BGMPI 090 - Air conditioner BEKO - Free user manual and instructions

Find the device manual for free BGMPI 090 BEKO in PDF.

BEKO BGMPI 090 - Air conditioner
📄 124 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice BEKO BGMPI 090 - page 5
View the manual : English EN Italiano IT
Pick your language and provide your email: we'll send you a specifically translated version.
Brand Beko
Model BGMPI 090
Product Type Split Air Conditioner (Indoor Unit)
Cooling Capacity 9000 BTU/h
Heating Capacity 9000 BTU/h (Heat Pump)
Energy Efficiency Class A++ (Cooling)
Power Supply 220-240 V ~ 50 Hz
Refrigerant R32
Dimensions (Indoor Unit) 80 x 28 x 20 cm (WxHxD)
Weight (Indoor Unit) 9 kg
Noise Level (Indoor) 22-35 dB(A)
Airflow Rate 450 m³/h
Remote Control Included
Timer Function 24-hour timer
Sleep Mode Yes
Filter Type Washable Anti-Bacterial Filter
Air Purification Electrostatic Air Purification
Self-Diagnosis LED Indicator
Installation Professional installation required
Operating Temperature Range -10°C to 46°C (Cooling)
Warranty 2 years (parts and labor)
Spare Parts Availability Beko authorized service centers
Manual Languages English, Italian, and more

Frequently Asked Questions - BGMPI 090 BEKO

How do I clean the air filter?
Turn off the unit and unplug it. Open the front panel, remove the filter, and wash it with lukewarm water. Let it dry completely before reinserting. Clean every 2 weeks for optimal performance.
Does this air conditioner have a heating function?
Yes, the Beko BGMPI 090 is a heat pump model, providing both cooling and heating for year-round comfort.
What type of refrigerant does it use?
It uses R32 refrigerant, which is more environmentally friendly with lower global warming potential.
Can I install this unit myself?
Professional installation is recommended to ensure safety and proper operation. The installation must comply with local electrical and building codes.
What should I do if the unit displays an error code?
Refer to the manual for error code explanations. Common fixes include checking the filter, power supply, or outdoor unit. If the issue persists, contact Beko service.
How do I use the timer function?
Press the Timer button on the remote control. Set the desired time using the + and - buttons. The unit will automatically turn on or off at the set time.
What is the energy efficiency class of this model?
The cooling efficiency class is A++, meaning it provides high energy savings compared to lower classes.
How often should I service the air conditioner?
Annual professional maintenance is recommended to check refrigerant levels, clean coils, and ensure optimal performance.
Does the remote control require batteries?
Yes, the remote control uses two AAA batteries (not included). Replace them when the signal weakens.
Where can I find spare parts for this model?
Spare parts are available through Beko authorized service centers. Contact Beko customer support for assistance.

User questions about BGMPI 090 BEKO

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

Your email remains private: it is only used to notify you if someone answers your question.

No questions yet. Be the first to ask one.

Download the instructions for your Air conditioner in PDF format for free! Find your manual BGMPI 090 - BEKO and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. BGMPI 090 by BEKO.

USER MANUAL BGMPI 090 BEKO

BGMPI 090

BGMPI 120

BGMP0 181

BGMP0 211

BGMPO 271

EN-IT

CONTENTS

ENGLISH 3-59

ITALIANO 60-124

Please read this user manual first!

Dear Customer,

Thank you for preferring a Beko product. We hope that you get the best results from your product which has been manufactured with high quality and state-of-the-art technology. Therefore, please read this entire user manual and all other accompanying documents carefully before using the product and keep it as a reference for future use. If you handover the product to someone else, give the user manual as well. Follow all warnings and information in the user manual.

Meanings of the symbols

Following symbols are used in the various section of this manual:

BEKO BGMPI 090 - Meanings of the symbols - 1

Important information or useful hints about usage.

BEKO BGMPI 090 - Meanings of the symbols - 2

Warning for hazardous situations with regard to life and property.

BEKO BGMPI 090 - Meanings of the symbols - 3

Warning to actions that must never perform.

BEKO BGMPI 090 - Meanings of the symbols - 4

Warning for electric shock.

BEKO BGMPI 090 - Meanings of the symbols - 5

This symbol shows that information is available such as the operating manual or installation manual.

BEKO BGMPI 090 - Meanings of the symbols - 6

Do not cover it.

BEKO BGMPI 090 - Meanings of the symbols - 7

This symbol shows that the operation manual should be read carefully.

BEKO BGMPI 090 - Meanings of the symbols - 8

This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.

Warning sign depicting a flame symbol in a triangular frame.

(For R32/R290 gas type) This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.

BEKO BGMPI 090 - Meanings of the symbols - 10

This product has been manufactured at modern facilities respectful to the environment without harming nature.

CONTENTS

1 Safety Precautions ....5

2 Overview....13

2.1 Accessories....13

2.2 Controls and parts....14

2.3 Optional accessories ....16

3 Unit specifications and features 17

3.1 Operating temperature .....17

3.2 Features....18

3.3 Energy saving tips....19

4 Manual operations and maintenance 21

4.1 Operation mode selection....21

4.2 Maintenance....21

4.3 Optimal operation....21

4.4 When the air conditioner is to be used again:....22

5 Installation 23

5.1 Installation summary ......23

5.2 Installation Diagram....24

5.3 Specifications 25

5.4 Outdoor unit installation....26

5.4.1 Installation Instructions – Outdoor unit......27

5.5 Refrigerant piping connection....30

5.6 Connection Instructions – Refrigerant Piping......31

5.7 Wiring 34

5.7.1 Before performing any electrical work, read these regulations....34

5.7.2 Outdoor unit wiring....35

5.8 Harmonic declaration 36

5.9 Wiring Figure 36

6 Air evacuation....45

6.1 Preparations and precautions....45

6.1.1 Before performing evacuation ....45

6.1.2 Evacuation instructions....45

6.2 Safety and leakage check....48

6.2.1 Electrical safety check....48

6.2.2 Gas leak checks....48

7 Test run....49

7.1 Before test run....49

7.2 Test run instructions....49

8 Function of automatic wiring/piping correction.....50

8.1 Automatic wiring/piping correction function .....50

8.2 How to activate this function....51

9 Troubleshooting ....52

9.1 Common issues....52

9.2 Troubleshooting tips 54

10 European disposal guideline 56

11 Installation instructions....57

11.1 F-Gas instruction....57

12 Specifications ....58

Warning

This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision (European Union countries).

This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.

Warnings for product use

If an abnormal situation arises (like a burning smell), immediately turn off the unit and disconnect the power. Call your dealer for instructions to avoid electric shock, fire or injury.

Do not insert fingers, rods or other objects into the air inlet or outlet. This may cause injury, since the fan may be rotating at high speeds.

Do not use flammable sprays such as hair spray, lacquer or paint near the unit. This may cause fire or combustion.

Do not operate the air conditioner in places near or around combustible gases. Emitted gas may collect around the unit and cause explosion.

Do not operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water can cause electrical components to short circuit.

Do not expose your body directly to cool air for a prolonged period of time.

Do not allow children to play with the air conditioner. Children must be supervised

1 Important safety and environmental instructions

around the unit at all times.

- If the air conditioner is used together with burners or other heating devices, thoroughly ventilate the room to avoid oxygen deficiency.

In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended.

Cleaning and maintenance warnings

- Turn off the device and disconnect the power before cleaning. Failure to do so can cause electrical shock.

Do not clean the air conditioner with excessive amounts of water.

Do not clean the air conditioner with combustible cleaning agents. Combustible cleaning agents can cause fire or deformation.

Caution

• Turn off the air conditioner and

disconnect the power if you are not going to use it for a long time.

- Turn off and unplug the unit during storms.

Make sure that water condensation can drain unhindered from the unit.

Do not operate the air conditioner with wet hands. This may cause electric shock.

Do not use device for any other purpose than its intended use.

Do not climb onto or place objects on top of the outdoor unit.

- Do not allow the air conditioner to operate for long periods of time with doors or windows open, or if the humidity is very high.

Electrical warnings

- Only use the specified power cord. If the power cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified

1 Important safety and environmental instructions

persons in order to avoid a hazard.

- Keep power plug clean. Remove any dust or grime that accumulates on or around the plug. Dirty plugs can cause fire or electric shock.

Do not pull the power cord to unplug the unit. Hold the plug firmly and pull it from the outlet. Pulling directly on the cord can damage it, which can lead to fire or electric shock.

Do not modify the length of the power supply cord or use an extension cord to power the unit.

Do not share the electrical outlet with other appliances. Improper or insufficient power supply can cause fire or electrical shock.

The product must be properly grounded at the time of installation, or electrical shock may occur.

For all electrical work, follow all local and national wiring standards, regulations, and the

Installation Manual. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections can overheat and cause fire, and may also cause shock. All electrical connections must be made according to the Electrical connection diagram located on the panels of the indoor and outdoor units.

All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to heat up, catch fire, or cause electrical shock.

If connecting power to fixed wiring, an all-pole disconnection device which has at least 3mm clearances in all poles, and have a leakage current that may exceed 10mA, the residual current device (RCD) having a rated residual operating current not exceeding

1 Important safety and environmental instructions

30mA, and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.

Take note of fuse specifications

The air conditioner's circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board, such as: T20A/250VAC (for <24000Btu/h unit), T30A/250VAC (for >24000Btu/h unit)

BEKO BGMPI 090 - Take note of fuse specifications - 1

Note: For the units using R32 or R290 refrigerant, only the blast-proof ceramic fuse can be used.

Warnings for product installation

  1. Installation must be performed by an authorized dealer or specialist. Defective installation can cause water leakage, electrical shock, or fire.
  2. Installation must be performed according to the installation instructions. Improper

installation can cause water leakage, electrical shock, or fire.

  1. Contact an authorized service technician for repair or maintenance of this unit. This appliance shall be installed in accordance with national wiring regulations.
  2. Only use the included accessories, parts, and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, fire, and can cause the unit to fail.
  3. Install the unit in a firm location that can support the unit's weight. If the chosen location cannot support the unit's weight, or the installation is not done properly, the unit may drop and cause serious injury and damage.
  4. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
  5. For units that have an auxiliary

1 Important safety and environmental instructions

electric heater, do not install the unit within 1 meter (3 feet) of any combustible materials.

