ModelFCM (Fan Coil Cassette)
Product TypeCeiling-mounted cassette fan coil unit
Versions Available2-pipe (400, 600, 850, 1500) and 4-pipe (400-4T, 750-4T)
Power Supply230 V, 1-phase, 50 Hz
Cooling Capacity (Max)3.93 – 10.64 kW (2-pipe); 2.88 – 5.18 kW (4-pipe)
Heating Capacity (Max)5.34 – 14.38 kW (2-pipe); 4.73 – 7.41 kW (4-pipe)
Air Flow (Max)717 – 1850 m³/h (2-pipe); 717 – 1233 m³/h (4-pipe)
Sound Pressure Level (Max)40 – 50 dB(A)
Pipe Connections3/4" for main coil; 1/2" for secondary coil (4-pipe models)
Condensate DrainRigid PVC 32 mm inner tube; pump included (max lift 500 mm for 400 models, 750 mm for others)
Net Weight (Body)16.5 – 29 kg (depending on model)
Net Weight (Panel)2.5 – 6 kg
Dimensions (Body, L×A×P)655×290×655 mm (400) to 900×330×900 mm (1500)
Dimensions (Panel, L×A×P)715×123×715 mm (400) to 1035×90×1035 mm (1500)
Fan Speeds3 speeds (Low, Medium, High)
Control OptionsRemote control (included), optional wall-mounted panels (REM W1)
Valve Requirement3-way valve obligatory for cooling mode to prevent condensation
MountingCeiling suspended using brackets and threaded rods (M10 nuts and washers supplied)
FilterWashable filter housed in the grille
Safety StandardsCE mark, complies with Low Voltage Directive 2006/95/EC, EMC 2004/108/EC, RoHS 2002/95/EC
Accessories IncludedCardboard template, bolts M6, hose, insulating tube, metal clamp, remote control, manuals

Frequently Asked Questions - FCM FERROLI

What is the Ferroli FCM and what is its purpose?
The Ferroli FCM is a ceiling-mounted cassette fan coil unit designed to heat and cool indoor spaces. It treats room air by circulating it through a finned heat exchanger, using chilled or hot water from a central system.
What versions of the FCM are available?
The FCM is available in 2-pipe models (400, 600, 850, 1500) and 4-pipe models (400-4T, 750-4T). The 4-pipe versions allow simultaneous heating and cooling using separate water circuits.
What are the power supply requirements?
The unit requires a 230 V, 1-phase, 50 Hz power supply. Electrical connections must be made by qualified personnel in accordance with national wiring rules.
How do I install the FCM unit?
Installation involves marking the support positions using the supplied cardboard template, hanging the unit on threaded rods with brackets, leveling it, and connecting the water pipes and condensate drain. The grille is then mounted. Refer to the manual for detailed steps and required clearances.
What is the maximum condensate lift of the pump?
For models 400 and 400-4T, the pump can lift condensate up to 500 mm. For models 600, 750-4T, 850, and 1500, the maximum lift is 750 mm. If draining to a higher point, an auxiliary pump and collector tray are needed.
Is a valve required for cooling operation?
Yes, a 3-way valve is obligatory for cooling mode. It stops chilled water flow when the fan stops, preventing excessive condensation on the casing. The valve is also used for temperature control.
What should I do if an error code appears?
Error codes are displayed on the receiver via LEDs. For 400 models, codes include E2 (room sensor), E3/E4 (evaporator sensor), E7 (EEPROM), E8 (water level). For other models, codes include PH (setting error) and E8 (fan motor). See the troubleshooting table in the manual for exact meanings.
How do I clean or maintain the unit?
Regularly clean the filter (accessible by removing the intake grille) with a vacuum or water. Check condensate drain for blockages. Ensure the unit is switched off and disconnected from power before any maintenance. Periodic inspection of water system pressure and electrical connections is recommended.
What is the typical application for the FCM?
It is ideal for commercial or residential spaces where ceiling-mounted HVAC is desired, such as offices, hotels, shops, and homes. It provides efficient heating and cooling with a discreet appearance.
Where can I download the full manual?
The complete installation and user manual can be downloaded for free from notice-facile.com in PDF format. It contains detailed instructions, wiring diagrams, and technical specifications.

