DAB EVOSTA2 - Pump

EVOSTA2 - Pump DAB - Free user manual and instructions

Find the device manual for free EVOSTA2 DAB in PDF.

📄 53 pages English EN Download 💬 AI Question
Notice DAB EVOSTA2 - page 4
View the manual : Français FR English EN Español ES
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about EVOSTA2 DAB

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Pump in PDF format for free! Find your manual EVOSTA2 - DAB and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EVOSTA2 by DAB.

USER MANUAL EVOSTA2 DAB

8.1 Mechanical installation....5
8.2 User Interface Position....6
8.3 Rotation of the user interface 7
8.4 Non-return valve.... 8

  1. ELECTRICAL CONNECTIONS 9

9.1 Power supply connection.... 10

  1. START.... 10

10.1 Degassing the pump.... 11
10.2 Automatic Degassing 11

  1. FUNCTIONS.... 12

11.1 Regulating Modes 12

11.1.1 Regulation with Proportional Differential Pressure 12
11.1.2 Regulation with Constant Differential Pressure 12
11.1.3 Regulation with constant curve 13

  1. CONTROL PANEL.... 13

12.1 Elements on the Display.... 13
12.2 Graphic Display.... 14

  1. FACTORY SETTINGS.... 16

  2. TYPES OF ALARM.... 16

  3. MAINTENANCE.... 16
  4. DISPOSAL 16
  5. DIMENSIONS....49
  6. PERFORMANCE CURVES ....50

INDEX OF FIGURES

Figure 1: Pumped liquids, warnings and operating conditions.... 3
Figure 2: Mounting EVOSTA2, EVOSTA2d 5
Figure 3: Assembly position .... 6
Figure 4: Positions of the user interface....7
Figure 5: Positions of the user interface....7
Figure 6: Changing the position of the user interface....8
Figure 7: Venting of the pump 11
Figure 8: Automatic venting of the pump....11
Figure 9: Display....13
Figura 10: EVOSTA2d Display 14

INDEX OF TABLES

Table 1: Functions ...... 3
Table 2: Technical data .... 4
Table 3: Maximum head (Hmax) and maximum flow rate (Qmax) of EVOSTA2, EVOSTA2d circulators..... 4
Tabella 4: Wiring Evosta2, EVOSTA2d 10
Table 5: Pump operating modes 15
Table 6: Types of Alarm.... 16

1. KEY

The frontispiece shows the version of this document in the form Vn.x. This version indicates that the document is valid for all software versions of the device n.y. For example: V3.0 is valid for all Sw: 3.y.

In this document the following symbols will be used to avoid situations of ranger:

DAB EVOSTA2 - KEY - 1

Situation of general danger. Failure to respect the instructions that follow may cause harm to persons and property.

DAB EVOSTA2 - KEY - 2

Situation of electric shock hazard. Failure to respect the instructions that follow may cause a situation of grave risk for personal safety.

2. GENERAL

DAB EVOSTA2 - GENERAL - 1

Read this documentation carefully before installation.

Skilled personnel: Installation must be carried out by competent, skilled personnel in possession of the technical qualifications required by the specific legislation in force. The term skilled personnel means persons whose training, experience and instruction, as well as their knowledge of the respective standards and requirements for accident prevention and working conditions, have been approved by the person in charge of plant safety, authorizing them to perform all the necessary activities, during which they are able to recognize and avoid all dangers. (Definition for technical personnel IEC 364).

The appliance may not be used by children under 8 years old or by persons with reduced physical, sensory or mental capacities, or who lack experience or knowledge, unless they are under supervision or after they have received instructions concerning the safe use of the appliance and the understanding of the dangers involved. Children must not play with the appliance.

DAB EVOSTA2 - Read this documentation carefully before installation. - 1

Ensure that the product has not suffered any damage during transport or storage. Check that the outer casing is unbroken and in excellent conditions.

2.1 Safety

Use is allowed only if the electric system is in possession of safety precautions in accordance with the regulations in force in the country where the product is installed.

2.2 Responsibility

The Manufacturer does not vouch for correct operation of the machine or answer for any damage that it may cause if it has been tampered with, modified and/or run outside the recommended work range or in contrast with other indications given in this manual.

