HONEYWELL BA298I-F - Network separator

BA298I-F - Network separator HONEYWELL - Free user manual and instructions

Find the device manual for free BA298I-F HONEYWELL in PDF.

📄 22 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice HONEYWELL BA298I-F - page 6
View the manual : Français FR Deutsch DE English EN Polski PL
Pick your language and provide your email: we'll send you a specifically translated version.
Product typeNetwork separator (disconnector)
BrandHONEYWELL
ModelBA298I-F
FluidWater
Max. upstream pressure10.0 bar
Service pressure1.5 bar
Max. service temperature65 °C
Outlet connectionDN150
Connection dimensionsDN65 to DN150
Connection typeFlanged PN 10
Mounting positionHorizontal, outlet connection downward
Body materialsStainless steel, red brass, brass
Delivery contentsBody, check valves, drain valve, 3 ball valves
Applicable standardDIN EN 1717
InspectionEvery 6 months with kit TKA295 or TK295
MaintenanceEvery 1 to 3 years by a professional
CleaningWithout solvents or alcohol, entrusted to an installer
Main spare partsDrain valve (0901856), check valves (0901652/0901653), ball valve (0901662), gaskets (0904031/0904032), clip (0904033/0904034)
Recommended accessoriesStrainer FY69P, test kits TK295/TKA295, valve replacement tool WBA-298
Frost protectionMounting location protected from frost
Drain opening differential pressure0.14 bar

Frequently Asked Questions - BA298I-F HONEYWELL

What is the main function of the BA298I-F network separator?
The BA298I-F protects the drinking water network from backflow and back-siphonage by interrupting the piping via three pressure zones and a drain valve.
What maximum pressure and temperature does the device support?
Max. upstream pressure 10.0 bar, service pressure 1.5 bar, max. service temperature 65 °C.
In what position should the separator be mounted?
Horizontal mounting with outlet connection downward, in an accessible, ventilated and frost-free location.
What are the inspection and maintenance intervals?
Inspection every 6 months with the TKA295 or TK295 kit; full maintenance every 1 to 3 years by a professional.
How to clean the synthetic parts of the BA298I-F?
Use non-solvent and alcohol-free products to avoid damage. Entrust cleaning to an installer.
What to do if the drain valve opens for no reason?
This may be due to pressure surges or pressure variations. Install a pressure reducer upstream or clean the valves/valve.
How to check the operation of the check valves?
Use the TKA295 or TK295 test device according to the procedure described in the manual.
What are the essential spare parts for the BA298I-F?
Drain valve (0901856), check valves (0901652 inlet side, 0901653 outlet side), ball valve (0901662), gaskets and clips.
Can the check valves be replaced by oneself?
No, replacement must be carried out by a professional, with a specific tool (WBA-298). The valves are under spring pressure and cannot be repaired.
What accessories are recommended for maintenance?
The FY69P strainer, TKA295/TK295 test kits, and the WBA-298 valve replacement tool (depending on diameter).

User questions about BA298I-F HONEYWELL

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Network separator in PDF format for free! Find your manual BA298I-F - HONEYWELL and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. BA298I-F by HONEYWELL.

USER MANUAL BA298I-F HONEYWELL

natural_image Technical line drawing of a mechanical valve assembly (no text or symbols)

HONEYWELL BA298I-F - 1

Keep instructions for later use!

11. Ersatzteile

BA298-F

  1. Follow the installation instructions.
  2. Use the appliance

• according to its intended use
- in good condition
• with due regard to safety and risk of danger.
3. Note that the appliance is exclusively for use in the applications detailed in these installation instructions. Any other use will not be considered to comply with requirements and would invalidate the warranty.
4. Please take note that any assembly, commissioning, servicing and adjustment work may only be carried out by authorized persons.
5. Immediately rectify any malfunctions which may influence safety.

2. Functional description

BA type backflow preventers are divided into three pressure zones. The pressure in zone ① is higher than in zone ②, which in turn is higher than in zone ③. A discharge valve is connected to zone ② which opens at the latest when the differential pressure between zones ① and ② falls to 0.14 bar. The water from zone ② discharges to atmosphere. In this way the danger of back pressure or back syphonage into the supply network is prevented. The pipework connection is interrupted and the drinking water network is protected.

