Tripp Lite SUPDMB20KIEC - Inverter

SUPDMB20KIEC - Inverter Tripp Lite - Free user manual and instructions

Find the device manual for free SUPDMB20KIEC Tripp Lite in PDF.

📄 48 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Tripp Lite SUPDMB20KIEC - page 1
View the manual : Français FR English EN Español ES Русский RU
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypeParallel Power Distribution Module (PDU) for UPS 16/20 kVA
ModelSUPDMB20KIEC
BrandTripp Lite
ConfigurationN+1 redundant up to 50% load, full capacity beyond
Input Voltage200-240 V AC
Output Voltage200-240 V AC
Output Receptacles6x IEC-320-C19
Output Circuit Breakers20 A bipolar
Bypass SwitchYes, for maintenance (100 A)
Input ConnectionWired terminal block (L1, L2, ground)
MountingIn rack, on shelves with guide rails
Parallel OperationUp to 2 power modules
Hot SwapYes, for power modules (with bypass)
Operating Temperature0°C to 40°C
Relative Humidity5% to 95% non-condensing (estimated)
CoolingNatural convection
Warranty2 years limited
MaintenanceNo periodic maintenance required

Frequently Asked Questions - SUPDMB20KIEC Tripp Lite

How to install the SUPDMB20KIEC parallel PDU?
Installation should be performed by a qualified electrician. First, mount the power modules on the shelves, then install the guide rails and cable guide. Connect the parallel cables between the PDU and each module, then connect the input power and output receptacles. Finally, power on the power modules one by one.
Can I hot-swap a power module?
Yes, the system allows hot-swapping of power modules. To do so, switch the bypass switch to the BYPASS position to power loads directly from the mains, then remove the faulty module. Caution: in bypass mode, battery protection is disabled.
What is the difference between redundant and non-redundant configuration?
In redundant configuration (load ≤ 50%), the system tolerates a power module failure without interruption. In non-redundant configuration (load > 50%), full capacity is used but there is no fault tolerance. The choice depends on your need for security or power.
What types of output receptacles are available?
The SUPDMB20KIEC model is equipped with 6 IEC-320-C19 receptacles. Other models in the range offer L6-30R, L6-20R receptacles or output terminal blocks. See the manual for variants.
How to perform a manual bypass for maintenance?
For a manual bypass, follow the procedure: 1) Disconnect the communication cables. 2) Identify the module to repair. 3) Turn off the module. 4) Switch the bypass switch to ON to power loads from the mains. 5) Disconnect the batteries and remove the module. Reverse the operation for reassembly.
What is the required input voltage?
The input voltage must be between 200 and 240 V AC (phase-to-phase: L-L). Neutral (L2) and ground are also required. Use appropriate gauge cables according to the table in the manual.
What to do in case of a power module failure?
In redundant mode, the other module takes over automatically. You can then hot-swap the faulty module after switching to bypass. If you are in full capacity mode, the load will be lost if a module fails. It is recommended to plan for redundancy.
Is regular maintenance required for the PDU?
No, the PDU does not require any periodic maintenance. Do not open it, as internal parts are not user-serviceable. Only a qualified technician can work on connections or batteries.
What is the warranty for this product?
Tripp Lite offers a 2-year limited warranty from the date of original purchase. To benefit from the warranty, you must register the product within 10 days of purchase. Extended warranties are available.
Where can I download the full manual?
The user and installation manual is available for free on notice-facile.com in PDF format. You can also request a translation in another language via the form on the site.

User questions about SUPDMB20KIEC Tripp Lite

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Inverter in PDF format for free! Find your manual SUPDMB20KIEC - Tripp Lite and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. SUPDMB20KIEC by Tripp Lite.

USER MANUAL SUPDMB20KIEC Tripp Lite

SmartOnline® 16 & 20kVA UPS with N+1 Configuration Options

Models: SU16KRT, SU16KRT-1TF, SU16KRT8, SU16KRTG, SU16KRTHW, SU20KRT, SU20KRT-1TF, SU20KRT8, SU20KRTG, SU20KRTHW, SU20KRTHWTFASSM

Introduction 2

Important Safety Warnings 3

Mounting 4

Features 6

Connection 8

Manual Bypass Operation 10

Storage & Service 12

Warranty & Product Registration 12

Español 13

Français 25

Русский 37

PROTECT YOUR INVESTMENT!

