ST 593414 - Motion detector STEINEL - Free user manual and instructions
Find the device manual for free ST 593414 STEINEL in PDF.
| Product type | Passive infrared (PIR) motion detector |
| Brand | Steinel |
| Model | ST 593414 |
| Dimensions | 120 x 80 x 80 mm |
| Weight | 150 g |
| Power supply | 230 V AC, 50 Hz |
| Power consumption | 0.5 W standby, 2 W operating |
| Detection range | Up to 12 m (180° angle) |
| Detection angle | 180° |
| Sensitivity adjustment | Yes, via potentiometer (2-100%) |
| Adjustable time delay | 5 seconds to 15 minutes |
| Adjustable brightness threshold | 2-2000 lux |
| Protection rating | IP44 (weather-resistant) |
| Operating temperature | -20 °C to +50 °C |
| Housing material | UV-resistant ABS plastic |
| Mounting type | Wall or ceiling, with swivel bracket |
| Electrical connection | 3-wire terminal block (live, neutral, lamp) |
| Main functions | Motion detection, automatic on/off, energy saving |
| Maintenance and cleaning | Clean with a soft, dry cloth. Do not use solvents or abrasive products. |
| Safety | Installation by a qualified electrician. Follow applicable electrical standards. |
| Spare parts and repairability | Replaceable PIR sensor. Estimated lifespan: 10 years. |
| General information | Compliant with European directives. 3-year warranty. |
Frequently Asked Questions - ST 593414 STEINEL
User questions about ST 593414 STEINEL
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Motion detector in PDF format for free! Find your manual ST 593414 - STEINEL and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ST 593414 by STEINEL.
USER MANUAL ST 593414 STEINEL
Fax: +44/1733/966-701 - www.stinel.co.uk
(iii) Socket Tool Company Ltd
Unit 714 Northwest Business Park - Kishare Drive
Ballycojin: Dublin 15: Tel: 00353/1/8809120
Fax: 00353/18612061, info@rockettccia
FAX: 0000017002001 STEINEL FRANCE SAS
STEINEL FRANCE SAS ACTICENTRE, CRL 2
AUTOCENTRE - ORT 2 Puy des Famerie, Pât M., Let 9, F. 508101 L'ouin Odeau
Rue des Fairhards - Bal., M - Lot 3 - F-596 18 Los Tel: +22/2/20 20 24 00 - Fax: +22/2/20 20 24 00
Tel. 433/27/31 00: Fax: 458
info@steineffrance.com
OVAN SPIJK AGENTUREN
Postous 2 - 5688 HP OIRSCHOT
De Scheper 260 · 5688 HP OIRSCHOT
Tel. +31 499 571810 - Fax. +31 499 575795
Largo Doneganitz 2-1-20121 Main Tel: +29/07/56/57731 - Fax: +39/07/56/59795 - www.doiport
TEL: 405023
5NET-94 S.I
C/ Trepadella, n° 10 · Pol. Ind. Castellbisbal Sud
E-08755 Castellbisbal (Barcelona)
Tel.: +34/93/772 28 49 - Fax: +34/93/772 01 60 · www.saet94.com
© Wine a Rupet Brunnan AS
Hidokarvej 52 - DK-6250 Odense SV
Tel: +45 6593 0357 · Fax: +45 6593 2757 · www.twine-rope.dk
(AM) Oy Hedied Ab Loudhagnette 50, FL 05020 He###
Lubilasalienne 3D - P-Platzub Hesink T.1: 055/5702.071 - E - 0591477
Tel.: +305/9/82 881 · Fax: +305/9/673 813 www.hedtec.it/vali-
sus - finguengenediec.
© Milan AS
general forestland-153.19
STEINEL®
PROFESSIONAL

Information
IR Quattro SLIM

-2--3-
IR Quattro SLIM COM 1/COM 2/DIM/DALI


-4--5-
IR Quattro SLIM COM 2IR Quattro SLIM COM 1

IR Quattro SLIM DIM IR Quattro SLIM DALI

![graph TD subgraph Upper_Circuit S1["S1"] --> N["L"] S2["S2"] --> N N --> DAL12["DALI2 GND"] S1 --> P["P"] S2 --> P DAL12 --> N DAL12 --> L DAL12 --> DALI2_GND DAL12 --> DALI1_GND DAL12 --> DALI1_GND DAL12 --> 0.5m["0.5 m"] end subgraph Middle_Circuit N --> Z["7"] Z --> Dali2["Dali2 GND SENSOR"] Dali…](/content/2026/06/1282149/images/f8d1a7a68d5d544985084bb8f619078155f958b056129acf536cb4c8ae9922bd.jpg)
⑤

RC 8

-8--9-

Bedienungsanleitung
Operating instructions
Dear Customer,
Congratulations on purchasing your new STEINEL presence detector and thank you for the confidence you have shown in us. You have chosen a high-quality product that has been manufactured, tested and packed with the greatest care.
Please familiarise yourself with these instructions before attempting to install the light because prolonged, reliable and trouble-free operation will only be ensured if it is fitted and used properly.
We hope your new STEINEL presence detector will bring you lasting pleasure.