3. Application

MediumWater
Inlet pressure10.0 bar
Operating pressure1.5 bar

4. Technical data

Installation position Horizontal with discharge valve downwards

Max. operating temperature65 °C

Discharge pipe connection DN150

Connection size DN65 - DN150

5. Scope of delivery

The backflow preventer consists of:

  • Housing
  • Inlet and outlet check valves
  • Discharge valve
  • Three ball valves for the connection of a differential pressure gauge

6. Options

BA298-... FA = Standard version, in sizes DN 65 - 150 flanges in sizes, PN 10

BA298I-... FA = Standard version, in sizes DN 65 - 150 flanges in sizes, PN 10 Connection size

7. Assembly

7.1 Installations Guidelines

• Install shutoff valves before and after backflow preventer
- Install in horizontal pipework with the discharge valve downwards
- Ensure good access o Simplifies maintenance and inspection
- Do not install in places where flooding can occur
- The installation environment should be protected against frost and ventilated well
• Install discharge pipework which has adequate capacity
- Where backflow preventers are installed care must be taken that discharges are safely carried away by the discharge pipework.
- Inlet pressure fluctuation, even without water draw off, can lead to brief operation of the discharge valve. It is therefore recommended that a pressure reducing valve be fitted upstream of the backflow preventer.
- No other unprotected potable water system may be connected downstream of the back flow preventer.
- Individual connections in the downstream system are not protected against backflow or back syphonage. If required, further protective measures can be installed as necessary to protect individual parts of the system
- The backflow preventer must be installed so that the discharge valve is above the surrounding maximum water table..

HONEYWELL BA298I-F - Installations Guidelines - 1

Use and type of installation according to DIN EN 1717

7.2 Assembly instructions

  1. Thoroughly flush pipework
  2. Ensure that connections on back flow preventer are clean
  3. Install backflow preventer

  4. Install in horizontal pipework with discharge connection directed downwards

  5. Note flow direction (indicated by arrow) o Install without tension or bending stresses
  6. Provide a straight section of pipework of at least five times the nominal valve size after the backflow preventer
  7. Observe required clearances
  8. Connect discharge pipework close coupled and without tight bends according to connection dimensions (see table)
  9. Install discharge pipework in such a way that the discharge connection and the discharge valve can be removed for inspection

8. Maintenance

HONEYWELL BA298I-F - Maintenance - 1

We recommend a planned maintenance contract with an installation company

HONEYWELL BA298I-F - Maintenance - 2

Maintenance of backflow preventer must be carried out by authorized personnel!

8.1 Inspection

HONEYWELL BA298I-F - Inspection - 1

• Frequency: every 6 month (depending on local operating conditions)
• To be carried out by an installation company
- Inspection with a test control unit and maintenance-set (see accessories)

The inspection should also include ancillary equipment such as strainers and shutoff valves.

8.1.1 Testing inlet check valve

HONEYWELL BA298I-F - Testing inlet check valve - 1

Take note of the instructions of the test control unit TKA295 or TK295

  1. Procedure according to instruction of the test control unit TKA295 resp. TK295

8.1.2 Testing discharge valve

HONEYWELL BA298I-F - Testing discharge valve - 1

Take note of the instructions of the test control unit TKA295 or TK295

  1. Procedure according to instruction of the test control unit TKA295 resp. TK295

HONEYWELL BA298I-F - Testing discharge valve - 2

Quick test for the discharge valve:

- Lower the inlet pressure o if the discharge valve opens (it drops), the function is o.k.

8.1.3 Testing outlet check valve

HONEYWELL BA298I-F - Testing outlet check valve - 1

Take note of the instructions of the test control unit TKA295 or TK295

  1. Procedure according to instruction of the test control unit TKA295 resp. TK295

8.2 Maintenance

HONEYWELL BA298I-F - Maintenance - 1

We recommend a planned maintenance contract with an installation company

In accordance with DIN EN 1717 a regular maintenance must be taken.

HONEYWELL BA298I-F - Maintenance - 2

Frequency: every 1-3 years (depending on local operating conditions)

To be carried out by an installation company

HONEYWELL BA298I-F - Maintenance - 3

Under no circumstances may check valves and discharge valves be disassembled. To doso is highly dangerous!

8.2.1 Discharge valve

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut off valve on outlet
  4. Unscrew pressure control line
  5. Loosen screws, pull the discharge connection downwards and unscrew the discharge valve with the aid of an oil filter strap wrench.

  6. Remove the discharge valve o Clean or replace as required

  7. Lubricate the 'O' ring well with grease, replace damaged 'O' rings

  8. Reassemble in reverse order

  9. Test function (see chapter inspection)

8.2.2 Check valve

  1. Close shutoff valve on inlet
  2. Release pressure on outlet side (e.g. through water tap)
  3. Close shut off valve on outlet
  4. Open the fixing clip
  5. Remove cover

HONEYWELL BA298I-F - Check valve - 1

Risk of injury - Check valves are under spring tension!

  1. Remove the check valves o first unscrew the outlet and then the inlet check valve. An assembly tool is available as an accessory.