Register your product for quicker service and ultimate peace of mind. You could also win an ISOBAR6ULTRA surge protector—a \$100 value!

www.tripplite.com/warranty

Introduction

Your Tripp Lite 16/20kVA UPS system includes two 8/10kVA power modules along with a parallel PDU and communications cable that combines the output of the two UPS power modules to directly power your equipment. Your UPS automatically supports N+1 fault tolerance at load levels up to 50% and non-redundant operation at loads greater than 50%. The included parallel PDU with bypass switch also enables hot-swappable replacement of either or both power modules without downtime. For additional configuration assistance, contact Tripp Lite.

10kVA Redundant Configuration (10kVA max load)
Tripp Lite SUPDMB20KIEC - Introduction - 1

flowchart
graph TD
    A["10kVA UPS"] --> B["Parallel PDU"]
    C["10kVA UPS"] --> B
    B --> D["Loads 10kVA and lower"]
    D --> E["Redundant Operation YES"]
    D --> F["Fault-Tolerance YES"]
    D --> G["Hot-Swappable UPS Replacement YES"]
    D --> H["Increased Capacity NO"]
    E --> I["When two UPS systems are loaded to a maximum of 50%, your configuration will receive full redundancy—fault-tolerance with full support for hot-swappable UPS replacement in the case of sudden UPS failure."]

To ensure fault-tolerance, load the two parallel UPS systems to a maximum of 50% of the combined rating for both UPS systems. For example, if you have two 10kVA UPS systems, you will have fault-tolerant operation if the load level remains at 10kVA or lower.

20kVA Non-Redundant Configuration (20kVA max load)
Tripp Lite SUPDMB20KIEC - Introduction - 2

flowchart
graph LR
    A["10kVA UPS"] --> B["Parallel PDU"]
    C["10kVA UPS"] --> B
    B --> D["Loads 10-20kVA"]
    E["Redundant Operation NO"] --> F
    G["Fault-Tolerance NO"] --> H
    I["Hot-Swappable UPS Replacement YES"] --> J
    K["Increased Capacity YES"] --> L

When two UPS systems are loaded to a maximum of 100%, your configuration will receive the full capacity of both UPS systems combined to power larger loads. This configuration does NOT carry redundancy or fault-tolerance options. Hot-swappable UPS replacement is possible if you put the PDU in bypass mode (See "Manual Bypass Operation" Section).

Your can use this configuration to grow your UPS power capacity to 16kVA (when two 8kVA UPS systems are used) or 20kVA (when two 10kVA UPS systems are used). In this configuration, fault-tolerance is NOT available.

Note: Use the included 8/10kVA power module manual for UPS operation and configuration options once you have completed the setup of your 16/20kVA UPS per the installation information on the following pages.

For 16/20KVA UPS Configurations

• Economy-mode operation is not supported
- For best results, connect an equal number of external battery packs to each UPS power module.

SAVE THESE INSTRUCTIONS.

This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite Parallel PDUs. Failure to heed these warnings may affect your warranty.

Location Warnings

• Install your PDU indoors, away from excess moisture or heat, direct sunlight, dust and conductive contaminants.
• Install your PDU in a structurally sound area. Your PDU is heavy; take care when moving and lifting the unit.
- Only operate your PDU at indoor temperatures between 32^ F and 104^ F (between 0^ C and 40^ C). For best results, keep indoor temperatures between 62^ F and 84^ F (between 17^ C and 29^ C).
- Leave adequate space around all sides of the PDU for proper ventilation.
- Do not install the PDU near magnetic storage media, as this may result in data corruption.

Equipment Connection Warnings

  • Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
  • When connecting to a UPS, the UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply.

Maintenance Warnings

- Your PDU does not require routine maintenance. Do not open for any reason. There are no user-serviceable parts inside.

Battery Warnings

  • Service and repair should be done only by trained personnel. During any service work to the UPS, it should be turned off or manually bypassed via the PDU. Note that potentially lethal voltages exist within this unit as long as the battery supply is connected.
  • Do not connect or disconnect battery module(s) while the UPS is operating from the battery supply or when the detachable PDU is not in bypass mode.
  • During "hot-swap" battery module replacement your UPS will be unable to provide battery backup in the event of a blackout.

Mounting

Note: It is recommended that the following mounting instructions only be used in standard rack enclosures and 4-Post Open Frame Racks.

1 It is important to note that in order to accommodate paralleling applications, equipment must be mounted in the following order (see diagram): UPS Power Module 1, UPS Power Module 2, Battery Module 1 and Battery Module 2.

