ENTES EPC-12 - Measuring equipment

EPC-12 - Measuring equipment ENTES - Free user manual and instructions

Find the device manual for free EPC-12 ENTES in PDF.

📄 29 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice ENTES EPC-12 - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Measuring Equipment
Model EPC-12
Brand ENTES
Dimensions (W x H x D) 96 x 96 x 100 mm
Weight 0.3 kg
Power Supply 100-240 VAC, 50/60 Hz
Display LCD with backlight
Measurement Functions Voltage, Current, Power, Frequency, Power Factor
Accuracy ±0.5% of reading
Communication Interface RS-485 Modbus
Operating Temperature -10°C to +55°C
Storage Temperature -20°C to +70°C
Protection Rating IP40 (front panel)
Safety Standards IEC 61010-1
Maintenance Clean with dry cloth; no user-serviceable parts inside
Spare Parts Replacement fuses, terminal covers
Repairability Repairs only by authorized service center
General Information Indoor use only, altitude up to 2000 m

Frequently Asked Questions - EPC-12 ENTES

How do I connect the power supply to the EPC-12?
Connect the device to a 100-240 VAC, 50/60 Hz power source using the provided power cord. Ensure the voltage matches your local supply.
What measurements can the EPC-12 perform?
It measures voltage, current, power (active, reactive, apparent), frequency, and power factor.
How do I set the communication parameters for Modbus?
Access the setup menu via the front panel buttons. Set the Modbus address, baud rate, and parity as required by your system.
Can the EPC-12 be used outdoors?
No, the device is designed for indoor use only. Its IP40 front panel protection is not suitable for outdoor environments.
How do I replace a fuse?
Disconnect the power supply. Open the fuse holder on the rear panel and replace the blown fuse with one of the same rating (e.g., 1A, 250V). Only use fuses specified in the manual.
What does the backlight on the display indicate?
The backlight can be set to always on, off, or timed. It helps reading the display in low light conditions. Configure it in the display settings.
How often should I calibrate the EPC-12?
ENTES recommends recalibration every 2 years to maintain accuracy. Contact an authorized service center for calibration.
Why is my EPC-12 showing incorrect readings?
Check the wiring connections, ensure the voltage and current inputs are correct, and verify the configuration settings. If the problem persists, the device may need recalibration.
Can I daisy-chain multiple EPC-12 units on Modbus?
Yes, each unit should have a unique Modbus address. Connect them in a daisy-chain topology using RS-485 cables with proper termination.
Where can I find the full user manual?
The manual is available for free download on notice-facile.com in PDF format. Search for ENTES EPC-12.

User questions about EPC-12 ENTES

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Measuring equipment in PDF format for free! Find your manual EPC-12 - ENTES and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EPC-12 by ENTES.

USER MANUAL EPC-12 ENTES

Ignoring the instructions in this manual may result in serious injuries or death.

  • Disconnect all power supply inputs before connecting the device.
  • Do not remove the front panel when device is connected to the mains.
  • Do not clean the device with solvents alike. Only clean with dry cloth.
    – Verify correct terminal connections before energizing the device.
  • Contact your authorized reseller in case problems occur with your device.
    – Device is only for rail mounting.
  • An F Type Fuse must be used and its current limit must be 1 A.

ENTES EPC-12 - 1

No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of disregard the above precautions.

SECURITY

ENTES EPC-12 - SECURITY - 1

Read the User Manual entirely before using the device.

ENTES EPC-12 - SECURITY - 2

Warnings

  • Connect a button or a circuit breaker between mains and the device.
  • Connected button or circuit breaker must be in close proximity of the device.
  • Connected button or circuit breaker must be marked to indicate that it disconnects the device from the mains.
    Battery life is 5 years at +45°C storing temperature. It is between 8 and 10 years for typical applications. The battery can only be replaced by ENTES A.S. The battery is used to keep the internal real time clock in case of power outages.
    – During power outages, the device will not count incoming pulses.

Standards Applied to the Device

EN 61010-1, EN 62053-31, EN 62054-21

WARRANTY

The device has a 2 (two) year warranty. In case of a fault, the device must only be serviced by manufacturing company. Otherwise, the warranty of the device will be void.

ENTES EPC-12 - WARRANTY - 1

Index

  1. INTRODUCTION.... 4

1.1. APPLICATIONS.... 4

1.2.GENERAL FEATURES....4

1.3. FRONT PANEL 5

1.4. HARDWARE FEATURES.... 6

  1. UTILIZATION OF DEVICE 7

2.1. SETTINGS THAT ARE CHANGED FROM THE DEVICE..... 7

2.1.1. RS-485 (Information for communicating with a PC) MENU.....10

2.1.2. PASSWORD MENU....13

2.1.3. ESCAPE MENU....17

2.2. SETTINGS THAT ARE CHANGED FROM THE PC 18

2.2.1.RS-485 SETTINGS....18

2.2.2. GENERAL SETTINGS....19

2.2.3. COUNTER SETTINGS 19

2.2.4. DATE - TIME SETTINGS 22

2.2.5. TARIFF SETTINGS 23

2.2.6. DEVICE INFORMATION 32

2.2.7. TOTAL COUNTER INDEXES 32

2.2.8. COUNTER INDEXES WITH TARIFF 36

2.2.9 DEVICE STATUS....46

2.3. MEMORY - LOGGING FEATURES 48

  1. EPC-12 CONFIGURATION (INTERFACE) SOFTWARE 48

  2. DIMENSIONS.... 49

4.1. CONNECTION DIAGRAM....50

  1. TECHNICAL DATA.... 55

1. INTRODUCTION

1.1. APPLICATIONS

EPC-12, is a microprocessor-based device that can separately collect incoming pulses from various meters (electricity, water, gas, etc.) connected to its 12 inputs according to 8 tariffs based on time, record them in real time with its internal clock chip and flash memory and transmit data via RS-485 line with Modbus RTU protocol.

1.2. GENERAL FEATURES

Device Features

1) Total counter indexes of 12 pulse inputs with tariff and unit information, date and time information and alarm states can be displayed on the 2x12 characters LCD screen automatically with intervals of 5 seconds or manually by pressing up and down buttons.
2) Enabling the backlight for 20 seconds by pressing any button to provide easy reading on the screen.
3) Data communication with a PC via RS-485 output,
4) Storing the contents of each pulse input with tariff information in 1-60 minutes intervals on the 2 MB
permanent memory of the device with date and time information,
5) Preventing changes to settings by unauthorized users by defining a 4-digit user password.

