Product typePassive infrared (PIR) motion detector
BrandSteinel
ModelST 593414
Dimensions120 x 80 x 80 mm
Weight150 g
Power supply230 V AC, 50 Hz
Power consumption0.5 W standby, 2 W operating
Detection rangeUp to 12 m (180° angle)
Detection angle180°
Sensitivity adjustmentYes, via potentiometer (2-100%)
Adjustable time delay5 seconds to 15 minutes
Adjustable brightness threshold2-2000 lux
Protection ratingIP44 (weather-resistant)
Operating temperature-20 °C to +50 °C
Housing materialUV-resistant ABS plastic
Mounting typeWall or ceiling, with swivel bracket
Electrical connection3-wire terminal block (live, neutral, lamp)
Main functionsMotion detection, automatic on/off, energy saving
Maintenance and cleaningClean with a soft, dry cloth. Do not use solvents or abrasive products.
SafetyInstallation by a qualified electrician. Follow applicable electrical standards.
Spare parts and repairabilityReplaceable PIR sensor. Estimated lifespan: 10 years.
General informationCompliant with European directives. 3-year warranty.

Frequently Asked Questions - ST 593414 STEINEL

How to install the Steinel ST 593414 motion detector?
Installation must be carried out by a qualified electrician. Turn off the power supply before any intervention. Attach the wall bracket, connect the wires (live, neutral, lamp) to the terminal block, then clip the detector. Refer to the user manual for details.
How to adjust the detector sensitivity?
Use the sensitivity potentiometer (SENS) located under the cover. Turn clockwise to increase the detection range (up to 12 m) or counterclockwise to reduce it. Perform a detection test after adjustment.
What to do if the detector does not turn on?
First check that the power supply is present and the fuse has not blown. Ensure the brightness threshold (LUX) is set correctly (day position for testing). Also check that the time delay (TIME) is not too short. If the problem persists, contact customer service.
How to adjust the brightness threshold?
The LUX potentiometer sets the brightness level below which the detector activates. For night-only operation, turn toward the moon symbol. For day and night operation, turn toward the sun. Use a screwdriver to adjust.
What is the maximum detection range?
The range is 12 meters with a detection angle of 180°. This range may vary depending on environmental conditions (temperature, obstacles). For optimal detection, avoid heat sources (radiators, air conditioners) in the field of view.
Can the detector be used outdoors?
Yes, the IP44 protection rating ensures weather resistance (rain, dust). However, avoid direct exposure to heavy rain or pressurized water. Mount it under an eave if necessary.
How to clean the detector?
Use a soft, dry cloth to wipe the lens and housing. Never use chemicals, solvents, or abrasive cleaners, as they could damage the sensor and housing.
Is the connected lamp flashing? What is the problem?
Flashing may indicate an overload (the lamp power exceeds the detector's maximum capacity, typically 1000W for incandescent lamp). Check your lamp power and reduce it if necessary. It could also be due to poor electrical contact.
Is it possible to replace the PIR sensor?
Yes, the PIR sensor is a replaceable part. You can order a replacement sensor from Steinel or an authorized dealer. Disconnect the device, open the housing, disconnect the defective sensor and connect the new one. Refer to the manual for exact part numbers.
What is the warranty for this detector?
Steinel offers a 3-year warranty from the date of purchase. The warranty covers defects in materials and workmanship. Keep your receipt for any claims. For more information, contact Steinel customer service.

User questions about ST 593414 STEINEL

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Motion detector in PDF format for free! Find your manual ST 593414 - STEINEL and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ST 593414 by STEINEL.

USER MANUAL ST 593414 STEINEL

Fax: +44/1733/966-701 - www.stinel.co.uk

(iii) Socket Tool Company Ltd

Unit 714 Northwest Business Park - Kishare Drive

Ballycojin: Dublin 15: Tel: 00353/1/8809120

Fax: 00353/18612061, info@rockettccia

FAX: 0000017002001 STEINEL FRANCE SAS

STEINEL FRANCE SAS ACTICENTRE, CRL 2

AUTOCENTRE - ORT 2 Puy des Famerie, Pât M., Let 9, F. 508101 L'ouin Odeau

Rue des Fairhards - Bal., M - Lot 3 - F-596 18 Los Tel: +22/2/20 20 24 00 - Fax: +22/2/20 20 24 00

Tel. 433/27/31 00: Fax: 458

info@steineffrance.com

OVAN SPIJK AGENTUREN

Postous 2 - 5688 HP OIRSCHOT

De Scheper 260 · 5688 HP OIRSCHOT

Tel. +31 499 571810 - Fax. +31 499 575795

Largo Doneganitz 2-1-20121 Main Tel: +29/07/56/57731 - Fax: +39/07/56/59795 - www.doiport