Note: The power module and battery module must be installed in separate shelves.

2 The included plastic pegs A will temporarily support the empty rackmount shelves B while you install the permanent mounting hardware. Insert a peg near the center of the front and rear bracket of each shelf as shown. (Each front bracket has 6 holes and each rear bracket has 3 holes.) The pegs will snap into place.

After installing the pegs, expand each shelf to match the depth of your rack rails. The pegs will fit through the square holes in the rack rails to support the shelves. Refer to the rack unit labels to confirm that the shelves are level in all directions.

Note: The support ledge of each shelf must face inward.

3 Secure the shelves B to the mounting rails permanently using the included screws and cup washers C as shown.

  • For 2U equipment mounting, place 4 screws total at the front and 4 screws total at the back.
  • For 3U equipment mounting, place 6 screws total at the front and 4 screws total at the back.

Tighten all screws before proceeding.

Warning: Do not attempt to install your equipment until you have inserted and tightened the required screws. The plastic pegs will not support the weight of your equipment.

4 Attach mounting ears D to the front mounting holes of your equipment E using the screws provided F. The ears should face forward.

5 Using an assistant, lift your equipment and slide it onto the mounting shelves. Attach your equipment to the rack by passing the screws, nuts and washers (user-provided) G through its mounting ears and into the rack rails.

Tripp Lite SUPDMB20KIEC - Mounting - 1

text_image UPS Power Module 1 UPS Power Module 2 Battery Module 1 Battery Module 2

Tripp Lite SUPDMB20KIEC - Mounting - 2

text_image A B A 2

Tripp Lite SUPDMB20KIEC - Mounting - 3

text_image B C 3 C B C 3

Tripp Lite SUPDMB20KIEC - Mounting - 4

text_image E D F 4

Tripp Lite SUPDMB20KIEC - Mounting - 5

text_image G 5

Mounting

6 With the included screws, attach the 4 placement guide brackets to the power modules (2 per power module).
7 Install wiring bustle using the included screws.
8 Remove the terminal covers by unscrewing the 2 screws and expose the PDU contacts. Save for future use.
9 Connect Battery Module 2 to Power Module 2 before installing PDU.
10 Using the 4 placement pegs as a guide, slide the PDU into the placement guide brackets on the power modules. When lined up properly, the guidance pegs on the rear of the PDU should fit into the clearance holes on the power modules and a tight connection will be made.
Connect Battery Module 1 to Power Module 1. Attach the PDU to the power modules by tightening the 4 screws.

Tripp Lite SUPDMB20KIEC - Mounting - 1

natural_image Technical diagram of server rack with fan and door holders, showing internal structure and ventilation system (no text or labels)

Tripp Lite SUPDMB20KIEC - Mounting - 2

text_image Technical diagram of a mechanical housing with labeled components and dimension lines

Tripp Lite SUPDMB20KIEC - Mounting - 3

natural_image Technical diagram of a mechanical or electrical enclosure with internal components and directional arrows (no text or symbols)

Tripp Lite SUPDMB20KIEC - Mounting - 4

natural_image Technical line drawing of an internal server rack with ventilation ducts and a hand operating a device (no text or symbols)

Tripp Lite SUPDMB20KIEC - Mounting - 5

natural_image Technical diagram of an industrial air conditioning unit with cooling fans and heat exchangers (no text or labels)

Tripp Lite SUPDMB20KIEC - Mounting - 6

natural_image Technical line drawing of an electronic server rack with ventilation ducts and control panel (no text or symbols)

Features

SUPDMB20K
(Included with SU16KRT, SU16KRT-1TF, SU20KRT and SU20KRT-1TF)
SUPDMB20KIEC
(Included with SU16KRTG & SU20KRTG)
SUPDMB20KHW
(Included with SU16KRTHW & SU20KRTHW)
Tripp Lite SUPDMB20KIEC - Features - 1

text_image Diagram of an electronic device rack with labeled components and connectors

Tripp Lite SUPDMB20KIEC - Features - 2

text_image Technical diagram of an electronic device with labeled components including ports, connectors, and internal modules

Tripp Lite SUPDMB20KIEC - Features - 3

text_image 3 14 5 4 6

SUPDMB20K8
(Included with SU16KRT8 & SU20KRT8)
Back Panel
(All models)
Tripp Lite SUPDMB20KIEC - Features - 4

text_image Electrical wiring diagram showing connections between numbered components including switches, relays, and connectors

