FERROLI DIVAtech D LN C24 - Central heating boiler

DIVAtech D LN C24 - Central heating boiler FERROLI - Free user manual and instructions

Find the device manual for free DIVAtech D LN C24 FERROLI in PDF.

📄 44 pages English EN Download 💬 AI Question
Notice FERROLI DIVAtech D LN C24 - page 16
View the manual : Français FR English EN Italiano IT
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about DIVAtech D LN C24 FERROLI

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Central heating boiler in PDF format for free! Find your manual DIVAtech D LN C24 - FERROLI and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. DIVAtech D LN C24 by FERROLI.

USER MANUAL DIVAtech D LN C24 FERROLI

DIVAtech D LN C24/C32

FERROLI DIVAtech D LN C24 - DIVAtech D LN C24/C32 - 1

FERROLI DIVAtech D LN C24 - DIVAtech D LN C24/C32 - 2

FERROLI DIVAtech D LN C24 - DIVAtech D LN C24/C32 - 3

IT

1. AVVERTENZE GENERALI

16 Connession Service Tool

17 Idrometro

  • Carefully read and follow the instructions contained in this instruction booklet.
  • After boiler installation, inform the user regarding its operation and give him this manual, which is an integral and essential part of the product and must be kept with care for future reference.
  • Installation and maintenance must be carried out by professionally qualified personnel, in compliance with the current regulations and according to the manufacturer's instructions. Do not carry out any operation on the sealed control parts.
  • Incorrect installation or inadequate maintenance can result in damage or injury. The Manufacturer declines any liability for damage due to errors in installation and use, or failure to follow the instructions.
  • Before carrying out any cleaning or maintenance operation, disconnect the unit from the electrical power supply using the switch and/or the special cut-off devices.
  • In case of a fault and/or poor operation, deactivate the unit and do not try to repair it or directly intervene. Contact professionally qualified personnel. Any repair/replacement of the products must only be carried out by qualified personnel using original replacement parts. Failure to comply with the above could affect the safety of the unit.
  • This unit must only be used for its intended purpose. Any other use is deemed improper and therefore hazardous.
  • The packing materials are potentially hazardous and must not be left within the reach of children.
  • The unit must not be used by people (including children) with limited physical, sensory or mental abilities or without experience and knowledge of it, unless instructed or supervised in its use by someone responsible for their safety.
  • The unit and its accessories must be appropriately disposed of, in compliance with the current regulations.
  • The images given in this manual are a simplified representation of the product. In this representation there may be slight and insignificant differences with respect to the product supplied.

FERROLI DIVAtech D LN C24 - AVVERTENZE GENERALI - 1

THE CE MARKING CERTIFIES THAT THE PRODUCTS MEET THE ESSENTIAL REQUIREMENTS

OF THE RELEVANT DIRECTIVES IN FORCE.

THE DECLARATION OF CONFORMITY MAY BE REQUESTED FROM THE MANUFACTURER.

2. OPERATING INSTRUCTIONS

2.1 Introduction

Dear Customer,

DIVATEch D LN C is a high-efficiency for heating and hot water production running on natural gas or LPG, and equipped with a microprocessor control system.

2.2 Control panel

FERROLI DIVAtech D LN C24 - Control panel - 1
Panel
fig.1 - Control panel

Key of panel fig. 1

1 DHW temperature setting decrease button
2 DHW temperature setting increase button
3 Heating system temperature setting decrease button
4 Heating system temperature setting increase button
5 Display
6 "Sliding Temperature" Menu - Summer/Winter mode selection - Reset button
7 Unit On/Off - Economy/Comfort mode selection button
8 DHW symbo
9 DHW mode
10 Summer mode
11 Multifunction
12 Eco (Economy) mode
13 Heating
14 Heating symbol
15 Burner lit and actual power level (flashing during combustion fault function)
16 Service Tool connection
17 Water gauge

Indication during operation

Heating

A heating demand (generated by the Room Thermostat or Remote Timer Control) is indicated by flashing of the hot air above the radiator on the display.

The display (detail 11 - fig. 1) shows the actual heating delivery temperature and, during heating standby time, the message "d2".

Domestic hot water (DHW)

A DHW demand (generated by drawing domestic hot water) is indicated by flashing of the hot water under the tap on the display.

The display (detail 11 - fig. 1) shows the actual DHW outlet temperature and, during DHW standby time, the message "d1".

Comfort

A Comfort demand (reinstatement of temperature inside the boiler) is indicated by flashing of the water under the tap on the display. The display (detail 11 - fig. 1) shows the actual temperature of the water in the boiler.

Fault

In case of a fault (see cap. 4.4) the display shows the fault code (detail 11 - fig. 1) and during safety pause times the messages "d3", "d4" and "d5".

2.3 Lighting and shutdown

Connection to the power supply

  • During the first 5 seconds the display will also show the card software release.
  • Open the gas cock ahead of the boiler.
  • The boiler is now ready to function automatically whenever domestic hot water is drawn or in case of a heating demand (generated by Room Thermostat or Remote Temperature Control).

Turning the boiler off and on

Press the on/off button (detail 7 - fig. 1) for 5 seconds.

FERROLI DIVAtech D LN C24 - Turning the boiler off and on - 1
fig. 2 - Turning the boiler off

When the boiler is turned off, the circuit board is still powered. Domestic hot water and heating are disabled. The frost protection system remains activated. To relight the boiler, press the on/off button (detail 7 fig. 1) again for 5 seconds.

FERROLI DIVAtech D LN C24 - Turning the boiler off and on - 2
fig. 3

The boiler will be immediately ready to work whenever domestic hot water is drawn or in case of a heating demand (generated by the Room Thermostat or the Remote Timer control).