Safety warnings
■ Disconnect the power supply before attempting any work on the presence detector.
During installation, the electric power cable to be connected must not be live. Therefore, switch off the power first and use a voltage tester to make sure the wiring is off circuit.
Installing the presence detector involves work on the mains power supply. This work must therefore be carried out professionally in accordance with the applicable national wiring regulations and electrical operating conditions (VDE 0100).
Note: The external button's cable ⑦ is not intended for connecting loads to the neutral terminal.
Terminal B 1, B 2 is a switching contact for low-energy circuits, not more than 1 A. This must be protected a fuse of the appropriate rating.
■ Only electronic ballasts with a floating control signal may be used at DIM 1-10 V control output.
Assembly / Installation (see fig. on page 2)
The presence detector is only intended for recessed installation in cavity ceilings and in the Kaiser HaloX-O system.
Presence detector and load module are supplied disconnected. The presence detector must be plugged into load module after connecting the load module to the power supply. The maximum cable diameter for connection leads is 12 mm. Cable length between sensor and button < 50 m.
Accessories (optional): Service remote control, RC 8 EAN no.: 4007841 559410 User remote control RC 5 EAN number 4007841 592806 Extension cable (4P4C): EAN no.: 4007841 006419
System components
① Load module
② Sensor module
③ Sensor connector
④ Kaiser HaloX-O
⑤ Film shrouds for minimising detection zone
⑥ Functions
⑦ Refer to safety precautions
How it works / Basic function
| The infrared presence detectors from the Control PRO range control lighting as well as heating, ventilation and air-conditioning (COM 2 only), e.g. in offices, schools, public buildings or at home, in relation to ambient light level and the presence of per- |
| sons. The pyro-sensor with highly advanced lens provides a square detection zone, as the typical shape of a room, in which the smallest of movements are sensed. The presence detector's switching outputs are set using the remote controls RC 5 and RC 8. |
| Presence Control has a low intrinsic power consumption. |
IR Quattro SLIM COM 1
| 1 switching output operating in relation to brightness setting and presence of persons. |
IR Quattro SLIM DIM
| 1 switching output operating in relation to brightness setting and presence of persons. |
IR Quattro SLIM DALI
| 2 DALI switching outputs operating in relation to brightness setting and presence of persons. |
IR Quattro SLIM COM 2
| 1 switching output as COM 1. An additional 2nd switching output for operating HVAC (heating/ventilation/air-conditioning) in relation to the presence of persons. |
| Year Ended December 31, | ||
| 2018 | 2017 | |
| Revenues | 1,465 | 1,395 |
| Costs and expenses | (1,465) | (1,395) |
| Net income | 1,465 | 1,395 |
Settings:
| - Brightness setting |
| - Stay-ON time, IQ mode |
| - Orientation light(DIM/DALI only) |
| - Constant lighting control(DIM/DALI only) |
| - Scenario control (DALI only) |
Detection zone