  1. Do not install the unit in a location that may be exposed to combustible gas leaks. If combustible gas accumulates around the unit, it may cause fire.
  2. Do not turn on the power until all work has been completed.
  3. When moving or relocating the air conditioner, consult experienced service technicians for disconnection and reinstallation of the unit.
  4. How to install the appliance to its support, please read the information for details in "indoor unit installation" and "outdoor unit installation" sections.

Note about fluorinated gasses (Not applicable to the unit using R290 Refrigerant)

  1. This air-conditioning unit contains fluorinated greenhouse gasses. For specific information on the

For the type of gas and the amount, please refer to the relevant label on the unit itself or the "User Manual - Product Fiche" in the packaging of the outdoor unit. (European Union products only).

  1. Installation, service, maintenance, and repair of this unit must be performed by a certified technician.
  2. Product uninstallation and recycling must be performed by a certified technician.
  3. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more, but less than 50 tonnes of CO2 equivalent, if the system has a leak-detection system installed, it must be checked for leaks at least every 24 months.
  4. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.

Warning for Using R32/R290 Refrigerant

- When flammable refrigerants are employed, the appliance shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for operation. For R32 refrigerant models: The appliance shall be installed, operated, and stored in a room with a floor area larger than X m2. The appliance shall not be installed in an unventilated space if that space is smaller than X m2. (Please see the following form).

Amount of refrigerant to be charged (kg)Installation height (m)Minimum room area ( m2 )Amount of refrigerant to be charged (kg)Installation height (m)Minimum room area ( m2 )
1.0 0.6 /1.8/2.2 9 /1 /1 1.95 0.6 /1.8 /2.2 33/4 /2.5
1.05 0.6 /1.8/2.2 9.5 /1.5 /12.0 0.6 /1.8 /2.234.5 /4 /3
1.1 0.6 /1.8/2.2 10.5 /1.5 /12.05 0.6 /1.8 /2.236 /4 /3
1.15 0.6 /1.8/2.2 11.5 /1.5 /12.1 0.6 /1.8 /2.2 38 /4.5/3
1.2 0.6 /1.8/2.2 12.5 /1.5 /12.15 0.6 /1.8 /2.240 /4.5 /3
1.25 0.6 /1.8/2.2 13.5 /1.5 /12.2 0.6 /1.8 /2.241.5 /5 /3.5
1.3 0.6 /1.8/2.2 14.5 /2 /1.52.25 0.6 /1.8 /2.243.5 /5 /3.5
1.350.6 /1.8 /2.216 /2 /1.52.30.6 /1.8 /2.245.5/5 /3.5
1.4 0.6 /1.8/2.2 17/2/1.5 2.35 0.6 /1.8/2.2 47.5/5.5 /4
1.450.6 /1.8 /2.218 /2 /1.52.40.6 /1.8 /2.249.5 /5.5 /4
1.5 0.6 /1.8/2.2 19.5 /2.5 /1.52.45 0.6 /1.8 /2.2 51/5 /6 /4
1.55 0.6 /1.8/2.2 21 /2.5 /22.5 0.6 /1.8 /2.2 54/6 /4
1.60.6 /1.8 /2.222 /2.5 /22.550.6 /1.8 /2.256 /6.5 /4.5

1 Important safety and environmental instructions

Amount of refrigerant to be charged (kg)Installation height (m)Minimum room area ( m2 )Amount of refrigerant to be charged (kg)Installation height (m)Minimum room area ( m2 )
1.65 0.6 /1.8/2.2 23.5 /3 /22.6 0.6 /1.8 /2.2 58 /6.5 /4.5
1.7 0.6 /1.8/2.2 25 /3 /2 2.65 0.6 /1.8 /2.2 605/7 /4.5
1.75 0.6 /1.8/2.2 26.5 /3 /22.7 0.6 /1.8 /2.2 637 /7 /5
1.8 0.6 /1.8/2.2 28 /3.5 /2.5 2.75 0.6 /1.8 /2.265 /7.5 /5
1.85 0.6 /1.8/2.2 29.5 /3.5/2.5 2.8 0.6 /1.8 /2.2 67.5 /7.5 /5
1.9 0.6 /1.8/2.2 31/3.5/2.585 0.6 /1.8 /2.2 70/8 /5.5
  • Reusable mechanical connectors and flared joints are not allowed indoors. (EN Standard Requirements).
  • Mechanical connectors used indoors shall have a rate of not more than 3g/year at 25% of the maximum allowable pressure. When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated. (UL Standard Requirements)
  • When mechanical connectors are reused indoors, sealing parts shall be renewed. When flared joints are reused indoors, the flare part shall be re-fabricated. (IEC Standard Requirements)

- Mechanical connectors used indoors shall comply with ISO 14903.

European disposal guidelines

This marking shown on the product or its literature indicates that waste electrical and electronic equipment should not be mixed with general household waste.

Symbol of a waste sorting machine with crossed-out bins and a blank rectangular block below.

Correct disposal of this product (Waste electrical & Electronic equipment)

This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the following options:

1 Important safety and environmental instructions

  • Dispose of the appliance at a designated municipal electronic waste collection facility.
  • When buying a new appliance, the retailer will take back the old appliance free of charge.
  • The manufacturer will take back the old appliance free of charge. (for some countries)
  • Sell the appliance to certified scrap metal dealers. (for some countries)

BEKO BGMPI 090 - Important safety and environmental instructions - 1

Special notice: Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

2 Overview

2.1 Accessories

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail. The items that are not included with the air conditioner must be purchased separately.

Name of AccessoriesQ'ty(pc) Shape Name of Accessories Q'ty(pc) Shape
Manual 2-4 Drain joint (some models) 1 BEKO BGMPI 090 - Accessories - 1BEKO BGMPI 090 - Accessories - 2
Installation plate (some models)1 Seal ring (some models) 1BEKO BGMPI 090 - Accessories - 3
Plastic expansion sheath (some models)5-8 (depending on models)Magnetic ring (Hitch it on the connective cable between indoor unit and outdoor unit after installation.) (some models)Varies by modelBEKO BGMPI 090 - Accessories - 4
Self-Tapping Screw A (some models)5-8 (depending on models)
Transfer connector (packed with the indoor or outdoor unit, depending on models)Optional part (one piece/ one indoor unit)BEKO BGMPI 090 - Accessories - 5Cord protection rubber ring(If the cord clamp cannot fasten on a small cord, use the cord protection rubber ring [supplied with accessories] to wrap around the cord. Then fix it in place with the cord clamp.) (some models)1BEKO BGMPI 090 - Accessories - 6
Optional part (1-5 pieces for outdoor unit, depending on models)
Wireless USB kit1 (For Wifi models only)BEKO BGMPI 090 - Accessories - 7

BEKO BGMPI 090 - Accessories - 8

Pipe size may differ from appliance to appliance. To meet different pipe size requirements, sometimes the pipe connections need a transfer connector installed on the outdoor unit.

(A) Wall-mounted typeOne-five One-four One-three One-two Air outlet

(B) Duct/Ceiling typeOne-five One-four One-three One-two ⑨ ⑥ ⑦ ⑧

2.2 Controls and parts

Indoor unit

  1. Panel frame
  2. Rear air intake grille
  3. Front panel
  4. Air purifying filter & Air filter (behind)
  5. Horizontal louver
  6. LCD display window
  7. Vertical louver
  8. Manual control button (behind)
  9. Remote controller holder

Outdoor unit

  1. Drain hose, refrigerant connecting pipe
  2. Connective cable
  3. Stop valve
  4. Fan hood

Indoor unit

  1. Air outlet
  2. Air inlet
  3. Air filter
  4. Electric control cabinet
  5. Wire controller

Outdoor unit

  1. Drain hose, refrigerant connecting pipe
  2. Connective cable
  3. Stop valve
  4. Fan hood

(C) Floor and standing type (console)One-five One-four One-three One-twin

(D) Compact four-way cassette typeOne-five One-four One-three One-twin ① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩

Indoor unit

  1. Air flow louver (at air outlet)
  2. Air inlet (containing air filter)
  3. Remote controller
  4. Installation part
  5. Display panel

Outdoor unit

  1. Drain hose, refrigerant connecting pipe
  2. Connective cable
  3. Stop valve
  4. Fan hood

Indoor unit

  1. Drain pump (drain water from indoor unit)
  2. Drain hose
  3. Air outlet
  4. Air inlet
  5. Air-in grill
  6. Display panel
  7. Remote controller

Outdoor unit

  1. Refrigerant connecting pipe
  2. Connective cable
  3. Stop valve
  4. Fan hood

BEKO BGMPI 090 - Outdoor unit - 1

For multi-split type air conditioners, one outdoor unit can be matched to different types of indoor units. All of the pictures in this manual are for demonstration purposes only. Your air conditioner may be slightly different, if similar in shape. The following pages introduce several kinds of indoor units that can be matched with the outdoor units.

2.3 Optional accessories

There are two types of remote controls: wired and wireless. Select a remote controller based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote controller.

Name Shape Quantity(PC)
Connecting pipe assemblyLiquid side∅ 6.35 (1/4 in)Parts you must purchase separately. Consult the dealer about the proper pipe size of the unit you purchased.
∅ 9.52 (3/8in)
Gas side∅ 9.52 (3/8in)
∅ 12.7 (1/2in)
∅ 16 (5/8in)

3 Unit specifications and features

3.1 Operating temperature

When your air conditioner is used outside of the following temperature ranges, certain safety protection features may activate and cause the unit to disable.

COOL mode HEAT mode DRY mode
Room Temperature7°C - 32°C (62°F - 90°F)0°C - 30°C(32°F - 86°F)10°C - 32°C(50°F - 90°F)
Outdoor Temperature0°C - 50°C (32°F - 122°F)-15°C - 24°C(5°F - 75°F)0°C - 50°C(32°F - 122°F)
-15°C - 50°C (5°F - 122°F)(For models with low temp. cooling systems.)
0°C - 52°C (32°F - 126°F)(For special tropical models)0°C - 52°C(32°F - 126°F)(For special tropical models)

BEKO BGMPI 090 - Operating temperature - 1

For outdoor units with auxiliary electric heater. When outside temperature is below 0° C ( 32° F), we strongly recommend keeping the unit plugged in at all time to ensure smooth ongoing performance.