The frost protection system does not work when the power and/or gas to the unit are turned off. To avoid damage caused by freezing during long shutdowns in winter, it is advisable to drain all water from the boiler, the DHW circuit and the heating system water; or drain just the DHW circuit and add a suitable antifreeze to the heating system, as prescribed in sec. 3.3.

2.4 Adjustments

Summer/Winter Sustainover

Press the summer/winter button (detail 6 - fig. 1) for 2 seconds.

The display activates the Summer symbol (detail 10 - fig. 1): the boiler will only deliver domestic hot water. The antifreeze system remains activated.

To deactivate the Summer mode, press the summer/winter button (detail 6 - fig. 1) again for 2 seconds.

Heating temperature adjustment

Use the heating buttons (details 3 and 4 - fig. 1) to adjust the temperature from a min. of 30^ to a max. of 80^ ; in any case, it is advisable not to operate the boiler below 45^ .

FERROLI DIVAtech D LN C24 - Heating temperature adjustment - 1
fig. 4

DHW temperature adjustment

Use the DHW buttons (details 1 and 2 - fig. 1) to adjust the temperature from a min. of 40^ to a max. of 55^ .

FERROLI DIVAtech D LN C24 - DHW temperature adjustment - 1
fig.5

Room temperature adjustment (with optional room thermostat)

Using the room thermostat, set the temperature required in the rooms. If the room thermostat is not installed, the boiler will keep the system at the set system delivery setpoint temperature.

Room temperature adjustment (with optional remote timer control)

Using the remote timer control, set the required temperature in the rooms. The boiler will adjust the system water according to the required room temperature. For operation with remote timer control, please refer to the relevant instruction manual.

ECO/COMFORT selection

The unit has a function that ensures a high domestic hot water delivery speed and maximum comfort for the user. When the device is activated (COMFORT mode), the water contained in the boiler is kept hot, thereby ensuring immediate availability of hot water on opening the tap, without waiting times.

The user can deactivate the device (ECO mode) by pressing the eco/comfort button (detail 7 - fig. 1). In ECO mode the display activates the ECO symbol (detail 12 - fig. 1). To activate the COMFORT mode, press the eco/comfort button (detail 7 - fig. 1) again.

Sliding Temperature

When the optional external probe is installed the boiler adjustment system works with "Sliding Temperature". In this mode, the heating system temperature is regulated according to weather conditions, to ensure the high comfort and energy efficiency throughout the year. In particular, as the outside temperature increases the system delivery temperature decreases according to a specific "compensation curve".

With the Sliding Temperature adjustment, the temperature set with the heating buttons (detail 3 - fig. 1) becomes the maximum system delivery temperature. It is advisable to set a maximum value to allow system adjustment throughout its useful operating range.

The boiler must be adjusted at the time of installation by qualified personnel. However, the user can make any further adjustments necessary to optimise comfort levels.

Compensation curve and curve offset

Press the reset button (detail 6 - fig. 1) for 5 seconds to access the "Sliding temperature" menu; the display shows "CU" flashing.

Use the DHW buttons (detail 1 - fig. 1) to adjust the desired curve from 1 to 10 according to the characteristic (fig. 6). By setting the curve to 0, the sliding temperature adjustment is disabled.

Press the heating buttons (detail 3 - fig. 1) to access parallel curve offset; the display shows "OF" flashing. Use the DHW buttons (detail 1 - fig. 1) to adjust parallel curve offset according to the characteristic (fig. 7).

Press the reset button (detail 6 - fig. 1) again for 5 seconds to exit the "Sliding Temperature" menu.

If the room temperature is lower than the required value, it is advisable to set a higher order curve and vice versa. Proceed by increasing or decreasing in steps of one and check the result in the room.

FERROLI DIVAtech D LN C24 - Sliding Temperature - 1
fig.6 - Compensation curves

FERROLI DIVAtech D LN C24 - Sliding Temperature - 2
OFFSET=20

FERROLI DIVAtech D LN C24 - Sliding Temperature - 3
OFFSET=40
fig. 7 - Example of compensation parallel curve offset

Adjustments from Remote Timer Control

FERROLI DIVAtech D LN C24 - Adjustments from Remote Timer Control - 1

If the Remote Timer Control (optional) is connected to the boiler, the above adjustments are managed according to that given in table 1.

Table. 1

Heating temperature settingAdjustment can be made from the Remote Timer Control menu and the boiler control panel.
DHW temperature adjustmentAdjustment can be made from the Remote Timer Control menu and the boiler control panel.
Summer/Winter SwitchoverSummer mode has priority over a possible Remote Timer Control heating demand.
Eco/Comfort selectionOn disabling DHW from the Remote Timer Control menu, the boiler selects the Economy mode. In this condition, the eco/comfort button (detail 7 - fig. 1) on the boiler panel is disabled.
On enabling DHW from the Remote Timer Control menu, the boiler selects the Comfort mode. In this condition it is possible select one of the two modes with the eco/comfort button (detail 7 - fig. 1) on the boiler panel.
Sliding TemperatureBoth the Remote Timer Control and the boiler card manage Sliding Temperature adjustment: the boiler card Sliding Temperature has priority.

System water pressure adjustment

The filling pressure read on the boiler water gauge (detail 2 - fig. 8) with system cold must be approx 1.0 bar. If the system pressure falls below minimum values, the boiler stops and fault F37 is displayed. Pull out the filling knob (detail 1 - fig. 8) and turn it anticlockwise to return it to the initial value. Always close it afterwards.

Once the system pressure is restored, the boiler will activate the 300-second air venting cycle indicated on the display by Fh.

To prevent boiler shutdown, it is advisable to periodically check the pressure on the gauge with system cold. In case of a pressure below 0.8 bar, it is advisable to restore it.