2.3 Particular warnings

DAB EVOSTA2 - Particular warnings - 1

Always switch off the mains power supply before working on the electrical or mechanical part of the system. Wait for the warning lights on the control panel to go out before opening the appliance. The capacitor of the direct current intermediate circuit remains charged with dangerously high voltage even after the mains power has been turned off.

Only firmly cabled mains connections are admissible. The appliance must be earthed (IEC 536 class 1, NEC and other applicable standards).

DAB EVOSTA2 - Particular warnings - 2

Mains terminals and motor terminals may still have dangerous voltage when the motor is stopped.

DAB EVOSTA2 - Particular warnings - 3

If the power cable is damaged, it must be replaced by the technical assistance service or by qualified personnel, so as to avoid any risk.

3. PRODUCT DESCRIPTION

DAB EVOSTA2 - PRODUCT DESCRIPTION - 1

text_image Min. / Max. 14 °F / +230 °F -10 / +110 °C Max. 1.0 MPa (145 psi /10 bar) Min. / Max. 32 °F / +104 °F 0 / +40 °C < 43 dB (A) Max. 95% RH IPX5

Figure 1: Pumped liquids, warnings and operating conditions

The circulators in the EVOSTA2, EVOSTA2d series represent a complete range of circulators.

These installation and operating instructions describe EVOSTA2, EVOSTA2d models. The type of model is indicated on the pack and on the identification plate.

The table below shows the EVOSTA2, EVOSTA2d models with built-in functions and features.

Functions/features EVOSTA 2 EVO$TA 2d
Proportional pressure ● ●
Constant pressure ● ●
Constant curve ● ●
Dry-running protection ●
Automatic degassing

Table 1: Functions

4. PUMPED LIQUIDS

Clean, free from solids and mineral oils, not viscous, chemically neutral, close to the properties of water (max. glycol contents 30%).

5. APPLICATIONS

EVOSTA2, EVOSTA2d series circulators allow integrated adjustment of the differential pressure which enables the circulator performance to be adapted to the actual requirements of the system. This determines considerable energy saving, a greater possibility of control of the system, and reduced noise.

EVOSTA2, EVOSTA2d circulators are designed for the circulation of:

– water in heating and conditioning systems.
– water in industrial water circuits.
– domestic water only for the versions with stainless steel pump body.

EVOSTA2, EVOSTA2d circulators are self-protected against:

  • Overloads
    – Lack of phase
    – Excess temperature
  • Over-voltage and under-voltage

6. TECHNICAL DATA

Supply voltage110-127V (+/-10%), 60 Hz
Absorbed power See electrical data plate
Maximum current See electrical data plate
Grade of protection IPX5
Protection class F
TF Class TF 110
Motor protector No external motor protector is needed
Maximum environment temperature 104 °F / 40°C
Liquid temperature 14 °F ÷ 230 °F / -10 °C ÷ 110 °C
Flow rate See Table3
HeadSee
Maximum working pressure 1.0 Mpa- 145 psi / 10 bar
Minimum working pressure0.1 Mpa - 14.5 psi / 1 bar
Lpa [dB(A)]≤ 43

Table 2: Technical data

Designation index

(example)

Series name

2 = without display

2d = with display

Maximum head (feet)

Centre distance (inches)

DAB EVOSTA2 - Designation index - 1

text_image EVOSTA 2 70/ 130
EVOSTA2, EVOSTA2dHmax (ft / m)Qmax (gpm / m^3/h )
EVOSTA2 110-127V 60Hz18 / 5.516 / 3.6
EVOSTA2d 110-127V 60Hz18 / 5.516 / 3.6

Table 3: Maximum head (Hmax) and maximum flow rate (Qmax) of EVOSTA2, EVOSTA2d circulators

7. MANAGEMENT

7.1 Storage

All the circulators must be stored in a dry covered place, with possibly constant air humidity, free from vibrations and dust. They are supplied in their original pack in which they must remain until the time of installation. If this is not the case, accurately close the suction and delivery mouth.