BEKO BGMPI 090 - Operating temperature - 2

Room relative humidity less than 80%. If the air conditioner operates in excess of this figure, the surface of the air conditioner may attract condensation. Please sets the vertical air flow louver to its maximum angle (vertically to the floor), and set HIGH fan mode.

3 Unit specifications and features

To further optimize the performance of your unit, do the following:

  • Keep doors and windows closed.
  • Limit energy usage by using TIMER ON and TIMER OFF functions.
  • Do not block air inlets or outlets.
  • Regularly inspect and clean air filters.

3.2 Features

Install the HomeWhiz kit (wireless module).

  1. Remove the protective cap of the HomeWhiz kit (wireless module).
  2. Open the front panel and insert the HomeWhiz kit (wireless module) into the reserved interface.

Diagram of a device being inserted into a housing, showing a curved arrow indicating direction (no text or symbols present).

Insert

BEKO BGMPI 090 - Install the HomeWhiz kit (wireless module). - 3

Warning:

This interface is only compatible with the HomeWhiz kit (wireless module) provided by the manufacturer.

Protection of the air conditioner Compressor protection

The compressor cannot restart for 3 minutes after it stops.

Anti-cold air (Cooling and heating models only)

The unit is designed not to blow cold air on HEAT mode, when the indoor heat exchanger is in one of the following three situations and the set temperature has not been reached.

  • When heating has just started.
  • During defrosting.
  • Low temperature heating.

The indoor or outdoor fan stops running when defrosting (Cooling and heating models only).

Defrosting (Cooling and heating models only)

  • Frost may be generated on the outdoor unit during a heat cycle when outdoor temperature is low and humidity is high, resulting in lower heating efficiency in the air conditioner.
  • Under these conditions, the air conditioner will stop heating operations and start defrosting automatically.
  • The time to defrost may vary from 4 to 10 minutes, depending on the outdoor temperature and the amount of frost buildup on the outdoor unit.

Auto-Restart (some models)

In case of power failure, the system will immediately stop. When power returns, the Operation light on the indoor unit will flash. To restart the unit, press the ON/OFF button on the remote control. If the system has an auto restart function, the unit will restart using the same settings.

White mist emerging from the indoor unit

- A white mist may be generated due to a large temperature difference between air inlet and air outlet on COOL mode in places with high relative humidity.

3 Unit specifications and features

- A white mist may be generated due to moisture created in the defrosting process when the air conditioner restarts in HEAT mode operation after defrosting.

Noise coming from the air conditioner

- You may hear a low hissing sound when the compressor is running or has just stopped running. This sound is the sound of the refrigerant flowing or coming to a stop.

- You may also hear a low “squeaking” sound when the compressor is running or has just stopped running. This is caused by thermal expansion and cold contraction of the plastic parts in the unit when the temperature is changing.

- A noise may be heard due to the louver restoring itself to its original position when power is first turned on.

Dust blowing out from the indoor unit

This happens when the air conditioner has not been used for a long time or during its first use.

Smell emitting from the indoor unit.

This is caused by the indoor unit giving off smells permeated from building materials, furniture, or smoke.

The air conditioner turns to FAN ONLY mode from COOL or HEAT (for cooling and heating models only) mode.

When the indoor temperature reaches the set temperature setting, the compressor will stop automatically, and the air conditioner turns to FAN only mode. The compressor will start again when the indoor temperature rises on COOL mode or falls on HEAT mode to the set point.

Droplets of water may form on the surface of the indoor unit when cooling occurs in relatively high humidity (defined as higher than 80%). Adjust the horizontal louver to the maximum air outlet position and select HIGH fan speed.

Heating mode (For cooling and heating models only)

The air conditioner draws in heat from the outdoor unit and releases it via the indoor unit during heating. When the outdoor temperature falls, heat drawn in by the air conditioner decreases accordingly. At the same time, heat loading of the air conditioner increases due to larger difference between indoor and outdoor temperature. If a comfortable temperature cannot be achieved with the air conditioner alone, it is recommended that you use a supplementary heating device. Lightning or a car wireless telephone operating nearby may cause the unit to malfunction. Disconnect the unit from its power source and then re-connect the unit with the power source again. Push the ON/OFF button on the remote controller to restart operations.

3.3 Energy saving tips

  • DO NOT set the unit to excessive temperature levels.
  • While cooling, close the curtains to avoid direct sunlight.
  • Doors and windows should be kept closed to keep cool or warm air in the room.
  • DO NOT place objects near the air inlet and outlet of the unit. This will reduce the efficiency of the unit.
  • Set a timer and use the built-in SLEEP/ECONOMY mode if applicable.
  • If you don't plan to use the unit for a long time, remove the batteries from the remote control.
  • Clean the air filter every two weeks. A dirty filter can reduce cooling or heating efficiency.
  • Adjust louvers properly and avoid direct airflow.

3 Unit specifications and features

Simple line drawing of two vertical scroll panels with curved lines, no text or symbols present.

Closing curtains during heating also helps keep the heat in.

Simple line drawing of a door and a window (no text or symbols).

Doors and windows should be kept closed.

4.1 Operation mode selection

While two or more indoor units are simultaneously operating, make sure the modes do not conflict with each other. The heat mode claims precedence over all other modes. If the unit initially started to operate in HEAT mode, the other units can operate in HEAT mode only. For example: If the unit initially started operates under COOL (or FAN) mode, the other units can operate under any mode except HEAT. If one of the unit selects HEAT mode, the other operating units will stop operation and display “--” (for units with display window only) or the auto and operation indication light will flash rapidly, the defrost indication light will turn off, and the timer indication light will remain on (for units without a display window). Alternatively, the defrost and alarm indication light (if applicable) will light up, or the operation indication light will flash rapidly, and the timer indication light will turn off (for the floor and standing type).

4.2 Maintenance

If you plan to leave the unit idle for a long time, perform the following tasks:

  1. Clean the indoor unit and air filter.
  2. Select FAN ONLY mode and let the indoor fan run for a time to dry the inside of the unit.
  3. Disconnect the power supply and remove the battery from the remote control.
  4. Check components of the outdoor unit periodically. Contact a local dealer or a customer service centre if the unit requires servicing.

BEKO BGMPI 090 - Maintenance - 1

Before you clean the air conditioner, be sure to switch off the unit and disconnect the power supply plug.

4.3 Optimal operation

To achieve optimal performance, please note the following:

  • Adjust the direction of the air flow so that it is not blowing directly on people.
  • Adjust the temperature to achieve the highest possible level of comfort. Do not adjust the unit to excessive temperature levels.
  • Close doors and windows in COOL mode or HEAT mode.
  • Use the TIMER ON button on the remote controller to select a time you want to start your air conditioner.
  • Do not place any object near the air inlet or air outlet, as the efficiency of the air conditioner may be reduced and the air conditioner may stop running.
  • Clean the air filter periodically, otherwise cooling or heating performance may be reduced.
  • Do not operate unit with horizontal louvre in closed position.

BEKO BGMPI 090 - Optimal operation - 1

For units that feature an electric heater, when the outside ambient temperature is below 0° C ( 32° F), it is strongly recommended that you to keep the machine plugged in so as to guarantee smooth operation.

4 Manual operations and maintenance

4.4 When the air conditioner is to be used again:

  • Use a dry cloth to wipe off the dust accumulated on the rear air intake grille in order to avoid the dust being dispersed from the indoor unit.
  • Check that the wiring is not broken off or disconnected.
  • Check that the air filter is installed.
  • Check if the air outlet or inlet is blocked after the air conditioner has not been used for a long time.

5 Installation

5.1 Installation summary

BEKO BGMPI 090 - Installation summary - 1

5.2 Installation Diagram

4 More than 12cm Air Filter Remote controller 5 More than 12cm Air filter Remote controller 3 More than 12cm Air filter Remote controller 2 Air-break Switch Mounting screw ST3.9 × 25-C-H More than 15cm Air break Switch More than 12cm More than 15cm Air break plate Clear refrigerator Air-break pipe D…

BEKO BGMPI 090 - Installation Diagram - 2

The installation must be performed in accordance with the requirement of local and national standards. The installation may be slightly different in different areas.

5.3 Specifications

Number of units that can be used togetherConnected units1-5 units
Compressor stop/start frequencyStop time 3 minor more
Power source voltagevoltage fluctuationwithin ±10% of rated voltage
voltage drop during startwithin ±15% of rated voltage
interval unbalancewithin ±3% of rated voltage
1 drive 21 drive 31 drive 41 drive 5
Max. length for all rooms40/13160/19780/262 80/262
Max. length for one indoor unit25/8230/9835/11535/115
Max. height different between indoor and outdoor unit15/4915/4915/4915/49
Max. height different between indoor units10/3310/3310/3310/33

BEKO BGMPI 090 - Installation Diagram - 3

For the units adopt quick connectors, no more than two pipes can be connected, and the Max. length for each pipe is 7.5 meters.

When installing multiple indoor units with a single outdoor unit, ensure that the length of the refrigerant pipe and the drop height between the indoor and outdoor units meet the requirements illustrated in the following diagram:

5 Installation

Outdoor Unit Indoor Unit Max.Height difference 15m (49ft) 10m (32.8ft) 15m (49ft) Indoor unit

5.4 Outdoor unit installation

Install the unit by following local codes and regulations, there may be differ slightly between different regions.

60cm (24in) above 30cm (12in) from fr back wall 30cm (12in) on left 2000pt (78in) in front 650pt (24in) on right

5.4.1 Installation Instructions – Outdoor unit

Step 1: Select installation location

Before installing the outdoor unit, you must choose an appropriate location. The following are standards that will help you choose an appropriate location for the unit.

Proper installation locations meet the following standards:

  • Meets all spatial requirements shown in Installation Space Requirements above. • Good air circulation and ventilation
  • Firm and solid—the location can support the unit and will not vibrate
  • Noise from the unit will not disturb others
  • Protected from prolonged periods of direct sunlight or rain
  • Where snowfall is anticipated, raise the unit above the base pad to prevent ice buildup and coil damage. Mount the unit high enough to be above the average accumulated area snowfall. The minimum height must be 18 inches.