Tripp Lite SUPDMB20KIEC - Features - 5

text_image 12 13 10 11 13 12 14

Features

1 L6-30R Output Receptacles: Accept direct plug-in connection of L6-30P equipment plugs.
2 Output Breakers (30 Amp): One double-pole circuit breaker provides bypass for the parallel system to the load.
3 Parallel Cable Connectors: For UPS communication in parallel.
4 Maintenance Switch (100 Amp): Controls maintenance to the power module.
5 Utility Input Terminal Block: Use this terminal to connect your power module to utility power or to the transformer module. Unscrew and remove the cover over the block for access.
6 Equipment Output Terminal Block (SUPDMB20KHW only): Use this terminal to connect your power module to your equipment or to the transformer module. Unscrew and remove the cover over the block for access.
7 Output Breakers (20 Amp): One double-pole circuit breaker provides bypass for the parallel system to the load.
8 IEC-320-C19 Output Receptacles: Accept direct plug-in connection of IEC-320-C19 equipment plugs.
9 L6-20R Output Receptacles: Accept direct plug-in connection of locking L6-20P equipment plugs
10 PDU Connection Access Covers: Remove to make connections between the PDU and power modules.
1.1 PDU Input Terminal Block: Use these terminals to connect the PDU to the power module.
PDU Guidance Pegs: Found on the side of the PDU to help guide PDU installation placement. Used in conjunction with PDU placement guide brackets (see Mounting section for more details).
13 PDU Guidance Posts: Found on the back panel of the PDU to help guide PDU installation placement. See “Mounting” section for more details.
14 Wiring Bustle: Must be installed prior to mounting PDU. See Mounting section for more details.

Connection

Hardwiring Cautions

  • Wiring must be done by a qualified electrician.
  • When making wiring connections, observe the cable connection regulations appropriate to your area [e.g. National Electrical Code (NEC) in the U.S.] at all times. Be sure to install an easily accessible disconnect switch in your installation wiring so you may cut off the UPS's AC input during fires and other emergencies. Ensure that cables are fitted with cable sleeves and are secured by connector clamps. Tighten connections with a torque of not less than 24-28 inch-pounds (2.7-3.2 NM).
  • Make sure that your equipment is properly grounded.
  • Using cables of improper size may damage your equipment and cause fire hazards. Choose appropriate cabling and protection circuits to make wiring connections. Ground conductors must be the same size and type as the power conductors used.
    • Refer to National Electrical Code (NEC) guidelines for proper wire gauge and output protection circuit requirements.

Input & Output* Ratings and Recommended Wire Sizing

For N+1 Redundant Operation
Models (Bundles)Input Voltage (L-L/L-N)Max Rated Input CurrentInput Service OCPD**Typical Input Wire SizeMax Rated Output CurrentTypical Output Wire Size
SU16KRT, SU16KRT-1TF, SU16KRTG, SU16KRTHW, SU16KRT8200V-240V 46A50A 10 mm ^2 (#8 AWG)40A 10 mm ^2 (#8 AWG)
SU20KRT, SU20KRT-1TF, SU20KRTG, SU20KRTHW, SU20KRT8200V-240V 56A60A 16 mm ^2 (#6 AWG)50A 10 mm ^2 (#8 AWG)
For Capacity Operation
Models (Bundles)Input Voltage (L-L/L-N)Max Rated Input CurrentInput Service OCPD**Typical Input Wire SizeMax Rated Output CurrentTypical Output Wire Size
SU16KRT, SU16KRT-1TF, SU16KRTG, SU16KRTHW, SU16KRT8200V-240V 92A100A 35 mm ^2 (#3 AWG)80A 25 mm ^2 (#4 AWG)
SU20KRT, SU20KRT-1TF, SU20KRTG, SU20KRTHW, SU20KRT8200V-240V 112A125A 50 mm ^2 (#1 AWG)100A 35 mm ^2 (#3 AWG)

* Input - hardwired; Output - hardwired or receptacles/outlets ** OCPD - Overcurrent protective device

Terminal Wiring Connections

SUPDMB20K, SUPDMB20KIEC & SUPDMB20K8

1 Unscrew the 2 screws to remove the Input Terminal Access covers.

2 Connect the N (L2), Ground and L (L1) input wires according to markings on the connectors as seen in the diagram.
3 After input wire attachments have been made, replace the Input Terminal Access covers.

