BrandRavanson
ModelPM-7500S
Product TypePortable Air Conditioner
Cooling Capacity2.05 kW (7000 BTU/h approx.)
Power Supply220-240 V ~ 50 Hz
Power Consumption (Cooling)0.78 kW
Energy Efficiency Ratio (EER)2.60
Refrigerant / WeightR290 (Propane) / 165 g
Sound Power Level65 dB(A)
Dimensions (Approx.)700 x 350 x 350 mm (H x W x D)
Weight (Approx.)28 kg
Operating ModesCooling, Dehumidifying, Fan
Fan SpeedsHigh, Low
Thermostat Range16°C to 31°C (Cooling mode)
Timer1-24 hours (delayed start/stop)
Remote ControlInfrared, requires 2 x AA batteries
Sleep ModeAvailable in Cooling mode; raises temperature gradually
Swing (Louvre)Manual airflow direction control
Filter CleaningEvery 2 weeks; washable with mild detergent
Water Tank CapacityInternal tank; auto shut-off when full
Window Kit IncludedYes, for sliding windows/doors
Safety FeaturesCompressor delay (3 min); auto off on full tank; R290 safety
Room Size RequirementMinimum floor area 12 m²

Frequently Asked Questions - PM-7500S Ravanson

How do I install the window kit for the PM-7500S?
The window kit is designed for sliding windows or doors. Measure your window, cut the slide if too long, or buy a longer one if too short. Connect the draining hose to the connector and then to the air discharge at the rear. Insert the hose connector into the window adapter, adjust the adapter to the window width, tighten the screw, and close the window so the adapter sits between the window and frame.
What should I do if the 'W.F.' indicator lights up?
The 'W.F.' (Water Full) indicator means the internal water tank is full. Turn off and unplug the unit. Place a container under the drain hole, twist off the plug, remove the rubber stopper, and drain the water. Replace the stopper and tighten the plug. The light should go out.
How often should I clean the air filter?
Clean the filter every two weeks. A dirty filter reduces efficiency. Pull out the upper and lower filters, vacuum them, then wash with mild detergent and running water. Rinse thoroughly and let dry before reinstalling.
Can I use the air conditioner in a room smaller than 12 m²?
No. The manual states the appliance must be installed, operated, and stored in a room with a floor area larger than 12 m² due to the flammable refrigerant R290.
What is the refrigerant used and is it safe?
The refrigerant is R290 (propane), a natural gas with low global warming potential (GWP=3). It is flammable. Ensure the cooling circuit is not damaged before use. If damaged, avoid open flames and ventilate the room immediately. Service must be done by certified technicians.
Why does the compressor not start immediately after turning off?
The unit has a built-in compressor protection delay of at least 3 minutes to prevent damage from rapid cycling. If you switch off and on quickly, the compressor will wait before restarting.
How do I set the timer for delayed start or stop?
For delayed start: With the unit in standby, press the TIMER button. The display shows time left before start. Each press adds 1 hour (up to 24h). For delayed stop: While the unit is running, press TIMER to set hours until shutdown. To cancel, keep pressing TIMER until '00' appears.
What does the Sleep mode do?
Sleep mode is available only in Cooling mode. It sets the fan to low speed and automatically increases the temperature by 1°C after the first hour and another 1°C after the second hour to save energy and provide comfort during sleep.
Can I use an extension cord with this air conditioner?
Do not use an extension cord unless it has been inspected and tested by a qualified electrician. Improper extension cords pose a fire and electric shock risk. Always plug directly into a suitable wall outlet.
What maintenance is required before storing the unit?
Always empty the water tank completely before storage. Allow the unit to cool down. Clean the filter. Store in a dry place in original packaging to protect from humidity and mechanical damage. Keep it upright to avoid compressor damage.

User questions about PM-7500S Ravanson

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air-conditioner in PDF format for free! Find your manual PM-7500S - Ravanson and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PM-7500S by Ravanson.

