ENTES EPM-04C-DIN - Measuring equipment

EPM-04C-DIN - Measuring equipment ENTES - Free user manual and instructions

Find the device manual for free EPM-04C-DIN ENTES in PDF.

📄 4 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice ENTES EPM-04C-DIN - page 1
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type DIN-Rail Mounted Power Meter
Model EPM-04C-DIN
Brand ENTES
Dimensions Approx. 72 x 90 x 65 mm (4 modules wide)
Weight Approx. 200 g
Power Supply Self-powered from measurement inputs (L1-L2) or auxiliary 230 V AC
Measured Parameters Voltage (V), Current (A), Active Power (W), Reactive Power (VAR), Apparent Power (VA), Power Factor, Frequency, Active Energy (kWh), Reactive Energy (kVARh)
Input Voltage Range 3x230/400 V AC (L-N / L-L)
Input Current Range 1 A or 5 A via external CT (option)
Accuracy Class Class 1 (active energy) per IEC 61557-12
Display Backlit LCD, 4 lines
Communication Modbus RTU via RS485
Operating Temperature -10°C to +55°C
Mounting DIN rail (EN 60715)
Protection Degree IP20 (front face), IP10 (terminals)
Safety Standards IEC 61010-1, IEC 61557-12
Maintenance No user-serviceable parts; wipe with dry cloth only
Spare Parts / Repairability Not individually repairable; replace unit if faulty
Warranty 2 years (standard)

Frequently Asked Questions - EPM-04C-DIN ENTES

How do I install the EPM-04C-DIN?
Mount the device on a DIN rail (EN 60715). Connect voltage inputs (L1, L2, L3, N) and current inputs via external CTs (1A or 5A). Ensure the power supply is connected as per the wiring diagram in the manual.
What is the accuracy of the power meter?
The EPM-04C-DIN has an accuracy class of 1 for active energy according to IEC 61557-12, meaning a maximum error of ±1%.
Can I read the energy consumption remotely?
Yes, the device supports Modbus RTU communication via RS485, allowing remote reading of all measured parameters.
What is the maximum current it can measure?
The meter measures current via external current transformers (CTs) with a secondary rating of 1A or 5A. The primary current depends on the CT ratio chosen.
Does the meter require an external power supply?
It can be self-powered from the voltage measurement inputs (L1-L2) or optionally powered by an auxiliary 230 V AC supply. Refer to the manual for details.
How do I reset the energy counters?
Press and hold the 'SET' button for 3 seconds to access the reset menu. Use the arrow keys to select 'Reset' and confirm. Partial and total counters can be reset separately.
What Modbus settings are available?
The default baud rate is 9600 bps, with 8 data bits, no parity, 1 stop bit. The device ID can be set from 1 to 247 via the front panel.
Is the meter suitable for single-phase systems?
Yes, it can be used in single-phase (1P2W) or three-phase (3P4W, 3P3W) configurations by selecting the appropriate wiring mode in the settings.
What does the LCD display show?
The backlit LCD shows multiple pages: voltage per phase, current per phase, power values, power factor, frequency, and energy counters. Scroll using the arrow keys.
How do I clean the device?
Disconnect power before cleaning. Use a soft, dry cloth to wipe the front panel. Do not use solvents or abrasive cleaners.

User questions about EPM-04C-DIN ENTES

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Measuring equipment in PDF format for free! Find your manual EPM-04C-DIN - ENTES and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EPM-04C-DIN by ENTES.

USER MANUAL EPM-04C-DIN ENTES

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : ENTES

Model : EPM-04C-DIN

Category : Measuring equipment