Tripp Lite SUPDMB20KIEC - SUPDMB20K, SUPDMB20KIEC & SUPDMB20K8 - 1

text_image Technical diagram of an electronic device with labeled components and connection points

Tripp Lite SUPDMB20KIEC - SUPDMB20K, SUPDMB20KIEC & SUPDMB20K8 - 2

text_image N(L2) GROUND L(L1) AC INPUT 200-240/ac 50/60Hz OUTPUT BREAKER 20A

Connection

Terminal Wiring Connections

SUPDMB20KHW

1 Unscrew the 2 screws to remove the Input and Output Terminal Access covers.

2 Connect the 2 sets of N (L2), Ground and L (L1) wires (1 Input, 1 Output) according to markings on the connectors as seen in the diagram below. Be sure to connect one set of wires to the input terminals and the other set to the output terminals.

Parallel Connection

1 Being sure that all switches are off and all units are powered down, connect the 2 parallel cables. Both will originate from the parallel PDU with 1 connecting to the primary power module and the other to the secondary power module. (Refer to the diagram.)

Ensure that each of the parallel cables is securely attached to the PDU and UPS by tightening the thumbscrews on each connection.

2 Connect the input (SUPDMB20K, SUPDMB20KIEC & SUPDMB20K8), and/or hardwired input/output (SUPDMB20KHW) AC power connections located on the PDU. The AC input cord attaches to the facility's AC source while the AC output cord connects to the intended equipment.

Tripp Lite SUPDMB20KIEC - Parallel Connection - 1

natural_image Pure electrical circuit lines without any symbols

Tripp Lite SUPDMB20KIEC - Parallel Connection - 2

text_image Diagram of computer power connector showing fan, socket, and connections with Chinese labels

Tripp Lite SUPDMB20KIEC - Parallel Connection - 3

text_image INPUT OUTPUT 2 INPUT OUTPUT

SUPDMB20K, SUPDMB20KIEC, SUPDMB20K8
SUPDMB20KHW

Connection

3 Power ON the primary power module, being sure that all output breakers (SUPDMB20K, SUPDMB20KIEC & SUPDMB20K8) are OFF.

4 After primary power module start-up is complete, power ON the secondary power module. The UPS systems will self detect the Parallel Mode and show the following screen shots for the master and slave power modules:

When the unit is in Parallel Mode the primary power module will display "Parallel: Master" and the secondary power module will display "Parallel: Slave".

5 Once Parallel Mode is detected, turn ON all output breakers (SUPDMB20K, SUPDMB20KIEC & SUPDMB20K8) on the PDU.

Tripp Lite SUPDMB20KIEC - Connection - 1

text_image OUTPUT BREAKER 30A OFF OUTPUT BREAKER 20A OFF

Tripp Lite SUPDMB20KIEC - Connection - 2

text_image PARALLEL : MASTER 00.00kVA / 000% PARALLEL : SLAVE 00.00kVA / 000%

Tripp Lite SUPDMB20KIEC - Connection - 3

text_image OUTPUT BREAKER 30A ON OUTPUT BREAKER 20A ON

Manual Bypass Operation (for UPS maintenance or replacement)

Tripp Lite SUPDMB20KIEC - Manual Bypass Operation (for UPS maintenance or replacement) - 1

WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not adequately power down the UPS, resulting in the continued risk of death or injury from potential contact with high voltage. The UPS and detachable PDU are extremely heavy. This procedure requires several people to perform. Please read the procedure completely before proceeding. Failure to follow the UPS removal procedure correctly may result in a loss of power to the protected load.

The UPS system includes an independent, detachable PDU with a Maintenance Breaker Switch. This switch allows qualified service personnel to remove the detachable PDU from the UPS for routine maintenance without disrupting power to connected loads. While this switch is set to “BYPASS”, connected equipment will receive unfiltered AC mains power. However, equipment will not receive battery power in the event of a blackout.

UPS Removal

STEP 1. Disable PowerAlert and disconnect the SNMP, serial or USB communication cables from the communication ports on the UPS. Do NOT remove the parallel cable at this point. A disconnection of the cable before the power module is properly shut down can result in multiple error messages depending on your configuration.
STEP 2. Before proceeding, determine your maintenance status (i.e. which UPS system requires maintenance and whether you are in Redundancy or Power Mode per the Output/Bypass Breaker Operation chart on page 9).

Manual Bypass Operation (for UPS maintenance or replacement)

STEP 3. Part A: When the output is coming from the Primary UPS and the Secondary UPS needs repair, press the Secondary UPS system's OFF button, if the UPS is powered, until you hear a beep and see a "STANDBY MODE" message shown in the LCD display.