FERROLI DIVAtech D LN C24 - System water pressure adjustment - 1
fig. 8- Filling knob

System draining

The drain faucet ring nut is located under the safety valve inside the boiler.

To drain the system, turn the ring (ref. 1 - fig. 9) counter-clockwise to open the faucet. Do not use any tools; use hands only.

To drain only the water in the boiler, first close the shut-off valves between the system and boiler before turning the ring.

FERROLI DIVAtech D LN C24 - System draining - 1
fig. 9-Safety valve with drain faucet

3. INSTALLATION

3.1 General Instructions

BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF NATIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.

3.2 Place of installation

FERROLI DIVAtech D LN C24 - Place of installation - 1

This unit is an "open chamber" type and can only be installed and operated in permanently ventilated rooms. An insufficient flow of combustion air to the boiler will affect its normal operation and fume evacuation. Also, the fumes forming under these conditions are extremely harmful to health if dispersed in the domestic environment.

The unit is designed to operate in a partially protected place, with a minimum temperature of -5^ . If provided with the special antifreeze kit, it can be used with a minimum temperature down to -15^ . The boiler must be installed in a sheltered place, for instance under the slope of a roof, inside a balcony or in a protected recess.

The place of installation must be free of flammable materials, objects and dusts or corrosive gases.

The boiler is arranged for wall mounting and comes as standard with a hooking bracket. Wall fixing must ensure stable and effective support for the generator.

FERROLI DIVAtech D LN C24 - Place of installation - 2

If the unit is enclosed in a cabinet or mounted alongside, there must be sufficient space for removing the casing and for normal maintenance activities

3.3 Plumbing connections

Important

FERROLI DIVAtech D LN C24 - Important - 1

The safety valve outlet must be connected to a funnel or collection pipe to prevent water spurting onto the floor in case of overpressure in the heating circuit. Otherwise, if the discharge valve cuts in and floods the room, the boiler manufacturer cannot be held liable.

FERROLI DIVAtech D LN C24 - Important - 2

Before making the connection, check that the unit is arranged for operation with the type of fuel available and carefully clean all the system pipes.

Carry out the relevant connections according to the diagram in fig. 2.3 and the symbols on the unit.

Note: The unit is equipped with an internal bypass in the heating circuit.

Water system characteristics

In the presence of water harder than 25^ r (1^ = 10ppmCaCO_3) use suitably treated water in order to avoid possible scaling in the boiler.

Antifreeze system, antifreeze fluids, additives and inhibitors

When necessary, antifreeze fluids, additives and inhibitors can be used only if the manufacturer of such fluids or additives guarantees that they are suitable and do not cause damage to the exchanger or other components and/or materials of the boiler and system. Do not use generic antifreeze fluids, additives or inhibitors that are not specific for use in heating systems and compatible with the materials of the boiler and system.

3.4 Gas connection

The gas must be connected to the relevant connection (see fig. 2.3) in conformity with the current standards, using a rigid metal pipe or a continuous surface flexible s/steel tube and installing a gas cock between the system and boiler. Make sure all the gas connections are tight.

3.5 Electrical connections

IMPORTANT

FERROLI DIVAtech D LN C24 - IMPORTANT - 1

BEFORE CARRYING OUT ANY OPERATION THAT REQUIRES REMOVING THE CASING, DISCONNECT THE BOILER FROM THE ELECTRIC MAINS WITH THE MAIN SWITCH.

NEVER TOUCH THE ELECTRICAL COMPONENTS OR CONTACTS WITH THE MAIN SWITCH TURNOED ON! DANGER OF ELECTRIC SHOCK WITH RISK OF INJURY OR DEATH!

FERROLI DIVAtech D LN C24 - IMPORTANT - 2

The unit must be connected to an efficient grounding system in accordance with applicable safety regulations. Have the efficiency and suitability of the grounding system checked by professionally qualified personnel; the Manufacturer declines any liability for damage caused by failure to earth the system.

The boiler is prewired and provided with a three-pole cable, without a plug, for connection to the electric line. The connections to the grid must be made with a permanent connection and equipped with a bipolar switch whose contacts have a minimum opening of at least 3mm , interposing fuses of max. 3A between the boiler and the line. Make sure to respect the polarities (LINE: brown wire / NEUTRAL: blue wire / GROUND: yellow-green wire) in the connections to the electric line.

FERROLI DIVAtech D LN C24 - IMPORTANT - 3

The unit's supply cable MUST NOT BE REPLACED BY THE USER. If the cable gets damaged, turn the unit off and have the cable replaced only by professionally qualified personnel. In case of replacement, only use cable "HAR H05 VV-F" 3 × 0.75 ~mm^2 with max. external diameter of 8 ~mm .

Room thermostat (optional)

FERROLI DIVAtech D LN C24 - Room thermostat (optional) - 1

IMPORTANT: THE ROOM THERMOSTAT MUST HAVE VOLTAGE-FREE CONTACTS. CONNECTING 230 V TO THE ROOM THERMOSTAT TERMINALS WILL PERMANENTLY DAMAGE THE ELECTRONIC BOARD.

When connecting time controls or a timer, do not take the power supply for these devices from their breaking contacts. Their power supply must be by means of direct connection from the mains or with batteries, depending on the kind of device.

Accessing the electrical terminal block

The electrical terminal block can be accessed after removing the casing. The layout of the terminals for the various connections is also given in the wiring diagram in fig. 23.

FERROLI DIVAtech D LN C24 - Accessing the electrical terminal block - 1
fig. 10 - Accessing the terminal block

3.6 Air/fume ducts

The diameter of the flue connection pipe must not be less than that of the connection on the anti-backflow device. Starting from the anti-backflow device it must have a vertical section at least 50~cm long. Current standards must be complied with regarding sizing and installation of the flues and connection pipe.