User questions about FCM FERROLI

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Uncategorized in PDF format for free! Find your manual FCM - FERROLI and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. FCM by FERROLI.

USER MANUAL FCM FERROLI

Fan coil cassette EC

Fan coil de tipo cassette EC

Fan coil cassette EC

Exterior view of a ceiling-mounted HVAC unit with ventilation grilles and mounting bracket (no text or symbols visible)

CE

EN INSTALLATION MANUAL

Gentile cliente,

Thank you for having purchased a FERROLI product. It is the result of many years of experiences and of particular research studies and has been made with top quality materials and advanced technologies. The CE mark guarantees that the products satisfy all the applicable European Directives.

The qualitative level is kept under constant control and FERROLI products therefore offer SAFETY, QUALITY and RELIABILITY. Due to the continuous improvements in technologies and materials, the product specification as well as performances are subject to variations without prior notice.

Thank you once again for your preference

FERROLI

S.p.A

The manufacturer declines all responsibility for any inaccuracies in this manual due to printing or typing errors. The manufacturer reserves the right to modify the products contents in this catalogue without previous notice.

SOMMARIO

INTRODUZIONE 4

DIRETTIVE EUROPEE....4

CARATTERISTICHE ....5

SCOPO DELLA MACCHINA 5

VERSIONI DISPONIBILI ....5

FERROLI FCM - CARATTERISTICHE ....5 - 1
Attacchi idraulici

FERROLI FCM - CARATTERISTICHE ....5 - 2
Scarico condensa

OUT S OUT S OUT

Fig. 5
Pure electrical circuit lines without any symbols

Fig. 6

A 30 max h

Fig. 7
Diagram showing a mechanical assembly with labeled parts 1 and 2, indicating a step or process in a tool or device.

Fig. 8
Simple line drawing of a vertical pipe mounted on a rectangular base with two rectangular cutouts (no text or symbols)

Fig. 9

10-12 mm

INSTALLAZIONE

COLLEGAMENTI IDRAULICI

COLLEGAMENTI SCARICO CONDENSA

INSTALLAZIONE

Fig. 2

45°

Fig. 3
Technical line drawing of a mechanical assembly with no visible text or symbols

Fig. 4

B ① A

Fig. 5
Two technical line drawings showing mechanical components with no visible text or symbols

VERSIONES DISPONIBLES....5

950-panel panel-0-56

OUT S OUT S OUT

FERROLI FCM - INSTALLAZIONE - 7
Conexiones agua

Fig. 5
Pure electrical circuit lines without any symbols

Fig. 6

A 30 max h

Fig. 7
Diagram showing a mechanical assembly with labeled parts 1 and 2, including a directional arrow indicating movement or force.

Fig. 8
Simple line drawing of a vertical pipe mounted on a rectangular base with three slots, no text or symbols present.

Fig. 9
10-12 mm

INSTALACIÓN

CONEXIONES DE AGUA

Technical line drawing of a device rear panel with labeled ports and a red circle highlighting a component (no text or symbols present)

D
Technical line drawing of a mechanical assembly with two views (top and side), no visible text or symbols

INSTALACIÓN

Fig. 2

45°

Fig. 3
Technical line drawing of a mechanical assembly with no visible text or symbols

Fig. 4

B ① A

Fig. 5
Two technical line drawings showing mechanical components with no visible text or symbols