| 2.5 m | 2.8 m | 3.5 m | 4 m | |
| tangential_ | 4 m | 4 m | 5.5 m | 6 m |
| radial_ | 3.2 m | 4 m | 4 m | 5 m |
| presence_ | 3.8 m | 4 m | 4.5 m | - |
The square detection zone and the ability to interconnect the master/slave versions provide the basis for creating optimum configurations quickly and easily.
Electrical installation / Automatic mode
| In selecting the wiring leads, it is important to meet the wiring regulations laid down in VDE 0100 (see Safety warnings on page 17). Wiring up the presence detector: Under section 6 of VDE 0100 520, a multiple-core |
| lead containing both the mains voltage leads and the control leads (e.g. NYM 5 x 1.52) may be used for the wiring between sensor and electronic ballast. The mains connection lead must be no greater than 10 mm in |
| diameter. The mains connection terminal accepts 2 x 2.5 mm 2 cables. When installing the surface-mounting version, connect a circuit breaker (16 A) on the line side. |
Technical specifications
| Dimensions (W x H x D): load module sensor module | |
| 61.3 x 126.5 x 42.5 mm 77 x 77 x 60 mm | |
| Power supply: | 120 - 250 V, 50 Hz / 60 Hz |
| Capacity, switching output 1:(COM 1/COM 2) | 230 V2000 W max. resistive load (cos φ = 1)1000 VA max. (cos φ = 0.5)120 VResistive load 1000 W max. (cos φ = 1)500 VA max. (cos φ = 0.5) |
| Electronic ballast(COM 1/COM 2/DIM) | max. inrush current 800 A/200 μs30 x (1 x 18 W), 25 x (2 x 18 W)25 x (1 x 36 W), 15 x (2 x 36 W)20 x (1 x 58 W), 10 x (2 x 58 W)Note: each electronic ballast has its own particular inrush current. A relay or contactor must be provided on line side for higher switching capacities. |
| Capacity, switching output 2:(COM 2 only) | Presence230 W/230V max. / 120 W/120V max.1A max. (cos φ = 1) for HVAC(heating/ventilation/air-conditioning) |
| Square detection zones: | IR Quattro SLIMPresence: 4 x 4 m max. (16 sq.m.)Radial: 4 x 4 m max. (16 sq.m.)Tangential: 4 x 4 m max. (16 sq.m.) |
| Light-level setting: | 10 - 1000 lux, = / daylight /DIM 100 - 1000 lux control threshold |
| Switching output 1:Time setting | 1 - 15 min.IQ mode time (automatic adjustment to usage profile) |
| Switching output 2:Time setting | only COM2 for HVAC0 or 10 min. switch-ON delay5/10/15 min. stay-ON time (factory setting: 5 min.)Automatic room surveillance |
| DIM: | |
| Basic brightness: | 10 % |
| Control output: | 1 - 10 V / 50 electronic ballasts max., 100 mA max. |
| DALI: | |
| Basic brightness: | 10 % |
| DALI output 1 / output 2 | 2-core DALI control cable / broadcast |
| Time setting: | OFF / 10/30 min. / all night |
| Mounting height (ceiling mounting): | 2.5 m - 4 m |
| Point of installation: | Indoors |
| IP rating: | IP 20 |
| Protection class: | II |
| Temperature range: | 0 °C to +40 °C |
Service remote control RC 8 (optional)

Functions – Settings
COM 1 + COM 2
Normal mode / Test mode (Test / Norm)

Test mode has priority over all other settings on the presence detector and serves the purpose of checking for proper working order as well for testing the detection zone. Irrespective of am-
bient light level, the presence detector activates the light to stay ON for approx. 8 sec. in response to movement in the room (blue LED flashes when movement is detected). All user-
selected settings apply in normal mode. The presence detector can also be set by means of the blue LED without any load connected.
Semi-automatic (Semi) / fully automatic mode (Full) Semi-automatic mode: (Semi)

The light now only switches OFF automatically. Light is switched ON manually. Light must be requested using the button and
Fully automatic mode: (Full)
The light automatically switches ON and OFF in relation to brightness when someone is present. Light can be switched ON and OFF manually at any time. This temporarily interrupts the auto-
stays ON for the time set at the potentiometer. (pressing twice switches ON for 4 hours).
Blue LED stays ON all the time in the 4h mode.
matic switching function. Irrespective of the settings selected, light stays ON for 4 hours after manually pressing the button twice or switches OFF after manually pressing the button once.
Blue LED stays ON all the time in the 4h ON/OFF mode. Pressing the button before the 4 hours elapse returns the Presence Control IR Quattro Slim to the normal operating mode.
DIM + DALI
Constant light ON/OFF

Provides a constant level of brightness. Detector measures the prevailing level of daylight and activates sufficient artificial light to achieve the required lev-
el of brightness. As daylight changes, the switched-in artificial lighting component is adjusted accordingly. In addition to the daylight component, artificial
light is also switched ON and OFF in relation to whether or not persons are present.
Functions – Settings by potentiometer
COM 1 + COM 2
Twilight setting

The chosen response threshold can be set from approx. 10 - 1000 lux.
| Examples of use Brightness settings | |
| Night-time mode min | |
| Corridors, foyers 1 | |
| Stairs, escalators, moving walkways 2 | |
| Washrooms, toilets, switchrooms, canteens 3 | |
| Sales floor, kindergartens, nursery school rooms, sports halls | 4 |
| Work rooms: offices, conference and meeting rooms, precision assembly activities, kitchens | 5 |
| Working areas requiring good light:Laboratory, technical drawing, precision work | >=6 |
| Daylight mode max |
Note: Depending on the site of installation, the setting may need to be corrected (e.g. Teach). Light level is measured at the sensor.
Time setting

Stay-ON time for switching output 1 Settings 5 min. / 10 min. / 15 min.
The chosen stay-ON time can be varied from 1 min. to a maximum of 15 min.(1 press of the button = 1 min.). Intrinsic light is calibrated
after 3 min. When the threshold is exceeded, the sensor switches OFF after the stay-ON time expires.
IQ mode

The stay-ON time is self-learning and adjusts dynamically to user behaviour.
The optimum time cycle is determined by means of a learning algorithm.
The shortest time is 5 min., the longest 20 min.
Teach mode

This memorises the current level of ambient brightness at which you
want the sensor to respond to movement from now on.
COM 2
Stay-ON time for switching output 2 HVAC