7.2 Transport

Avoid subjecting the products to needless impacts and collisions. To lift and transport the circulator use lifting devices with the aid of the pallet supplied with it (if contemplated).

7.3 Weight

The adhesive plate on the packaging indicates the total weight of the circulator.

8. INSTALLATION

DAB EVOSTA2 - INSTALLATION - 1

Always switch off the mains power supply before working on the electrical or mechanical part of the system. Wait for the warning lights on the control panel to go out before opening the appliance. The capacitor of the direct current intermediate circuit remains charged with dangerously high voltage even after the mains power has been turned off.

Only firmly cabled mains connections are admissible. The appliance must be earthed (IEC 536 class 1, NEC and other applicable standards).

DAB EVOSTA2 - INSTALLATION - 2

Ensure that the voltage and frequency on the data plate of the EVOSTA2, EVOSTA2d circulator are the same as those of the power mains.

8.1 Mechanical installation

DAB EVOSTA2 - Mechanical installation - 1

text_image A B

Figure 2: Mounting EVOSTA2, EVOSTA2d

The arrows on the pump housing indicate the flow direction through the pump. See fig. 1, pos. A.

  1. Fit the two gaskets when you mount the pump in the pipe. See fig. 1, pos. B.
  2. Install the pump with a horizontal motor shaft. See fig. 1, pos. C.
  3. Tighten the fittings.

8.2 User Interface Position

DAB EVOSTA2 - User Interface Position - 1

Always install the EVOSTA2, EVOSTA2d circulator with the motor shaft in a horizontal position.

Install the electronic control device in a vertical position.

DAB EVOSTA2 - User Interface Position - 2

text_image evoytred OK OK evoytred OK NO NO

Figure 3: Assembly position

  • The circulator may be installed in heating and conditioning systems on either the delivery pipe or the return pipe; the arrow marked on the pump body indicates the direction of flow.
  • Install the circulator as far as possible above the minimum boiler level and as far as possible from bends, elbows and junction boxes.
  • To facilitate control and maintenance operations, install an interception valve both on the suction pipe and on the delivery pipe.
    Before installing the circulator, accurately flush the system with only water at 80^ . Then drain the system completely to eliminate any harmful substance that may have got into circulation.
  • Avoid mixing additives derived from hydrocarbons and aromatic products with the circulating water. It is recommended that the addition of antifreeze, where necessary, should not exceed 30% .
  • In the event of heat insulation use the special kit (if provided) and ensure that the condensate draining holes in the motor casing are not closed or partly blocked.
  • In the case of maintenance, always use a set of new gaskets.

DAB EVOSTA2 - User Interface Position - 3

Never insulate the electronic control device.

8.2.1 Positioning of the user interface in heating and domestic hot water systems

It is possible to position the user interface with the cable facing to the left, to the right, or downwards.

DAB EVOSTA2 - Positioning of the user interface in heating and domestic hot water systems - 1

text_image EVGTRED EVGO PEALONG IPx5

Figure 4: Positions of the user interface

8.2.2 Positioning of the user interface in conditioning and cold water systems The user interface can be positioned only with the cable facing downwards.

DAB EVOSTA2 - Positioning of the user interface in conditioning and cold water systems The user interface can be positioned only with the cable facing downwards. - 1

text_image Diagram showing various smart lockers with warning symbols and labels, including 'EVOYTRAD' and 'DELLINO' variants.

Figure 5: Positions of the user interface

8.3 Rotation of the user interface

If the circulator is installed on pipes in a horizontal position, it will be necessary to rotate the interface with the respective electronic device through 90 degrees in order to maintain the grade of IP protection and to allow the user a more convenient interaction with the graphic interface.

ENGLISH

DAB EVOSTA2 - ENGLISH - 1

Before rotating the circulator, ensure that it has been completely drained.

To rotate the EVOSTA2, EVOSTA2d circulator, proceed as follows:

  1. Remove the 4 fixing screws of the circulator head.
  2. Rotate the motor casing with the electronic control device through 90 degrees clockwise or counterclockwise, as necessary.
  3. Reassemble and tighten the 4 screws that fix the circulator head.