DECLARATION OF CONFORMITY 4

PURPOSE OF THE MACHINE 5

AVAILABLE VERSIONS 5

DESCRIPTION OF THE MAIN COMPONENTS....5

AVAILABLE ACCESSORIES....7

INSTALLATION....8

DIMENSIONS FOR INSTALLING MODELS: 400 400-4T 8

DIMENSIONS FOR INSTALLING MODELS: 600 e 750-4T 850 1500....9

SAFETY REGULATIONS 10

PRELIMINARY OPERATIONS PRIOR TO INSTALLATION 10

ACCESSORIES SUPPLIED AT THE CORRECT OF UNITS 10

TOOLS REQUIRED FOR INSTALLATION 11

ACCESSORY PARTS NORMALLY AVAILABLE ON THE MARKET AND REQUIRED FOR INSTALLATION . . .11

CHOICE OF THE INSTALLATION SITE 11

BEFORE INSTALLATION 12

HOW TO INSTALL THE APPLIANCE....13

CONNECTIONS 14

PIPES AND DRAINING OFF CONDENSATION....14

EVACUATION OF AIR DURING THE FILLING OF THE PLAN 15

NOTES ABOUT VALVE ACTIVATION....15

INSTALLATION BACINELLA CONDENSA COLLECTION 15

GRILLE INSTALLATION 16

Procedure for connecting the unit 17

CONNECTION DIAGRAMS 18

OPTIONS INSTALLATIONS 19

PRELIMINARY INSPECTIONS PRIOR TO STARTING 19

TROUBLESHOOTING....20

TROUBLESHOOTING 20

INTRODUCTION

DECLARATION OF CONFORMITY

The manufacturer declares that the machines described in this instruction manual meet the requirements of the following directives and subsequent modifications:

  • Low voltage directive 2006/95/EC;
    • Electromagnetic compatibility directive 2004/108/EC;
    • Directive 2002/95/EC RoHS.

It conforms to what is stated in the legislation

• EN 60335-2-40
• EN 60335-1
• EN 55014-1
• EN 55014-2
• EN 61000-3-2
• EN 6100-3-3

FERROLI FCM - DECLARATION OF CONFORMITY - 1

GENERAL SPECIFICATIONS

PURPOSE OF THE MACHINE

The cassette convector fan is a terminal appliance that treats the air in a room both in the summer and winter. The appliance must be installed on the ceiling. It is equipped with a very pleasantly designed grille.

AVAILABLE VERSIONS

This new series of cassette type convector fans is available in the version with 2 pipes in 4 sizes and 3.93 to 10.64 kW nominal cooling capacity ratings and in the version with 4 pipes (-4T) in 2 sizes with 2.88 to 5.18 kW nominal cooling capacity ratings.

DESCRIPTION OF THE MAIN COMPONENTS

UNITA' VERSIONE
4002 TUBI
600
850
1500
400-44 TUBI
750-4

The unit consists of a module or main structure containing a finned exchanger, the ventilating unit formed by a three speed motor and a centrifugal axial fan, a tray to collect the condensation equipped with a pump to drain this off.

Applied externally houses the electrical box.

The unit also has a grille made of thermoplastic material and formed by a frame which houses the filter and air flow directing fins plus an intake grille: the air flow directing fins are installed on each side of the grille and can be positioned by remote control. The intake grille is fixed in a practical way that allows it to be easily inspected for servicing and filter cleaning operations.

GENERAL VIEW OF THE UNIT

The drawings below highlight the fundamental parts of the unit.

It is reported:

Unit: Includes battery, fan assembly, pump and electrical box

Panel: Plastic material includes frame, grille and air filter, air orientation vents and signal receiver from the remote control.

Brackets: arranged on four corners of the unit serve for the suspension and fastening of the unit.

Condensate discharge pipe: for the evacuation of the condensate that is formed in cold operation.

Air vent valves: placed on the upper manifold allows the evacuation of the air in the system.

Exhaust Valve: present on the lower manifold allows water drainage from the plant.

Hole for connecting with auxiliary basin: bring the water on the auxiliary basin to the main basin and then evacuate it from the pump.

