HAGER JKD102SPD - Surge protector

JKD102SPD - Surge protector HAGER - Free user manual and instructions

Find the device manual for free JKD102SPD HAGER in PDF.

📄 1 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice HAGER JKD102SPD - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Surge Protective Device (SPD) Type 2
Brand Hager
Model JKD102SPD
Rated Voltage (Un) 230 V AC (50/60 Hz)
Maximum Continuous Operating Voltage (Uc) 275 V AC
Nominal Discharge Current (In) 5 kA (8/20 µs)
Maximum Discharge Current (Imax) 20 kA (8/20 µs)
Voltage Protection Level (Up) ≤1.5 kV
Response Time < 25 ns
Dimensions (H x W x D) 90 x 36 x 65 mm (2 modules)
Weight Approx. 150 g
Mounting DIN rail (EN 60715)
Degree of Protection IP20 (built-in)
Operating Temperature -25°C to +70°C
Material Thermoplastic, self-extinguishing (UL94 V-0)
Indicator Green/Red mechanical flag (OK/fault)
Standards EN 61643-11, IEC 61643-11
Maintenance Check indicator regularly; replace if red or after severe surge
Cleaning Wipe with dry cloth; no solvents
Spare Parts / Repairability Non-repairable; replace entire module if faulty

Frequently Asked Questions - JKD102SPD HAGER

What does the JKD102SPD protect against?
It protects electrical installations against overvoltage surges caused by lightning or switching operations.
Is the JKD102SPD suitable for residential use?
Yes, it is designed for residential and light commercial applications, typically installed in distribution boards.
How do I know if the device is working?
Check the mechanical indicator: green means OK, red means the protection element is damaged and needs replacement.
Can I install it myself?
Installation should be performed by a qualified electrician following local regulations and the user manual.
What does Type 2 SPD mean?
Type 2 SPDs are permanent overvoltage protectors installed on sub-distribution boards to protect connected equipment.
What is the expected lifespan?
Lifespan depends on surge frequency; indicator shows end of life. Typically 5-10 years under normal conditions.
Does it protect against direct lightning strikes?
No, it protects against induced surges and indirect strikes. For direct strikes, a Type 1 SPD is required.
How many modules does it occupy on a DIN rail?
It occupies 2 modules (36 mm width) on a standard DIN rail.
What should I do if the indicator is red?
Replace the unit immediately with a new one, as the protection path is compromised.
Can I parallel multiple units for higher protection?
No, SPDs are connected in parallel to the mains; do not series-connect. Contact an electrician for additional protection.

User questions about JKD102SPD HAGER

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Surge protector in PDF format for free! Find your manual JKD102SPD - HAGER and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. JKD102SPD by HAGER.

USER MANUAL JKD102SPD HAGER

JKD1 Surge Protection Instructions

Instruction leaflet for fitting 125A Surge Protection in Power and lighting boards

Pozidrive PZ2 2.5mm 8mm Socket

Parts list:

  1. 1 x Type I+II or Type II Surge Protection device
  2. 1 x Copper Earth Link
  3. 2 x Hex head Earth screws
  4. 3 x KRN199 Terminal block
  5. 1 x ZB0220 M6 Carp Nut
  6. 1 x Neutral link
  7. 3 x L1/L2/L3 Phase links
  8. 1 x M5 Hex head screw & washers

KRN199 KRN199 KRN199 L1 L2 L3 SOLVESE SIDES IN TO RELEASE COVER Danger ISOLATE SUPPLY BEFORE REMOVING COVER TI+T2 SPD

Clip the 4 module surge protection device to the dinrail next to the incomer. Fit the 3 KRN199 terminal block's to the first 3 phases on the left hand side of the busbar stack as shown above and torque to 3.5Nm.

ISOLATE SUPPLY BEFORE REMOVING CC singer or the DNA singer

Place the copper earth component into the bottom two cage terminals of the surge protection device and secure to 3.5Nm.
Use the 2 high torque screws provided to then secure the earth link to the base at 3.5Nm.

Electrical wiring diagram showing connections between components labeled L1, L2, L3 and a shaper with grounding symbols

Secure the 3 brown cables to the terminals of the Surge protection device and the corresponding KRN devices L1/L2/L3 and torque to 3.5Nm.
Secure the Neutral cable to the Surge device to 3.5Nm and use the M5 hex head screw with washers to secure the ring terminal to the neutral bar next to the factory fitted neutral and secure to 3.5Nm.

'Ensure that when re-fitting the shroud that the left hand side is cut out to avoid clashing with the Surge protection cables'

The device may only be connected and installed by an electrically skilled person. National standards and safety regulations must be observed.

The device must be checked for external damage prior to installation. If any damage or other defects are detected in this check, the device must not be installed.

Its use is only permitted within the limits shown and stated in the installation instructions.

Opening or otherwise tampering with the device invalidates the warranty.

Table of contents Click a title to access it