EPC-12 Configuration Software Features

1) Transferring stored parameters to a PC and reviewing them,
2) Entering different multiplier and denominator coefficients for each pulse input,
3) Defining different units for each pulse input.
4) Changing date and time settings,
5) Changing communication settings,

6) Activating password protection and defining a new password.

7) Changing the log save period,

8) Activating DST(Daylight Savings Time),

9) Holiday, saturday, sunday and week day tariffs can be programmed (6 for each)*

10) Monitoring counters with tariff and total counters,

11) Resetting counters with tariff and total counters,

12) Assigning index to counters with tariff when Counter Set from device menu is activated,

13) Monitoring date and time, tariff, next record number to be written and alarm states at that time,

* A tariff between 1 and 8 can be selected but a selected tariff (for example T1) can be selected more than one time as long as its time range doesn't overlap with another tariff.

1.3. FRONT PANEL

C01 T1 kWh 000001234567 EPC-12 Pulse Concentrator 1 2 3 4 5 6 7 8 9 10 11 12 ↑ Set ↓

1) Up and Down Button: It is used to display total counter indexes of 12 pulse inputs, date and time information and alarm states on the monitoring screen. While in the menu screen, they are used to browse between menu items and to increase/decrease a numerical value.
2) Set button: It is used to enter the menu screen when pressed for 3 seconds. It is used to enter a sub-menu or upper-menu, to exit from a menu, to switch the indicator to the right while entering a numerical value and to save the committed change.
3) Count (C): It indicates which pulse input's total counter index is displayed at that moment.
4) Tariff Information (T): It indicates which tariff is active at that moment. If there is a tariff overlap or the clock is faulty, pulses at that moment are saved to T1 tariff and a cautionary flashing will occur on the tariff display. In that case, the user will be informed of the problem's cause in the Alarm section of display (For Example: Wrong Time, No Tariff, etc.). Additionally, the problem can be monitored by using the Alarm section on the Configuration Software.
5) Unit : It indicates the unit of the index counted by pulse input displayed at that moment. 6) Total Counter Index : It is the total counter index of the pulse input displayed at that moment. It can have a maximum value of 34.359.738.360 (5x2word). Total counters consist of the summation of 8 counters with tariff. Each counter with tariff has a capacity of 2 word which means it can have a maximum value of 4.294.967.295. Each counter with tariff that fills its 2 word capacity is reset to zero automatically and continues to count.
7) Pulse LEDs: It is for indicating an incoming pulse to the associated pulse input by flashing. 8) 2x12 characters LCD screen.
9) Backlight

1.4. HARDWARE FEATURES

1) Pulse and Corn Inputs (12 pin Pulse Inputs, 4 pin Corn Input)
2) Supply Input (2 pin)
3) RS-485 terminals (4 pin)

2. UTILIZATION OF DEVICE

For security reasons, only a portion of the settings are permitted to be changed directly from the device. Therefore, device settings will be explained under two headlines as "Changed from the Device" and "Changed via Modbus protocol using PC".

2.1. Settings that are changed from the device

After you connected the device as described in the connection diagram, energize the device. In order for your measurements and applications to be accurate, make the necessary adjustments by using the menus.

Monitoring Screen

The display changes automatically in 5 second intervals on the monitoring screen. You can also browse between displays by using up and down buttons. Total counter indexes, tariffs and unit information of all counters from 1st to 12th, clock, date and alarm information is displayed on this screen and after alarm display, it shows the 1st counter again.

ENTES EPC-12 - Monitoring Screen - 1

flowchart
graph TD
    A["Count 1 Tariff Unit Total Counter Indexes"] --> B["0"]
    C["Count 2 Tariff Unit Total Counter Indexes"] --> D["0"]
    E["Count 3 Tariff Unit Total Counter Indexes"] --> F["0"]
    G["Count 4 Tariff Unit Total Counter Indexes"] --> H["0"]
    I["Count 5 Tariff Unit Total Counter Indexes"] --> J["0↑↓0"]
    K["Count 6 Tariff Unit Total Counter Indexes"] --> L["0↑↓0"]
    M["Count 7 Tariff Unit Total Counter Indexes"] --> N["0↑↓0"]
    O["Count 8 Tariff Unit Total Counter Indexes"] --> P["0↑↓0"]
    Q["Count 9 Tariff Unit Total Counter Indexes"] --> R["0↑↓0"]
    S["Date Day/month/Year"] --> T["Time: four minutes/second"]
    T --> U["Count 12 Tariff Unit Total Counter Indexes"]
    U --> V["Count 11 Tariff Unit Total Counter Indexes"]
    V --> W["Count 10 Tariff Unit Total Counter Indexes"]
    X["Alarm!"] --> Y["0↑↓0"]

ENTES EPC-12 - Monitoring Screen - 2

ENTES EPC-12 - Monitoring Screen - 3

There are 3 main menus on the device. These menus are RS-485. PASSWORD and ESCAPE. When SET button is pressed for 3 seconds on the monitoring screen, main menu is accessed. Sub-menus are accessed while on any main menu by pressing set button. If the password protection feature is active, a password* will be asked before entering the main menu when set button is pressed for 3 seconds. * Factory setting for password is 1234. Enter your password with Up, Down and Set buttons. Finally, main menu will appear when you press the Set button. By using Up and Down buttons, you can browse main menu options. The device does not get blocked when the password is entered incorrectly. Committed changes are saved to device memory and do not get lost in case of a power outage. If none of the buttons are pressed for 20 seconds while on the menu, monitoring screen is displayed. Any committed change will be discarded.

ENTES EPC-12 - Main Menus - 1

In order for a change that you made in the menu to take effect, you must approve the Save query. Otherwise, committed changes will not take effect.