Fig. 1
Unit Panel brackets Condensate exhaust pipe Air vent valve discharge valve Hole for connecting auxiliary basin Brackets Unit Panel brackets Condensate exhaust pipe Air vent valve discharge valve Hole for connecting auxiliary basin Brackets Air vent valve discharge valve

GENERAL SPECIFICATIONS

MODELS 400 600 850 1500 400-4 750-4 U.M
Version 2 pipes 4 pipes \
Power supply 230-1-50 V-f-Hz
Max 717 1133 1441 1850 717 1233 m3/h
Air FlowMed 502 793 1009 1295 502 863 m3/h
Min359 567 721 925 359 617 m3/h
Max3930558068401064028805180W
Cooling capacity (1)Med3070 4350 5330 8090 2190 3940W
Min2480 3520 4300 6600 1800 3260 W
Water flow676 960 1176 1830 495 891 l/h
Cooling water pressure drop1221273414,512kPa
Max53407720937014380\\W
Heating Capacity (2)Med40005920725011290\\W
Min3150450055008440\\W
Max\\\\47307410W
Heating Capacity (3)Med\\\\36005640W
Min\\\\29804670W
Water flow (2)67696011761830\\ m3/h
Water flow (3)\\\\407637 m3/h
Heating water pressure drop10,622233429,142kPa
Power input2742701242750W
Max404246504042dB(A)
Sound pressure levelMed363336403634dB(A)
Min282628332826dB(A)
Pipe connection3/4"3/4"3/4"3/4"3/4"3/4"
Pipe connection auxiliary\\\\1/2"1/2"
Net \ Gross weight Body16.5/21.523/2827/3329/34.517/2328/34Kg
Net \ Gross weight Panel2.5/4.5 6/96/96/9 2.5/4.5 6/9Kg
L 655 900 900 655 900 mm
Packing Body dimensionA 290260 330 330 290 330 mm
P 655900 900 900 655 900 mm
L 715 1035 1035 1035 715 1035 mm
Packing Panel dimensionA12390909012390mm
P 715 1035 1035 715 1035 mm

NOTE:
(1) Air T=27°C D.B. / 19°C W.B., Water IN/OUT 7°/12°C, design air flow; For medium and low fan speed, water flow as in maximum fan speed mode.
(2) Air T=20°C D.B., water inlet temperature 50°C, water flow as in cooling mode.
(3) Air T=20°C D.B., water IN/OUT 70°/60°C, design air flow; For medium and low fan speed, water flow as in maximum fan speed mode.
(4) Sound pressure level in 100m2 room with 0.5sec of reverberation time

ACCESSORIES

AVAILABLE ACCESSORIES

The following accessories are available for this category:

- Control and Monitoring Panels REM W1

A set of panels is available for remote wall installation formed by three different types of control: commutator, basic thermostat and evolved thermostat.

- 3-way valve (obligatory for operation in the cooling mode)

The three-way valve is not only required to control the ambient temperature, but also to block the flow of chilled water to the coil if the level of condensed water in the tray should rise in an abnormal way.

It is obligatory to install this valve if the unit is used for operation in the Cooling mode during summer as this stops it from cooling too much during the periods when the fan remains at a standstill, thus preventing the unpleasant formation of condensation on the casing of the machine.

The dimensions are given in mm.

49 261

MOD. Unit weight Grille weight
400 400-4T16.5 2.5

HYDRAULIC CONNECTIONS

1- Main cold battery input
2- Cold water main output battery
3 - Secondary battery hot water inlet
4- Secondary battery outlet hot water
5- Condensate drain outlet

1 2 3 4 5

Mod. 400 (2 tubi) Mod 400 (4 tubi)
190 124 E1

190 124 110 157

Mod Size of main coil connections [∅] Size of secondary coil connections [∅]
400 3/4" -
400-4T 3/4" 1/2"

INSTALLATION

DIMENSIONS FOR INSTALLING MODELS: 600 e 750-4T 850 1500

Technical line drawing of a cabinet or enclosure with labeled dimensions (no text or symbols present)

950-pannello 950-pannello

The dimensions are given in mm.

A 140

MOD. A [mm] B [mm] Unit weight Grille weight
600 230 170 23 6
750-4T 850300 19027 6
1500 300190 29 6

HYDRAULIC CONNECTIONS

1- Main cold battery input
2- Cold water main output battery
3 - Secondary battery hot water inlet
4- Secondary battery outlet hot water
5- Condensate drain outlet

Technical diagram of a device with numbered components, likely an electronic or mechanical assembly.

