AC2729 - Electronic board IFM - Free user manual and instructions
Find the device manual for free AC2729 IFM in PDF.
Questions des utilisateurs sur AC2729 IFM
0 question sur cet appareil. Repondez a celles que vous connaissez ou posez la votre.
Poser une nouvelle question sur cet appareil
Download the instructions for your Electronic board in PDF format for free! Find your manual AC2729 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. AC2729 by IFM.
USER MANUAL AC2729 IFM
9 10 10Function and features The AS-i PCB detects up to two unsafe switching states, e.g. 1 or 2- channel mechanical contacts. Mounting Install the AS-i PCB in a protected location (e. g. control cabinet, hous- ing). The appropriate housing must have a protection rating of at least IP 54. Carry out a set-up test after installation of the AS-i PCB. Electrical connection Connect the AS-i PCB to two mechanical NO or NC contacts. In doing so, the two outer mechanical pins are connected to one side of the contacts (I1-2 / I2-2). The other side of the contacts is connected to the two black wires (I1-1 / I2-1). Insulate unused open wires. The connection wires of the AS-i PCB must not be extended. ENGLISH
AS-i Fault LED I-1 LED I-2Wiring A+: AS-i + A-: AS-i - I1-1/I1-2 I2-1/I2-2: switching input mechanical contact I1 / I2 LEDs 1: switching status indication inputs I1, I2 LEDs 2: AS-i, FAULT X1-X2: external LED output Data bits Addressing When mounted and wired the PCB can be addressed via the address- ing unit AC1144 using the cable (E70032). Assign a free address between 1A/1B and 31A/31B. At the factory the address is set to 0. If a slave with the extended addressing mode is used in combination with a master of the first generation (version 2.0), the parameter P3 must be 1 and the output bit D3 must be 0*. The output bit D3 and the parameter bit P3 must not be used.
Default setting If a slave with the extended addressing mode is used in combination with a master of the first generation (version 2.0), an address between 1A and 31A must be assigned to this slave.
- LEDs 1 yellow: inputs switched (I1, I2)
- LED 2 green: voltage supply ok (PWR)
- LED 2 red lights: AS-i communication error, slave does not participate in the “normal“ exchange of data, e.g. slave address 0 (FAULT)
- External LED output (X1-X2): output O-1 (The output LED can be set as a static or dynamic output by the host system) Limited voltage The device shall be supplied from an isolating transformer having a secondary Listed fuse rated 5.0 A. Technical data You can download the data sheet from our website at www.ifm.com. ENGLISH
EasyManual