FERROLI DIVAtech D LN C24 - Air/fume ducts - 1

The boiler is also equipped with a safety device (fume thermostat) that stops operation of unit in case of inadequate draught of obstruction of the flue. This device must never be tampered with or deactivated.

4. SERVICE AND MAINTENANCE

Important

FERROLI DIVAtech D LN C24 - Important - 1

All adjustment, conversion, commissioning and maintenance operations described below must only be carried out by Qualified Personnel (meeting the professional technical requirements of current regulations) such as the personnel of the Local After-Sales Technical Service.

FERROLI declines any liability for damage and/or injury caused by unqualified and unauthorized persons tampering with the unit.

4.1 Adjustments

Gas conversion

ALL COMPONENTS DAMAGED DURING CONVERSION OPERATIONS MUST BE REPLACED.

The unit can operate on natural gas or LPG and is factory-set for use with one of these two gases, as clearly shown on the packing and on the data plate. Whenever a gas different from that for which the unit is arranged has to be used, the special conversion kit will be required, proceeding as follows:

  1. Disconnect the boiler power supply and close the gas cock.
  2. Replace the nozzles at the main burner, fitting the nozzles specified in the technical data table in cap. 5, according to the type of gas used
  3. Switch the boiler power on and open the gas cock.
  4. Modify the parameter for the type of gas:

  5. put the boiler in standby mode

  6. press the DHW buttons details 1 and 2 - fig. 1 for 10 seconds: the display shows "b01" flashing.
  7. press the DHW buttons details 1 and 2 - fig. 1 to set the parameter 00 (for natural gas operation) or 01 (for LPG operation).
  8. press the DHW buttons details 1 and 2 - fig. 1 for 10 seconds.
    the boiler will return to standby mode

  9. Adjust the minimum and maximum pressures at the burner (ref. relevant paragraph), setting the values given in the technical data table for the type of gas used

  10. Apply the sticker contained in the conversion kit, near the data plate as proof of the conversion.

Activation of Auto-setting function for gas valve calibration

THIS PROCEDURE MUST ONLY BE CARRIED OUT IN THE FOLLOWING CASES: GAS VALVE REPLACEMENT, CARD REPLACEMENT, CONVERSION FOR GAS CHANGE.

The B&P Gas Valve (with integrated modulating operator) does not provide for mechanical calibration: the minimum and maximum power adjustments are therefore electronically done via two parameters:

ContentsDescriptionNatural GasPropane Gas
q01Absolute minimum current offset 0÷1000÷150
q02Absolute maximum current offset0÷1000-150

Gas valve pre-calibration

  1. Connect a pressure gauge to monitor the gas valve outlet pressure.
  2. Enable the Auto-setting function (Parameter b12=1).
  3. Activate the calibration procedure by pressing the heating + button and Eco/Comfort button together for 5 seconds. The message "Au-to" immediately appears (in two successive flashes) and the burner is lit. Within 8 seconds (natural gas and LPG) the boiler finds the ignition point. The ignition point, absolute minimum current Offset (Parameter q01) and absolute maximum current Offset (Parameter q02) values are stored by the card.

Gas valve calibration

  1. The display will show "q02" flashing; the modulation current is forced to the pre-calibration value of the absolute maximum current Offset parameter (Parameter q02)
  2. Press the DHW buttons to adjust the parameter "q02" until the maximum nominal pressure minus 1mbar is reached on the pressure gauge. Wait 10 seconds for the pressure to stabilise.
  3. Press the DHW "+?" button to set the parameter "q02" until the maximum nominal pressure is reached on the pressure gauge. Wait 10 seconds for the pressure to stabilise.
  4. If the pressure read on the pressure gauge is different from the maximum nominal pressure, proceed in increments of 1 or 2 units of the parameter "q02" by pressing the DHW "+" button: after each change, wait 10 seconds for the pressure to stabilise.
  5. When the pressure read on the pressure gauge is equal to the maximum nominal pressure (the newly calibrated value of the parameter "q02" is automatically saved), press the heating - button: the display will show "q01" flashing; the modulation current is forced to the pre-calibration value of the absolute minimum current Offset parameter (Parameter q01).
  6. Press the DHW buttons to adjust the parameter "q01" until the minimum nominal pressure plus 0.5mbar is reached on the pressure gauge. Wait 10 seconds for the pressure to stabilise.
  7. Press the DHW "..." button to adjust the parameter "q01" until the minimum nominal pressure is reached on the pressure gauge. Wait 10 seconds for the pressure to stabilise.
  8. If the pressure read on the pressure gauge is different from the minimum nominal pressure, proceed in decrements of 1 or 2 units of the parameter "q01" by pressing the DHW "..." button: after each change, wait 10 seconds for the pressure to stabilise
  9. When the pressure read on the pressure gauge is equal to the minimum nominal pressure (the newly calibrated value of the parameter "q01" is automatically saved.), recheck both adjustments by pressing the healing buttons and correct them if necessary by repeating the procedure described above.
  10. The calibration procedure ends automatically after 15 minutes or by pressing the heating "+" and Eco/Comfort buttons together for 5 seconds.

Checking of gas pressure values and adjustment with limited range

  • Check that the supply pressure complies with that indicated in the technical data table.
  • Connect a suitable pressure gauge to the pressure sampling point "B" located downstream from the gas valve.
  • Activate the TEST mode and follow the instructions for checking the gas pressures at maximum power and minimum power (see next par.).

If the maximum and/or minimum nominal pressures read on the pressure gauge are different from those indicated in the technical data table, proceed with the next sequence.