DO NOT install unit in the following locations:

  • Near an obstacle that will block air inlets and outlets
  • Near a public street, crowded areas, or where noise from the unit will disturb others
  • Near animals or plants that will be harmed by hot air discharge • Near any source of combustible gas
  • In a location that is exposed to large amounts of dust.
  • In a location exposed to a excessive amounts of salty air.

BEKO BGMPI 090 - DO NOT install unit in the following locations: - 1

If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. See Figures below.

Strong wind Strong wind Wind Baffle Strong wind

BEKO BGMPI 090 - DO NOT install unit in the following locations: - 3

If the unit is frequently exposed to heavy rain or snow: Build a shelter above the unit to protect it from the rain or snow. Be careful not to obstruct air flow around the unit. If the unit is frequently exposed to salty air (seaside): Use outdoor unit that is specially designed to resist corrosion.

Step 2: Install drain joint (Heat pump unit only)

Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. Note that there are two different types of drain joints depending on the type of outdoor unit.

If the drain joint comes with a rubber seal (see Fig. A), do the following:

  1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
  2. Insert the drain joint into the hole in the base pan of the unit.
  3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.

5 Installation

  1. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

If the drain joint doesn't come with a rubber seal (see Fig. B), do the following:

  1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
  2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

Base pan hole of outdoor unit. Seal. Seal. Drain joint (A) (B).

Warning symbol: exclamation mark inside a triangle.

CAUTION! In cold climates, make sure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.

Step 3: Anchor outdoor unit

The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolt (M10). Prepare the installation base of the unit according to the dimensions below.

BEKO BGMPI 090 - Step 3: Anchor outdoor unit - 1

The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below.

Outdoor Unit Types and Specifications

Split Type Outdoor UnitH, W, W, H, A, D, B.

5 Installation

(unit: mm/inch)

Outdoor Unit Dimensions (mm) Mounting Dimensions
W x H x D Distance A (mm)Distance B (mm)
760x590x285 (29.9x23.2x11.2) 530 (20.85) 290 (11.4)
810x558x310 (31.9x22x12.2) 549 (21.6) 325 (12.8)
845x700x320 (33.27x27.5x12.6) 560 (22) 335 (13.2)
900x860x315 (35.4x33.85x12.4) 590 (23.2) 333 (13.1)
945x810x395 (37.2x31.9x15.55) 640 (25.2) 405 (15.95)
990x965x345 (38.98x38x13.58) 624 (24.58) 366 (14.4)
938x1369x392 (36.93x53.9x15.43) 634 (24.96) 404 (15.9)
900x1170x350 (35.4x46x13.8) 590 (23.2) 378 (14.88)
800x554x333 (31.5x21.8x13.1) 514 (20.24) 340 (13.39)
845x702x363 (33.27x27.6x14.3) 540 (21.26) 350 (13.8)
946x810x420 (37.2x31.9x16.53) 673 (26.5) 403 (15.87)
946x810x410 (37.2x31.9x16.14) 673 (26.5) 403 (15.87)
952x1333x410 (37.5x52.5x16.14) 634 (24.96) 404 (15.9)
952x1333x415 (37.5x52.5x16.14) 634 (24.96) 404 (15.9)
890x673x342 (35.0"x 26.5"x 13.5") 663 (26.1") 354 (13.9")

Rows of series installation

The relations between H, A and L are as follows.

LA
L ≤ H L ≤ 1/2H 25 cm / 9.8" or more
1/2H < L ≤ H 30 cm / 11.8" or more
L > H Can not be installed

250 cm / 10 ft. H. 250 cm / 10 ft. H. 250 cm / 10 ft. H. 250 cm / 10 ft. H. A. L.

5 Installation

Notes on drilling hole in wall: You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.

  1. Determine the location of the wall hole based on the location of the outdoor unit.
  2. Using a 65-mm (2.5") core drill, drill a hole in the wall.

BEKO BGMPI 090 - Installation - 1

When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

  1. Place the protective wall cuff in the hole. This protects the edges of the hole and helps seal it when you finish the installation process.

BEKO BGMPI 090 - Installation - 2

WARNING! When drilling into concrete, eye protection is recommended at all times.

When selecting a 24k indoor unit

The 24K indoor unit can only be connected with an A system. If there are two 24K indoor units, they can be connected with A and B systems.

Connective pipe size of an A and B system

Indoor Unit capacity (Btu/h)Liquid Gas
7K/9K/12K 1/43/8
12K/18K 1/41/2
24K 3/8 5/8

E, D, C, B, A.

5.5 Refrigerant piping connection

BEKO BGMPI 090 - Refrigerant piping connection - 1

For quick-connect models, please refer to the internal machine manual for the installation method of the connecting pipe. The external machine manual does not repeat the instructions.

When connecting refrigerant piping, do not let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit's capacity, and can cause abnormally high pressure in the refrigeration cycle. This can cause explosion and injury.

5 Installation

5.6 Connection Instructions – Refrigerant Piping

BEKO BGMPI 090 - Connection Instructions – Refrigerant Piping - 1

CAUTION!

- The branching pipe must be installed horizontally. An angle of more than 10° may cause malfunction.

- DO NOT install the connecting pipe until both indoor and outdoor units have been installed.

• Insulate both the gas and liquid piping to prevent water leakage.

Step 1: Cut pipes

When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.

  1. Measure the distance between the indoor and outdoor units.
  2. Using a pipe cutter, cut the pipe a little longer than the measured distance.
  3. Make sure that the pipe is cut at a perfect 90° angle.

90°. Oblique / Rough / Warped.

BEKO BGMPI 090 - Step 1: Cut pipes - 2

WARNING! Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.

Step 2: Remove burrs

Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.

  1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
  2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.

Pipe. Reamer. Point down.

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight seal.

  1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
  2. Sheath the pipe with insulating material.
  3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can't put them on or change their direction after flaring.

Flare nut. Copper pipe.

  1. Remove PVC tape from ends of pipe when ready to perform flaring work.
  2. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.

5 Installation

Flare form. A. Pipe.

  1. Place flaring tool onto the form.
  2. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions.

Piping extension beyond flare form

Pipe gaugeTightening torqueFlare dimension (A) (Unit: mm/Inch)Flare shape
Min. Max.BEKO BGMPI 090 - Installation - 2
∅ 6.4 18-20 N.m (183-204 kgf.cm) 8.4/0.33 8.7/0.34
∅ 9.5 25-26 N.m (255-265 kgf.cm) 13.2/0.52 13.5/0.53
∅12.7 35-36 N.m (357-367 kgf.cm) 16.2/0.64 16.5/0.65
∅ 15.9 45-47 N.m (459-480 kgf.cm) 19.2/0.76 19.7/0.78
∅ 19.1 65-67 N.m (663-683 kgf.cm) 23.2/0.91 23.7/0.93
∅ 22 75-85N.m (765-867 kgf.cm) 26.4/1.04 26.9/1.06
  1. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high-pressure pipe.

  1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
  2. Align the center of the two pipes that you will connect.

5 Installation

Indoor unit tubing. Flare nut. Pipe. Flare nut. Pipe.

  1. Tighten the flare nut as tightly as possible by hand.
  2. Using a spanner, grip the nut on the unit tubing.
  3. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in the table above.

BEKO BGMPI 090 - Installation - 2

Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.

Line drawing of hands using a tool to adjust or install a mechanical component.

BEKO BGMPI 090 - Installation - 4

CAUTION!

  • Ensure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite.
  • Make sure the pipe is properly connected. Over tightening may damage the bell mouth and under tightening may lead to leakage.

BEKO BGMPI 090 - CAUTION! - 1

Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.

Bend the pipe with thumb

Line drawing of two hands stretching a curved object.

min-radius 10cm (3.9")

  1. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.

BEKO BGMPI 090 - CAUTION! - 3

DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.

  1. Thread this pipeline through the wall and connect it to the outdoor unit.
  2. Insulate all the piping, including the valves of the outdoor unit.
  3. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.

BEKO BGMPI 090 - CAUTION! - 4

CAUTION! Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).

5.7 Wiring

5.7.1 Before performing any electrical work, read these regulations

  1. All wiring must comply with local and national electrical codes, regulations and must be installed by a licensed electrician.
  2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
  3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
  4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
  5. If connecting power to fixed wiring, a surge protector and main power switch should be installed.
  6. If connecting power to fixed wiring, a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1/8in (3mm) must be incorporated in the fixed wiring. The qualified technician must use an approved circuit breaker or switch.
  7. Only connect the unit to an individual branch circuit outlet. Do not connect another appliance to that outlet.
  8. Make sure to properly ground the air conditioner.
  9. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in product malfunction and possible fire.
  10. Do not let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
  11. If the unit has an auxiliary electric heater, it must be installed at least 1 meter (40in) away from any combustible materials.
  12. To avoid getting an electric shock, never touch the electrical components soon after the power supply has been turned off. After turning off the power, always wait 10 minutes or more before you touch the electrical components.
  13. Make sure that you do not cross your electrical wiring with your signal wiring. This may cause distortion and interference.
  14. The unit must be connected to the main outlet. Normally, the power supply must have an impedance of 32 ohms.
  15. No other equipment should be connected to the same power circuit.
  16. Connect the outdoor wires before connecting the indoor wires.

BEKO BGMPI 090 - Before performing any electrical work, read these regulations - 1

WARNING! Before performing any electrical or wiring work, turn off the main power to the system.

BEKO BGMPI 090 - Before performing any electrical work, read these regulations - 2

WARNING! When the maximum current of the air conditioner is more than 16A, an air switch or leakage protection switch with protective device shall be used (purchased separately). When the maximum current of the air conditioner is less than 16A, the power cord of the air conditioner shall be equipped with a plug (purchased separately). The North American market is wired according to NEC and CEC requirements.