Part B: When the output is coming from the Secondary UPS and the Primary UPS needs repair, press the Primary UPS system's OFF button, if the UPS is powered, until you hear a beep and see a "STANDBY MODE" message shown in the LCD display.

Part C: When both power modules show output is in Bypass, set the Maintenance Breaker Switch to the ON position before servicing.

STEP 4. Disconnect any external battery module(s) from the UPS power module being serviced.

STEP 5. At the rear of the UPS being serviced, remove the 2 screws that secure the PDU to the power module. If both power modules are in need of service, remove all 4 screws.

STEP 6. Remove the rackmounting hardware from the front panel of the UPS. Using an assistant at each end, carefully pull the power module away from the PDU, being careful not to disconnect the parallel cable. Once the power module is pulled from the PDU and powers down, disconnect the parallel cable from the power module.

Tripp Lite SUPDMB20KIEC - Manual Bypass Operation (for UPS maintenance or replacement) - 1

text_image MAINTENANCE SWITCH 100A OUTPUT BREAKER 3C

Tripp Lite SUPDMB20KIEC - Manual Bypass Operation (for UPS maintenance or replacement) - 2

natural_image Diagram of server rack with connected equipment and a directional arrow indicating flow or movement (no text or symbols present)

The UPS power/battery module is now safely powered down and it can be detached from the PDU to perform maintenance/replacement.

During this process, ensure that each section is properly supported after they are separated. If the sections are detached in a rackmount application, be sure that each section remains adequately supported by the UPS system's rackmount rails. If the sections are detached in a tower application, be sure that the PDU is supported by the UPS system's tower feet. Adjust the tower feet so they are as close together as possible.

Tripp Lite SUPDMB20KIEC - Manual Bypass Operation (for UPS maintenance or replacement) - 3

text_image WARNING! High Voltage! Risk of electrical shock! Warning: Use extreme caution when handling the PDU. Do not allow the contacts to touch any surface.

To reattach the PDU, reverse the process listed above.

Output/Bypass Breaker Operation

Output Status (Normal Operation) Parallel PDU Output Breakers Maintenance Bypass Breaker
Output coming from both UPS systems. ON OFF
Output Status (Redundancy Mode) Parallel PDU Output Breakers Maintenance Bypass Breaker
Output coming from Primary UPS. Secondary UPS needs repair. (Refer to Step 3, Part A.)ON OFF
Output coming from Secondary UPS. Primary UPS needs repair. (Refer to Step 3, Part B.)ON OFF
Output Status (Power Mode) Parallel PDU Output Breakers Maintenance Bypass Breaker
Primary and Secondary UPS output coming from Bypass. (Refer to Step 3, Part C.)ON ON

Note: Units will operate in Redundancy Mode up to 8 or 10kVA and switch to Power Mode at loads greater than 8 or 10kVA.

Storage & Service

Storage

Before storing your PDU, be sure all connections have been disconnected and all breakers are turned OFF. Also replace any input or output access covers so as not to damage any contacts.

Service

Your Tripp Lite product is covered by the warranty described in this manual. A variety of Extended Warranty and On-Site Service Programs are also available from Tripp Lite. For more information on service, visit www.triplite.com/support. Before returning your product for service, follow these steps:

  1. Review the installation and operation procedures in this manual to insure that the service problem does not originate from a misreading of the instructions.
  2. If the problem continues, do not contact or return the product to the dealer. Instead, visit www.tripplite.com/support.
  3. If the problem requires service, visit www.triplite.com/support and click the Product Returns link. From here you can request a Returned Material Authorization (RMA) number, which is required for service. This simple on-line form will ask for your unit's model and serial numbers, along with other general purchaser information. The RMA number, along with shipping instructions will be emailed to you. Any damages (direct, indirect, special or consequential) to the product incurred during shipment to Tripp Lite or an authorized Tripp Lite service center is not covered under warranty. Products shipped to Tripp Lite or an authorized Tripp Lite service center must have transportation charges prepaid. Mark the RMA number on the outside of the package. If the product is within its warranty period, enclose a copy of your sales receipt. Return the product for service using an insured carrier to the address given to you when you request the RMA.

Warranty & Product Registration

2-Year Limited Warranty

TRIPP LITE warrants its products to be free from defects in materials and workmanship for a period of two years from the date of initial purchase. To obtain service under this warranty, you must call TRIPP LITE or an authorized TRIPP LITE service center. Products must be returned to TRIPP LITE or an authorized TRIPP LITE service center with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of date and place of purchase. This warranty does not apply to equipment which has been damaged by accident, negligence or misapplication or has been altered or modified in any way. This warranty applies only to the original purchaser who must have properly registered the product within 10 days of purchase.