USER MANUAL PM-7500S Ravanson

EN User's manual Local Air Conditioner

natural_image White portable air conditioner unit with control panel and ventilation grille (no visible text or symbols)

Ravanson PM-7500S - 1

natural_image Exterior view of a white and black portable air conditioner unit (no visible text or symbols)

MODEL:

PM-7500S/ PM-9500S/ PM-9500/ PM-9000

Producent

Ravanson®

RAVANSON LTD Sp. z o.o.

Przód:

natural_image Simple line drawing of a mechanical component with a curved end and central slot (no text or symbols)

Adapter okienny

Ravanson PM-7500S - Przód: - 1
Łącznik węża

UWAGA!

natural_image Technical line drawing showing two mechanical assembly steps with no visible text or symbols

16. INSTALACJA URZĄDZ4NIA ZA POMOCA Z4STAWU OKI4NN4GO9

UWAGA!

Congratulations on the purchase and welcome to the family of the Ravanson products' users.

Ravanson PM-7500S - UWAGA! - 1

When you use electric devices, comply with the basic precautions to reduce the risk of fire, electric shock and/or personal injuries.

Ravanson PM-7500S - UWAGA! - 2

Be sure to carefully review this manual before using the product for the first time and keep it at hand for future reference.

Before first use, always read the safety instructions and warnings included in this guide.

Failure to observe the below mentioned safety warnings and safety guidelines for may cause to electric shock, fire and/or serious injuries

Keep safety instructions and warnings at hand for future reference9 G4N4RAL SAF4TY GU124L1N4SS

This9appliance9is9not9intended9for9use9by9children9under9the9age9of989 or9other9persons,9without9assistance9or9supervision,9if9their9physical,9 sensory9or9mental9capabilities9prevent9them9from9using9it9safely9or9by9 persons99without99experience99and99knowledge99on99the99use99thereof.9 People99using99this99product99must99understand99the99risks99related99to9 use9of9the9appliance.9Do9not9allow9children9to9use9the9appliance9as9a9 toy.9Cleaning9and9maintenance9by9children9without9supervision9is9not9 allowed.9

Children9are9not9aware9of99dangers9that99may9arise99during99the9use99ofelectric99devices.99Keep99the99appliance99and99corresponding99cord99out9the9reach9of9children9under9the9age9of98.9

Children99should9be9supervised9to9ensure9that9they9do9not9play9with9the9appliance.9

WARN1NG!99Do99not99operate99the99appliance99with99a99damaged99cord

Damaged9power9cord9must9be9replaced9by9manufacturer,9authorized9

service9centre9or9other9qualified9persons9in9order9to9avoid9risk.9

Do99not99allow99the9power9cord9to99touch99sharp99edges99or9hot99surfa

Damaged9cord9poses9a9risk9of9electric9shock9

The9plug9must9fit9the9socket.9

The9plug9must9not9be9modified9in9any9way.9

Installation9must9comply9with9the9regulations9in9force9in9the9country9

where9 the9 device9 is9 used.9 5f9 you9 have9 any9 doubts9 concerning9 1 electrical9system,9ask9a9qualified9electrician.9

The9device9must9be9placed9so9as9the9access9to9the9electrical9socket9is9not9obstructed.9

Do99not99use99any99extension99cord99for99the99air-conditioner99unless99it been9inspected9and9tested9by9a9qualified9electrician9or9electrical9part9 supplier.9

Do9not9use9outside.9Do9not9expose9to9rain.9Protect9against9humidity.9 Do9not9operate9with9wet9hands.9

+se9only9a9soft9damp98not9wet)9cloth9with9mild9detergent9to9clean9the9 appliance.9Do9not9use9solvents,9petrol9or9other9measures9that9would9 damage9the9device.9

Transport99in99an99original99packaging99that99protects99against99mechanic damages.9

The9appliance9must9be9repaired9only9by9a9qualified9person9and9with9the9use9of9original9spare9parts.9

;ARN1NG!99Ventilation99openings99in99the99device99housing99or99in99the9 adjacent99partitions99must99be99perfectly99patent99and99free99from99any9 obstacles.9

;ARN1NG!9Do9not9put9any9objects9through9the9device9openings. ;ARN1NG! Do9not9damage9the9cooling9circuit.9