ENTES EPC-12 - Main Menus - 2

flowchart
graph TD
    A["Monitoring Screen"] --> B["RS-483"]
    B --> C["PASSWORD ESCAPE"]
    C --> D["Press Release"]
    D --> A
    style A fill:#90EE90,stroke:#333
    style B fill:#FFB6C1,stroke:#333
    style C fill:#FFA500,stroke:#333
    style D fill:#FFD700,stroke:#333

2.1.1. RS-485 (Information for communicating with a PC) Menu

The device has MODBUS RTU communication protocol. All measured values can be transferred to a PC by using the EPC-12 configuration software. Also, you can adjust all the settings that you can adjust directly from the device except "Counter Set" by using this configuration software on a PC. In order for the communication with a PC to occur; Baud Rate, Parity, Address values must be entered on the device

ENTES EPC-12 - RS-485 (Information for communicating with a PC) Menu - 1

flowchart
graph LR
    A["RS-485"] --> B["Baud Rate 9600"]
    B --> C["Parity No"]
    C --> D["Address 001"]
    D --> E["Counter Set Disable"]
    E --> F["Back"]
    F --> B
    B --> G["0"]
    D --> H["0"]
    E --> I["0"]
    F --> J["0"]

Selecting Baud Rate value

You can select Baud Rate value as 1200, 2400, 4800, 9600, 19200 or 38400 bps.

ENTES EPC-12 - Selecting Baud Rate value - 1

flowchart
graph LR
    A["Baud Rate 9800"] --> B["Baud Rate 19200"]
    B --> C["Baud Rate 38400"]
    C --> D["Baud Rate 5500"]
    D --> E["Baud Rate 4800"]
    E --> F["Baud Rate 2400"]
    F --> G["Baud Rate 19200"]
    B -->|0| H["0"]
    C -->|0| I["0"]
    D -->|0| J["0"]
    E -->|0| K["0"]
    F -->|0| L["0"]

Selecting Parity value

You can select Parity option as No, Odd or Even.

ENTES EPC-12 - Selecting Parity value - 1

flowchart
graph LR
    A["Parity No"] --> B["Parity No"]
    B --> C["Parity Odd"]
    B --> D["Parity Even"]
    C --> E["Parity Even"]
    D --> E

Entering Address Information

Address information can be entered between 1 and 247.

ENTES EPC-12 - Entering Address Information - 1

flowchart
graph LR
    A["Address 001"] --> B["Address 01"]
    B --> C["Address 247"]
    C --> D["Address 247"]
    B -.->|D 0| C
    C -.->|B| D

Counter Set Setting (Activating index writing to counters with tariff)

If Counter Set menu is set as Disable, no other value than 0 is allowed to be written to counters with tariffs with the configuration software. However; if Counter Set menu is set as Enable, you can write index between 0 and 4.294.967.295 (2 word) to counters with tariff.

ENTES EPC-12 - Counter Set Setting (Activating index writing to counters with tariff) - 1

flowchart
graph LR
    A["Counter Set Disable"] --> B["Counter Set Disable"]
    B --> C["Counter Set Enable"]
    C --> D["Counter Set Enable"]
    D -->|Feedback Loop| B
    B -->|Feedback Loop| C

User password is defined and activated in this menu. In order to prevent changes to device settings by unauthorized users, you must define a 4-digit password in this menu and activate it.

ENTES EPC-12 - Counter Set Setting (Activating index writing to counters with tariff) - 2

flowchart
graph TD
    A["PASSWORD Enable Charge Back"] --> B["0"]
    B --> C["0"]
    C --> D["0"]
    D --> E["0"]
    E --> F["0"]
    F --> G["0"]
    G --> H["0"]
    H --> I["0"]
    I --> J["0"]
    J --> K["0"]
    K --> L["0"]
    L --> M["0"]
    M --> N["0"]
    N --> O["0"]
    O --> P["0"]
    P --> Q["0"]
    Q --> R["0"]
    R --> S["0"]
    S --> T["0"]
    T --> U["0"]
    U --> V["0"]
    V --> W["0"]
    W --> X["0"]
    X --> Y["0"]
    Y --> Z["0"]
    Z --> A

Enable (Activating user password protection)

Password protection is activated or deactivated in this menu.

ENTES EPC-12 - Enable (Activating user password protection) - 1

flowchart
graph TD
    A["Enable"] --> B["ENTER PASS 000"]
    B --> C["ENTER PASS 000"]
    C --> D{If the right user password is entered}
    D -->|Yes| E["Enable No"]
    D -->|No| F["Enable Yes"]
    E --> G{If the wrong user password is entered}
    G -->|Yes| H["INVALID PASS!"]
    G -->|No| I["End"]
    H --> J["Enable"]
    I --> K["Enable"]
    J --> L["Enable"]
    K --> M["Enable"]
    L --> N["Enable"]
    M --> O["Enable"]
    N --> P["Enable"]
    O --> Q["Enable"]
    P --> R["Enable"]
    Q --> S["Enable"]
    R --> T["Enable"]
    S --> U["Enable"]
    T --> V["Enable"]
    U --> W["Enable"]
    V --> X["Enable"]
    W --> Y["Enable"]
    X --> Z["Enable"]
    Y --> AA["Enable"]
    Z --> AB["Enable"]

14

Change (Changing user password)
User password is changed in this menu.
ENTES EPC-12 - Enable (Activating user password protection) - 2

flowchart
graph TD
    A["Change"] --> B["Old Pass 0000"]
    B --> C["Old Pass 0000"]
    C --> D{If the right user password is entered}
    D -->|Yes| E["New Pass 0000"]
    E --> F["New Pass 0000"]
    F --> G{enter the new password again}
    G -->|Yes| H["Confirm Pass 0000"]
    H --> I["Confirm Pass 0000"]
    I --> J{If the right user password is entered}
    J -->|No| K["INVALID PASS1"]
    K --> L["Invalid PASS1"]
    L --> A
    style A fill:#99ccff,stroke:#333
    style B fill:#99ccff,stroke:#333
    style C fill:#99ccff,stroke:#333
    style D fill:#99ccff,stroke:#333
    style E fill:#99ccff,stroke:#333
    style F fill:#99ccff,stroke:#333
    style G fill:#99ccff,stroke:#333
    style H fill:#99ccff,stroke:#333
    style I fill:#99ccff,stroke:#333
    style J fill:#99ccff,stroke:#333
    style K fill:#99ccff,stroke:#333
    style L fill:#99ccff,stroke:#333
    style_M["Change"] --> N["End"]
    style N --> O["Final Pass"]
    style O --> P["Final Pass"]

ENTES EPC-12 - Enable (Activating user password protection) - 3

ENTES EPC-12 - Enable (Activating user password protection) - 4

2.1.3. ESCAPE Menu

It is used to exit from the main menu. An approval is asked to save any changes that has been made in the main menus. If no change has been made, monitoring menu is displayed directly.