5 Installation

graph TD A["Air Switch (purchased separately)"] --> B["Outdoor unit power wires"] B --> C["Outdoor unit"] C --> D["Indoor unit"] D --> E["Indoor & Outdoor connective wires (purchased separately)"] E --> D F["Ground"] --> C

graph TD A["Indoor unit power wires"] --> B["Air switch (purchased separately)"] C["Outdoor unit"] --> D["Indoor unit"] E["Indoor & Outdoor connective wires (purchased separately)"] --> D D --> F["Ground"]

graph TD A["Air switch (purchased separately)"] --> B["Indoor unit power wires"] B --> C["Outdoor unit power wires"] C --> D["Outdoor unit"] D --> E["Indoor unit"] E --> F["Air switch (purchased separately)"] F --> G["Indoor unit"] G --> H["Indoor & Outdoor connective wires (purchased separately)"]…

graph TD A["Air switch (purchased separately)"] --> B["Outdoor unit power wires"] B --> C["Outdoor unit"] C --> D["Indoor unit"] D --> E["Indoor & Outdoor connective wires (purchased separately)"] E --> F["Indoor unit"] F --> G["Air switch (purchased separately)"] G --> H["Ground"] style A fill:#f9f…

BEKO BGMPI 090 - Installation - 5

The diagrams are for explanation purposes only. Your machine may be slightly different. The actual shape shall prevail.

5.7.2 Outdoor unit wiring

BEKO BGMPI 090 - Outdoor unit wiring - 1

WARNING! Before performing any electrical or wiring work, turn off the main power to the system.

  1. Prepare the cable for connection

- You must first choose the right cable size. Be sure to use H07RN-F cables.

BEKO BGMPI 090 - Outdoor unit wiring - 2

In North America, choose the cable type according to the local electrical codes and regulations.

Minimum Cross-Sectional Area of Power and Signal Cables (For reference)

Rated Current of Appliance (A)Nominal Cross-Sectional Area (mm2)
>3 and ≤ 60.75
>6 and ≤ 101
>10 and ≤ 161.5
>16 and ≤ 252.5
>25 and ≤ 324
>32 and ≤ 406

The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum current of the unit. The maximum current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch.

BEKO BGMPI 090 - Outdoor unit wiring - 3

In North America, please choose the right cable size according to the minimum circuit ampacity indicated on the nameplate of the unit.

  • Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal approximately 15cm (5.9") of wire. – Strip the insulation from the ends.
  • Using a wire crimper, crimp u-lugs on the ends.

BEKO BGMPI 090 - Outdoor unit wiring - 4

When connecting the wires, strictly follow the wiring diagram found inside the electrical box cover.

  1. Remove the electric cover of the outdoor unit. If there is no cover on the outdoor unit, take off the bolts from the maintenance board and remove the protection board.

Cover. Screw.

  1. Connect the u-lugs to the terminals Match the wire colors/labels with the labels on the terminal block, and firmly screw the u-lug of each wire to its corresponding terminal.
  2. Clamp down the cable with designated cable clamp.
  3. Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts.
  4. Reinstall the cover of the electric control box.

5.8 Harmonic declaration

"The equipment M40B-36HFN8-Q complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to 4787737.5 at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to 4787737.5." "The equipment M50D-42HFN8-Q complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to 3190042.5 at the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to 3190042.5."

5.9 Wiring Figure

BEKO BGMPI 090 - Wiring Figure - 1

CAUTION! Connect the connective cables to the terminals, as identified, with their matching numbers on the terminal block of the indoor and outdoor units. For example, Terminal L1(A) of the outdoor unit must connect with terminal L1/1 on the indoor unit. The outdoor unit can match different types of indoor unit, the numbers on the terminal block of the indoor unit may be slightly different. Please pay special attention while connecting the wire.

5 Installation

L1 L2 L1A L2A S A L1B L2B S B. POWER. L1 L2 S ⊕. TO A. L1 L2 S ⊕. TO B. ✓.

L1 L2 L1A L2A S1A L1B L2B1 S3. POWER. OFF-QUAL. TO A. TO B.

L1 L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) PWRTR L1L2S Or 1 2 3 L1L2S Or 1 2 3 TO A TO B

BEKO BGMPI 090 - Installation - 4

For quick-connector models, please refer to < > packed with the indoor unit.

BEKO BGMPI 090 - Installation - 5

Refer to the following figures if end-users wish to perform their own wiring. Run the main power cord through the lower line-outlet of the cord clamp. ---- This symbol indicates field wiring.

One-two models:

L N L A N A S A L B N D S E O B P R O N A L POWER O B P R O N A L L N S TO A L N S TO B Model A

L N L(A)N(A)S(A)L(B)W(B)B OPTIONAL POWER OPTIONAL OPTIONAL TO A TO B Model B

L1 L2 L3 L4 L5 L6 L7 L8 OFF/ON/LE POWER N S TO A N S TO B COTIOMALL COTIOMALL Model C

L1 L2 L3 L4 L5 L6 L7 L8 OP/NO.100 POWER TO A TO B TRNO.100 Model D

5 Installation

750VDC POWER TO A TO B

Model E

L1 L2 T0 T1 T2 T3 T4 T5 T6 T7 T8 T9 POWER TO A TO B T0 T1 T2 T3 T4 T5 T6 T7 T8 T9 T0 T1 T2 T3 T4 T5 T6 T7 T8 T9

Model F

W L N U T0: N N S1A U P: N N S2U POWER SUPPLY TO A Y/G COP TOMAL TO B

Model G

graph TD A["POWER SUPPLY"] --> B["Terminal Block 1"] A --> C["Terminal Block 2"] B --> D["Terminal Block 3"] C --> E["Terminal Block 4"] D --> F["Terminal Block 5"] E --> G["Terminal Block 6"] F --> H["Terminal Block 7"] G --> I["Terminal Block 8"] H --> J["Terminal Block 9"] I --> K["Terminal Block…

Model H

BEKO BGMPI 090 - Installation - 5

Use the magnetic ring (not supplied, optional part) to hitch the connective cable of indoor and outdoor units after installation. One magnetic ring is used for one cable.

L N POWER SUPPLY L4A M4 S4A L6A M6 S6A OPTIONAL LN SB TO A LN SB TO B Y/G Y/G

Model I

graph TD A["Component 1"] --> B["THYCOR"] C["Component 2"] --> D["CUTRICAL"] E["Component 3"] --> F["CUTRICAL"] G["Component 4"] --> H["10 A"] I["Component 5"] --> J["10 A"] K["Component 6"] --> L["10 A"] M["Component 7"] --> N["10 A"] O["Component 8"] --> P["10 A"] Q["Component 9"] --> R["10 A"] S[…

Model J

graph TD A["S11"] --> B["T00"] C["S12"] --> D["T00"] E["S13"] --> F["T00"] G["S14"] --> H["T00"] I["S15"] --> J["T00"] K["S16"] --> L["T00"] M["S17"] --> N["T00"] O["S18"] --> P["T00"] Q["S19"] --> R["T00"] S["S20"] --> T["T00"] U["S21"] --> V["T00"] W["S22"] --> X["T00"] Y["S23"] --> Z["T00"] AA["S…

Model K

graph TD A["Switch S2"] --> B["Coil"] C["Switch S1"] --> D["Coil"] E["Switch L"] --> F["Coil"] G["T00"] --> H["Coil"] I["T0A"] --> J["Coil"] K["T0B"] --> L["Coil"] M["T0C"] --> N["Coil"] O["T0D"] --> P["Coil"] Q["T0E"] --> R["Coil"] S["T0F"] --> T["Coil"] U["T0G"] --> V["Coil"] W["T0H"] --> X["Coil"…

Model L

W L N L1 OPTIONAL POWER SUPPLY L1A N/A S/A L3 N/B S/B OPTIONAL L N S B L N S B TO A TO B

Model M

W L N L1 POWER SURRY L0 L1 L2 L3 L4 OCTOR TO A TO B

Model N, Model O

L1 L2 L1A L2A S1 L1B L2B S3 POWER L N S D TO A L N S D TO B OPTIMAL

5 Installation

L1 L2 L1A L2A S1A L1B L2B S3B OPTIONAL POWER OPTIONAL OPTIONAL 1 2 3 TO A 1 2 3 TO B

I1 I2 I10 I20 S0 I18 I28 S0 OPTIONAL POWER OPTIONAL OPTIONAL TO A TO B

1 2 3 4 5 6 7 8 9 10 OPTIONAL POWER OPTIONAL OPTIONAL 1 2 3 4 TO A 1 2 3 4 TO B

Model P, Model Q, Model RL1 L2 1(A) 2(A) 3(A) 1(B) 2(B) 3(B) OPTIONAL POWER SUPPLY OPTIONAL 1 2 3 TO A 1 2 3 TO B

L1 L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) OPTIONAL POWER SUPPLY L1 2 3 1 2 3 TO A 1 2 3 TO B OPTIONAL OPTIONAL

Model T, Model S

graph TD A["To indoor unit A"] --> B["POWER"] C["To indoor unit B"] --> D["OPTIMUM"] E["Power Supply"] --> F["Optimum"] G["Power Supply"] --> H["Optimum"] I["Power Supply"] --> J["Optimum"] K["Power Supply"] --> L["Optimum"] M["Power Supply"] --> N["Optimum"] O["Power Supply"] --> P["Optimum"] Q["Po…

Model U

L N TWIN/LEGO POWER SUPPLY

graph TD subgraph_Unit_A["To indoor unit A"] A1["Terminal L"] --> B1["Component L N S"] A2["Terminal L"] --> B2["Component L N S"] A3["Terminal L"] --> B3["Component L N S"] A4["Terminal L"] --> B4["Component L N S"] A5["Terminal L"] --> B5["Component L N S"] A6["Terminal L"] --> B6["Component L N S…

Model V, Model U

L N ORIGINAL POWER SUPPLY

LAY N/A SI LAY N/A SI OPTIONAL OPTIONAL LN S or or or LN S or or or TO-INDOOR unit A TO-INDOOR unit B

Model W

5 Installation

One-three models:POWER LNS TO A CYPEDUCTOR LNS TO B CYPEDUCTOR LNS TO C

Model A

graph TD A["POWER"] --> B["TINRULU"] B --> C["TO A"] B --> D["TINRULU"] D --> E["TO B"] D --> F["TINRULU"] F --> G["TO C"] H["OPTIONAL"] --> I["TO A"] H --> J["TO B"] H --> K["TO C"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style H fill:#cfc,stroke:#333 style I fill:#fcc,stroke:#3…