Mod 600 - 850 - 1500 (2 tubi) Mod 750 (4 tubi)
D C

MOD.C [mm]D [mm]
600145195
850 - 1500155205

220 150 160 210

MODELLO Size of main coil connections [∅] Size of secondary coil connections [∅]
600 3/4"-
850 3/4"-
15003/4"-
750-4T3/4"1/2"

INSTALLATION

SAFETY REGULATIONS

The manufacturer declines all liability for failure to comply with the safety regulations and recommendations described below. The manufacturer also declines all liability for damage caused by improper use of the convector fan and/or by modifications made without authorization.

The convector fan must be installed by expert, authorized personnel.

· Wear adequate safety clothing when installing the machine, e.g. goggles, gloves, etc.

· Work in a safe, clean and uncluttered place when installing the appliance.

· Comply with the laws in force in the country where the convector fan is installed during use and when disposing of the packaging materials and products used to clean and service the appliance. Also comply with the instructions given by the manufacturers of such products.

- Comply with the pertinent anti-pollution laws if the convector fan is dismantled.

- It is absolutely forbidden to touch moving parts or to get between the same.

- Before starting the convector fan, make sure that its parts and the whole system are in a perfect condition.

- Spare parts must comply with the requirements established by the manufacturer. Only use genuine spare parts.

- It is absolutely forbidden to touch moving parts or to move between the same.

- Only qualified personnel may be allowed to service or replace damaged or worn parts of the convector fan. Moreover, such work must be carried out in compliance with the instructions in this manual.

- before proceeding with the servicing or cleaning operations, make sure that the unit is not connected to the electricity main and that it cannot be accidentally powered.

This installation manual must be read, memorized and kept ready to hand throughout the life of the convector fan.

PRELIMINARY OPERATIONS PRIOR TO INSTALLATION

Comply with the following instructions before beginning to install the appliance:

· Make sure that all parts of the convector fan are in a perfect condition.

- Make sure that the appliance has not sustained damage during transport. Immediately notify the haulage contractor if damage is discovered. Check to make sure that the accessories required for installation and the relative documentation are included in the pack. As a further safeguard, the grille is supplied in a separate pack. Remote control kits (if applicable) are also wrapped separately.

- Convey the packed appliance as near to the installation site as possible.

· Do not stack weights or place tools on top of the packed appliance.

ACCESSORIES SUPPLIED AT THE CORRECT OF UNITS

All units are supplied with a range of accessories for proper installation and use.

Make sure that what is described is present in the packaging:

Application Description Q,ty
Grid mountingCardboard template 1
Bolts M6 4
Exhaust installationHose isolated 1
Insulating 1
Metal clamp 1
InsulationInsulating tubes 2
Insulating4
Mounting unitsDadi M10 8
Washers 8
ControlRemote control 1
Remote control port 1
ManualsUnit Installation Manual 1
Remote control user manual 1

INSTALLATION

TOOLS REQUIRED FOR INSTALLATION

The following tools are required in order to install the convector fan:

  • Pipe wrench for the wet connections
  • Flat tip and cross-headed screwdrivers
    · Drill
    · Scissors

  • Wire stripper

  • Pipe cutters
    · Pipe benders
  • Measuring tape
    · Level
    · Goggles and protective gloves

ACCESSORY PARTS NORMALLY AVAILABLE ON THE MARKET AND REQUIRED FOR INSTALLATION

The following items are also required for installation purposes:

· Water pipe unions
- Condensation-proof tape
· Adhesive tape

CHOICE OF THE INSTALLATION SITE

Positions to avoid:

  • Places in direct sunlight.
  • Positions near heat sources.
    · Damp places and positions where the unit could come into contact with water (e.g.: washrooms).
  • Places where shelves or furniture could prevent the air from circulating correctly.

Fig. 1

What to do:

  • Choose a position without obstructions that could hamper the air inlets and outlets.
  • Choose a position where the appliance is easy to install.
  • Choose a position that complies with the recommended minimum space for maintenance work.
  • Choose a position that allows air to freely circulate around the room.
    · Install the appliance so that the condensation can be easily drained off.
  • Choose a position possibly in the middle of the room. Adjustment of the outlet air can then be optimized to reach all parts of the room.