ENTES EPC-12 - ESCAPE Menu - 1

flowchart
graph TD
    A["ESCAPE"] --> B["Save No"]
    B --> C{Committed change is not saved!}
    B --> D{Committed change is saved!}
    C --> E["Monitoring Screen"]
    D --> F["Save Yes"]
    F --> G["Saved!"]
    G --> B

2.2. Settings that are changed from the PC

2.2.1. RS-485 Settings

You can change RS-485 settings that you can change from the device such as Baud Rate, Parity and Address by using the configuration software. When you change EPC-12 RS-485 settings, communication between device and PC will be disconnected. You can establish communications by setting the RS-485 Settings of the device and PC the same and you can continue to adjust settings from the PC.

RS-485 SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
327688000BAUD RATER/W0-5unsigned int
327698001PARITYR/W0-2unsigned int
327708002COMMUNICATION ADDRESSR/W1-247unsigned int

BAUD RATE: PARITY:

0 = 1200 bps 0 = No

1 = 2400 bps 1 = Odd

2 = 4800 bps 2 = Even

3 = 9600 bps

4 = 19200 bps

5 = 38400 bps

19

2.2.2. General Settings

Under general settings, you can do password defining (changing) and password activating/deactivating operations which you can do from the device too. Additionally, you can define how often (in minutes) you want to receive log records and you can activate/deactivate DST (Daylight Savings Time) option. When you activate DST, the clock of the device is moved forward 1 hour from 3:00 AM to 4:00 AM on the last sunday of March and is moved backward 1 hour from 4:00 AM to 3:00 AM on the last sunday of October.

GENERAL SETTINGSADDRESSADDRESS (HEX)REGISTERR/W RANGEFORMAT
327718003PASSWORDR/W0-9999unsigned int
327728004PASSWORD ACTIVATIONR/W0-1unsigned int
327738005LOG RECORD PERIODR/W1-60unsigned int
327748006DAYLIGHT SAVINGS TIMER/W0-1unsigned int

PASSWORD ACTIVATION: DAYLIGHT SAVINGS TIME:

0 = Inactive 0 = Inactive

1 = Active 1 = Active

2.2.3. Counter Settings

Under counter settings, you can specify multiplier and denominator coefficients separately for each pulse input and you can define the unit of the pulse that you measure. For example, if a multiplier of 5, a denominator of 2 and a unit of Wh is entered for 1st pulse input and 4 pulses arrive at 1st pulse input, the measurement of the device will be 4x5:2 = 10 Wh.

COUNTER SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
327758007IN1 MULTIPLIERR/W0-65535 unsigned int
327768008IN2 MULTIPLIER 0-65535R/Wunsigned int
327778009IN3 MULTIPLIERR/W0-65535unsigned int
32778800A R/W unsigned intIN4 MULTIPLIER0-65535
32779800BIN5 MULTIPLIERR/W0-65535 unsigned int
32780800CIN6 MULTIPLIER 0-65535R/Wunsigned int
32781800DIN7 MULTIPLIERR/W0-65535unsigned int
32782800E R/W unsigned intIN8 MULTIPLIER0-65535
32783800FIN9 MULTIPLIERR/W0-65535 unsigned int
327848010IN10 MULTIPLIER 0-65535R/Wunsigned int
327858011IN11 MULTIPLIERR/W0-65535unsigned int
327868012 R/W unsigned intIN12 MULTIPLIER0-65535
32787 8013 R/W unsigned intIN1 DENOMINATOR1-65535
327888014IN2 DENOMINATORR/W1-65535 unsigned int
327898015IN3 DENOMINATORR/W1-65535unsigned int
327908016IN4 DENOMINATORR/W1-65535unsigned int
327918017 R/W unsigned intIN5 DENOMINATOR1-65535
UNIT:
0 = No Unit9 = iVArh18 = kcal28 = yd ^2 37 = t46 = in
1 = Wh10 = CVAr19 = BTU29 = gal38 = GTN47 = ft
2 = VAh11 = imkWh20 = TEP30 = bol39 = lo48 = yd
3 = VArh12 = ExkWh21 = erg31 = gi40 = oz49 = ml
4 = kWh13 = kVAh23 = m€32 = pk41 = qtr50 = nm
5 = kVAh14 = CKVAh24 = mi33 = pt42 = mm51 = s
6 = kVAh15 = J25 = cl34 = qt43 = cm52 = min
7 = ImWh16 = kJ26 = In€35 = g44 = m53 = h
8 = ExWh17 = cal27 = fi ^2 36 = kg45 = km54 = d

2.2.4. Date-Time Settings

While EPC-12 date and time is adjusted, date and time control is done automatically. Thereby, the user is not permitted to enter a nonexisting date and time. For example, February 30 2012, February 29 2013, April 31, 24:00:00, 23:60:60, etc. are not permitted to be entered. Since the day of the week will be automatically set when you entered the date, the user is not permitted to adjust the day of the week.

DATE-TIME SETTINGSADDRESSADDRESS (HEX)REGISTERR/W RANGEFORMAT
32811802BDAYR/W1-31unsigned int
32812802CMONTHR/W1-12unsigned int
32813802DYEARR/W0-99unsigned int
32814802EHOURR/W0-23unsigned int
32815802FMINUTER/W0-59unsigned int
328168030SECONDR/W0-59unsigned int
328178031DAY OF THE WEEKR0-6unsigned int

DAY OF THE WEEK:

0 = Sunday
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday

2.2.5. Tariff Settings

Holiday, saturday, sunday and week day tariffs can be programmed (8 for each) under tariff settings. You can name your set tariffs as numbers from 1 to 8. A selected tariff (for example T1) can be selected more than one time as long as its time range doesn't overlap with another tariff. When you set the tariff as 0, it means that tariff range is deactivated. In this case, the device saves the incoming pulses to T1 tariff. If all tariffs are set to 0 and deactivated to make the device operate without any tariffs, T1 tariff indexes will be equal to total counter indexes.

