the list.
  • In case of check from indoor unit with wireless remote controller: See "Sensor block display of receiving unit" in the list.

AI-NET: Artificial Intelligence.

IPDU: Intelligent Power Drive Unit

O: Lighting, O: Flashing, Goes off

ALT.: Flashing is alternately when there are two flashing LED.

SIM: Simultaneous flashing when there are two flashing LED.

Check codeWireless remote controllerCheck code nameJudging device
Wired remote controller displayOutdoor 7-segment displaySensor block display of receiving unit
Auxiliary codeOPERATION TIMER PRE.DEF.Flash
E01Communication error between indoor and remote controller (Detected at remote controller side)Remote controller
E02Remote controller transmission errorRemote controller
E03Communication error between indoor and remote controller (Detected at indoor side)Indoor
E04Communication circuit error between indoor/outdoor (Detected at indoor side)Indoor
E06E06No. of indoor units in which sensor has been normally receivedDecrease of No. of indoor unitsI/F
E07Communication circuit error between indoor/outdoor (Detected at outdoor side)I/F
E08E08Duplicated indoor addressesDuplicated indoor addressesIndoor / I/F
E09Duplicated main remote controllersRemote controller
E10Communication error between indoor MCUIndoor
E12E1201: Indoor/Outdoor communication 02: Communication between outdoor unitsAutomatic address start errorI/F
E15E15Indoor is nothing during automatic addressingI/F
E16E1600: Capacity over 01 ~:No. of connected unitsCapacity over / No. of connected indoor unitsI/F
E18Communication error between indoor unitsIndoor
E19E1900: Header is nothing 02: Two or more header unitsOutdoor header units quantity errorI/F
E20E2001: Outdoor of other line connected 02: Indoor of other line connectedOther line connected during automatic addressI/F
E23E23Sending error in communication between outdoor unitsI/F
E25E25Duplicated follower outdoor addressesI/F
E26E26No. of outdoor units which received signal normallyDecrease of No. of connected outdoor unitsI/F
E28E28Detected outdoor unit numberFollower outdoor unit errorI/F
E31E3101: IPDU1 error02: IPDU2 error03: IPDU1, 2 error04: Fan IPDU error05: IPDU + Fan IPDU error06: IPDU2 + Fan IPDU error07: All IPDU errorIPDU communication errorI/F
F01ALTIndoor TCJ sensor errorIndoor
F02ALTIndoor TC2 sensor errorIndoor
F03ALTIndoor TC1 sensor errorIndoor
F04F04ALTTD1 sensor errorI/F
F05F05ALTTD2 sensor errorI/F
F06F06ALTTE1 sensor errorI/F
F07F07ALTTL sensor errorI/F
F08F08ALTTO sensor errorI/F
F10ALTIndoor TA sensor errorIndoor
F12F12ALTTS1 sensor errorI/F
F13F1301: Comp. 1 side02: Comp. 2 sideALTTH sensor errorIPDU
F15F15ALTOutdoor temp. sensor miscabling (TE, TL)I/F
F16F16ALTOutdoor pressure sensor miscabling (Pd, Ps)I/F
F23F23ALTPs sensor errorI/F
F24F24ALTPd sensor errorI/F
F29SIMIndoor other errorIndoor
F31F31SIMIndoor EEPROM errorI/F
H01H0101: Comp. 1 side02: Comp. 2 sideCompressor break downIPDU
H02H0201: Comp. 1 side02: Comp. 2 sideMagnet switch errorOvercurrent relay operationCompressor trouble (lock)MG-SWOvercurrent relayIPDU
H03H0301: Comp. 1 side02: Comp. 2 sideCurrent detect circuit system errorIPDU
H04H04Comp 1 case thermo operationI/F
H06H06Low pressure protective operationI/F
H07H07Oil level down detective protectionI/F
H08H0801: TK1 sensor error02: TK2 sensor error03: TK3 sensor error04: TK4 sensor errorOil level detective temp sensor errorI/F
H14H14Comp 2 case thermo operationI/F
H16H1601: TK1 oil circuit system error02: TK2 oil circuit system error03: TK3 oil circuit system error04: TK4 oil circuit system errorOil level detective circuit errorMagnet switch errorOvercurrent relay operationI/MG-SWOvercurrent relay
L03SIMIndoor centre unit duplicatedIndoor
L04L04SIMOutdoor line address duplicatedI/F
L05SIMDuplicated indoor units with priority(Displayed in indoor unit with priority)I/F
L06L06No. of indoor units with prioritySIMDuplicated indoor units with priority(Displayed in unit other than indoor unit with priority)I/F
L07SIMGroup line in individual indoor unitIndoor
L08L08SIMIndoor group/Address unsetIndoor, I/F
L09☐ ☐ ☐SIMIndoor capacity unsetIndoor
L10L10☐ ☐ ☐SIMOutdoor capacity unsetI/F
L20☐ ☐ ☐SIMDuplicated central control addressesAI-NET, Indoor
L28L28☐ ☐ ☐SIMOver No. of connected outdoor unitsI/F
L29L2901: IPDU1 error02: IPDU2 error03: IPDU3 error04: Fan IPDU error05: IPDU1 + Fan IPDU error06: IPDU2 + Fan IPDU error07: All IPDU error☐ ☐ ☐SIMNo. of IPDU errorI/F
L30L30Detected indoor address☐ ☐ ☐SIMIndoor outside interlockIndoor
L31Extended I/C errorI/F
P01☐ ☐ ☐ALTIndoor fan motor errorIndoor
P03P03☐ ☐ ☐ALTDischarge temp. TD1 errorI/F
P04P0401: Comp. 1 side02: Comp. 2 side☐ ☐ ☐ALTHigh-pressure SW system operationIPDU
P05P0501: Phase-missing detection02: Phase error☐ ☐ ☐ALTPhase-missing detection /Phase errorI/F
P07P0701: Comp. 1 side02: Comp. 2 side☐ ☐ ☐ALTHeat sink overheat errorIPDU, I/F
P10P10Detected indoor address☐ ☐ ☐ALTIndoor overflow errorIndoor
P12☐ ☐ ☐ALTIndoor fan motor errorIndoor
P13P13☐ ☐ ☐ALTOutdoor liquid back detection errorI/F
P15P1501: TS condition02: TD condition☐ ☐ ☐ALTGas leak detectionI/F
P17P17☐ ☐ ☐ALTDischarge temp. TD2 errorI/F
P19P19Detected outdoor unit number☐ ☐ ☐ALT4-way valve inverse errorI/F
P20P20☐ ☐ ☐ALTHigh-pressure protective operationI/F
P22P220_____:IGBT short1_____:Fan motor positiondetective circuit error3_____:Fan motor troubleC_____:TH sensor temp. error(Heat sink overheat)D_____:TH sensor errorE_____:Vdc output error☐ ☐ ☐ALTOutdoor fan IPDU errorIPDU
P26P2601: Comp. 1 side02: Comp. 2 side☐ ☐ ☐ALTG-TR short protection errorIPDU
P29P2901: Comp. 1 side02: Comp. 2 side☐ ☐ ☐ALTComp position detective circuit systemerrorIPDU
P31P31☐ ☐ ☐ALTOther indoor unit error(Group terminal unit error)Indoor
By alarm device ALTError in indoor groupAI-NET