Model B, Model C

graph TD A["POWER"] --> B["TO A"] B --> C["OPTOFFINAL"] C --> D["TO B"] D --> E["OPTOFFINAL"] E --> F["TO C"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333 style E fill:#cff,stroke:#333 style F fill:#ffc,stroke:#333

graph TD subgraph Power Input L1["Power Input L1"] --> T0A["1 2 3 4"] L2["Power Input L2"] --> T0B["1 2 3 4"] L3["Power Input L3"] --> T0C["1 2 3 4"] end subgraph Transformer T0A --> TOA["T0 A"] T0B --> TOB["T0 B"] T0C --> TOC["T0 C"] end subgraph Terminal T0A --> TOA T0B --> TOB T0C --> TOC end L1…

Model D, Model E, Model F

POWER TO A TO B TO C

graph TD subgraph Terminal_Block1 A["Terminal Block 1"] --> B["Terminal Block 2"] B --> C["Terminal Block 3"] C --> D["Terminal Block 4"] D --> E["Terminal Block 5"] E --> F["Terminal Block 6"] F --> G["Terminal Block 7"] G --> H["Terminal Block 8"] H --> I["Terminal Block 9"] I --> J["Terminal Bloc…

TOMMOLADO POWER SUPPLY L N 1/4 3/4 5/4 1/4 4/4 5/4 1/2 NO. SO CUTI/RUOAL CUTI/RUOAL CUTI/RUOAL TO A TO B TO C Y/G Y/G W/G

Model G

1.1 1.2 1.3 1.4 1.5 1.6 TO A TO B TO C PUMS TO A TO B TO C TO D TO E TO F TO G TO H TO I TO J TO K TO L TO M TO N TO O TO P TO Q TO R TO S TO T TO U TO V TO W TO X TO Y TO Z TO A TO B TO C

L1 L2 T1 T2 T3 T4 T1 T2 T3 T4 T5 T6 T7 T8 POWER TO A TO B TO C

Model I, Model H, Model G

graph TD A["Industrial Unit L N L(A) N(A) S(A) L(B) N(B) S(B)"] --> B["TM(01L2A)"] B --> C["POWER"] D["TM(01L2B)"] E["TM(01L3D)"] F["Control Panel"] --> G["L N S"] F --> H["L N S"] F --> I["LN S"] F --> J["LN S"] F --> K["LN S"] F --> L["LN S"] F --> M["LN S"] F --> N["LN S"] F --> O["LN S"] F --> P…

MadeyJ

One-four models:N L A N A S A POWER L NS TO A L NS TO B L NS TO C L NS TO D TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO TWO

Model A

L N LCA NCA SCA POWER LEA NL25 TO A TEV20/140 TEV20/140 LEA NL25 TO B TEV20/140 LEA NL25 TO C TEV20/140 LEA NL25 TO D

Model B

L N L A N A S A POWER POWER TO A TO B TO C TO D

Model C

L1 L2 70 100 30 TOUT POWER OPTIONAL 2 3 TO A 1R 2R 3R 4R 5R 6R 7R 8R 9R 10R OPTIONAL 1 2 3 TO B 1 2 3 TO C 1 2 3 TO D

Model D

1 2 3 TO A POWER CYPICUM CYPICUM 1 2 3 TO B 1 2 3 TO C 1 2 3 TO D POWER CYPICUM CYPICUM 1 2 3 TO B 1 2 3 TO C 1 2 3 TO D

Model E

L N TO PDC POWER SUPPLY OPTIONAL LN S TO A Y/G TOPICAL TOP B LN S TO B Y/G TOP DIAL LN S TO A Y/G TOP DIO LN S TO B Y/G

Model F

1/2 50 30 1/2 30 2/2 TWOLED/O TO A TO B TWOLED/O TO C TO D TWOLED/O POWER SUPPLY

Model G

POWER SUPPLY 1 2 10 20 30 40 50 60 CUTRUM TO A TO B CUTRUM TO C TO D

Model H

5 Installation

L1 L2 OPTIONAL OPTIONAL OPTIONAL TO A TO B TO C TO D POWER SUPPLY

Model I

L1 L2 OPTIONAL POWER SUPPLY OPTIONAL TO A TO B OPTIONAL TO C TO D OPTIONAL

Model J

L1 2 A 2A 3A OPTIONAL POWER 1 2 3 TO A OPTIONAL 1 2 3 TO B 1 2 3 TO C 1 2 3 TO D

Model K

1 2 T0 T1 T2 T3 S4 GENERAL OPTIONAL POWER 1 2 3 4 TO A OPTIONAL GENERAL OPTIONAL 1 2 3 4 TO B 1 2 3 4 TO C 1 2 3 4 TO D

Model L

L N L(A) N(A) S(A) L(B) N(B) S(B) ORPHORNAL POWER L N S O L N S O L(L) 20N1 d L(L) 20N1 d W 11L 20N1 S W 11L 20N1 S TO indoor unit A To indoor unit B TO indoor unit C TO indoor unit D

Model M

One-five models:POWER LNS LNS DT TO A TO B LNS LNS DT TO C TO D TO E

Model A

TINNOOL1-800 POWER TO A TO B TO C TO D TO E

Model B

1.1 1.2 1.3 1.4 1.5 1.6 POWER TO A TO B 1.2 1.3 1.4 1.5 1.6 TO C TO D TO E

Model 6

POWER TO A TO B 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 5 1 2 3 6 1 2 3 7 1 2 3 8 1 2 3 9 1 2 3 10 1 2 3 11 1 2 3 12 1 2 3 13 1 2 3 14 1 2 3 15 1 2 3 16 1 2 3 17 1 2 3 18 1 2 3 19 1 2 3 20 1 2 3 21 1 2 3 22 1 2 3 23 1 2 3 24 1 2 3 25 1 2 3 26 1 2 3 27 1 2 3 28 1 2 3 29 1 2 3 30 1 2 3 31 1 2 3 32 1 2 3…

Model D

L1 L2 TO A TO B TO C TO D TO E POWER SUPPLY

Model E

L0 M0 S0 LB H5 S8 L1 N1 SD Z3 N2 SP Z2 N3 SB L4 N4 L5 TWOOLLED TO A TO B L1 B1 L2 B2 L3 B3 L4 B4 L5 B5 L6 B6 L7 B7 L8 B8 L9 B9 L10 B11 L12 B13 L14 B15 L16 B17 L18 B19 L20 B21 L22 B23 L24 B25 L26 B27 L28 B29 L30 B31 L32 B33 L34 B35 L36 B37 L38 B39 L40 B41 L42 B43 L44 B45 L46 B47 L48 B49 L50 B51 L52 B…

L1 L2 C 100 105 106 108 200 201 L1 L2 C 100 105 106 108 200 201 POWER TO A TO B L1 L2 C 100 105 106 108 200 201 L1 L2 C 100 105 106 108 200 201 POWER TO A TO B L1 L2 C 100 105 106 108 200 201 L1L2C TO D TO E

Model G

1.1 1.2 C LUN 1.2A 1.3A LUN 1.3B 1.4B POWER TO A TO B TRANSFORM TRANSFORM TO C TO D TO E

Model H

CAUTION! After confirmation of the above conditions, follow these guidelines when performing wiring:

  • Always have an individual power circuit specifically for the air conditioner. Always follow the circuit diagram posted on the inside of the control cover.
  • Screws fastening the wiring in the casing of electrical settings may come loose during transportation. Because loose screws may cause wire burn-out, check that the screws are tightly fastened.
  • Check the specifications for the power source.
  • Confirm that electrical capacity is sufficient.
  • Confirm that starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
  • Confirm that the cable thickness is as specified in the power source specifications.
  • Always install an earth leakage circuit breaker in wet or moist areas.
  • The following can be caused by a drop in voltage: vibration of a magnetic switch, damaging the contact point, broken fuses, and disturbance of normal functioning.
  • Disconnection from a power supply must be incorporated into the fixed wiring. It must have an air gap contact separation of at least 3mm in each active (phase) conductors.
  • Before accessing terminals, all supply circuits must be disconnected.

BEKO BGMPI 090 - Installation - 14

To satisfy the EMC compulsory regulations, which is required by the international standard CISPR 14-1:2005/A2:2011 in specific countries or districts, please make sure you apply the correct magnetic rings on your equipment according to the wiring diagram that adhere to the your equipment. Please contact your distributor or installer to get further information and purchase magnetic rings (The supplier of magnetic ring is TDK (model ZCAT3035-1330) or similar).

6.1 Preparations and precautions

Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant circuit, removing any non-condensable gas and moisture from the system.

Evacuation should be performed upon initial installation and when unit is relocated.

6.1.1 Before performing evacuation

  • Check to make sure the connective pipes between the indoor and outdoor units are connected properly.
  • Check to make sure all wiring is connected properly.

6.1.2 Evacuation instructions

Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know how to use them properly.

Manifold Gauge, Compound gauge, -76cmHg, Pressure gauge, Low pressure, Low pressure valve, Pressure hose / Charge hose, High pressure valve, Charge hose, Vacuum, Vacuum pump, Low pressure valve

  1. Connect the manifold gauge's charge hose to the service port on the outdoor unit's low pressure valve.
  2. Connect the manifold gauge's charge hose from the to the vacuum pump.
  3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.
  4. Turn on the vacuum pump to evacuate the system.
  5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-1x105Pa).
  6. Close the manifold gauge's Low Pressure valve and turn off the vacuum pump.
  7. Wait for 5 minutes, then check that there has been no change in system pressure.

BEKO BGMPI 090 - Evacuation instructions - 2

If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.

  1. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system, then close the valve after 5 seconds.

Flare nut, valve body, valve stem, Cap

  1. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. It should read slightly higher than the atmospheric pressure.
  2. Remove the charge hose from the service port.
  3. Using hexagonal wrench, fully open both the high pressure and low pressure valves.

6 Air evacuation

BEKO BGMPI 090 - Air evacuation - 1

CAUTION! When opening valve stems, turn the hexagonal wrench until it hits against the stopper. Do not try to force the valve to open further.