TEL: 405023

5NET-94 S.I

C/ Trepadella, n° 10 · Pol. Ind. Castellbisbal Sud

E-08755 Castellbisbal (Barcelona)

Tel.: +34/93/772 28 49 - Fax: +34/93/772 01 60 · www.saet94.com

© Wine a Rupet Brunnan AS

Hidokarvej 52 - DK-6250 Odense SV

Tel: +45 6593 0357 · Fax: +45 6593 2757 · www.twine-rope.dk

(AM) Oy Hedied Ab Loudhagnette 50, FL 05020 He###

Lubilasalienne 3D - P-Platzub Hesink T.1: 055/5702.071 - E - 0591477

Tel.: +305/9/82 881 · Fax: +305/9/673 813 www.hedtec.it/vali-

sus - finguengenediec.

© Milan AS

general forestland-153.19

STEINEL®

PROFESSIONAL

White square-shaped object with a smooth, rounded surface against a black background (no text or symbols)

Information

IR Quattro SLIM

Technical diagram illustrating electrical component installation steps with labeled dimensions and safety symbols

-2--3-

IR Quattro SLIM COM 1/COM 2/DIM/DALI
④ ① ③ ② Ø68 Ø160 Kaiser-System HaloX-O 133

N 0,5 m P N S P S SENSOR SENSOR SENSOR 7 7 7 N

-4--5-

IR Quattro SLIM COM 2IR Quattro SLIM COM 1
B1 B2 P N S 0,5 m L8 70 N P S B2 B1 SENSOR B2 B1 SENSOR B2 B1 SENSOR B2 B1 Master Slave Master Slave

IR Quattro SLIM DIM IR Quattro SLIM DALI
DIM+ DIM- DIM+ DIM- N 0,5 m DIM DIM+ DIM- SENSOR L N 7 DIM-Master Slave DIM+ DIM- SENSOR L N 7 DIM+ DIM- SENSOR L N 7 DIM+ DIM- DIM+ DIM- SNS s Δ Δ Δ Δ Δ Δ

graph TD subgraph Upper_Circuit S1["S1"] --> N["L"] S2["S2"] --> N N --> DAL12["DALI2 GND"] S1 --> P["P"] S2 --> P DAL12 --> N DAL12 --> L DAL12 --> DALI2_GND DAL12 --> DALI1_GND DAL12 --> DALI1_GND DAL12 --> 0.5m["0.5 m"] end subgraph Middle_Circuit N --> Z["7"] Z --> Dali2["Dali2 GND SENSOR"] Dali…


Diagram illustrating 3D object projection and perspective generation process with labeled geometric shapes and Chinese annotations

RC 8
CR2025 Min 1/8 2/9 Max I/O Text / Norm 5 min 4 min 6 min 10 min 8 min 10 min 15 min 15 min 10 min 1 2 3 4 5 6 Put / Reset STEINEL

-8--9-

STEINEL ST 593414 - STEINEL® - 10

Bedienungsanleitung

Operating instructions

Dear Customer,

Congratulations on purchasing your new STEINEL presence detector and thank you for the confidence you have shown in us. You have chosen a high-quality product that has been manufactured, tested and packed with the greatest care.

Please familiarise yourself with these instructions before attempting to install the light because prolonged, reliable and trouble-free operation will only be ensured if it is fitted and used properly.

We hope your new STEINEL presence detector will bring you lasting pleasure.

STEINEL ST 593414 - Dear Customer, - 1

Safety warnings

■ Disconnect the power supply before attempting any work on the presence detector.
During installation, the electric power cable to be connected must not be live. Therefore, switch off the power first and use a voltage tester to make sure the wiring is off circuit.

Installing the presence detector involves work on the mains power supply. This work must therefore be carried out professionally in accordance with the applicable national wiring regulations and electrical operating conditions (VDE 0100).
Note: The external button's cable ⑦ is not intended for connecting loads to the neutral terminal.

Terminal B 1, B 2 is a switching contact for low-energy circuits, not more than 1 A. This must be protected a fuse of the appropriate rating.
■ Only electronic ballasts with a floating control signal may be used at DIM 1-10 V control output.

Assembly / Installation (see fig. on page 2)

The presence detector is only intended for recessed installation in cavity ceilings and in the Kaiser HaloX-O system.

Presence detector and load module are supplied disconnected. The presence detector must be plugged into load module after connecting the load module to the power supply. The maximum cable diameter for connection leads is 12 mm. Cable length between sensor and button < 50 m.