;ARN1NG! Do99not99use99electric99devices99inside99chambers99designated9 for9 food9 storage,9 unless9 they9 are9 the9 type9 recommended9 by9 the9 manufacturer.9

Before9dismounting,9assembly9or9cleaning9the9air-conditioner,9unplug9it.9

The9 air-conditioner9 must9 always9 be9 stored9 and9 transported9 in9 th upright9 position9 as9 otherwise9 the9 compressor9 can9 be9 damaged9 permanently.99

Place9the9air-conditioner9in9the9destination9place9and9wait9249h9before9switching9it9on.99

Avoid restarting the air-conditioner less than 4 minutes after switching it off as the compressor may be damaged otherwise.

Do not use the plug to switch the air-conditioner on and off. Always use the ON/OFF switch on the control panel.

Despite operating the unit in accordance with its intended use and in accordance with all safety guidelines, it is impossible to eliminate all residual risk factors.

-L4A"4 NOT4!

Any service maintenance other than regular filter cleaning or replacements should be carried out by the authorised repair team.

The failure to comply with this requirement can render your guarantee void.

;ARN1NG!

The air-conditioner contains eco-friendly natural gas propane R290.

Before switching the device on, ensure the cooling circuit has not been damaged. A direct contact with evaporating R290 medium can lead to skin frostbiting and eye irritation.

Ravanson PM-7500S - ;ARN1NG! - 1

Ravanson PM-7500S - ;ARN1NG! - 2

Ravanson PM-7500S - ;ARN1NG! - 3

Ravanson PM-7500S - ;ARN1NG! - 4

Appliance shall be installed, operated and stored in a room with a floor area larger than 12 m^2

Keep any required ventilation openings clear of obstruction;

Servicing shall be performed only as recommended by the manufacturer.

The appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation.

Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification.

If the circuit has been damaged:

- avoid open fire

- ventilate the room where the cooler/air-conditioner is placed immediately

1. 24"1GNAT1ON

The device is not designated to cool server rooms or other rooms where heat is generated constantly. The device must be used indoors.

If the socket is not available, the installation should be carried out by a qualified electrician. The device is safe. However, just as any other electric device, it must be used with care.

  1. -ART"
    Ravanson PM-7500S - 24"1GNAT1ON - 1

Labeled diagram of an industrial device with numbered components for identification

Front:

  1. Handle
  2. Control panel
  3. Air outlet
  4. Louvre controlling airflow direction
  5. Castors

Rear:

  1. +pper filter
  2. Air discharge
  3. Lower filter
  4. Drain hole
  5. Plug
  6. Power cord

Remote control
Ravanson PM-7500S - Rear: - 1
Window adapter

Hose connector
Ravanson PM-7500S - Rear: - 2

natural_image Simple line drawing of a mechanical component with a handle and end cap (no text or symbols)

Draining hose
Ravanson PM-7500S - Rear: - 3

Ravanson PM-7500S - Rear: - 4

WARNING!

The device can be moved easily from one room to another. Bear in mind, however, that:

• The9air-conditioner9must9always9be9in9the9upright9position9on9an9even9surface;9
- Do9not9put9near9a9bathtub,9washbasin9or9other9wet9or9damp9surfaces.9

9
Store9the9device9at9least9509cm9from9the9wall,9curtains,9drapes9and9sources9of9heat9to9ensure9appropriate9heat9circulation.9
Ravanson PM-7500S - WARNING! - 1

natural_image Line drawing of a portable air conditioner unit with 50cm height dimension标注 (no text or symbols on the device itself)

Ravanson PM-7500S - WARNING! - 2

natural_image Technical line drawing showing two mechanical or electrical component configurations with no visible text or symbols

16. INSTALLING TH4 D46IC4 USING TH4 WINDOW KIT9

PL4AS4 NOT4!