  2. Fill with water and check for leakage o Leaking check valves must be replaced. They cannot be repaired

  3. Reassemble in reverse order

• Well lubricate check valve 'O' ring with grease
- Do not damage 'O' ring during assembly
• The check valve tightening torque is 100 to 120 Nm

  1. Test function (see chapter inspection)

8.3 Cleaning

HONEYWELL BA298I-F - Cleaning - 1

- To be carried out by an installation company - To be carried out by the operator

HONEYWELL BA298I-F - Cleaning - 2

Do not use any cleaning agents containing solvents and/or alcohol to clean the plastic parts!

HONEYWELL BA298I-F - Cleaning - 3

Detergents must not be allowed to enter the environment or the sewerage system!

  1. Procedure see Maintenance

9. Disposal

The backflow preventer consists of:

  • Stainless steel
  • Red bronze
  • Brass

HONEYWELL BA298I-F - Disposal - 1

Observe the local requirements regarding correct waste recycling/disposal!

  1. Troubleshooting
DisturbanceCauseRemedy
Discharge valve opens without apparent reasonPressure strokes in water supply systemInstall a pressure reducing valve upstream the backflow preventer
Fluctuating inlet pressureInstall a pressure reducing valve upstream the backflow preventer
Inlet check valve and/or discharge valves are dirtyRemove check valve or discharge valve and clean it
Leaky inlet check valveReplace check valve
Discharge valve don’t closeDeposits on valve seatRemove discharge valve, clean or replace it
Damaged ’o’ringRemove discharge valve and replace ’o’ring
Leaky discharge valveRemove discharge valve, clean or replace it
Discharge valve don’t openBlocked pressure control pipeRemove control pipe and clean it

Exploded view diagram of a mechanical assembly with numbered parts for identification

11. Spare Parts

BA298-F

1 Discharge valve DN65-150 0901855
2 Inlet check valve DN65 -100 0901650
DN150 0901654
3 Outlet check valve DN65-100 0901651
DN150 0901655
4 Ball valve DN65-150 0901659
5 Sealing set DN65-100 0904031
DN150 0904032
6 Clamp complete DN65-100 0904033
DN150 0904034

12. Spare Parts

BA298I-F

1 Discharge vlave DN65 -150 0901856
2 Inlet check valve DN65 -100 0901652
3 DN150 0901656
4 Outlet check valve DN65 -100 0901653
DN150 0901657
5 Ball valve DN65 -150 0901662
6 Sealing set DN65-100 0904031
DN150 0904032
7 Clamp complete DN65 -100 0904033
DN150 0904034

FY69P TK295 TKA295 WBA-298

13. Accessories

FY69P Strainer

With double mesh, grey cast iron housing, powder coated inside and outside.

A = Mesh size approximately 0.5 mm

TK295 Test kit

Electronic pressure measuring device with digital indicator, battery-operated.

With case and accessories, ideal for inspection and maintenance of backflow preventer type BA.

TKA295 Test kit

Analogue pressure measuring device with differential pressure display.

With case and accessories, ideal for inspection and maintenance of backflow preventer type BA.

WBA-298 Check valve replacement tool

WBA-298-100 for connection sizes DN 65 - 100

WBA-298-150 for connection size DN 150

11. Części zamienne

BA298-F

Automation and Control Solutions

Honeywell GmbH

Hardhofweg

D-74821 Mosbach

Phone: (49) 6261 810

Fax: (49) 6261 81309

http://europe.hbc.honeywell.com

www.honeywell.com

Manufactured for and on behalf of the

Environmental and Combustion Controls Division of

Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16,

Switzerland by its Authorised Representative Honeywell GmbH

MU1H-1218GE23 R0309

Subject to change

natural_image Technical diagram of a mechanical piping system with pressure gauges and valves (no text or labels)
ABCDEFG
6565060016015034539575
8065060016015034539575
10065060016015034539575
15065060020015037543575

HONEYWELL BA298I-F - Automation and Control Solutions - 1

natural_image Technical diagram of a mechanical piping system with gauges and valves (no text or labels)

HONEYWELL BA298I-F - Automation and Control Solutions - 2

natural_image Technical line drawing of a mechanical valve assembly with pressure gauge and actuator (no text or symbols)

8.2.1 7. 6. 5. 4. 4.

8.2.2 4. 5. 6. 6.

D

  1. Safety Guidelines 6
  2. Functional description ...... 6
  3. Application 6
  4. Technical data 6
  5. Scope of delivery 6
  6. Options ...... 6
  7. Assembly 6
  8. Maintenance 7
  9. Disposal 8
  10. Troubleshooting 8
  11. Spare Parts BA298-F....9
  12. Spare Parts BA298I-F....9
  13. Accessories 9

F

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : HONEYWELL

Model : BA298I-F

Category : Network separator