  1. Tighten valve caps by hand, then tighten it using the proper tool.
  2. If the outdoor unit uses all vacuum valves, and the vacuum position is at the main valve, the system is not connected with the indoor unit. The valve must be tightened with a screw nut. Check for gas leaks before operation to prevent leakage.

6.1.3 Note on adding refrigerant

CAUTION!

• Refrigerant charging must be performed after wiring, vacuuming, and the leak testing. - DO NOT exceed the maximum allowable quantity of refrigerant or overcharge the system. Doing so can damage the unit or impact its functioning. - Charging with unsuitable substances may cause explosions or accidents. Ensure that the appropriate refrigerant is used. - Refrigerant containers must be opened slowly. Always use protective gear when charging the system. - DO NOT mix refrigerants types. - For the R290 or R32 refrigerant model, make sure the conditions within the area have been made safe by control of flammable material when the refrigerant added into air conditioner.

N=2 (one-twin models), N=3 (one-three models), N=4 (one-four models), N=5 (one-five models). Depending on the length of connective piping or the pressure of the evacuated system, you may need to add refrigerant. Refer to table below for refrigerant amounts to be added:

Additional refrigerant per pipe length

Connective pipe length (m)Air purging methodAdditional refrigerant
Pre-charge pipe length (ft/m) (pre-charge pipe length xN )Vacuum PumpN/A
More than (pre-charge pipe lengthxN) ft/mVacuum PumpLiquid Side: ∅ 6.35 (∅ 1/4") R32:(Total pipe length - pre-charge pipe lengthxN) x 12g/m(Total pipe length - pre-charge pipe lengthxN) x 0.13oZ/ftLiquid Side: ∅ 9.52 (∅ 3/8") R32:(Total pipe length - pre-charge pipe lengthxN) x 24g/m(Total pipe length - pre-charge pipe lengthxN) x 0.26oZ/ft
Liquid Side: ∅ 6.35 (∅ 1/4") R410A:(Total pipe length - pre-charge pipe lengthxN) x 15g/m(Total pipe length - pre-charge pipe lengthxN) x 0.16oZ/ftLiquid Side: ∅ 9.52 (∅ 3/8") R410A:(Total pipe length - pre-charge pipe lengthxN) x 30g/m(Total pipe length - pre-charge pipe lengthxN) x 32oZ/ft

BEKO BGMPI 090 - CAUTION! - 1

The standard pipe length is 7.5m.

Only for Australia models:

- DO NOT mix refrigerants types. N = 2 (one-twin models), N = 3 (one-three models), N = 4 (one-four models), N = 5 (one-five models). Some systems require additional charging depending on pipe lengths. The standard pipe length is 10m. The additional refrigerant to be charged can be calculated using the following formula:

Additional refrigerant per pipe length

Connective pipe length(m)Air purging methodAdditional refrigerant
Less than Standard pipe length x NVacuum PumpN/A
More than Standard pipe length x NVacuum PumpLiquid Side: ∅ 6.35 (∅ 1/4") (Total pipe length - pre-charge pipe lengthxN) x15g/mLiquid Side: ∅ 9.52 (∅ 3/8") (Total pipe length - pre-charge pipe lengthxN) x30g/m

Make sure to remove the additional refrigerant charge according to the rated volume (5m refrigerant piping) when doing market or government verification test.

6.2 Safety and leakage check

6.2.1 Electrical safety check

Perform the electrical safety check after completing installation. Cover the following areas:

  1. Insulated resistance
  2. The insulated resistance must be more than 2MΩ .
  3. Grounding work After finishing grounding work, measure the grounding resistance by visual detection and using the grounding resistance tester. Make sure the grounding resistance is less than 4Ω .
  4. Electrical leakage check (performing during test while unit is on).
  5. During a test operation after completed installation, the use the electroprobe and multimeter to perform an electrical leakage check. Turn off the unit immediately if leakage happens. Try and evaluate different solutions until the unit operates properly.

6.2.2 Gas leak checks

  1. Soap water method: Apply a soap-water solution or a liquid neutral detergent on the indoor unit connection or outdoor unit connections with a soft brush to check for leakage of the connecting points of the piping. If bubbles emerge, the pipes are experiencing leakage.
  2. Leak detector Use the leak detector to check for leakage.

BEKO BGMPI 090 - Gas leak checks - 1

The illustration is for example purposes only. The actual order of A, B, C, D, and E on the machine may be slightly different from the unit you purchased but the general shape will remain the same.

Outdoor unit check point, Indoor unit check point, A, B, C, D, E

A, B, C, D are points for one-four type. A, B, C, D, and E are points for the one-five type.

7.1 Before test run

A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:

  1. The indoor and outdoor units are properly installed.
  2. Piping and wiring are properly connected.
  3. No obstacles near the inlet and outlet of the unit that might cause poor performance or product malfunction.
  4. The refrigeration system does not leak.
  5. Drainage system is unimpeded and draining to a safe location.
  6. The heating insulation is properly installed.
  7. The grounding wires are properly connected.
  8. Length of the piping and additional refrigerant stow capacity have been recorded.
  9. The power voltage is the correct voltage for the air conditioner.

BEKO BGMPI 090 - Before test run - 1

CAUTION! Failure to perform the test run may result in unit damage, property damage or personal injury.

7.2 Test run instructions

  1. Open both the liquid and gas stop valves.
  2. Turn on the main power switch and allow the unit to warm up.
  3. Set the air conditioner to COOL mode.
  4. For the Indoor Unit
  5. Ensure the remote control and its buttons work properly.
  6. Ensure the louvers move properly and can be changed using the remote control.
  7. Double check to see if the room temperature is being registered correctly.
  8. Ensure the indicators on the remote control and the display panel on the indoor unit work

properly.

  • Ensure the manual buttons on the indoor unit works properly.
  • Check to see that the drainage system is un- impeded and draining smoothly.
  • Ensure there is no vibration or abnormal noise during operation.

5. For the Outdoor Unit

  • Check to see if the refrigeration system is leaking.
  • Make sure there is no vibration or abnormal noise during operation.
  • Ensure the wind, noise, and water generated by the unit do not disturb your neighbors or pose a safety hazard.

BEKO BGMPI 090 - For the Outdoor Unit - 1

If the unit malfunctions or does not operate according to your expectations, please refer to the Troubleshooting section of the Owner's Manual before calling customer service.

8 Function of automatic wiring/piping correction

8.1 Automatic wiring/piping correction function

More recent models now feature automatic correction of wiring/piping errors. Press the “check switch” on the outdoor unit PCB board for 5 seconds until the LED displays “CE”, indicating that this function is working. Approximately 5-10 minutes after the switch is pressed, the “CE” disappears, meaning that the wiring/piping error is corrected and all wiring/piping is properly connected.

8 Function of automatic wiring/piping correction

Check switch, LED display

graph LR A["Outdoor unit"] --> B["Terminal block"] A --> C["Liquid/ Gas pipe"] B --> D["Indoor unit B"] C --> E["Indoor unit A"] D --> F["Indoor unit B"] E --> F

graph LR A["Outdoor unit"] -->|Incorrect wiring| B["Terminal block"] A -->|Incorrect wiring| C["Liquid/ Gas pipe"] B --> D["Indoor unit B"] C --> E["Indoor unit A"] D --> F["Indoor unit B"] E --> G["Indoor unit A"]

Incorrect wiring, Terminal block, Liquid/liquid gas pipe, Outdoor unit, B, A, B, A, Indoor unit B, Indoor unit A

8.2 How to activate this function

  1. Check that outside temperature is above 5°C. (This function does not work when outside temperature is not above 5°C)
  2. Check that the stop valves of the liquid pipe and gas pipe are open.
  3. Turn on the breaker and wait at least 2 minutes.
  4. Press the check switch on the outdoor PCB board unit LED display "CE"

9 Troubleshooting

BEKO BGMPI 090 - Troubleshooting - 1

CAUTION! If any of the following conditions occurs, turn off your unit immediately!

  • The power cord is damaged or abnormally warm.
  • You smell a burning odor.
  • The unit emits loud or abnormal sounds.
  • A power fuse blows or the circuit breaker frequently trips. • Water or other objects fall into or out of the unit.

- Do not attempt to fix these yourself! Contact an authorized Service provider immediately!

9.1 Common issues

The following problems are not a malfunction and in most situations will not require repairs.

Issue Possible Causes
Unit does not turn on when pressing ON/OFF buttonThe Unit has a 3-minute protection feature that prevents the unit from overloading. The unit cannot be restarted within three minutes of being turned off.
Cooling and Heating Models: If the Operation light and PRE-DEF (Pre-heating/ Defrost) indicators are lit up, the outdoor temperature is too cold and the unit's anti-cold wind is activated in order to defrost the unit.
In Cooling-only Models: If the “Fan Only” indicator is lit up, the outdoor temperature is too cold and the unit's anti-freeze protection is activated in order to defrost the unit.
The unit changes from COOL mode to FAN modeThe unit changes its setting to prevent frost from forming on the unit. Once the temperature increases, the unit will start operating again.
The set temperature has been reached, at which point the unit turns off the compressor. The unit will resume operating when the temperature fluctuates again.
The indoor unit emits white mistIn humid regions, a large temperature difference between the room's air and the conditioned air can cause white mist.
Both the indoor and outdoor units emit white mistWhen the unit restarts in HEAT mode after defrosting, white mist may be emitted due to moisture generated from the defrosting process.
The indoor unit makes noisesA squeaking sound is heard when the system is OFF or in COOL mode. The noise is also heard when the drain pump (optional) is in operation.
A squeaking sound may occur after running the unit in HEAT mode due to expansion and contraction of the unit's plastic parts.

9 Troubleshooting

Both the indoor unit and outdoor unit make noisesA low hissing sound may occur during operation. This is normal and is caused by refrigerant gas flowing through both the indoor and outdoor units.
A low hissing sound may be heard when the system starts, has just stopped running or is defrosting. This noise is normal and is caused by the refrigerant gas stopping or changing direction.
The outdoor unit makes noisesThe unit will make different sounds based on its current operating mode.
Dust is emitted from either the indoor or outdoor unitThe unit may accumulate dust during extended periods of non-use, which will be emitted when the unit is turned on. This can be mitigated by covering the unit during long periods of inactivity.
The unit emits a bad odorThe unit may absorb odors from the environment (such as furniture, cooking, cigarettes, etc.) which will be emitted during operations.
The unit's filters have become moldy and should be cleaned.
The fan of the outdoor unit does not operateDuring operation, the fan speed is controlled to optimize product operation.