The best position of the fans is generally the one that allows air to be blown on to the ceiling by means of the Coanda effect. The fins can also be set in the fully closed position, with the limitations shown in the figure.

  • Check to make sure that the chosen position allows the panels to be sufficiently removed from the ceiling to allow the installation and maintenance operations to be carried out.
  • Do not install the appliance where water can drip on to it.

>30 >1000 >2500

INSTALLATION

BEFORE INSTALLATION

Transporting the unit packed as close as possible to the place of installation.

IMPORTANT: Do not move the unit through the exhaust pipe of the condensate or attacks; grasp on the four corners.

The installation of the unit will be facilitated using un'elevatore

The fan must be installed in a position to allow routine maintenance and repairs, as well as access to the air vent valve on the side of the unit (housed in the water connections). (See figure 3 position indication hatch)

Fig. 2
Line drawing of a vertical mechanical lift or support structure with wheels and control panel (no text or symbols)

Fig. 3

Mod. 400 400-4T Mod. 600-850-1500 750-4T
graph TD A["OUT"] --> B["Central Device"] C["IN"] --> B D["OUT"] --> B E["IN"] --> B F["OUT"] --> B G["IN"] --> B H["OUT"] --> B I["IN"] --> B J["OUT"] --> B K["IN"] --> B L["OUT"] --> B M["IN"] --> B N["OUT"] --> B O["IN"] --> B P["OUT"] --> B Q["IN"] --> B R["OUT"] --> B S["IN"] --> B T["OUT"] -->…

FERROLI FCM - BEFORE INSTALLATION - 3
Hydraulic connections
Condensate drain

Diagram of a mechanical component with labeled directional indicators and symbols, including OUT, S, and directional arrows.

FERROLI FCM - BEFORE INSTALLATION - 5
Renewal air inlet
Air outlet to the adjacent room

INSTALLATION

HOW TO INSTALL THE APPLIANCE

- Mark the position of each support, the connecting pipes and discharge of the condensate, of the electrical cables and power commands (see dimensions). The cardboard template can be supplied with help in this operation (Fig.4).

- Hang up the bearing brackets supplied with the appliance. Take care to keep them a certain distance (h) (Fig.6) from the false ceiling (See attached table). Do not tighten the nut or check nut. This will only be done after the unit is levelled, at the end of the installation phase.

Note: Depending on the type of ceiling, choose the most appropriate tie rods (Fig. 6A).

Remember the total weight for the different units.

MOD. Weight [kg] h [mm]
400 19 49
400-4T19.2 49
600 29 140
750-4T33.5 140
850 33 140
1500 35 140

Lift the unit (without the frame) carefully by gripping it on the four corners.

Match the side slots (1 Fig. 7) to the four brackets (2 Fig. 7).

Insert the brackets into the slots and screw the safety screws (Fig.8).

  • Level the appliance with a level and allow 10-12 mm between the sheet metal casing and the lower surface of the false ceiling (Fig.9).
  • Connect the condensation drain pipes and make the wet connections, then check to make sure that the appliance is still level.

Diagram showing two layered rectangular structures with vertical dashed lines, labeled 'Fig. 4' (no text or symbols on the shapes themselves)

Pure structural diagram of a truss structure with vertical supports (no text or symbols)

Fig. 6 A 30 max h

Fig. 7 1 2

Technical diagram of a mechanical clamp or bracket assembly with a vertical rod and mounting bracket (no text or symbols)

Fig. 9 10-12 mm

INSTALLATION

CONNECTIONS

Fig. 1

The selection and sizing of the hydraulic lines is delegated responsibility for the designer who must operate under the rules of good practice and legislation.

  • Position the hydraulic lines
  • Tighten the connections using the "key against key" (Fig 1)
  • Check for leakage
  • Coat the connections with insulating material
    The hydraulic lines and joints must be thermally insulated. Avoid partial insulation of pipes.
    Do not over tighten to avoid damaging the insulation.

