Honeywell's BACnet® Fixed Function Thermostat, BACnet FF, is a configurable device with 19 pre-loaded applications. The thermostat is a communicating, intelligent sensor-controller combination with built-in temperature and humidity sensors used to control applications such as roof top units, fan-coil units and heat pumps. The thermostat communicates over an MS/TP LAN so it operates as a fully-functioning BACnet controller and easily integrates with the building automation system. The two available models are TB3026B and TB3026B-W, which includes a wireless sensor option.
Table 1. BACnet Standardized Device Profile (Annex L).
| √ | Description |
| BACnet Advanced Workstation (B-AWS) | |
| BACnet Operator Workstation (B-OWS) | |
| BACnet Operator Display (B-OD) | |
| BACnet Building Controller (B-BC) | |
| BACnet Advanced Application Controller (B-AAC) | |
| √ | BACnet Application Specific Controller (B-ASC) |
| BACnet Smart Sensor (B-SS) | |
| BACnet Smart Actuator (B-SA) |
Table 2. List all BACnet Interoperability Building Blocks Supported (see Annex K).
| DS-RP-A,B SCHED-I-B DM-DDB-A,B | |
| DS-RPM-B DM-DOB-B | |
| DS-WP-A,B DM-DCC-B | |
| DS-WPM-B DM-PT-A,B | |
Table 3. Segmentation Capability.
| √ | Description | |
| Able to transmit segmented messages | Window Size: ____ | |
| Able to receive segmented messages | Window Size: ____ | |
Table 4. Standard Object Types Supported.
| Device | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Location | ||
| Description | ||
| Local_Time | ||
| Local_Date | ||
| Daylight_Saving_Status | ||
| UTC_Offset | ||
| Max_Master | ||
| MAX_Info_Frames | ||
| Writable Properties: Object_Name Limit: 30 | Characters | |
| Location Limit: 30 Characters | ||
| Description Limit: 30 Characters | ||
| UTC_Offset Range: -780...780 | ||
| APDU_Timeout Range: 1000...60000 | ||
| Number_Of_APDU_Retries Range: 0...16 | ||
| MAX_Info_Frames Range: 1...60 | ||
| Proprietary Properties: aler-devinfo (512) | Datatype: Octet String | |
| Purpose: Diagnostics. | ||
| Analog Input | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: Description | Limit: 30 Characters | |
| Proprietary Properties: n/a | ||
| Analog Output | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: Present_Value | Range: 0...102.4 | |
| Description | Limit: 30 Characters | |
| Proprietary Properties: n/a | ||
| Analog Value | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: Present_Value | Range: REAL | |
| Description | Limit: 30 Characters | |
| Proprietary Properties: n/a | ||
| Binary Input | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: Description Limit: 30 | Characters | |
| Proprietary Properties: n/a | ||
| Binary Output | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: Present_Value | ||
| Description Limit: 30 Characters | ||
| Proprietary Properties: n/a | ||
| Binary Value | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Priority_Array (only on BV40) | ||
| Relinquish_Default (only on BV40) | ||
| Writable Properties: Present_Value | ||
| Description Limit: 30 Characters | ||
| Relinquish_Default | ||
| Proprietary Properties: n/a | ||
| Calendar | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: Date_List | ||
| Proprietary Properties: n/a | ||
| Multistate Value | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: State_Text | ||
| Writable Properties: Present_Value Limit: Preset Values | ||
| Proprietary Properties: n/a | ||
| File | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Writable Properties: n/a | ||
| Proprietary Properties: n/a | ||
| Program | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Reason_for_Halt | ||
| Description_of_Halt | ||
| Program_Location | ||
| Instance_of | ||
| Writable Properties: Program_Change | ||
| Proprietary Properties: n/a | ||
| Schedule | ||
| Dynamically Creatable: No | ||
| Dynamically Deletable: No | ||
| Optional Properties Supported: Description | ||
| Weekly_ScheduleException-Schedule | ||
| Writable Properties: Weekly_Schedule | Priority-for-Writing | |
| Proprietary Properties: n/a | ||
Table 5. Data Link Layer Options.
| ✓ | Options |
| BACnet IP, (Annex J) | |
| BACnet IP, (Annex J), Foreign Device | |
| ISO 8802-3, Ethernet (Clause 7) | |
| ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8) | |
| ANSI/ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) ____ | |
| ✓ | MS/TP master (Clause 9), baud rate(s): 9.6K, 19.2K, 38.4K, 76.8K, 115.2K |
| MS/TP slave (Clause 9), baud rate(s): | |
| Point-To-Point, EIA 232 (Clause 10), baud rate(s): | |
| Point-To-Point, modem, (Clause 10), baud rate(s): | |
| LonTalk, (Clause 11), medium: ____ | |
| Other: |
Device Address Binding
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.) Yes √ No
Table 6. Networking Options.
| √ | Description |
| Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc. | |
| BACnet IP to/from Ethernet | |
| BACnet IP to/from MS/TP | |
| Ethernet to/from MS/TP | |
| Annex H, BACnet Tunneling Router over IP | |
| BACnet/IP Broadcast Management Device (BBMD) | |
| Does the BBMD support registrations by Foreign Devices? |
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
| √ | Character Set | √ | Character Set | √ | Character Set |
| √ | ANSI X3.4 IBM /Microsoft DB | CS ISO 8859-1 | |||
| ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226 | |||||
If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the gateway supports:
Not a gateway
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys' fees, arising out of, or resulting from, any modification to the literature by you.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
* U.S. Registered Trademark
© 2016 Honeywell International Inc.
31-00102-02 M.S. Rev. 06-16
Printed in United States