The9kit9is9designated9solely9for9installing9at9the9sliding9windows9or9doors.9

Do9not9use9the9kit9for9installing9in9basement9windows.9

Step 1

Check9the9exact9dimensions9of9the9window9and9the9kit9of9accessories9for9window99installation.9If9the9slide9for9window9regulation9is9too9long,9cut9it9using9the9appropriate9tools.9If9it9is9too9short,9you9can9buy9a9longer9slide9in9DIY9stores.9

Step 2

Connect9the9draining9hose9with9the9connector98Fig.9A).9Connect9the9hose9to9the9air9discharge9at9the9rear98Fig.9B).9 Turn9it9in9by9rotating9counterclockwise.9

9
9
9
9
9
9
Figure A Draining9hose Hose9connector9

Figure B Air discharge

Step 3

Insert9the9hose9connector9into9the9window9adapter98Fig.9C).9Adjust9the9adapter9to9the9window9width98vertically9or9horizontally)9and9then9tighten9the9screw9to9prevent9the9adapter9displacement98Fig.9D).9Ensure9the9adapter9matches9the9window9and9stays9in9place.9Close9the9window9so9as9the9adapter9remains9in9the9slot9between9the9window9and9the9frame9or9the9sill98Fig.9E).9

9

9

Ravanson PM-7500S - Step 3 - 1

PM-7500S PM-9500S
SWING TIMER HIGH LOW W.F 88 COOL DEPTH FAN SLEEP SWING TIMER SPEED UP DOWN MODE SLEEP POWER 8 7 3 5 4 2 6 1

PM-9500
W.F COMP HIGH LOW TIMER 8.8 SLEEP COOL DEHUM FAN POWER 999999999999999999999999999999999993 7 5 4 6 2 1

PM-9000
TIMER FAN UP 6 7 3 5 DOWN MODE POWER 4 2 1

  1. POW4R9-9On/off9switch9
  2. MO249-9switch9between9COOLING,9DEH+MIDIFYING9AND9FAN;9The9selected9function9is9signalled9by9a9LED,9 respectively:9COOL9(Cooling),9DEH+M9(Dehumidifying),9FAN9
  3. SP442 -9setting9fan9speed9(H-highest,9L-9lowest)9
  4. 2OWN9-9in9the9COOLING9mode,9to9reduce9target9temperature99
  5. UP9-9in9the9COOLING9mode,9to9increase9target9temperature9
  6. SL44P -9(work9at9night)9-9in9the9COOLING9mode,9to9switch9the9sleep9mode9on/off99
  7. SW1NG9-9 airflow9 control9 by 9 the 9 appropriate 9 positioning 9 of 9 the 9 louvre 9
  8. T1M4R- Setting9the9air-conditioner9unit9operating9time.9lt9is9possible9to9set9the9air-conditioner9unit9operating9time9from919h9to9249h.9

9

61. R4MOT4 CONTROL

  1. WŁĄCZ9/9WYŁĄCZ9
  2. TIMER9
  3. DOWN99
  4. MODE99
  5. +P99
  6. SPEED99
  7. SLEEP99
  8. SWING 9

6 5 4 3 2 7 1 8 PM-7500S PM-9500S PM-9500

Cool Fan Dry 88°C Svng Swap 1 - + 3/5 2 4 8 6 7 - F PM-9000

611. OP4RAT1ON

After the device is plugged, the current temperature in the room where the air-conditioner has been placed is displayed.

When9the9air-conditioner9is9first9switched9on9by9the9POWER9button,9it9starts9operation9with9low9speed9in9the9cooling9mode,9with9229C9set9by9default.

MO24 button

By9pressing9the9MODE9button9you9can9change9the9device9operation9mode:9

  1. COOL9(cooling)9

Press9+P/DOW9to9set9the9temperature9(from9169C9to9319C)9

Press9SPEED9to9select9high9or9low9speed99

FAN9

Press9SPEED9to9switch9on9quick9or9slow9fan9rotational9speed9

9

PL4AS4 NOT4!

In9the9FAN9mode:9

a. you9cannot9set9the9SLEEP9mode;9
b. you9cannot9set9the9temperature,9the9device9operates9like9an9ordinary9fan9

  1. 24HUM9(dehumidifying)9

9

PL4AS4 NOT4!