Error detected by TCC-LINK central control device

Check codeWireless remote controllerCheck code nameJudging device
Central control device indicationOutdoor 7-segment displaySensor block display of receiving unit
Auxiliary codeOPERATION TIMER PRE.DEF.Flash
C05Sending error in TCC-LINK central control deviceTCC-LINK
C06Receiving error in TCC-LINK central control deviceTCC-LINK
C12Batch alarm of general-purpose equipment control interfaceGeneral-purpose equipment I/F
P30Differs according to error contents of unit with occurrence of alarmGroup control branching unit errorTCC-LINK
(L20 is displayed.)Duplicated central control addresses

TCC-LINK: TOSHIBA Carrier Communication Link.

MEMO

TCC-LINK: TOSHIBA Carrier Communication Link.

MEMO

MEMO

请在安装空调之前仔细阅读本安装手册。

Check of Concentration Limit

The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.

The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).

In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device.

The concentration is as given below.

Total amount of refrigerant (kg)

Min. volume of the indoor unit installed room (^3) ≤ Concentration limit (kg/m)

The concentration limit of R410A which is used in multi air conditioners is 0.3kg / m^3

NOTE 1

If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.

TOSHIBA MMK-AP0153H - NOTE 1 - 1
For the amount of charge in this example: The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg

NOTE 2

The standards for minimum room volume are as follows.

(1) No partition (shaded portion)

TOSHIBA MMK-AP0153H - NOTE 2 - 1

(2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).

TOSHIBA MMK-AP0153H - NOTE 2 - 2

(3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.