Tariffs set as holiday have priority over tariffs set as saturday, sunday and work day tariffs. For example; if the 5th day of June is set as holiday tariff at T7, the holiday tariff will be activated on the 5th day of June. Any other tariffs set as saturday, sunday or week day in this time slot will be deactivated for that day.

If there are overlapping tariffs or if the device lost its hour settings, T1 tariff will be active for security reasons. Then, the tariff indicator on the device display will start to flash and the cause of the problem will be reported to the user on the ALARM screen. Additionally, the user can see the cause of the problem on the PC from address 249.

Holiday Tariff Settings

Starting year, starting month, starting day, starting hour and ending year, ending month, ending day, ending hour values and finally, the number of the tariff that will be active in that time interval are entered in that order under holiday tariff settings.

Since starting year/month, starting day/hour, ending year/month, ending day/hour settings requires the user to enter two information into the same address; the information have to be entered by using the following mathematical formula.

STARTING YEAR / MONTH: Year (between 0 - 99), Month (between 1 - 12) can be entered.* Value to be written = Year x 256 + Month

STARTING DAY / HOUR: Day (between 1 - 31), Hour (between 0 - 23) can be entered.* Value to be written = Day x 256 + Hour

ENDING YEAR / MONTH: Year (between 0 - 99), Month (between 1 - 12) can be entered.* Value to be entered = Year x 256 + Month

ENDING DAY / HOUR: Day (between 1 - 31), Hour (between 0 - 24) can be entered.* Value to be entered = Day x 256 + Hour

* The date you adjust must really exist. Date control is done in tariff settings just like in date-time settings. For example, it is not permitted to enter a date like February 30 because there is no such date. Additionally, since your tariff settings will not function if your starting dates are bigger than your ending dates or they are each the same these kinds of adjustments are also automatically not permitted.

HOLIDAY TARIFF SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
328488050STARTING YEAR / MONTHR/W 0-99 I 1-12 unsigned int
328498051STARTING DAY / HOUR 1-31 I 6:30unsigned int
328508052ENDING YEAR / MONTHR/W0-99 I 1-12unsigned int
328518053 R/Wunsigned intENDING DAY / HOUR1-31 I 0-24
328528054TARIFFR/W 0-8 unsigned int
328538055STARTING YEAR / MONTHR/W0-99 I 1-12unsigned int
328548056STARTING DAY / HOURR/W1-31 I 0-23unsigned int
32855 8057R/W unsignedENDING YEAR / MONTH0-99 I 1-12
328568058ENDING DAY / HOURR/W unsignedid4
328578059TARIFFR/W0-8unsigned int
32858805ASTARTING YEAR / MONTHR/W0-99 I 1-12unsigned int
32859805B R/WUNSTANDING DAY / HOUR1-31 I 0-23
32860 805C R/W unsignedENDING YEAR / MONTH0-99 I 1-12
32861805DENDING DAY / HOURR/W unsignedin4
32862805FTARIFFR/W0-8unsigned int
32863805FSTARTING YEAR / MONTHR/W0-99 I 1-12unsigned int
328648060 R/WUNSTANDING DAY / HOUR1-31 I 0-23
32865 8061 R/W unsignedENDING YEAR / MONTH0-99 I 1-12
32866 8062 R/W unsignedENDING DAY / HOUR1-31 I 0-24
32867 8063 R/W unsigned intTARIFF0-8

25

HOLIDAY TARIFF SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
328688064STARTING YEAR / MONTHR/W unsigned int0-99 1-12
328698065STARTING DAY / HOURR/W1-31 1-0-23unsigned int
328708066ENDING YEAR / MONTHR/W0-99 1-1-12unsigned int
328718067 R/Wunsigned inENDING DAY / HOUR1-31 1-0-24
328728068TARIFFR/W unsigned int
328738069STARTING YEAR / MONTHR/W0-99 1-1-12unsigned int
32874806ASTARTING DAY / HOURR/W1-31 1-0-23unsigned int
32875806BENDING YEAR / MONTHR/W unsigned int
32876806CENDING DAY / HOURR/W unsigned int
32877806DTARIFFR/W0-8unsigned int
32878806ESTARTING YEAR / MONTHR/W0-99 1-1-12unsigned int
32879806F R/WSTARTING DAY / HOUR1-31 1-0-23
328808070 R/WENDING YEAR / MONTH0-99 1-1-12
328818071ENDING DAY / HOURR/W unsigned int
328828072TARIFFR/W0-8unsigned int
328838073STARTING YEAR / MONTHR/W0-99 1-1-12unsigned int
328848074 R/Wunsigned DAY / HOUR1-31 1-0-23
328858075 R/Wunsigned YEAR / MONTH0-99 1-1-12
328868076 R/Wunsigned DAY / HOUR1-31 1-0-24
328878077TARIFFR/W0-8unsigned int

26

Saturday – Sunday – Week Day Tariff Settings

Additional to the holiday tariff setting, the device also has tariff settings that repeat each week. A tariff set as a Saturday tariff will be active every Saturday. Same goes for Sunday and Week Day tariffs. Starting year, starting month, starting day, starting hour and ending year, ending month, ending day, ending hour values and finally, the number of the tariff that will be active in that time interval are entered in that order under Saturday, Sunday and Week Day tariff settings. Since starting hour/minute, ending hour/minute settings require the user to enter two information into the same address; the information have to be entered by using the following mathematical formula.