In9the9DEH+M9mode:99

  • you9cannot9change9fan9speed99
  • you9cannot9set9the9SLEEP9mode9

SPEED9and9SLEEP9functions9are9inactive9The9device9operates9with9low9speed.9

9

T1M4R button

Delayed start

The9device9can9be9programmed9to9switch9on9after9the9specific9time9has9elapsed9-9delayed9start.9Press9TIMER9in9 the9standby9mode.9The9time9left9before9the9device9is9switched9on9is9displayed.9By9pressing9the9button9once9you9 can9increase9the9time9left9to9start9by919h.9

To9 cancel9 the9 timer9 setting,9 switch9 the9 air-conditioner9 on9 manually9 by9 pressing9 POWER9 or9 keep9 pressing9 the9

TIMER button until its LED goes out and "00" appears on the display.

Delayed switch-off

The device can be programmed to switch off after the specific time has elapsed - delayed switch-off. Press TIMER in the work mode. The time left before the device is switched off

is displayed. By pressing the button once you can increase the time left to switch-off by 1 h.

To cancel the timer setting, switch the air-conditioner off manually by pressing POWER or keep pressing the TIMER button until its LED goes out and "00" appears on the display.

SL44P button - (PM-9000 – „FAN+UP“) sleep mode - only in the COOLING mode

Press SLEEP - the fan is set to slow speed.

When the SLEEP function is on in the cooling mode, the temperature will increase by 1 degree after 1st hour of device operation and by another 1 degree after 2nd hour. After that the temperature will not change.

PL4AS4 NOT4!

To protect the compressor against excessive switching on and off, the device was designed so as the compressor switches on after at least 3-minute break if the device has been switched off and/or any function was changed too soon.

6III. TO 4MPTY WAT4R TANK - "W.F." L4D ON TH4 CONTROL PAN4L

If the control lamp ("W.F.") of the water tank overflow is on, empty the tank.

PL4AS4 NOT4!

Unplug the device before you empty the tank.

Always empty the tank when the air-conditioner is no longer used, regardless of how much water is there.

TO 4MPTY TH4 TANK

  1. Switch the air-conditioner off. Unplug it.
  2. Put an appropriate container on the floor under the drain hole (9).

PL4AS4 NOT4!

Use the container only while emptying the tank. Water should not run into the container when the air-conditioner is on as this can lead to overflowing.

  1. Twist off the plug (10).
  2. Remove the rubber stopper and drain water from the device.
  3. Put the rubber stopper in again. The water tank overflow indicator (W.F.) should go out.
  4. Tighten the plug.

The air-conditioner should switch off automatically when the water tank is full.

Cleaning and maintenance

Before you start cleaning, switch the air-conditioner off and unplug it.

Use soft damp (not wet) cloth with mild detergent. Do not use solvents, petrol or other and other measures that would damage the device.

TO CL4AN TH4 FILT4R

The filter should be cleaned every two weeks. Dirty filters reduce the air-conditioner efficiency.

For this purpose, pull out the upper and lower filter from the device.

  1. Clean the filter with a vacuum cleaner.
  2. Wash the filter with a running water with a mild detergent.
  3. Rinse thoroughly.
  4. Dry the filter before you re-assembly it.

8. TRANSPORT AND STORAGE4

Always empty the water tank before you store and transport the device.

Before putting the device away, wait until it cools down. Keep and store in a package protecting from humidity and mechanical damages.

Transport in the original packaging, protecting against mechanical damage and dirt.

XI. POPULAR DEFECTS

PROBLEM CAUSE SOLUTION
The air-conditioner does not switch on.No power supply Plug the air-conditioner.
The water tank overflow indicator is onEmpty the water tank
The air-conditioner restarts Direct sunlight Cover the windows
Close the doors and windows, remove the heat sources from the room
Soiled filter Clean or remove the filter
Air inlet or outlet is obstructed Remove the obstacles
Noisy operation The air-conditioner is not level Put the air-conditioner onan even surface to prevent vibrations
The compressor does not operate Active compressor protection This should not last over 3 minutes Restart the air-conditioner

If the above-mentioned advice does not solve the problem, contact the repair service.