The warranties of all TRIPP LITE surge suppressors are null and void if they have been connected to the output of any UPS system. The warranties of all TRIPP LITE UPS Systems are null and void if a surge suppressor has been connected to its output receptacles.

EXCEPT AS PROVIDED HEREIN, TRIPP LITE MAKES NO WARRANTIES, EXPRESS OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation or exclusion of implied warranties; therefore, the aforesaid limitation(s) or exclusion(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL TRIPP LITE BE LIABLE FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Specifically, TRIPP LITE is not liable for any costs, such as lost profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data, costs of substitutes, claims by third parties, or otherwise.

PRODUCT REGISTRATION

Visit www.tripplite.com/warranty today to register your new Tripp Lite product. You'll be automatically entered into a drawing for a chance to win a FREE Tripp Lite product!* * No purchase necessary. Void where prohibited. Some restrictions apply. See website for details.

FCC Part 68 Notice (United States Only)

If your Modem/Fax Protection causes harm to the telephone network, the telephone company may temporarily discontinue your service. If possible, they will notify you in advance. If advance notice isn't practical, you will be notified as soon as possible. You will be advised of your right to file a complaint with the FCC. Your telephone company may make changes in its facilities, equipment, operations or procedures that could affect the proper operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain uninterrupted service. If you experience trouble with this equipment's Modem/Fax Protection, please call Tripp Lite Technical Support at (773) 869-1234 for repair/warranty information. The telephone company may ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the equipment is not malfunctioning. There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service provided by the telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation commission for information.)

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marking name or model number of the product.

WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 1

Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:

  • Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
  • Send the new equipment back for recycling when this ultimately becomes waste

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice.

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 2

text_image TRIPP·LITE

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 3

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

natural_image Technical diagram of server rack with fan and ventilation system, showing heat transfer paths (no text or labels)

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 4

text_image Technical diagram of a mechanical device with labeled components and dimension lines

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 5

natural_image Technical diagram of a mechanical or electrical enclosure with internal components and directional arrows (no text or symbols)

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 6

natural_image Technical line drawing of an internal server rack with a cable connector inserted (no text or symbols)

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 7

natural_image Technical diagram of an industrial server rack with cooling fans and heat exchangers (no text or labels)

Tripp Lite SUPDMB20KIEC - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 8

natural_image Technical line drawing of a server rack with ventilation ducts and connected ports (no text or symbols)

Características

text_image Diagram of an electronic device rack with labeled components and connectors
text_image Technical diagram of an electronic device with labeled components including ports, connectors, and internal modules
text_image Electrical wiring diagram showing connections between numbered components including switches, relays, and connectors
text_image Technical diagram of an electronic device showing labeled components and connections, including connectors, switches, and modules.

Tripp Lite SUPDMB20KIEC - Características - 1

text_image N(L2) TIERRA L(L1) AC INPUT 200-240V/ac 50/60Hz OUTPUT BREAKER 20A Z L

Conexión

natural_image Pure electrical circuit lines without any symbols

Tripp Lite SUPDMB20KIEC - Conexión - 1

text_image Technical diagram of an electronic device rear panel with labeled ports, connectors, and control buttons for ventilation or power management.

Tripp Lite SUPDMB20KIEC - Conexión - 2

natural_image Diagram of server rack with connected modules and ventilation ducts, no readable text or symbols present

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

natural_image Technical diagram of server rack with fan and door holders, showing internal structure and ventilation system (no text or labels)

Tripp Lite SUPDMB20KIEC - Conexión - 3

text_image Technical diagram of a mechanical housing with labeled components and dimension lines

Tripp Lite SUPDMB20KIEC - Conexión - 4

natural_image Technical diagram of a mechanical or electrical enclosure with internal components and directional arrows (no text or symbols)

Tripp Lite SUPDMB20KIEC - Conexión - 5

natural_image Technical line drawing of an internal server rack with ventilation ducts and a hand operating a device (no text or symbols)

Tripp Lite SUPDMB20KIEC - Conexión - 6

natural_image Technical diagram of an industrial air conditioning unit with cooling fans and heat exchangers (no text or labels)

Tripp Lite SUPDMB20KIEC - Conexión - 7

natural_image Technical line drawing of an electronic server rack with ventilation ducts and connectors (no text or symbols)

Caractéristiques

text_image Diagram of a server rack with labeled components including indicator lights, ports, and connectors
text_image Technical diagram of an electronic device with labeled components including ports, connectors, and internal modules
text_image Technical diagram of a device panel with numbered components and labeled connectors
text_image Technical diagram of an electronic device showing labeled components and connections, including connectors, switches, and modules.