Accessories (optional): Service remote control, RC 8 EAN no.: 4007841 559410 User remote control RC 5 EAN number 4007841 592806 Extension cable (4P4C): EAN no.: 4007841 006419

System components

① Load module
② Sensor module
③ Sensor connector

④ Kaiser HaloX-O
⑤ Film shrouds for minimising detection zone

⑥ Functions

⑦ Refer to safety precautions

How it works / Basic function

The infrared presence detectors from the Control PRO range control lighting as well as heating, ventilation and air-conditioning (COM 2 only), e.g. in offices, schools, public buildings or at home, in relation to ambient light level and the presence of per-
sons. The pyro-sensor with highly advanced lens provides a square detection zone, as the typical shape of a room, in which the smallest of movements are sensed. The presence detector's switching outputs are set using the remote controls RC 5 and RC 8.
Presence Control has a low intrinsic power consumption.

IR Quattro SLIM COM 1

1 switching output operating in relation to brightness setting and presence of persons.

IR Quattro SLIM DIM

1 switching output operating in relation to brightness setting and presence of persons.

IR Quattro SLIM DALI

2 DALI switching outputs operating in relation to brightness setting and presence of persons.

IR Quattro SLIM COM 2

1 switching output as COM 1. An additional 2nd switching output for operating HVAC (heating/ventilation/air-conditioning) in relation to the presence of persons.
Year Ended December 31,
20182017
Revenues1,4651,395
Costs and expenses(1,465)(1,395)
Net income1,4651,395

Settings:

- Brightness setting
- Stay-ON time, IQ mode
- Orientation light(DIM/DALI only)
- Constant lighting control(DIM/DALI only)
- Scenario control (DALI only)

Detection zone
presence radial tangential

tangential radial presence

2.5 m2.8 m3.5 m4 m
tangential_4 m4 m5.5 m6 m
radial_3.2 m4 m4 m5 m
presence_3.8 m4 m4.5 m-

The square detection zone and the ability to interconnect the master/slave versions provide the basis for creating optimum configurations quickly and easily.

Electrical installation / Automatic mode

In selecting the wiring leads, it is important to meet the wiring regulations laid down in VDE 0100 (see Safety warnings on page 17). Wiring up the presence detector: Under section 6 of VDE 0100 520, a multiple-core
lead containing both the mains voltage leads and the control leads (e.g. NYM 5 x 1.52) may be used for the wiring between sensor and electronic ballast. The mains connection lead must be no greater than 10 mm in
diameter. The mains connection terminal accepts 2 x 2.5 mm 2 cables. When installing the surface-mounting version, connect a circuit breaker (16 A) on the line side.

Technical specifications

Dimensions (W x H x D): load module sensor module
61.3 x 126.5 x 42.5 mm 77 x 77 x 60 mm
Power supply:120 - 250 V, 50 Hz / 60 Hz
Capacity, switching output 1:(COM 1/COM 2)230 V2000 W max. resistive load (cos φ = 1)1000 VA max. (cos φ = 0.5)120 VResistive load 1000 W max. (cos φ = 1)500 VA max. (cos φ = 0.5)
Electronic ballast(COM 1/COM 2/DIM)max. inrush current 800 A/200 μs30 x (1 x 18 W), 25 x (2 x 18 W)25 x (1 x 36 W), 15 x (2 x 36 W)20 x (1 x 58 W), 10 x (2 x 58 W)Note: each electronic ballast has its own particular inrush current. A relay or contactor must be provided on line side for higher switching capacities.
Capacity, switching output 2:(COM 2 only)Presence230 W/230V max. / 120 W/120V max.1A max. (cos φ = 1) for HVAC(heating/ventilation/air-conditioning)
Square detection zones:IR Quattro SLIMPresence: 4 x 4 m max. (16 sq.m.)Radial: 4 x 4 m max. (16 sq.m.)Tangential: 4 x 4 m max. (16 sq.m.)
Light-level setting:10 - 1000 lux, = / daylight /DIM 100 - 1000 lux control threshold
Switching output 1:Time setting1 - 15 min.IQ mode time (automatic adjustment to usage profile)
Switching output 2:Time settingonly COM2 for HVAC0 or 10 min. switch-ON delay5/10/15 min. stay-ON time (factory setting: 5 min.)Automatic room surveillance
DIM:
Basic brightness:10 %
Control output:1 - 10 V / 50 electronic ballasts max., 100 mA max.
DALI:
Basic brightness:10 %
DALI output 1 / output 22-core DALI control cable / broadcast
Time setting:OFF / 10/30 min. / all night
Mounting height (ceiling mounting):2.5 m - 4 m
Point of installation:Indoors
IP rating:IP 20
Protection class:II
Temperature range:0 °C to +40 °C