  • Press the Eco/Comfort button for 2 seconds to go to the gas valve Calibration with limited range mode.
    The card goes to the setting "q02"; displaying the currently saved value by pressing the DHW buttons.
  • If the maximum pressure read on the pressure gauge is different from the nominal one, proceed in increments/decrements of 1 or 2 units of the parameter "q02" by pressing the DHW buttons: after each change, the value is stored; wait 10 seconds for the pressure to stabilise.
  • Press the heating " - button (ref. 3 - fig. 1).
  • The card goes to the setting "q01"; displaying the currently saved value by pressing the DHW buttons.
  • If the minimum pressure read on the pressure gauge is different from the nominal one, proceed in increments/decrements of 1 or 2 units of the parameter "q01" by pressing the DHW buttons: after each change, the value is stored; wait 10 seconds for the pressure to stabilise.
  • Recheck both settings by pressing the heating buttons and if necessary correct them by repeating the procedure described above.
  • Pressing the Eco/Comfort button for 2 seconds returns to TEST mode.
  • Deactivate TEST mode (see next par.).
  • Disconnect the pressure gauge

FERROLI DIVAtech D LN C24 - Checking of gas pressure values and adjustment with limited range - 1
fig. 11 - Gas valve

A - Upstream pressure point
B-Downstream pressure point
I-Gas valve electrical connection
R-Gas outlet
S-Gas inlet

FERROLI DIVAtech D LN C24 - Checking of gas pressure values and adjustment with limited range - 2
fig. 12 - Gas valve connection

TYPE SGV100
PI max 65 mbar
24 Vdc-class B+A

TEST mode activation

Press the heating buttons (details 3 and 4 - fig. 1) together for 5 seconds to activate the TEST mode. The boiler lights at the maximum heating power set as described in the following section.

The heating and DHW symbols (fig. 13) flash on the display; the heating power will appear alongside.

FERROLI DIVAtech D LN C24 - TEST mode activation - 1
fig.13 - TEST mode (heating power = 100%

Press the heating buttons (details 3 and 4 - fig. 1) to increase or decrease the power (Min. = 0%, Max. = 100%).

By pressing the DHW "+" button (detail 1 - fig. 1), boiler output is immediately adjusted to min. (0%) . By pressing the DHW "+" button (detail 2 - fig. 1), boiler output is immediately adjusted to max. (100%) .

If the TEST mode is activated and enough hot water is drawn to activate the DHW mode, the boiler remains in TEST mode but the 3-way valve goes to DHW.

To deactivate the TEST mode, press the heating buttons (details 3 and 4 - fig. 1) together for 5 seconds.

The TEST mode is automatically deactivated in any case after 15 minutes or on stopping of hot water drawing (if enough hot water has been drawn to activate the DHW mode).

Heating power adjustment

To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the heating buttons detail 3 - fig. 1 to increase or decrease the power (min. = 00 - max. = 100). Press the reset button within 5 seconds and the max. power will remain that just set. Exit TEST mode (see sec. 4.1).

Configuration Menu

The configuration Menu is accessed by pressing the DHW buttons together for 10 seconds. 12 parameters, indicated by the letter "b" and not modifiable from Remote Timer Control, are available.

Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to view or modify the value of a parameter: the change will be automatically saved.

ContentsDescription Range Parameter
b01Gas type selection0 = Natural Gas0
1 = LPG
b02Boiler type selection2
b03Combustion chamber type selection5 = LOW NOx Open Chamber(with fume thermostat)5
b04Primary Exchanger type selection 0 ÷134 (for model C24)5 (for model C30)
b05---0
b06Mains Voltage Frequency0 = 50Hz0
1 = 60Hz
b07---5
b08Gas valve driver 0 = Standard, 1 0
b09DHW demand type selection 1 = Flowmeter (190 imp/t) 1
b10Flowmeter timing0 = Deactivated1-10=seconds0
b11DHW mode activation flow rate10 ÷ 100 L/min/1015
b12Enable Auto-Settings procedure0 = Disabled1 = Enabled0

Notes:

  1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter given in brackets.
  2. Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.

To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting occurs automatically after 2 minutes.

Service menu

The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub menus are available: press the Heating buttons to select, in increasing or decreasing order, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means Information Menu, "Hi" means History Menu; after selecting the submenu, press the Reset button again to access it; "rE" means History Menu Reset: see description.

“tS”-Transparent Parameters Menu

21 parameters indicated by the letter "P" are available, which are also modifiable from Remote Timer Control.

Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to view or modify the value of a parameter: the change will be automatically saved.

ContentsDescriptionRangeDIVAtech D LN C
P01Ignition ramp Offset0-4020
P02Heating ramp1-20°C/minute5
P03Heating standby time0-10 minutes2
P04Heating Post-Circulation0-20 minutes6
P05Heating user max. setpoint31-85°C80
P06Max. output in heating0-100%100
P07Burner shutdown in DHW0=Fixed0
1=Linked to set point
2=Solar
3 = DO NOT USE
4 = DO NOT USE
P08DHW standby time0-60 seconds30
P09DHW user max. setpoint50-65°C50
P10No effect on adjustment--0
P11DHW Post-Circulation0-60 Seconds30
P12Max. output in DHW0-100%100
P13Absolute min. power0-100%0
P14NOT AVAILABLE FOR THIS MODEL
P15No effect on adjustment (b03=5)--
P16Exchanger protection activation0=No F4310
1-15=1-15°C/second
P17Modulating pump max. speed - absoluteOperating at 100%. Adjustable with optional cable.100
P18Modulating pump max. speed - post circulation0-100% not operating. Always at 100% in this model60
P19Solar deactivation temperature0-20°C10
P20Solar ignition temperature0-20°C10
P21Solar standby time0-20 seconds10

Notes:

  1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter given in brackets.
  2. Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
  3. The Maximum Heating Power parameter can also be modified in Test Mode.

Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.

"In" - Information Menu

9 pieces of information are available.

Press the Heating buttons to scroll the list of information in increasing or decreasing order. Press the DHW buttons to display the value.

ContentsDescriptionRange
t01NTC Heating sensor (°C)between 05 and 125°C
t02NTC Safety sensor (°C)between 05 and 125°C
t03NTC DHW sensor (°C)between 05 and 125°C
t04NTC External sensor (°C)between -30 and 70°C (negative values flash)Without NTC = --
L05Actual burner power (%)00%=Min., 100%=Max.
F06Actual Flame resistance (kOhm)00-99 kOhm (--)=burner off!
St07NOT AVAILABLE FOR THIS MODEL
F08Actual DHW drawing (L min/10)L min/10 over 99 flashing 3 figures
PP09Actual modulating pump speed (%): 00:100% not working in this model

Notes:

  1. In case of damaged sensor, the card displays hyphens.

Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service Menu or exiting occurs automatically after 15 minutes.

"Hi" - History Menu

The card can store the last 11 faults: the History datum item H1: represents the most recent fault that occurred; the History datum item H10: represents the least recent fault that occurred.

The codes of the faults saved are also displayed in the corresponding menu of the Remote Timer Control.

Press the Heating buttons to scroll the list of faults in increasing or decreasing order. Press the DHW buttons to display the value.

Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.

"rE"-History Reset

Press the Eco/Comfort button for 3 seconds to delete all the faults stored in the History Menu: the card will automatically exit the Service Menu, in order to confirm the operation. Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.

4.2 Commissioning

Before lighting the boller

  • Check the seal of the gas system.
  • Check correct prefilling of the expansion tank.
  • Fill the water system and make sure all air contained in the boiler and the system has been vented.
    Make sure there are no water leaks in the system, DHW circuits, connections or boiler.
  • Check correct connection of the electrical system and efficiency of the earthing system.
  • Make sure the gas pressure for heating is that required.
  • Make sure there are no flammable liquids or materials in the immediate vicinity of the boiler

FERROLI DIVAtech D LN C24 - Before lighting the boller - 1

IF THE ABOVE INSTRUCTIONS ARE NOT OBSERVED THERE MAY BE RISK OF SUFFOCATION OR POISONING DUE TO GAS OR FUMES ESCAPING; DANGER OF FIRE OR EXPLOSION. ALSO, THERE MAY BE A RISK OF ELECTRIC SHOCK OR FLOODING THE ROOM.

Checks during operation

  • Switch the unit on.
  • Check the tightness of the fuel circuit and water systems.
  • Check the efficiency of the flue and air/fume ducts while the boiler is working
  • Make sure the water is circulating properly between the boiler and the systems.
  • Make sure the gas valve modulates correctly in the heating and domestic hot water production stages.
  • Check correct boiler lighting by performing various tests, turning it on and off with the room thermostat or remote control.
  • Make sure the fuel consumption indicated on the meter matches that given in the technical data table in cap. 5.
  • Make sure that with no demand for heating, the burner lights correctly on opening a hot water tap. Check that in heating mode, on opening a hot water tap, the heating circulating pump stops and there is regular production of hot water.
  • Make sure the parameters are programmed correctly and carry out any required customisation (compensation curve, power, temperatures, etc.).

4.3 Maintenance

IMPORTANT

FERROLI DIVAtech D LN C24 - IMPORTANT - 1

ALL MAINTENANCE WORK AND REPLACEMENTS MUST BE CARRIED OUT BY SKILLED QUALIFIED PERSONNEL.

Before carrying out any operation inside the boiler, disconnect the power and close the gas cock upstream. Otherwise there may be a danger of explosion, electric shock, suffocation or poisoning.

Periodical inspection

To ensure proper operation of the unit over time, have qualified personnel carry out a yearly inspection, providing for the following checks:

  • The control and safety devices (gas valve, flow switch, thermostats, etc.) must function correctly.
  • The fume exhaust circuit must be perfectly efficient. (Sealed chamber boiler: fan, pressure switch, etc. - The sealed chamber must be tight: seals, cable glands, etc.) (Open chamber boiler: anti-backflow device, fume thermostat, etc.)
    The air/fume terminal and ducts must be free of obstructions and leaks
  • The burner and exchanger must be clean and free of deposits. Do not use chemical products or wire brushes to clean.
    The electrode must be properly positioned and free of deposits.

FERROLI DIVAtech D LN C24 - Periodical inspection - 1
fig. 14 - Electrode positioning

The gas and water systems must be tight.
The pressure of the water in the system when cold must be approx. 1 bar; otherwise, bring it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
- The gas flow and pressure must match that given in the respective tables.

4.4 Troubleshooting

Diagnostics

The boiler has an advanced self-diagnosis system. In case of a boiler fault, the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault code.

There are faults that cause permanent shutdowns (marked with the letter "A"): to restore operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the optional remote timer control if installed. At this point the display will show "d4" for about 30 seconds or "d5" for about 5 minutes which indicates the waiting time after which the boiler will resume normal operation. If the boiler fails to restart, it is necessary to eliminate the fault.

Other faults cause temporary shutdowns (marked with the letter "F") which are automatically reset as soon as the value returns within the boiler's normal working range.