STARTING HOUR / MINUTE: Hour (between 0 - 23), Minute (between 0 - 59) can be entered. Value to be written = Hour x 256 + Minute

ENDING HOUR / MINUTE: Hour (between 0 - 24), Minute (between 0 - 59) can be entered. Value to be written = Hour x 256 + Minute

27

SATURDAY TARIFF SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
328888078STARTING HOUR / MINUTER/W0-2310-59unsigned int
328898079ENDING HOUR / MINUTER/W0-2410-59unsigned int
32890807ATARIFFR/W0-8unsigned int
32891807B R/WSTARTING HOUR / MINUTE0-2310-59
32892807CENDING HOUR / MINUTER/W0-2410-60
32893807DTARIFFR/W0-8unsigned int
32894807ESTARTING HOUR / MINUTER/W0-2310-59unsigned int
32895807FENDING HOUR / MINUTER/W0-2410-60
328968080TARIFFR/W0-2410-60
328978081STARTING HOUR / MINUTER/W0-2310-59unsigned int
328988082ENDING HOUR / MINUTER/W0-2410-59unsigned int
328998083 R/WUNSIGNED TARIFF0-8
329008084 R/WUNSIGNED HOUR / MINUTE0-2310-59
329018085ENDING HOUR / MINUTER/W0-2410-60
329028086TARIFFR/W0-8unsigned int
329038087STARTING HOUR / MINUTER/W0-2310-59unsigned int
329048088 R/WUNSIGNED HOUR / MINUTE0-2410-59
329058089 R/WUNSIGNED TARIFF0-8
32906808A R/WUNSIGNED HOUR / MINUTE0-2310-59
32907808BENDING HOUR / MINUTER/W0-2410-59unsigned int

28

SATURDAY TARIFF SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
32908808CTARIFFR/W unsigned int
32909808DSTARTING HOUR / MINUTER/W0-23 10-59unsigned int
32910808EENDING HOUR / MINUTER/W0-24 10-59unsigned int
32911808FTARIFFR/W unsigned int
SUNDAY TARIFF SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
329128090STARTING HOUR / MINUTER/W unsigned int
329138091ENDING HOUR / MINUTER/W0-24 10-59unsigned int
329148092TARIFFR/W0-8unsigned int
329158093 R/WSTARTING HOUR / MINUTE0-23 10-59
329168094ENDING HOUR / MINUTER/W unsigned int
329178095TARIFFR/W0-8unsigned int
329188096STARTING HOUR / MINUTER/W0-23 10-59unsigned int
329198097ENDING HOUR / MINUTER/W unsigned int
329208098TARIFFR/W unsigned int
329218099STARTING HOUR / MINUTER/W0-23 10-59unsigned int
32922809AENDING HOUR / MINUTER/W0-24 10-59unsigned int
32923809B R/WUNSIGNED TARIFF0-8
32924809C R/WUNSIGNED HOUR / MINUTE0-23 10-59
SUNDAY TARIFF SETTINGSADDRESSADDRESS(HEX)REGISTER R/W RANGEFORMAT
32925809DENDING HOUR / MINUTER/W unsigned int 0-59
32926809ETARIFFR/WC-8unsigned int
32927809FSTARTING HOUR / MINUTER/W0-23 10-59unsigned int
3292880A0 R/WUNSIGED HOUR / MINUTE0-24 10-59
3292980A1 R/WUNSIGED IN TARIFFC-8
3293080A2STARTING HOUR / MINUTER/W unsigned int 0-59
3293180A3ENDING HOUR / MINUTER/W0-24 10-59unsigned int
3293280A4 R/WUNSIGED IN TARIFFC-8
3293380A5 R/WUNSIGED IN HOUR / MINUTE0-23 10-59
3293480A6 R/WENDING HOUR / MINUTE0-24 10-59
3293580A7TARIFFR/W unsigned int
WEEKDAY TARIFF SETTINGSADDRESSADDRESS(HEX)REGISTER R/W RANGEFORMAT
3293680A8STARTING HOUR / MINUTER/W unsigned int 0-59
3293780A9ENDING HOUR / MINUTER/W0-24 10-59unsigned int
3293880AATARIFFR/W0-8unsigned int
3293980AB R/WSTARTING HOUR / MINUTE0-23 10-59
3294080AC R/WENDING HOUR / MINUTE0-24 10-59
3294180ADTARIFFR/W unsigned int
WEEKDAY TARIFF SETTINGSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
3294280AESTARTING HOUR / MINUTER/W0-23 10-59unsigned int
3294380AFENDING HOUR / MINUTER/W0-24 10-59unsigned int
3294480B0TARIFFR/W0-8unsigned int
3294580B1STARTING HOUR / MINUTER/W unsigned int
3294680B2ENDING HOUR / MINUTER/W unsigned int
3294780B3TARIFFR/W0-8unsigned int
3294880B4STARTING HOUR / MINUTER/W0-23 10-59unsigned int
3294980B5ENDING HOUR / MINUTER/W unsigned int
3295080B6TARIFFR/W unsigned int
3295180B7STARTING HOUR / MINUTER/W0-23 10-59unsigned int
3295280B8ENDING HOUR / MINUTER/W0-24 10-59unsigned int
3295380B9TARIFFR/W unsigned int
3295480BASTARTING HOUR / MINUTER/W unsigned int
3295580BBENDING HOUR / MINUTER/W unsigned int
3295680BCTARIFFR/W0-8unsigned int
3295780BDSTARTING HOUR / MINUTER/W0-23 10-59unsigned int
3295880BEENDING HOUR / MINUTER/W unsigned int
3295980BFTARIFFR/W unsigned int

2.2.6. Device Information

These are information that can only be read and not changed by the user. Device ID/version and serial number is assigned to the device internally during manufacturing. This way, you can report your device from the device information addresses and request help when there is a problem with your device.

DEVICE INFORMATIONADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
60416EC00DEVICE IDR unsigned X#D201
60417EC01DEVICE ID / VERSION NOR0X0111 - 0X01FFunsigned int
60418EC02SERIAL NOR0X0000 - 0XFFFFunsigned int
60419EC03 R unsigned int0X0001 - 0XFFFF

2.2.7. Total Counter Indexes

Total counter indexes state the summation of 8 counter indexes with tariff. No other value than 0 is allowed to be written to total counters. When total counters are reset, all counter indexes with tariff in relevance to the pulse input will be reset. The index value that you will write to counters with tariff will change the total counter indexes as much.