DAB EVOSTA2 - Before rotating the circulator, ensure that it has been completely drained. - 1

The electronic control device must always remain in vertical position!

DAB EVOSTA2 - The electronic control device must always remain in vertical position! - 1

text_image Diagram illustrating safety warning symbols and process steps for a mechanical device, showing transition from warning to checkmark.

Figure 6: Changing the position of the user interface

DAB EVOSTA2 - The electronic control device must always remain in vertical position! - 2

ATTENTION

Water at high temperature. High temperature.

DAB EVOSTA2 - ATTENTION - 1

ATTENTION

System under pressure

- Before dismantling the pump, empty the system or close the interception valves on both sides of the pump. The pumped liquid may be at a very high temperature and high pressure.

8.4 Non-return valve

If the system is equipped with a non-return valve, ensure that the minimum pressure of the circulator is always higher than the valve closing pressure.

9. ELECTRICAL CONNECTIONS

The electrical connections must be made by expert, qualified personnel.

DAB EVOSTA2 - ELECTRICAL CONNECTIONS - 1

ATTENTION! ALWAYS RESPECT THE LOCAL SAFETY REGULATIONS.

DAB EVOSTA2 - ATTENTION! ALWAYS RESPECT THE LOCAL SAFETY REGULATIONS. - 1

Always switch off the mains power supply before working on the electrical or mechanical part of the system. Wait for the warning lights on the control panel to go out before opening the appliance. The capacitor of the direct current intermediate circuit remains charged with dangerously high voltage even after the mains power has been turned off.

Only firmly cabled mains connections are admissible. The appliance must be earthed (IEC 536 class 1, NEC and other applicable standards).

DAB EVOSTA2 - ATTENTION! ALWAYS RESPECT THE LOCAL SAFETY REGULATIONS. - 2

THE SYSTEM MUST BE CORRECTLY AND SAFELY EARTHED!

DAB EVOSTA2 - THE SYSTEM MUST BE CORRECTLY AND SAFELY EARTHED! - 1

It is advised to install a correctly dimensioned differential switch to protect the system, type: class A with adjustable leakage current, selective.

The automatic differential switch must be marked with the following symbols:

DAB EVOSTA2 - THE SYSTEM MUST BE CORRECTLY AND SAFELY EARTHED! - 2

DAB EVOSTA2 - THE SYSTEM MUST BE CORRECTLY AND SAFELY EARTHED! - 3

– The circulator does not require any external motor protection.
- Ensure that the supply voltage and frequency are the same as the values indicated on the electrical data plate of the circulator.

9.1 Power supply connection

DAB EVOSTA2 - Power supply connection - 1

text_image 1 Prepare the wiring up to the terminal box. Slacken the two fixing screws. 2 Remove the cover Connect the cables to the terminal block cables.

Tabella 4: Wiring Evosta2, EVOSTA2d

10. START

DAB EVOSTA2 - START - 1

All the starting operations must be performed with the cover of the EVOSTA2, EVOSTA2d control panel closed.

Start the system only when all the electrical and hydraulic connections have been completed.

Avoid running the circulator when there is no water in the system.

DAB EVOSTA2 - START - 2

As well as being at a high temperature and pressure, the fluid in the system may also be in the form of steam. DANGER OF SCALDING!

It is dangerous to touch the circulator. DANGER OF SCALDING!

Once all the electrical and hydraulic connections have been made, fill the system with water and if necessary with glycol (for the maximum glycol percentage see par. 4) and feed the system.

Once the system has been started it is possible to modify the operating modes to adapt better to the plant requirements.

10.1 Degassing the pump

DAB EVOSTA2 - Degassing the pump - 1

text_image EVOTA2D DAB 1 EVOTA2 DAB 1 0.5X3.0X80 4 3 x 10min 2

Figure 7: Venting of the pump

DAB EVOSTA2 - Degassing the pump - 2

Always vent the pump before starting!

The pump must never run when dry.

10.2 Automatic Degassing

Automatic degassing occurs only for the Evosta2d pump. Hold down the Mode key for 3 sec and the function starts: 1 minute at maximum speed, then it passes to the set mode.