TOSHIBA MMK-AP0153H - NOTE 2 - 3

NOTE 3

The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)

TOSHIBA MMK-AP0153H - NOTE 3 - 1

CONFIRMATION OF INDOOR UNIT SETUP

Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed in this time and fill the check sheet (Table below). Data of four units can be entered in this check sheet. Copy this sheet according to the No. of the indoor units. If the installed system is a group control system, use this sheet by entering each line system into each installation manual attached to the other indoor units.

REQUIREMENT

This check sheet is required for maintenance after installation. Be sure to fill this sheet and then pass this Installation Manual to the customers.

Indoor unit setup check sheet

Indoor unitIndoor unitIndoor unitIndoor unit
Room nameRoom nameRoom nameRoom name
ModelModelModelModel
Check indoor unit address. (For check method, refer to Applicable controls in this sheet.)* In case of a single system, it is unnecessary to enter the indoor address. (CODE No.: Line [12], Indoor [13], Group [14], Central control [03])
LineIndoorGroupLineIndoorGroupLineIndoorGroupLineIndoorGroup
Central control addressCentral control addressCentral control addressCentral control address
Various setupVarious setupVarious setupVarious setup
Have you changed high ceiling setup? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively. (For check method, refer to Applicable controls in this sheet.) * In case of replacement of short plugs on indoor microcomputer P.C. board, setup is automatically changed.
High ceiling setup(CODE No. [5d])□ NO CHANGE□ STANDARD[0000]□ HIGH CEILING 1[0001]□ HIGH CEILING 3[0003]High ceiling setup(CODE No. [5d])□ NO CHANGE□ STANDARD[0000]□ HIGH CEILING 1[0001]□ HIGH CEILING 3[0003]High ceiling setup(CODE No. [5d])□ NO CHANGE□ STANDARD[0000]□ HIGH CEILING 1[0001]□ HIGH CEILING 3[0003]Hight ceiling setup(CODE No. [5d])□ NO CHANGE□ STANDARD[0000]□ HIGH CEILING 1[0001]□ HIGH CEILING 3[0003]
Have you changed lighting time of filter sign? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.(For check method, refer to Applicable controls in this sheet.)
Filter sign lighting time(CODE No. [01])□ NO CHANGE□ NONE[0000]□ 150H[0001]□ 2500H[0002]□ 5000H[0003]□ 10000H[0004]Filter sign lighting time(CODE No. [01])□ NO CHANGE□ NONE[0000]□ 150H[0001]□ 2500H[0002]□ 5000H[0003]□ 10000H[0004]Filter sign lighting time(CODE No. [01])□ NO CHANGE□ NONE[0010]□ 150H[0001]□ 2500H[0002]□ 5000H[0003]□ 10000H[0004]Filter sign lighting time(CODE No. [01])□ NO CHANGE□ NONE[0010]□ 150H[0001]□ 2500H [0002]□ 5000H[0003]□ 10000H[0004]
Have you changed detected temp. shift value? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.(For check method, refer to Applicable control in this sheet.)
Detected temp. shift value setup(CODE No. [06])□ NO CHANGE□ NO SHIFT[0000]□ +1°C[0001]□ +2°C[0002]□ +3°C[0003]□ +4°C[0004]□ +5°C[0005]□ +6°C[0006]Detected temp. shift value setup(CODE No. [06])□ NO CHANGE□ NO SHIFT[0000]□ +1°C[0001]□ +2°C[0002]□ +3°C[0003]□ +4°C[0004]□ +5°C[0005]□ +6°C[0006]Detected temp. shift value setup(CCODE No. [06])□ NO CHANGE□ NO SHIFT[0000]□ +1°C[0001]□ +2°C[0002]□ +3°C[0003]□ +4°C[0004]□ +5°C[0005]□ +6°C[0006]Detected temp. shift value setup(CODE No. [06])□ NO CHANGE☐ NO SHIFT[0000]□ +1°C[0001]□ +2°C[0002]□ +3°C[0003]□ +4°C[0004]□ +5°C[0005]□ +6°C[0006]
Incorporation of parts sold separatelyIncorporation of parts sold separatelyIncorporation of parts sold separatelyIncorporation of parts sold separately
Have you incorporated the following parts sold separately? If incorporated, fill check mark [×] in each [ITEM].(When incorporating, the setup change is necessary in some cases. For setup change method, refer to Installation Manual attached to each part sold separately.)
Panel□ Standard panelPanel□ Standard panelPanel□ Standard panelPanel□ Standard panel
Filter□ Super long life filterFilter□ Super long life filterFilter□ Super long life filterFilter□ Super long life filter
□ Others()□ Others()□ Others()□ Others()□ Others()□ Others()□ Others()□ Others()
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : TOSHIBA

Model : MMK-AP0153H

Category : Air-conditioner