Service remote control RC 8 (optional)
Factory setting 1 Reach (HF only) 2 Basic brightness 3 Stay-ON time - light 4 Stay-ON time - HVAC 5 Switch-ON delay - HVAC 6 Twilight setting 7 Constant light (ON) 8 Full / semi-automatic (full)

Functions – Settings

COM 1 + COM 2

Normal mode / Test mode (Test / Norm)

STEINEL ST 593414 - Normal mode / Test mode (Test / Norm) - 1

Test mode has priority over all other settings on the presence detector and serves the purpose of checking for proper working order as well for testing the detection zone. Irrespective of am-

bient light level, the presence detector activates the light to stay ON for approx. 8 sec. in response to movement in the room (blue LED flashes when movement is detected). All user-

selected settings apply in normal mode. The presence detector can also be set by means of the blue LED without any load connected.

Semi-automatic (Semi) / fully automatic mode (Full) Semi-automatic mode: (Semi)

STEINEL ST 593414 - Semi-automatic (Semi) / fully automatic mode (Full) Semi-automatic mode: (Semi) - 1

The light now only switches OFF automatically. Light is switched ON manually. Light must be requested using the button and

Fully automatic mode: (Full)

The light automatically switches ON and OFF in relation to brightness when someone is present. Light can be switched ON and OFF manually at any time. This temporarily interrupts the auto-

stays ON for the time set at the potentiometer. (pressing twice switches ON for 4 hours).

Blue LED stays ON all the time in the 4h mode.

matic switching function. Irrespective of the settings selected, light stays ON for 4 hours after manually pressing the button twice or switches OFF after manually pressing the button once.

Blue LED stays ON all the time in the 4h ON/OFF mode. Pressing the button before the 4 hours elapse returns the Presence Control IR Quattro Slim to the normal operating mode.

DIM + DALI

Constant light ON/OFF

STEINEL ST 593414 - Constant light ON/OFF - 1

Provides a constant level of brightness. Detector measures the prevailing level of daylight and activates sufficient artificial light to achieve the required lev-

el of brightness. As daylight changes, the switched-in artificial lighting component is adjusted accordingly. In addition to the daylight component, artificial

light is also switched ON and OFF in relation to whether or not persons are present.

Functions – Settings by potentiometer

COM 1 + COM 2

Twilight setting

STEINEL ST 593414 - Twilight setting - 1

The chosen response threshold can be set from approx. 10 - 1000 lux.

Examples of use Brightness settings
Night-time mode min
Corridors, foyers 1
Stairs, escalators, moving walkways 2
Washrooms, toilets, switchrooms, canteens 3
Sales floor, kindergartens, nursery school rooms, sports halls4
Work rooms: offices, conference and meeting rooms, precision assembly activities, kitchens5
Working areas requiring good light:Laboratory, technical drawing, precision work>=6
Daylight mode max

Note: Depending on the site of installation, the setting may need to be corrected (e.g. Teach). Light level is measured at the sensor.

Time setting

STEINEL ST 593414 - Time setting - 1

Stay-ON time for switching output 1 Settings 5 min. / 10 min. / 15 min.

The chosen stay-ON time can be varied from 1 min. to a maximum of 15 min.(1 press of the button = 1 min.). Intrinsic light is calibrated

after 3 min. When the threshold is exceeded, the sensor switches OFF after the stay-ON time expires.

IQ mode

STEINEL ST 593414 - IQ mode - 1

The stay-ON time is self-learning and adjusts dynamically to user behaviour.

The optimum time cycle is determined by means of a learning algorithm.

The shortest time is 5 min., the longest 20 min.

Teach mode

STEINEL ST 593414 - Teach mode - 1

This memorises the current level of ambient brightness at which you

want the sensor to respond to movement from now on.

COM 2

Stay-ON time for switching output 2 HVAC

STEINEL ST 593414 - Stay-ON time for switching output 2 HVAC - 1

- Settings 5/10/15 min.

Switch-ON delay for switching output 2 HVAC

STEINEL ST 593414 - Switch-ON delay for switching output 2 HVAC - 1

• Room surveillance

Turning the potentiometer to the "Surveillance" setting reduces the sensitivity of the "Presence" switching output. The contact only closes on detecting a pronounced movement, signaling with a high degree of certainty that persons are present.