DAB EVOSTA2 - Automatic Degassing - 1

text_image evoftred DAB x 3sec x 1min

Figure 8: Automatic venting of the pump

11. FUNCTIONS

11.1 Regulating Modes

EVOSTA2, EVOSTA2d circulators allow the following regulating modes depending on plant requirements:

– Proportional differential pressure regulation depending on the flow present in the plant.
- Constant differential pressure regulation.
- Regulation with constant curve.

The regulating mode may be set through the EVOSTA2, EVOSTA2d control panel.

11.1.1 Regulation with Proportional Differential Pressure

DAB EVOSTA2 - Regulation with Proportional Differential Pressure - 1

line | H | Q | | ---- | ---- | | 1.0 | 0.0 | | 0.5 | 0.2 | | 0.0 | 0.4 | | -0.5 | 0.6 | | -1.0 | 0.8 | | -1.5 | 1.0 | | -2.0 | 1.2 | | -2.5 | 1.4 | | -3.0 | 1.6 | | -3.5 | 1.8 | | -4.0 | 2.0 | | -4.5 | 2.2 | | -5.0 | 2.4 | | -5.5 | 2.6 | | -6.0 | 2.8 | | -6.5 | 3.0 | | -7.0 | 3.2 | | -7.5 | 3.4 | | -8.0 | 3.6 | | -8.5 | 3.8 | | -9.0 | 4.0 | | -9.5 | 4.2 | | -10.0| 4.4 | | -10.5| 4.6 | | -11.0| 4.8 | | -11.5| 5.0 | | -12.0| 5.2 | | -12.5| 5.4 | | -13.0| 5.6 | | -13.5| 5.8 | | -14.0| 6.0 | | -14.5| 6.2 | | -15.0| 6.4 | | -15.5| 6.6 | | -16.0| 6.8 | | -16.5| 7.0 | | -17.0| 7.2 | | -17.5| 7.4 | | -18.0| 7.6 | | -18.5| 7.8 | | -19.0| 8.0 | | -19.5| 8.2 | | -20.0| 8.4 | | -20.5| 8.6 | | -21.0| 8.8 | | -21.5| 9.0 | | -22.0| 9.2 | | -22.5| 9.4 | | -23.0| 9.6 | | -23.5| 9.8 | | -24.0| 10.0 |

DAB EVOSTA2 - Regulation with Proportional Differential Pressure - 2

text_image EVOSTA 2d EVOSTA 2

In this regulating mode the differential pressure is reduced or increased as the demand for water decreases or increases.

The Hs set point may be set from the display.

Regulation indicated for:

  • Heating and conditioning plants with high load losses
  • Plants with secondary differential pressure regulator
    – Primary circuits with high load losses
    – Domestic water recirculating systems with thermostatic valves on the rising columns

11.1.2 Regulation with Constant Differential Pressure

DAB EVOSTA2 - Regulation with Constant Differential Pressure - 1

line | Point | Value | |-------|-------| | 1 | High | | 2 | Medium| | 3 | Low |

DAB EVOSTA2 - Regulation with Constant Differential Pressure - 2

text_image EVOSTA2d EVOSTA2

In this regulating mode the differential pressure is kept constant, irrespective of the demand for water, The Hs set point may be set from the display.

Regulation indicated for:

  • Heating and conditioning plants with low load losses
  • Single-pipe systems with thermostatic valves
  • Plants with natural circulation
    – Primary circuits with low load losses
    – Domestic water recirculating systems with thermostatic valves on the rising columns

11.1.3 Regulation with constant curve

DAB EVOSTA2 - Regulation with constant curve - 1

text_image H Q

DAB EVOSTA2 - Regulation with constant curve - 2

text_image EVOSTA 2d 8.9 W IT 600 8.8 W IT 600 8.8 W IT 600 EVOSTA 2

In this regulating mode the circulator works on characteristic curves at a constant speed.

Regulation indicated for heating and conditioning plants with constant flow.

12. CONTROL PANEL

The functions of EVOSTA2, EVOSTA2d circulators can be modified by means of the control panel on the cover of the electronic control device.