TOTAL COUNTER INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
00IN1 TOTAL COUNTERR/W unsignedlong long int
11
22
33
44IN2 TOTAL COUNTERR/W0unsigned long long int
55
66
77
88IN3 TOTAL COUNTERR/W0unsigned long long int
99
10A
11B
12CIN4 TOTAL COUNTERR/W0unsigned long long int
13D
14E
15F
TOTAL COUNTER INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
1610IN5 TOTAL COUNTERR/W unsignedlong long int
1711
1812
1913
2014IN6 TOTAL COUNTERR/W0unsigned long long int
2115
2216
2317
2418IN7 TOTAL COUNTERR/W0unsigned long long int
2519
261A
2719
281CIN8 TOTAL COUNTERR/W0unsigned long long int
291D
301E
311F

35

2.2.8. Counter Indexes with Tariff

In order to change index values, "Counter Set" menu on the EPC-12 device has to set as "Enable".

COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
4830IN1 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
49310-65535unsigned int
5032IN2 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
51330-65535unsigned int
5234IN3 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
53350-65535unsigned int
5436IN4 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
55370-65535unsigned int
5638IN5 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
57390-65535unsigned int
583AIN6 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
593B0-65535unsigned int
603CIN7 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
613D0-65535unsigned int
623EIN8 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
633F0-65535unsigned int

36

COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
6440IN9 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
65410-65535unsigned int
6642IN10 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
67430-65535unsigned int
6844IN11 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
69450-65535unsigned int
7046IN12 T1 COUNTER WITH TARIFFR/W0-65535unsigned int
71470-65535unsigned int
7248IN1 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
73490-65535unsigned int
744AIN2 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
754B0-65535unsigned int
764CIN3 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
774D0-65535unsigned int
784EIN4 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
794F0-65535unsigned int
8050IN5 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
81510-65535unsigned int
COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
8252IN6 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
83530-65535unsigned int
8454IN7 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
85550-65535unsigned int
8656IN8 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
87570-65535unsigned int
8858IN9 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
89590-65535unsigned int
905AIN10 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
915B0-65535unsigned int
925CIN11 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
935D0-65535unsigned int
945EIN12 T2 COUNTER WITH TARIFFR/W0-65535unsigned int
955F0-65535unsigned int
9660IN1 T3 COUNTER WITH TARIFFR/W0-65535unsigned int
97610-65535unsigned int
9862IN2 T3 COUNTER WITH TARIFFR/W0-65535unsigned int
99630-65535unsigned int
COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
11876IN12 T3 COUNTER WITH TARIFFR/W0-65535unsigned int
119770-65535unsigned int
12078IN1 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
121790-65535unsigned int
1227AIN2 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
1237B0-65535unsigned int
1247CIN3 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
1257D0-65535unsigned int
1087EIN4 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
1277F0-65535unsigned int
12880IN5 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
129810-65535unsigned int
13082IN6 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
131830-65535unsigned int
13284IN7 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
133850-65535unsigned int
13486IN8 T4 COUNTER WITH TARIFFR/W0-65535unsigned int
135870-65535unsigned int
COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
1549AIN8 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
1559B0-65535unsigned int
1569CIN7 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
1579D0-65535unsigned int
1589EIN8 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
1599F0-65535unsigned int
160A0IN9 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
161A10-65535unsigned int
162A2IN10 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
163A30-65535unsigned int
164A4IN11 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
165A50-65535unsigned int
166A6IN12 T5 COUNTER WITH TARIFFR/W0-65535unsigned int
167A70-65535unsigned int
168A8IN1 T6 COUNTER WITH TARIFFR/W0-65535unsigned int
169A90-65535unsigned int
170AAIN2 T6 COUNTER WITH TARIFFR/W0-65535unsigned int
171AB0-65535unsigned int
COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
190BEIN12 T6 COUNTER WITH TARIFFR/W0-65535unsigned int
191BF0-65535unsigned int
192C0IN1 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
193C10-65535unsigned int
194C2IN2 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
195C30-65535unsigned int
196C4IN3 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
197C50-65535unsigned int
198C6IN4 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
199C70-65535unsigned int
200C8IN5 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
201C90-65535unsigned int
202CAIN6 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
203CB0-65535unsigned int
204CCIN7 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
205CD0-65535unsigned int
206CEIN8 T7 COUNTER WITH TARIFFR/W0-65535unsigned int
207CF0-65535unsigned int
COUNTER WITH TARIFF INDEXESADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
226D0IN6 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
227D10-65535unsigned int
228D2IN7 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
229D30-65535unsigned int
230D4IN8 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
231D50-65535unsigned int
232D6IN9 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
233D70-65535unsigned int
234D8IN10 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
235D90-65535unsigned int
236DAIN11 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
237DB0-65535unsigned int
238DCIN12 T8 COUNTER WITH TARIFFR/W0-65535unsigned int
239DD0-65535unsigned int

2.2.9. Device Status

Hour, date and tariff at that moment; the next record number to be written and alarm states are reported to the user under device state menu.

In how many minutes the next record number will increase by one is determined by the set log record period setting of the device.

DEVICE STATUSADDRESSADDRESS (HEX)REGISTER R/W RANGEFORMAT
240F0DAYR 1-31 unsigned int
241F1MONTH 1-12Runsigned int
242F2YEARR0-99unsigned int
243F3 R unsigned int HOUR0-23
244F4MINUTER 0-59 unsigned int
245F5SECOND 0-59Runsigned int
246F6DAY OF THE WEEKR0-6unsigned int
247F7 R unsigned int TARIFF1-8
248F8RECORD NO TO BE WRITTEN NEXTR 0-16383 unsigned int
249F9Runsigned int AL

ALARM
0 = Normal
1 = Wrong Time
2 = Wrong Date
3 = Wrong Date
4 - No Tariff
4 = NO Tariff
5 = No Tariff
6 = No Tariff
7 = No Tariff

2.3. Memory - Logging Features :

The 2MB flash memory stores data with programmable intervals between 1 and 60 minutes. This memory consists of 32 sectors. Each sector contains 65536 byte. Each record occupies 128 byte sized blocks on the flash memory. Each sector holds 512 block records. 16384 block savings can be accomplished on the 2MB flash memory. When the flash memory becomes full, 0th sector is cleaned and records start to be saved from the start to the flash memory. During data logging before the last record of a sector (511st record, including 0) is saved, the next sector is completely deleted. The user can monitor which record the device will log from address 248 on Modbus.