List of faults

Table. 2

Fault codeFault Possible cause Cure
A01No burner ignitionNo gasCheck the regular gas flow to the boiler and that the air has been eliminated from the pipes
Ignition/detection electrode faultCheck the wiring of the electrode and that it is correctly positioned and free of any deposits
Faulty gas valveCheck the gas valve and replace it if necessary
Gas valve wiring disconnectedCheck the wiring
Ignition power too low Adjust theIgnition power
A02Flame present signal with burner offElectrode faultCheck the ionisation electrode wiring
Card fault Check the card
A03Overtemperature protection activationHeating sensor damagedCheck the correct positioning and operation of the heating sensor
No water circulation in the systemCheck the circulating pump
Air in the system Vent the system
F04Fume thermostat activated (after activation of the fume thermostat, boiler operation is prevented for 20 minutes)Fume thermostat contact openCheck the thermostat
Wiring disconnected Check the wiring
Flue obstructed or not correctly sizedCheck the flue
Fault codeFault Possible cause Cure
F05Card parameter fault Wrong card parameter settingCheck the card parameter and modify it if necessary
A06No flame after the ignition phaseLow pressure in the gas systemCheck the gas pressure
Burner minimum pressure settingCheck the pressures
F07Card parameter fault Wrong card parameter settingCheck the card parameter and modify it if necessary
A09Gas valve faultWiring disconnected Check the wiring
Faulty gas valveCheck the gas valve and replace it if necessary
F10Delivery sensor 1 faultSensor damagedCheck the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11DHW sensor faultSensor damagedCheck the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F14Delivery sensor 2 faultSensor damagedCheck the wiring or replace the sensor
Wiring shorted
Wiring disconnected
A16Gas valve faultWiring disconnected Check the wiring
Faulty gas valveCheck the gas valve and replace it if necessary
F20Card parameter fault Wrong card parameter settingCheck the card parameter and modify it if necessary
A21Card parameter fault Wrong card parameter settingCheck the card parameter and modify it if necessary
A23Card parameter fault Wrong card parameter settingCheck the card parameter and modify it if necessary
A24Card parameter fault Wrong card parameter settingCheck the card parameter and modify it if necessary
F34Supply voltage under 170V.Electric mains troubleCheck the electrical system
F35Faulty mains frequencyElectric mains troubleCheck the electrical system
F37Incorrect system water pressurePressure too lowFill the system
Water pressure switch damaged or not connectedCheck the sensor
F39External probe faultProbe damaged or wiring shortedCheck the wiring or replace the sensor
Probe disconnected after acti- vating the sliding temperatureReconnect the external sensor or disable the sliding temperature
A41Sensor positioningDelivery sensor detached from the pipeCheck the correct positioning and operation of the sensor
F42Heating sensor faultSensor damagedReplace the sensor
F43Exchanger protection trips.No system \( H_2O \)circulationCheck the circulating pump
Air in the systemVent the system
F50Gas valve faultModulating Operator wiring dis- connectedCheck the wiring
Faulty gas valveCheck the gas valve and replace it if necessary
A51Card parameter fault Wrong card parameter settingcard parameter settingCheck the card parameter and modify it if necessary

5. TECHNICAL DATA AND CHARACTERISTICS

Table. 3-Legend, fig.20, fig.21 and fig.22

8DHW outlet - Ø 1/2"56Expansion vessel
9DHW inlet - Ø 1/2"74System filling faucet
10System delivery - Ø 3/4"78Anti-backflow device
11System return - Ø 3/4"81Ignition and detection electrode
14Safety valve95Divertor valve
22Burner114Water pressure switch
27Copper exchanger for heating and DHW126Fume thermostat
32Heating circulating pump136Flowmeter
36Automatic air vent137Pressure sensor
37Cold water inlet filter194DHW exchanger
42DHW temperature sensor241Automatic bypass
44Gas valve278Double sensor (Safety + heating)

5.1 Dimensions and connections

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 1

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 2

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 3

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 4

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 5
7 Gas inlet - 0 3/4"
8 DHW outlet - 01/2"
9 Cold water inlet - 0 1/2"
10 System delivery - 0 3/4"
11 System return - 0 3/4"

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 6
5.2 General view and main components
fig. 20- General view - DIVAtech D LN C24

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 7
fig. 21- General view - DIVATEch D LN C30

FERROLI DIVAtech D LN C24 - TECHNICAL DATA AND CHARACTERISTICS - 8
5.3 Hydraulic circuit
fig. 22- Heating circuit

5.4 Technical data table

Data Unit DIVatech D LN C24 DIVatech D LN C30
Max. heating capacity (CH - DHW) kW 25.0 33.0 (Q)
Min. heating capacity (CH - DHW) kW 8.3 12.6 (Q)
Max. Heat Output in heatingkW22.8 30.0(P)
Min. Heat Output in heatingkW7.3 11.1(P)
Max. Heat Output in DHWkW22.8 30.0
Min. Heat Output in DHWkW7.3 11.1
Efficiency Pmax (60-60°C)%91.2 91.0
Efficiency 30%%89.8 89.8
NOx emissions class-6 (<56 mg/kWh)(NOx)
Burner nozzles G20no. x Ω24 x 0.8532 x 0.85
Gas supply pressure G20mbar20.0 20.0
Max. gas pressure at burner (G20)mbar15.0 15.0
Min. gas pressure at burner (G20)mbar2.02.0
Max. gas flow G20m3/h2.65 3.49
Min. gas flow G20m3/h0.88 1.33
Burner nozzles G31no. x Ω24 x 0.532 x 0.5
Gas supply pressure G31mbar3737
Max. gas pressure at burner (G31)mbar35.5 35.5
Min. gas pressure at burner (G31)mbar5.05.0
Max. gas flow G31kg/h1.942.56
Min. gas flow G31kg/h0.64 0.98
Max. working pressure in heatingbar33(PMS)
Min. working pressure in heatingbar0.80.8
Max. heating temperature°C9090(tmax)
Heating water contentliters0.81.2
Heating expansion vessel capacityliters810
Heating expansion vessel precharge pressurebar11
Max. working pressure in DHWbar99(PMW)
Min. working pressure in DHWbar0.30.3
DHW flow rate,at 25°Cl/min13.1 17.2
DHW flow rate,at 30°Cl/min10.9 14.3(D)
Protection ratingIPIPX4D
Power supply voltageV/Hz230V/50Hz
Electrical power inputW4852
Electrical power input in DHWW4852
Empty weightkg2730
Type of unitB11BS