12.1 Elements on the Display

DAB EVOSTA2 - Elements on the Display - 1

text_image EVOSTA 2 DAB MODE 3 1 Figure 9: Display EVOSTA 2d DAB MODE 3.8 W 1 gpm 4 2

1 Luminous segments indicating the type of set curve

2 Display showing the instantaneous power absorption in Watt, the flow rate in m ^3 /h, the head in metres and the set curve.

3 Key for selecting the pump setting

4 Luminous segments indicating the set curve

12.2 Graphic Display

12.2.1 Luminous segments indicating the pump setting

DAB EVOSTA2 - Luminous segments indicating the pump setting - 1

The pump presents nine setting options that can be selected with the 'key'. The pump settings are indicated by six luminous segments on the display.

12.2.2 Key for selecting the pump setting

Whenever the key is pressed, the pump setting is changed. A cycle consists of pressing the key ten times.

12.2.3 Display Operation

DAB EVOSTA2 - Display Operation - 1

text_image EVOSTA2d DAB MODE 8.8 W ft gpm

Figura 10: EVOSTA2d Display

The Evosta3 circulator has a display that is able to show the following values.

DAB EVOSTA2 - Display Operation - 2

text_image W ft gpm

Height of the selected curve (1-2-3)

Instantaneous power absorption in Watt

Instantaneous head in feet

Instantaneous flow rate in gallon/minut

The values are shown in sequence for 3sec. Once the viewing cycle is ended, the display switches off and only the operating mode LED remains lit.

If the selection key is pressed within 10sec, the display performs 6 viewing cycles, then goes into stand-by.

If the key is pressed again within 10sec, the display performs 11 more viewing cycles to allow a greater reading time.

12.2.4 Settings of the pump operating mode

EVOSTA2dEVOSTA2
1DAB EVOSTA2 - Settings of the pump operating mode - 1DAB EVOSTA2 - Settings of the pump operating mode - 2Lower curve with proportional pressure, PP1
2DAB EVOSTA2 - Settings of the pump operating mode - 3DAB EVOSTA2 - Settings of the pump operating mode - 4Intermediate curve with proportional pressure, PP2
3DAB EVOSTA2 - Settings of the pump operating mode - 5DAB EVOSTA2 - Settings of the pump operating mode - 6Higher curve with proportional pressure, PP3
4DAB EVOSTA2 - Settings of the pump operating mode - 7DAB EVOSTA2 - Settings of the pump operating mode - 8Lower curve with constant pressure, CP1
5DAB EVOSTA2 - Settings of the pump operating mode - 9DAB EVOSTA2 - Settings of the pump operating mode - 10Intermediate curve with constant pressure, CP2
6DAB EVOSTA2 - Settings of the pump operating mode - 11DAB EVOSTA2 - Settings of the pump operating mode - 12Higher curve with constant pressure, CP3
7DAB EVOSTA2 - Settings of the pump operating mode - 13DAB EVOSTA2 - Settings of the pump operating mode - 14Lower constant curve, I
8DAB EVOSTA2 - Settings of the pump operating mode - 15DAB EVOSTA2 - Settings of the pump operating mode - 16Intermediate constant curve, II
9DAB EVOSTA2 - Settings of the pump operating mode - 17DAB EVOSTA2 - Settings of the pump operating mode - 18Higher constant curve, III

Table 5: Pump operating modes

13. FACTORY SETTINGS

Regulating mode: Minimum proportional differential pressure regulation

14. TYPES OF ALARM

Alarm Description
No. of curve height blinksEVOSTA2
2 BlinksTRIP: loss of motor control, may be caused by incorrect parameters, blocked rotor, disconnected phase, disconnected motor
3 Blinks SHORT CIRCUIT: short circuit on phases or between phase and earth
4 Blinks OVERRUN: software faultt
5 BlinksSAFETY: safety module error, may be caused by a sudden overcurrent or other hardware faults of the board
Alarm Code EVOSTA2d
E1DRY RUN
E2TRIP: loss of motor control, may be caused by incorrect parameters, blocked rotor, disconnected phase, disconnected motor
E3 SHORT CIRCUIT: short circuit on phases or between phase and earth
E4 OVERRUN: software faultt
E5SAFETY: safety module error, may be caused by a sudden overcurrent or other hardware faults of the board

Table 6: Types of Alarm

15. MAINTENANCE

DAB EVOSTA2 - MAINTENANCE - 1

Cleaning and maintenance activities must not be carried out by children (under 8 years of age) without supervision by a qualified adult. Before starting any work on the system, before starting to look for faults it is necessary to disconnect the power supply to the pump (take the plug out of the socket) and read the use and maintenance instructions.