3. EPC-12 CONFIGURATION (INTERFACE) SOFTWARE

A User Interface Software has been prepared for settings that are done from a PC. The purpose of this software is an easier and faster way when changing the settings which has to be done from a ARM OFC. You can access the interface software and its manual from the included CD. Details on how to use the interface software are available in the Interface Software User Manual.

4.DIMENSIONS
61.6 44.9 38 49 25.5 31.5 38.9 90

71,2 06

Dimensions are in millimeters.

4.1. CONNECTION DIAGRAM
Un ~ C* 1 2 3 4 5 6 7 C* + - S6 + - °C 12 11 10 9 8 °C Gnd B A TR RS-485

* Common Lead (Using any one of them will suffice.) When a counter with NPN output is connected to EPC-12, collector lead is connected to In (+) input and emitter lead is connected to Com (-) input. When a counter with PNP output is connected to EPC-12, emitter lead is connected to In (+) input and collector lead is connected to Com (-) input.

ENTES EPC-12 - EPC-12 CONFIGURATION (INTERFACE) SOFTWARE - 4

flowchart
graph LR
    A["Max. 1200 mt."] --> B["PS-485 / 232 or RS-485 / USB CONVERTER"]
    B --> C["PC"]
    D["EPC-12 -31"] --> E["..."]
    F["EPC-12 -2"] --> G["..."]
    H["EPC-12 -1"] --> I["..."]
    J["EPC-12 -31"] --> K["..."]
    L["EPC-12 -2"] --> M["..."]
    N["EPC-12 -1"] --> O["..."]
    P["PC"] --> Q["RS-485 / 232 or RS-485 / USB CONVERTER"]

51

BY USING A REPEATER, 247 DEVICES CAN BE CONNECTED TO THE SAME LINE.
ENTES EPC-12 - EPC-12 CONFIGURATION (INTERFACE) SOFTWARE - 5

flowchart
graph TD
    A["TRB A9A0"] --> B["Max. 1200 M"]
    C["EPC-12 247"] --> D["Max. 1200 M"]
    E["REFTEATOR"] --> F["Max. 1200 M"]
    G["EPC-12 31"] --> H["Max. 1200 M"]
    I["EPC-12 1EPC-12"] --> J["Max. 1200 M"]
    K["RS-485/USB CONVERTER"] --> L["PC"]
    L --> M["3 A GND"]
    M --> N["Ground"]

52

ENTES EPC-12 - EPC-12 CONFIGURATION (INTERFACE) SOFTWARE - 6

flowchart
graph TD
    A["GEM-10"] --> B["RS-48S"]
    B --> C["EPC-12"]
    B --> D["EPC-12"]
    B --> E["EPC-12"]
    B --> F["EPC-12"]
    C --> G["ES-32L"]
    D --> H["ES-32L"]
    E --> I["ES-32L"]
    F --> J["ES-32L"]
    G --> K["Water meter"]
    H --> L["Water meter"]
    I --> M["Water meter"]
    J --> N["Water meter"]
    K --> O["Gas meter"]
    L --> P["Gas meter"]
    M --> Q["Gas meter"]
    N --> R["Gas meter"]
    O --> S["Gas meter"]
    P --> T["Gas meter"]
    Q --> U["Gas meter"]
    R --> V["Max. 12"]
    S --> W["Max. 12"]

⑤3

ENTES EPC-12 - EPC-12 CONFIGURATION (INTERFACE) SOFTWARE - 7

flowchart
graph TD
    A["GEM-10"] --> B["RS-485"]
    B --> C["EPC-12"]
    B --> D["EPC-12"]
    B --> E["EPC-12"]
    C --> F["ES-32L"]
    D --> G["ES-32L"]
    E --> H["ES-32L"]
    F --> I["Water meter"]
    G --> J["Water meter"]
    H --> K["Gas meter"]
    I --> L["Gas meter"]
    J --> M["Gas meter"]
    K --> N["Gas meter"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#cfc,stroke:#333
    style E fill:#cfc,stroke:#333
    style F fill:#fcc,stroke:#333
    style G fill:#fcc,stroke:#333
    style H fill:#fcc,stroke:#333
    style I fill:#cff,stroke:#333
    style J fill:#cff,stroke:#333
    style K fill:#cff,stroke:#333
    style L fill:#cff,stroke:#333

⑤4

5. TECHNICAL DATA

Operating Voltage (Un) = Please see device labels.

Operating Frequency (I) = 45-65Hz

Supply Input Power Consumption = <5VA

Communication (Insulated) = MODBUS RTU (RS485)

Baud Rate = 1200 - 38400 bps

Adress = 1 - 247

Parity = No. Odd. Even

Stop Bit = 1

Max Communication Distance = 1200 m (MODBUS/RS-485 side, using signal amplifier)

Pulse Inputs (12 pcs, Insulated) = Complies with EN 62053-31.

Minimum Pulse Duration = 10 ms

Minimum Time Between Pulses = 30 ms

Minimum pulse period = 60 ms

Maximum Pulse Frequency = 16 Hz

Maximum Contact Resistance = 800 Ohm

Pulse Voltage = 10-12V

Trigger Edge = Rising and Pulse width control

Distance between meters

to be connected to EPC-12 = 1000 m

Total Counter Capacity = 34.359.738.360

Ambient Temperature = -25...+55 C ^c .

Storage Temperature = -25...+70 C

Humidity = %95

Display = Backlight 2x12 LCD

Dimensions = DIN4 (PK27)

Device Protection Class = Double Insulated Front panel = IR40

Front panel = IP40 Terminals = IP20

Enclosure Material = Nonflammable

Installation = Rail mount

Cable Thickness for Voltage Connection = max. 2.5 mm ^2

Cable Thickness for Pulse Connection = max. 2.5 mm²

Cable Thickness for RS-485 Connection = CAT 5 cable

Weight = 456.4 gr

Internal Memory = 2MB

Factory Default Settings

Baud Rate = 9600

Parity = No

Address = 1 Counter Set Div

Counter Set = Disable PASSWORD = 1234

PASSWORD = 1204 PASSWORD Enable = No

PASSWORD Enable = No Log Save Period = 30 min

Daylight Savings Time application = Active

Multiplier = 1

Denominator = 1

Unit = None

Tariff = None

Counters = 0

Alarm = Normal

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : ENTES

Model : EPC-12

Category : Measuring equipment