ErP product fiche

MODEL: DIVATECH D LN C24 - (ODCC4YWA)

Trademark: FERROLI
Condensing boiler: NO
Low-temperature boiler (**) : YES
B1 Boiler: YES
Combination heater: YES
Cogeneration space heater: NO
ItemSymbolUnitValue
Seasonal space heating energy efficiency class (from A+++ to D)C
Rated heat outputPnkW23
Seasonal space heating energy efficiencyηs%77
Useful heat output
Useful heat output at rated heat output and high-temperature regime (*)P4kW22,8
Useful heat output at 30% of rated heat output and low-temperature regime (**)P1kW4,5
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*)η4%82,1
Useful efficiency at 30% of rated heat output and low-temperature regime (**)η1%80,9
Auxiliary electricity consumption
At full loadelmaxkW0,015
At part loadelminkW0,007
In standby modePSBkW0,003
Other items
Standby heat lossPstbykW0,140
Ignition burner power consumptionPignkW0,000
Annual energy consumptionQHEGJ57
Sound power levelLWAdB51
Emissions of nitrogen oxidesNOxmg/kWh32
For combination heaters
Declared load profileXL
Water heating energy efficiency class (from A+ to F)B
Daily electricity consumptionQeleckWh0,129
Annual electricity consumptionAECkWh28
Water heating energy efficiencyηwh%78
Daily fuel consumptionQfuelkWh23,274
Annual fuel consumptionAFCGJ19

^ High-temperature regime means 60^ return temperature at heater inlet and 80^ feed temperature at heater outlet.
(1^
*) Low temperature means for condensing boilers 30^ for low-temperature boilers 37^ and for other heaters 50^ return temperature [at heater inlet].

ErP product fiche

MODEL: DIVATECH D LN C30 - (ODCC6YWA)

Trademark: FERROLI
Condensing boiler: NO
Low-temperature boiler (*): YES
B1 Boiler: YES
Combination heater: YES
Cogeneration space heater: NO
ItemSymbolUnitValue
Seasonal space heating energy efficiency class (from A+++ to D)C
Rated heat outputPnkW30
Seasonal space heating energy efficiencyηs%77
Useful heat output
Useful heat output at rated heat output and high-temperature regime (*)P4kW30,0
Useful heat output at 30% of rated heat output and low-temperature regime (**)P1kW6,1
Useful efficiency
Useful efficiency at rated heat output and high-temperature regime (*)η4%82,0
Useful efficiency at 30% of rated heat output and low-temperature regime (**)η1%80,9
Auxiliary electricity consumption
At full loademaxkW0,015
At part loadelminkW0,007
In standby modePSBkW0,003
Other items
Standby heat lossPstbykW0,150
Ignition burner power consumptionPignkW0,000
Annual energy consumptionQHEGJ77
Sound power levelLWAdB52
Emissions of nitrogen oxidesNOxmg/kWh30
For combination heaters
Declared load profileXL
Water heating energy efficiency class (from A+ to F)B
Daily electricity consumptionQeleckWh0,134
Annual electricity consumptionAECkWh28
Water heating energy efficiencyηwh%77
Daily fuel consumptionQfuelkWh25,865
Annual fuel consumptionAFCGJ21

(^) High-temperature regime means 60^ return temperature at heater inlet and 80^ feed temperature at heater outlet.
[
**] Low temperature means for condensing boilers 30^ , for low-temperature boilers 37^ and for other heaters 50^ return temperature (at heater inlet).

5.5 Diagrams

Pressure - power diagrams DIVAtech D LN C24

FERROLI DIVAtech D LN C24 - Diagrams - 1

A = LPG - B = NATURAL GAS

FERROLI DIVAtech D LN C24 - Diagrams - 2
Residual head available for system DIVAtech D LN C24

A = Boiler pressure losses - 1, 2 and 3 = Circulating pump speed

FERROLI DIVAtech D LN C24 - Diagrams - 3
Pressure - power diagrams DIVAtech D LN C30

A = LPG - B = NATURAL GAS

FERROLI DIVAtech D LN C24 - Diagrams - 4
Residual head available for system DIVAtech D LN C30

A = Boiler pressure losses - 1, 2 and 3 = Circulating pump speed

5.6 Wiring diagram

FERROLI DIVAtech D LN C24 - Diagrams - 5
fig. 23-Wiring diagram

FERROLI DIVAtech D LN C24 - Diagrams - 6

Attention: Remove the jumper on the terminal block before connecting the room thermostat or the remote timer control.

32 Heating circulating pump
42 DHW temperature sensor
44 Gas valve
72 Room thermostat (optional)
81 Ignition/detection electrode
95 Diverter valve
114 Water pressure switch
126 Fume thermostat
136 Flowmeter
138 External probe (optional)
139 Remote timer control (optional)
278 Double sensor (Safety + heating)

FR

1. GENÉRALITÉS

Selection Eco/Comfort

Vidange installation

3.4 Raccordement gaz

Pi maxi 65 mbar24 Vdc-class

Activation du mode TEST

MODELE: DIVATECH D LN C30 - (ODCC6YWA)

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : FERROLI

Model : DIVAtech D LN C24

Category : Central heating boiler