16. DISPOSAL

DAB EVOSTA2 - DISPOSAL - 1

This product or its parts must be disposed of in an environment-friendly manner and in compliance with the local regulations concerning the environment; use public or private local waste collection systems.

INDEX

  1. LÉGENDE 18
  2. GÉNÉRALITÉS....18
text_image Diagram showing various smart air condition indicators including thermometer, snowflake, and warning symbols with checkmarks.
text_image Diagram illustrating safety warning symbols and mechanical assembly steps with labeled warning signs and checkmark indicator
line | Q | H | | --- | --- | | 0 | 1.0 | | 1 | 0.8 | | 2 | 0.6 | | 3 | 0.4 | | 4 | 0.2 | | 5 | 0.0 |

DAB EVOSTA2 - INDEX - 1

text_image EVOSTA 2d EVOSTA 2
text_image EVOSTA 2d DAB MODE 8.8 W ft gpm

Image 10: Afficheur Evosta2d

text_image Diagram showing various EVOTRAG sensor modules with warning symbols and labels, including a checkmark for installation.
text_image Diagram illustrating safety compliance with warning symbols and a checkmark, showing mechanical assembly steps.
text_image evostred DAB x 3sec x 1min
line | Q | H | | --- | --- | | 0 | 1.0 | | 1 | 0.8 | | 2 | 0.6 | | 3 | 0.4 | | 4 | 0.2 | | 5 | 0.0 |

DAB EVOSTA2 - INDEX - 2

text_image EVOSTA 2d EVOSTA 2
text_image EVOSTA 2d DAB MODE 8.8 W ft gpm

Figura 10: Pantalla Evosta2d

17. DIMENSIONS – DIMENSIONS - DIMENSIONES

DAB EVOSTA2 - DIMENSIONS – DIMENSIONS - DIMENSIONES - 1

text_image L L1 EVOYRACD RAN 8.8 AWB 50

DAB EVOSTA2 - DIMENSIONS – DIMENSIONS - DIMENSIONES - 2

text_image B2 B1 B

DAB EVOSTA2 - DIMENSIONS – DIMENSIONS - DIMENSIONES - 3

text_image F1 F A H1 H2 H
Mod.L L1 BB1 B2H
inchmminchmminchmminchmminchmminchmm
EVOSTA2 55 110-127V 60Hz6-3/81623-7/8985-3/81373-7/8991-1/2385-5/814
EVOSTA2D 55 110-127V 60Hz
EVOSTA2 55 SAN 110-127V 60Hz
H1 H2 AF F1105
inchmminchmminchmminchmminchmm
3-13/16971-13/16461/2133-3/16814-1/8

18. PERFORMANCE CURVES PERFORMANCES COURBES CURVAS PRESTACIONES

DAB EVOSTA2 - PERFORMANCE CURVES PERFORMANCES COURBES CURVAS PRESTACIONES - 1

line | Q(gpm) | H(mt) - Line 1 | H(mt) - Line 2 | H(mt) - Line 3 | H(mt) - Line 4 | H(mt) - Line 5 | H(mt) - Line 6 | H(mt) - Line 7 | |--------|----------------|----------------|----------------|----------------|----------------|----------------|----------------| | 0 | 18 | 8 | 6 | 5 | 4 | 3 | 2 | | 2 | 18 | 10 | 8 | 5 | 5 | 4 | 3 | | 4 | 18 | 12 | 10 | 5 | 6 | 5 | 4 | | 6 | 15 | 14 | 12 | 5 | 7 | 6 | 5 | | 8 | 12 | 16 | 14 | 5 | 8 | 7 | 6 | | 10 | 9 | 18 | 16 | 5 | 9 | 8 | 7 | | 12 | 6 | 20 | 18 | 5 | 10 | 9 | 8 | | 14 | 3 | 22 | 20 | 5 | 11 | 10 | 9 | | 16 | 0 | 24 | 22 | 5 | 12 | 11 | 10 | | 18 | - | 26 | 24 | 5 | 13 | 12 | 11 |