Tripp Lite SUPDMB20KIEC - Caractéristiques - 1

text_image N(L2) TERRE L(L1) OUTPUT BREAKER 20A AC INPUT 200-240V/ac 50/60Hz Z L

Raccordement

Connections des borniers

SUPDMB20KHW

natural_image Pure electrical circuit lines without any symbols

Tripp Lite SUPDMB20KIEC - SUPDMB20KHW - 1

text_image N(L2) TERRE L(L1) N(L2) TERRE L(L1)

Tripp Lite SUPDMB20KIEC - SUPDMB20KHW - 2

text_image Technical diagram of an electronic device rear panel with labeled ports, connectors, and control buttons for ventilation or power management.

Tripp Lite SUPDMB20KIEC - SUPDMB20KHW - 3

text_image ENTRÉE SORTIE 2 ENTRÉE SORTIE

SUPDMB20K, SUPDMB20KIEC, SUPDMB20K8
SUPDMB20KHW

Conexión

natural_image Diagram of server rack with connected equipment and a directional arrow indicating flow or movement (no text or symbols present)

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

natural_image Technical diagram of server rack with fan and ventilation system, showing heat transfer paths (no text or labels)

Tripp Lite SUPDMB20KIEC - Conexión - 1

text_image Technical diagram of a mechanical housing or enclosure with labeled components and dimension lines

Tripp Lite SUPDMB20KIEC - Conexión - 2

text_image Technical diagram showing two mechanical or electrical components with labeled parts and directional arrows indicating flow or movement.

Tripp Lite SUPDMB20KIEC - Conexión - 3

natural_image Technical line drawing of a server rack with internal components and a connector (no text or symbols)

Tripp Lite SUPDMB20KIEC - Conexión - 4

natural_image Technical diagram of an industrial server rack with heat exchangers and cooling unit (no text or labels)

Tripp Lite SUPDMB20KIEC - Conexión - 5

natural_image Technical line drawing of a server rack with connected ports and ventilation ducts (no text or symbols)

Свойства

SUPDMB20K

text_image Technical diagram of an electronic device rack with numbered components and labeled connectors

SUPDMB20KIEC

text_image Technical diagram of an electronic device with labeled components and numbered parts

SUPDMB20KHW

text_image Technical diagram of a multi-pin electrical connector with numbered parts and labeled connectors

Задняя панель

(для всех моделей)

Tripp Lite SUPDMB20KIEC - Задняя панель - 1

flowchart
graph TD
    A["Terminal 10"] --> B["Terminal 11"]
    A --> C["Terminal 12"]
    A --> D["Terminal 13"]
    A --> E["Terminal 14"]
    B --> F["Terminal 13"]
    C --> G["Terminal 12"]
    D --> H["Terminal 13"]
    E --> I["Terminal 14"]

Свойства

text_image Technical diagram showing labeled components of an electronic device with numbered parts and dashed alignment lines

Tripp Lite SUPDMB20KIEC - Свойства - 1

text_image N(L2) ЗАЗЕМЛЕНИЕ L(L1) AC INPUT 200-240/ac 50/60+/- N MAINTENAN BREAKER 10 OUTPUT BREAKER 20A

Подключение

natural_image Pure electrical circuit lines without any symbols

Tripp Lite SUPDMB20KIEC - Подключение - 1

text_image N(L2) ЗАЗЕМЛЕНИЕ L(L1) N(L2) ЗАЗЕМЛЕНИЕ L(L1)

Tripp Lite SUPDMB20KIEC - Подключение - 2

text_image Technical diagram showing computer hardware components with labeled connectors and ports, including fan, buttons, and connectors.

Tripp Lite SUPDMB20KIEC - Подключение - 3

text_image BHOX BHXOY BHOX BHXOY

SUPDMB20K, SUPDMB20KIEC, SUPDMB20K8
SUPDMB20KHW

Подключение

natural_image Diagram of server rack with connected modules and ventilation ducts, no readable text or symbols present

1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Tripp Lite

Model : SUPDMB20KIEC

Category : Inverter