Technical parameters

Voltage 220-240 V

Frequency 50 Hz

PM-7500S PM-9500S PM-9500 PM-9000

Refrigerant/weight -R290 / 165 g220 g220 g230 g

The remote control Power supplied 2 x AA (3V d.c.)

PM-7500SPM-9500SPM-9500PM-9000
DescriptionSymbolUnitValueValueValueValue
Rated cooling efficiencyP rated CoolingkW2,052,63 2,632,63
Rated heating efficiencyP rated HeatingkW----
Nominal power consumption CoolingP EERkW0,781,011,011,01
Nominal power consumption HeatingP C'PkW----
Rated energy efficiency ratioEERd-2,602,602,602,60
Rated efficiency ratioC'Pd-----
Power consumed with the thermostat offPT'W----
Power consumption in standby modeP [”W1111
Power consumption of single-/dual-channel air-conditioners - Cooling - HeatingDD» Q DD [D» Q [D]DD: kWh/h SD: kWh/h0,7801,011,011,01
---
Sound powerL WAdB (A)65656565
Global Warming PotentialGWPkg CO2 equivalents3333
Further information can be obtained fromRAVANSON LTD. Sp. z o.o. ul. Mazowiecka 6, 09-100 Płońsk

The manufacturer reserves the right to introduce technical modifications!

Ravanson PM-7500S - Technical parameters - 1

The symbol presented below indicates that the used equipment cannot be placed together with other household waste. The user is obliged to bring this item to the waste electrical and electronic equipment collection point where a suitable system is created to allow safe disposal of these items.

Dangerous components present in electrical and electronic equipment have negative

consequences for the environment and human health therefore correct handling of the equipment is very important. Certain substances which may adversely affect the environment over the life of the product and after use have been limited in this device.

Product fiche

Supplier's name or trade markRAVANSON LTD. Sp. z o.o
Model identifier PM-7500S PM-9500S PM-9500PM-9000
Sound power level65
The name and GWP of the refrigerant usedR290 / 3
Refrigerant leakage contributes to climate change. Refrigerant with lower global warming potential (GWP) would contribute less to global warming than a refrigerant with higher GWP, if leaked to the atmosphere. This appliance contains a refrigerant fluid with a GWP equal to 3. This means that if 1 kg of this refrigerant fluid would be leaked to the atmosphere, the impact on global warming would be 3 times higher than 1 kg of CO2, over a period of 100 years. Never try to interfere with the refrigerant circuit yourself or disassemble the product yourself and always ask a professional.
Energy Efficiency ClassA
The indicative hourly electricity consumption QSDw kWh/60 min0,78 1,011,01 1,01
Energy consumption "X,Y" kWh per 60 minutes, based on standard test results. Actual energy consumption will depend on how the appliance is used and where it is located.
The cooling capacity Prated(kW)2,052,632,632,63
The heating capacity Prated(kW)-

CS

Přední strana:

natural_image Simple line drawing of a cylindrical object with a handle and circular end (no text or symbols)

Okenní adaptér

Ravanson PM-7500S - Přední strana: - 1
Odváděcí hadice

Ravanson PM-7500S - Přední strana: - 2
Spojka hadice

-O"OR!

natural_image Technical line drawing showing two views of a vehicle or device with connected components and a marked point (X), no text or symbols present.
  1. NAINSTALO6ÁNÍ ZAŘÍZ4NÍ S POUŽITÍM OK4NNÍ SOUPRA6Y9

POZOR!

Predná strana:

natural_image Simple line drawing of a cylindrical object with a flanged end and a looped opening (no text or symbols)

Okenný adaptér

Ravanson PM-7500S - Predná strana: - 1
Spojka hadice

-O"OR!

natural_image Technical line drawing showing two mechanical components connected by a pipe with a labeled X component (no text or symbols present)
  1. NAINŠTALO6ANI4 ZARIAD4NIA S POUŽITÍM OK4NN4J SÚPRA6Y9

POZOR!

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Ravanson

Model : PM-7500S

Category : Air-conditioner