DAB EVOSTA2 - PERFORMANCE CURVES PERFORMANCES COURBES CURVAS PRESTACIONES - 2

line | Q(gpm) | P(W) - Line 1 | P(W) - Line 2 | P(W) - Line 3 | P(W) - Line 4 | P(W) - Line 5 | P(W) - Line 6 | P(W) - Line 7 | |--------|---------------|---------------|---------------|---------------|---------------|---------------|---------------| | 0 | 10 | 17 | 10 | 7 | 5 | 3 | 23 | | 2 | 15 | 22 | 15 | 10 | 7 | 6 | 30 | | 4 | 20 | 28 | 20 | 15 | 10 | 9 | 38 | | 6 | 25 | 32 | 25 | 20 | 13 | 12 | 40 | | 8 | 30 | 35 | 30 | 25 | 16 | 15 | 40 | | 10 | 35 | 38 | 35 | 30 | 20 | 18 | 40 | | 12 | 40 | 40 | 40 | 35 | 25 | 22 | 40 | | 14 | 40 | 40 | 40 | 40 | 30 | 25 | 40 | | 16 | 40 | 40 | 40 | 40 | 35 | 28 | 40 | | 18 | 40 | 40 | 40 | 40 | 40 | 30 | 40 |

DAB PUMPS LTD.

6 Gilbert Court

Newcomen Way

Severalls Business Park

Colchester

Essex

C04 9WN - UK

salesuk@dwtgroup.com

Tel. +44 0333 777 5010

DAB PUMPS BV

'tHofveld 6 C1

info.belgium@dwtgroup.com

Tel. +32 2 4668353

DAB PUMPS INC.

3226 Benchmark Drive

Ladson, SC 29456 - USA

info.usa@dwtgroup.com

Tel. 1-843-797-5002

Fax 1-843-797-3366

000 DAB PUMPS

Novgorodskaya str. 1, block G

office 308, 127247, Moscow - Russia

info.russia@dwtgroup.com

Tel. +7 495 122 0035

Fax +7 495 122 0036

DAB PUMPS POLAND SP. z.o.o.

No.40 Kaituo Road, Qingdao Economic &

Technological Development Zone

Qingdao City, Shandong Province - China

PC: 266500

sales.cn@dwtgroup.com

Tel. +86 400 186 8280

Fax +86 53286812210

DAB PUMPS IBERICA S.L.

Calle Verano 18-20-22

28850 - Torrejón de Ardoz - Madrid

Spain

Info.spain@dwtgroup.com

Tel. +34 91 6569545

Fax: + 34 91 6569676

DAB PUMPS B.V.

Twenty One industrial Estate,

16 Purlin Street, Unit B, Warehouse 4

Olifantsfontein - 1666 - South Africa

info.sa@dwtgroup.com

Tel. +27 12 361 3997

info.germany@dwtgroup.com

Tel. +49 2151 82136-0

Fax +49 2151 82136-36

DAB PUMPS HUNGARY KFT.

H-8800

Nagykanizsa, Buda Ernő u.5

Hungary

Tel. +36 93501700

426 South Gippsland Hwy,

Dandenong South VIC 3175 – Australia

info.oceania@dwtgroup.com

Tel. +61 1300 373 677

DAB EVOSTA2 - DAB PUMPS HUNGARY KFT. - 1

WATER•TECHNOLOGY

DAB PUMPS S.p.A.

Via M. Polo, 14 - 35035 Mestrino (PD) - Italy

Tel. +39 049 5125000 - Fax +39 049 5125950

www.dabpumps.com

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DAB

Model : EVOSTA2

Category : Pump