- Settings 5/10/15 min.
Switch-ON delay for switching output 2 HVAC

• Room surveillance
Turning the potentiometer to the "Surveillance" setting reduces the sensitivity of the "Presence" switching output. The contact only closes on detecting a pronounced movement, signaling with a high degree of certainty that persons are present.
The stay-ON time remains active. The switch-ON delay is inactivated.
DIM / DALI
Basic brightness (DIM version)
Provides basic illumination for the selected stay-ON time when ambient light falls below the selected brightness threshold that is set. This is dimmed to 10% of maximum light intensity. As soon as a person enters the scene, the detector switches either to 100%
light Intensity (constant-lighting controller OFF) or adjusts to the preselected brightness level (constant-lighting controller ON). When no movement is being detected, the detector dims back to basic brightness after the stay-ON time expires. This is switched OFF when
stay ON time (10 / 30 min.) has expired or the daylight component is sufficient to exceed the selected level of brightness. In the ON setting, the detector switches basic brightness ON and OFF as soon as the level of light falls below the brightness threshold.
Constant-lighting control
Provides a constant level of brightness. Detector measures the prevailing level of daylight and activates sufficient artificial light to achieve the required lev-
el of brightness. As daylight changes, the switched-in artificial lighting component is adjusted accordingly. In addition to the daylight component, artificial
light is also switched ON and OFF in relation to whether or not persons are present.
Parallel-connected configurations
When using several detectors, they must be connected to the same phase!
As many as 10 sensors can be connected in parallel.
Master/master
A parallel-connected configuration also permits the use of several masters. In this case, each master operates the lighting group in accordance with the level of bright-
ness it measures. Delay times and brightness thresholds are selected at each master as required. The switched load is spread among the individual masters. Presence is still
detected collectively by all detectors. The presence output can be picked off from any master.
Master/slave
The master/slave configuration permits detection of movement in large-type rooms or spaces (load connected = master, no load =
slave). The level of brightness prevailing in the room is only evaluated at the master. The slaves report movements detected to the mas-
ter. Lighting or HVAC is switched ON and OFF by the master only.
Remote control
Using the remote control (optional), functions can be conveniently activated from the floor.
Service remote control (RC8): EAN no.: 4007841 559410 User remote control (RC5): EAN no.: 4007841 592806
Troubleshooting
Malfunction Cause Remedy
| Light does not switch ON | No supply voltageLux setting too lowNo movement detectionSemi-automaticoperation (Semi) | Check supply voltageSlowly increase lux setting until light switches ONEnsure unobstructed sensor visionCheck detection zoneSet to fully automatic operation (FULL) |
| Light does not switch OFF | Lux setting too highStay-ON time running outInterfering heat sources, e.g. fan heater, open doors and windows, pets, light bulb/halogen floodlight, moving objects4h ON active (LED stays ON all the time) | Reduce lux settingWait until stay-ON time elapses; reduce stay-ON time if necessaryUse stickers to mask out stationary sources of interferencePress button to discontinue 4h ON |
Troubleshooting
Malfunction Cause Remedy
| Sensor switches OFF in spite of persons being present | ■ Stay-ON time too short■ Light-level threshold too low■ Reach too short | ■ Increase stay-ON time■ Change light-level threshold■ Increase reach |
| Sensor does not switch OFF quickly enough | ■ Stay-ON time too long | ■ Reduce stay-ON time |
| Sensor does not switch ON quickly enough when approached from the front | ■ Reach is reduced when approached from the front | ■ Install additional sensors■ Reduce distance between two sensors |
| Sensor does not switch ON when persons are present in spite of it being dark | ■ Lux setting too low | ■ Sensor deactivated by switch/button?■ Semi-automaticmode?■ Increase light-level threshold |
CE Declaration of Conformity
This product complies with
- Low-Voltage Directive 2006/95/EC
- EMC Directive 2004/108/EC
- RoHS Directive 2011/65/EC
Functional warranty
This Steinel product has been manufactured with utmost care, tested for proper operation and safety accordance with applicable regulations and then subjected to random sample inspection. Steinel guarantees that it is in perfect condition and proper working order.
FUNCTIONAL
36 month
WARRANTY
The warranty period is 36 months and starts on the date of sale to the consumer. We will remedy defects caused by material flaws or manufacturing faults. The warranty will be met by repair or replacement of defective parts at our own discretion. The warranty shall not cover damage to wear parts, damage or defects caused by improper treatment or maintenance. Further consequential damage to other objects shall be excluded.
Claims under the warranty will only be accepted if the product is sent fully assembled and well-packed with a brief description of the fault, a receipt or invoice (date of purchase and dealer's stamp) to the appropriate Service Centre.
Repair service:
If defects occur outside the warranty period or are not covered by warranty, ask your nearest service station for the possibility of repair.