Technical line drawing of a mechanical assembly with labeled components (no text or symbols)

PIPES AND DRAINING OFF CONDENSATION

For the production of the condensate discharge pipe it is preferable to use a rigid PVC 32 mm inner tube.

The position of the trunks is shown in Fig.2.

FERROLI FCM - PIPES AND DRAINING OFF CONDENSATION - 1

- The units are equipped with a pump which is able to guarantee a rise in condensation water from the bottom of the unit (as shown in the figure) not exceeding 500 mm for the 400 and 400-4T models; and 750 mm for other models (Fig.3-A).

- To drain the water to a higher level of the unit, install an auxiliary condensate drain pump with collector tray and level regulator

-For a regular discharge of condensation it is necessary that the drain hose has an inclination of 1% downwards without bottlenecks or ascending tracts (Fig.3-B).

-In addition, have a deep siphon of at least 50 mm to prevent bad smells in the environment (Fig.3-C).

-For more than one unit installed in

FERROLI FCM - PIPES AND DRAINING OFF CONDENSATION - 2
Fig. 3

a room, the condensate drainage pipe must be as in (Fig.3-D). The main manifold must be dimensioned to drain all the units at the same time.

-The pipes must be covered with anti-condensate materials, eg polyurethane, polypropylene, neoprene or expanded foils of 5-10 mm thick.

INSTALLATION

EVACUATION OF AIR DURING THE FILLING OF THE PLAN

  • Open all system interception devices (manual or automatic);
  • Start filling by slowly opening the water tap of the plant water;
  • Operate (using a screwdriver) on the battery drain (Fig.1);
  • When water starts bleeding from the breather valves of the appliance, close them and continue charging until the rated value for the plant is reached. Check the hydraulic sealing of the gaskets. It is advisable to repeat this operation after the appliance has been operating for several hours and periodically check the system pressure.

Fig. 1
Technical line drawing of a cabinet with four switches and a bulb, no text or symbols present

NOTES ABOUT VALVE ACTIVATION

The appliance includes a condensation drain pump as part of the standard supply. Using a thermal contact sensor (TC), this pump always operates when the appliance is filled with cold water, thus in the cooling phase.

The pump remains stationary when the temperature of the water entering the bank exceeds 25\ °C and no condensation is formed. Connect the TC sensor to the cooling coil inlet pipe. If the valve kit accessory is used (this is obligatory if the unit is used for cooling), always place the sensor on the cooling exchanger inlet.

The valve can be controlled by means of the switch or the two thermostats supplied as accessories, depending on the type of installation.

INSTALLATION BACINELLA CONDENSA COLLECTION

Made of plastic material, it collects and conveys inside the main basin the condensate that forms on uninsulated hydraulic connections and valves kit (if present) during summer operation.

The mounting procedure is described in the instructions supplied with the basin.

Fig. 2
Technical line drawing of a mechanical assembly with no visible text or symbols

INSTALLATION

GRILLE INSTALLATION

Carefully unpack the assembly and check that it has not been damaged.

  1. Remove the grid:

-Alling the levers A on the grill at the same time unlock the grid (Fig.1)

- Open the 45° grid and unhook it from the frame (Fig.2) and unhook it from the frame

  1. For units with removable covers, remove the cover for installation at the four corners (Fig.3)

  2. Installing the Panel (Fig.4)

Align the spindle motor A at the hydraulic connections in the B-box.

Temporarily fix the frame to the unit using the hooks (detail 1) on the four sides of the unit.

Center the panel against the false ceiling and check the horizontal trim.

Using a cross-head screwdriver, attach the frame to the unit. The position of the hardware depends on the models (Fig.5)

Fig. 1
Technical diagram of a square component with internal grid structure and labeled point A (no text or symbols beyond label)

Fig. 2

45°

Fig. 3
Technical line drawing of a mechanical assembly with no visible text or symbols

Fig. 4

B ① A

Fig. 5
Two technical diagrams showing mechanical components with droplet-like features, no text or symbols present

Hang the grill for the air in the pan.

Connect the winder and the cable to the cassette electrically.