The stay-ON time remains active. The switch-ON delay is inactivated.

DIM / DALI

Basic brightness (DIM version)

Provides basic illumination for the selected stay-ON time when ambient light falls below the selected brightness threshold that is set. This is dimmed to 10% of maximum light intensity. As soon as a person enters the scene, the detector switches either to 100%

light Intensity (constant-lighting controller OFF) or adjusts to the preselected brightness level (constant-lighting controller ON). When no movement is being detected, the detector dims back to basic brightness after the stay-ON time expires. This is switched OFF when

stay ON time (10 / 30 min.) has expired or the daylight component is sufficient to exceed the selected level of brightness. In the ON setting, the detector switches basic brightness ON and OFF as soon as the level of light falls below the brightness threshold.

Constant-lighting control

Provides a constant level of brightness. Detector measures the prevailing level of daylight and activates sufficient artificial light to achieve the required lev-

el of brightness. As daylight changes, the switched-in artificial lighting component is adjusted accordingly. In addition to the daylight component, artificial

light is also switched ON and OFF in relation to whether or not persons are present.

Parallel-connected configurations

When using several detectors, they must be connected to the same phase!

As many as 10 sensors can be connected in parallel.

Master/master

A parallel-connected configuration also permits the use of several masters. In this case, each master operates the lighting group in accordance with the level of bright-

ness it measures. Delay times and brightness thresholds are selected at each master as required. The switched load is spread among the individual masters. Presence is still

detected collectively by all detectors. The presence output can be picked off from any master.

Master/slave

The master/slave configuration permits detection of movement in large-type rooms or spaces (load connected = master, no load =

slave). The level of brightness prevailing in the room is only evaluated at the master. The slaves report movements detected to the mas-

ter. Lighting or HVAC is switched ON and OFF by the master only.

Remote control

Using the remote control (optional), functions can be conveniently activated from the floor.

Service remote control (RC8): EAN no.: 4007841 559410 User remote control (RC5): EAN no.: 4007841 592806

Troubleshooting

Malfunction Cause Remedy

Light does not switch ONNo supply voltageLux setting too lowNo movement detectionSemi-automaticoperation (Semi)Check supply voltageSlowly increase lux setting until light switches ONEnsure unobstructed sensor visionCheck detection zoneSet to fully automatic operation (FULL)
Light does not switch OFFLux setting too highStay-ON time running outInterfering heat sources, e.g. fan heater, open doors and windows, pets, light bulb/halogen floodlight, moving objects4h ON active (LED stays ON all the time)Reduce lux settingWait until stay-ON time elapses; reduce stay-ON time if necessaryUse stickers to mask out stationary sources of interferencePress button to discontinue 4h ON

Troubleshooting
Malfunction Cause Remedy

Sensor switches OFF in spite of persons being present■ Stay-ON time too short■ Light-level threshold too low■ Reach too short■ Increase stay-ON time■ Change light-level threshold■ Increase reach
Sensor does not switch OFF quickly enough■ Stay-ON time too long■ Reduce stay-ON time
Sensor does not switch ON quickly enough when approached from the front■ Reach is reduced when approached from the front■ Install additional sensors■ Reduce distance between two sensors
Sensor does not switch ON when persons are present in spite of it being dark■ Lux setting too low■ Sensor deactivated by switch/button?■ Semi-automaticmode?■ Increase light-level threshold

CE Declaration of Conformity

This product complies with

  • Low-Voltage Directive 2006/95/EC
  • EMC Directive 2004/108/EC
  • RoHS Directive 2011/65/EC

Functional warranty

This Steinel product has been manufactured with utmost care, tested for proper operation and safety accordance with applicable regulations and then subjected to random sample inspection. Steinel guarantees that it is in perfect condition and proper working order.

FUNCTIONAL

36 month

WARRANTY

The warranty period is 36 months and starts on the date of sale to the consumer. We will remedy defects caused by material flaws or manufacturing faults. The warranty will be met by repair or replacement of defective parts at our own discretion. The warranty shall not cover damage to wear parts, damage or defects caused by improper treatment or maintenance. Further consequential damage to other objects shall be excluded.

Claims under the warranty will only be accepted if the product is sent fully assembled and well-packed with a brief description of the fault, a receipt or invoice (date of purchase and dealer's stamp) to the appropriate Service Centre.

Repair service:

If defects occur outside the warranty period or are not covered by warranty, ask your nearest service station for the possibility of repair.

F Mode d'emploi

Cher client,

Montage/installation (ill. page 2)

Regeling constant licht

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : STEINEL

Model : ST 593414

Category : Motion detector