Product Type Infrared motion detector (PIR) for ceiling
Brand Esylux
Model PD-C 180i/16 UC
Detection angle 180°
Maximum range 16 m (tangential)
Power supply 12-24 V AC/DC (universal)
Power consumption < 0.5 W (standby), < 1 W (active)
Output type Relay contact NO/NC (potential-free)
Maximum load 2000 W (resistive), 1000 VA (inductive)
Time setting From 10 s to 15 min (graduated)
Brightness threshold setting From 2 to 2000 lux (integrated twilight)
Sensitivity setting Yes, by potentiometer (10-100%)
Protection rating IP20 (indoor use)
Operating temperature -20 °C to +50 °C
Recommended mounting height 2.5 m to 6 m
Dimensions (diameter × height) 110 mm × 65 mm
Weight 100 g
Color White
Housing material Polycarbonate (PC)
Permissible cable cross-section Up to 2.5 mm²
Maintenance and cleaning Clean with a soft, dry cloth. Do not use abrasive products.
Safety Electrical installation reserved for a qualified professional. Disconnect power before any intervention.
Spare parts and repairability No spare parts available. The device does not contain user-repairable components.
General information Compliant with CE standards. Indoor use only. Do not expose to moisture.

Frequently Asked Questions - PD-C 180i/16 UC Esylux

How to install the PD-C 180i/16 UC detector?
Attach the detector to the ceiling using the provided bracket. Connect the power supply 12-24 V AC/DC and the relay (NO/NC) according to your wiring diagram. Adjust the time delay, sensitivity, and brightness threshold before closing.
What is the maximum detection range?
The range is 16 meters in tangential motion (crossing the detection zone). The radial range (towards the detector) is shorter.
Can I adjust the detector sensitivity?
Yes, turn the SENS potentiometer to adjust sensitivity from 10% to 100%. High sensitivity detects small movements.
How to set the time delay?
Use the TIME potentiometer to select a time delay between 10 seconds and 15 minutes. The output stays on for this duration after the last detection.
What does the brightness threshold (LUX) mean?
The LUX setting allows the output to activate only if ambient brightness is below the selected value (from 2 to 2000 lux). Turn fully towards the sun for 24-hour operation.
The detector does not activate, what to do?
Check the power supply (12-24 V AC/DC). Ensure the LUX threshold is high enough (if daylight mode) and that sensitivity is not too low. Also check the relay wiring.
The detector stays on all the time, why?
This may be due to a too long time delay, too high sensitivity (detecting false heat sources), or improper orientation (obstructed field of view). Reduce the time delay or sensitivity.
What is the recommended mounting height?
For optimal detection, mount the detector at a height of 2.5 to 6 meters. The higher the height, the wider the covered area, but the lower the sensitivity to small movements.
Can I use this detector outdoors?
No, the protection rating is IP20, which is intended for indoor use only. For outdoors, choose a suitable model (IP44 minimum).
How to clean the detector?
Use a soft, dry cloth. Never use chemical or abrasive products that could damage the housing or lens. Disconnect power before cleaning.

User questions about PD-C 180i/16 UC Esylux

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Alarm system in PDF format for free! Find your manual PD-C 180i/16 UC - Esylux and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PD-C 180i/16 UC by Esylux.

USER MANUAL PD-C 180i/16 UC Esylux

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Esylux

Model : PD-C 180i/16 UC

Category : Alarm system