Replace the inlet air grille in the original position and electrically connect the receiver

For models with corner covers, replace the cover at the corners of the panel.

INSTALLATION

PROCEDURE FOR CONNECTING THE UNIT

IMPORTANT:

  • The unit must be installed in accordance with national wiring rules.
  • All cables with the unit, including accessories, must be type H05 VV-F, with PVC insulation according to EN 6033-2-40.
  • Remove power to all circuits before accessing live parts.
  • Connect the ground before the electrical connections.

According to the rules of installation, the device disconnects the power supply must provide a contact aperture (4 mm) that allows complete disconnection in the conditions of overvoltage category III.

The general scheme of the connections to be performed is shown in Fig.1

Fig. 1
ALIM. 230V-1-50Hz ALIM. IC1 8 Rem Ric. VF VC ALIM: mains power supply Ric: receiver board on the grid Rem: remote wired panel (optional) VF: Cold / Hot valve (for 2 pipes) VC: Hot valve (for 4 pipes)

For connection proceed as follows:

-Insert the power cord inside the machine from the cable gland shown in Fig.
-Remove the cover of the power cabinet by removing the locking screws.
-Inside the panels are the terminal blocks to which the connections are made, as shown in the Schemes section.
-Extended connections with the grid will be executed once the grid is mounted.
- Disconnect the electrical box cover

Mod. 400 400-4T Mod. 600-850-1500 750-4T Fig. 2 A A

INSTALLATION

CONNECTION DIAGRAMS

Version 2 Tubes
ALIM. 230V-1-50Hz IG1 B L N Mod. 400 3 2 1 VF

Mod. 600-850-1500
ALIM. 230V-1-50Hz IG1 B L N 1 2 3 4 VF

Version 4 Tubes
ALIM. 230V-1-50Hz IG1 B Mod. 400-4T VF VC

Mod. 750-4T
ALIM. 230V-1-50Hz IG1 B L N 1 2 3 4 VF VC

VF: Cold / Hot valve (for 2 pipes)
VC: Hot valve (for 4 pipes)

INSTALLATION

OPTIONS INSTALLATIONS

Air supply in a room:

The air flow to the adjacent space requires the closure of one or two flaps corresponding to the duct. On the partition wall between the conditional room, where the unit is installed, and the adjacent room, an air intake should be applied.

Pretended for entry Air in the adjacent room Fig. 1

PRELIMINARY INSPECTIONS PRIOR TO STARTING

  • The unit must not be started until the pipes have been cleaned and bled until all the air has been eliminated from the system.
    · Make sure that the condensation drain pipes slope correctly.
    · Make sure that the filter is clean and well seated in its housing.
  • Check the voltage and current values and compare them with the values on the data plate of the appliance. Check the electrical connections.
    · Make sure that the delivery fins are not shut.

TROUBLESHOOTING

TROUBLESHOOTING

If there was an error condition during the unit running, a code will be displayed on the receiver. This code is identified by number of the system that caused the error or by an led combination. To interpret the error codes,

use the following table.

For models 400, 400-4T

OPERATION TIMER DEF/FAN ALARM

Error code displayedMalfunction descriptionLED view
OPERATIONTIMER DEFF./FAN ALARM
E2 Room temperature sensor is open or short-circuit x o x x
E3/E4 Evaporator sensor is open or short-circuito x x x
E7 EEPROM malfunctiono o x x
E8 Water-level switch malfunctionxxxo

x LED off

o LED lamp

For models 600, 750-4T, 850 and 1500

OPERATION TIMER DEF./FAN ALARM

Error code displayedMalfunction descriptionLED view
OPERATIONTIMERDEF./FANALARM
E2Room temperature sensor is open or short-circuitxoxx
E3Evaporator sensor is open or short-circuitoxxx
E7EEPROM malfunctionooxx
EEWater-level switch malfunctionxxxo
E8Anomaly fan motoroxox
PHError setting unitxxoo

x LED off

o LED lamp

*Some alarms may be generated by a lack of ordinary maintenance. It's recommend to do this procedure before call the Technical Assistance.