9 Troubleshooting

9.2 Troubleshooting tips

When troubles occur, please check the following points before contacting a repair company.

Problem Possible Causes Solution
The unit is not workingPower failure Wait for the power to be restored
The power is turned off Turn on the power
The fuse is burned out Replace the fuse
Remote control batteries are dead Replace batteries
The Unit's 3-minute protection has been activatedWait three minutes after restarting the unit
Poor cooling performanceTemperature setting may be higher than the ambient room temperatureLower the temperature setting
The heat exchanger on the indoor or outdoor unit is dirtyClean the a ected heat exchanger
The air filter is dirtyRemove the filter and clean it according to instructions
The air inlet or outlet of either unit is blockedTurn the unit off, remove the obstruction and turn it back on
Doors and windows are openMake sure that all doors and windows are closed while operating the unit
Excessive heat is generated by sunlightClose windows and curtains during periods of high heat or bright sunshine
Low refrigerant due to leak or long-term useCheck for leaks, re-seal if necessary and top off refrigerant
The unit starts and stops frequentlyThere's too much or too little refrigerant in the systemCheck for leaks and recharge the system with refrigerant
There is air, incompressible gas or foreign material in the refrigeration system.Evacuate and recharge the system with refrigerant
System circuit is blockedDetermine which circuit is blocked and replace the malfunctioning piece of equipment
The compressor is broken Replace the compressor
The voltage is too high or too low Installa manostat to regulate the voltage

9 Troubleshooting

Poor heating performanceThe outdoor temperature is lower than 7°C (44.5°F)Check for leaks and recharge the system with refrigerant
Cold air is entering through doors and windowsMake sure that all doors and windows are closed during use
Low refrigerant due to leak or long-term useCheck for leaks, re-seal if necessary and top off refrigerant

10 European disposal guideline

This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. Do not dispose of this product as household waste or unsorted municipal waste.

When disposing of this appliance, you have the following options:

  • Dispose of the appliance at designated municipal electronic waste collection facility.
  • When buying a new appliance, the retailer will take back the old appliance free of charge.
  • The manufacturer will take back the old appliance free of charge.
  • Sell the appliance to certified scrap metal dealers.

BEKO BGMPI 090 - European disposal guideline - 1

Special notice

Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

Symbol of a trash bin crossed out, representing environmental restriction (no text present)

This symbol indicates that this product shall not be disposed with other household wastes at the end of its service life. Used device must be returned to official collection point for recycling of electrical and electronic devices. To find these collection systems please contact to your local authorities or retailer where the product was purchased. Each household performs important role in recovering and recycling of old appliance. Appropriate disposal of used appliance helps prevent potential negative consequences for the environment and human health.

11 Installation instructions

11.1 F-Gas instruction

This product contains fluorinated greenhouse gases.

The fluorinated greenhouse gases are contained in hermetically sealed equipment.

Installs, services, maintains, repairs, checks for leaks or decommissions equipment and product recycling should be carried out by natural persons that hold relevant certificates.

If the system has a leakage detection system installed, leakage checks should be performed at least every 12 months, make sure system operate properly.

If product must be performed leakage checks, it should specify Inspection cycle, establish and save records of leakage checks.

BEKO BGMPI 090 - F-Gas instruction - 1

Note: For hermetically sealed equipment, local air conditioner, window air conditioner and dehumidifier, if CO2 equivalent of fluorinated greenhouse gases is less than 10 tonnes, it should not perform leakage checks.

12 Specifications

Model name Indoor unit BGMPI 120 BGMPI 090
Cooling Capacity (kW) 3.5172.638
Heating Capacity (kW) 3.8102.931
Voltage/Frequency (V/Hz)220V-240V, 1Ph, 50Hz220V-240V, 1Ph, 50Hz
Power Supply Connection OutdoorOutdoor
Noise Pressure Level - Indoor Unit (dBA)37/32/22/2037/32/22/21
Air flow volume ( m3/h )520/460/330530/400/350
Indoor unit Resistance ClassIPX0IPX0
Indoor Unit (WxHxD) mm729×292×200802×295×200
Indoor Unit Net Weight (kg)8.09.0
Model name Outdoor unit BGMPO 181BGMPO 211BGMPO 271
Product MixBGMPI 090(x1) BGMPI 120(x1)BGMPI 120(x2)BGMPI 090(x2) BGMPI 120(x1)
Refrigerant R32 R32 R32
Total Refrigerant Amount (g) 1250 1500 1850
GWP 675 675 675
CO2 equivalent (tonnes)0.8441.0131.249
Anti-ElectricClass IClass IClass I
Climate ClassT1T1T1
Heating TypeHeat pumpHeat pumpHeat pump
Power Supply ConnectionOutdoorOutdoorOutdoor
Pdesign C (kW)5.36.17.9
Pdesign H (kW)4.3 (EU Average Season)5.4 (EU Average Season)5.7(EU Average Season)
SEER/AEER/Weight EER (W/W)6.1(SEER, EU)6.5(SEER, EU)6.1(SEER, EU)
SCOP/ACOP/Weight EER (W/W)4.0(SCOP, EU Average)4.0(SCOP, EU Average)4.0(SCOP, EU Average)
Energy Level-CoolingA++(SEER, EU)A++(SEER, EU)A++(SEER, EU)
Energy Level-HeatingA+(EU Average Season)A+(EU Average Season)A+(EU Average Season)
Annual Energy Consumption-Cooling (kWh)304 328453

12 Specifications

Model name Outdoor unit BGMPO 181 BGMPO 211 BGMPO 271
Annual Energy Consumption-Heating (kWh)1508(AB)1584(AG) 1890 1995
The declared capacity for calculation of SCOP at reference design condition (kW)3.94.75.0
The back up heating capacity assumed for calculation of SCOP at reference design condition (kW)0.40.70.7
Power of Electric Heater (W)///
Cooling Power Input (kW)///
Heating Power Input (kW)///
Voltage/Frequency (V/Hz)220V-240V,50Hz,1Ph220V-240V,50Hz,1Ph220V-240V,50Hz,1Ph
Cooling Running Current (A)///
Heating Running Current (A)///
Noise Pressure Level - Outdoor Unit (dBA) 6565 67
Rated Power Input-EN 60335(W) 3050 39104100
Rated Current Input-EN 60335(A) 13 17 18
Outdoor unit Resistance Class IPX4IPX4IPX4
High Pressure Pipe Diameter (mm)∅6.35*2∅6.35*3∅6.35*3
Low Pressure Pipe Diameter (mm) ∅12.7*2∅12.7*3∅12.7*3
Power Supply Cord specification ( mm2 )1.5x32.5x32.5x3
Indoor & Outdoor Connection Cord ( mm2 )1.5x41.5x41.5x4
Max. elevation (m)1515 15
Max. pipe length (m)4060 60
Additional Gas Quantity (g/m)1212 12
Outdoor Unit (WxHxD) mm805x554x330890x673x342890x673x342
Outdoor Unit Net Weight (kg)35.043.0 48.0

Note: 1. Specifications are standard values calculated based on rated operating conditions. They will vary in different working conditions. 2. Our company has quick technical improvements. There will be prior notice for any change of technical data. Please read the nameplate on the air-conditioner. Please refer to detailed product information required in Regulation No 206/2012 from the leaflet of Product Fiche.

Insert

BEKO BGMPI 090 - Specifications - 2

Warning:

W

Technical line drawing of a dual-panel air conditioning unit with fan blades and ventilation slots (no text or symbols)

ATechnical line drawing of a mechanical component with labeled dimensions D and B (no text or symbols beyond labels).

5 Installation

(Unit: mm/inches)

Dimensioni unità esterna (mm) Dimensioni di montaggio
L x A x P Distanza A (mm)Distanza B (mm)
760x590x285 (29,9x23,2x11,2) 530 (20,85) 290 (11,4)
810x558x310 (31,9x22x12,2) 549 (21,6) 325 (12,8)
845x700x320 (33,27x27,5x12,6) 560 (22) 335 (13,2)
900x860x315 (35,4x33,85x12,4) 590 (23,2) 333 (13,1)
945x810x395 (37,2x31,9x15,55) 640 (25,2) 405 (15,95)
990x965x345 (38,98x38x13,58) 624 (24,58) 366 (14,4)
938x1369x392 (36,93x53,9x15,43) 634 (24,96) 404 (15,9)
900x1170x350 (35,4x46x13,8) 590 (23,2) 378 (14,88)
800x554x333 (31,5x21,8x13,1) 514 (20,24) 340 (13,39)
845x702x363 (33,27x27,6x14,3) 540 (21,26) 350 (13,8)
946x810x420 (37,2x31,9x16,53) 673 (26,5) 403 (15,87)
946x810x410 (37,2x31,9x16,14) 673 (26,5) 403 (15,87)
952x1333x410 (37,5x52,5x16,14) 634 (24,96) 404 (15,9)
952x1333x415 (37,5x52,5x16,14) 634 (24,96) 404 (15,9)
890x673x342 (35,0"x 26,5"x 13,5") 663 (26,1") 354 (13,9")

Pipe, Alesatore, Pointdown

BEKO BGMPI 090 - Installation - 2

ATTENTION!

L1 L2 L1A L2A S1A L1B L2B1 S3 POTENZA OFFICIAL 1 2 3 TO A 1 2 3 TO B

L1 L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) FOTINZA L1 L2 S Or 1 2 3 T0 A L1 L2 S Or 1 2 3 T0 B X

L N LCA NCA S A L C B W D S I R OBERGATE POTENZA COCOLIATION A TO B T0 A T0 B

Model B

1 2 3 4 5 6 7 8 CYPICAL POWER N S TO A N B TO B CYPICAL POWER N S TO A N B

Model C

1.1 1.2 1.0 1.2 A 1.0 1.2 B 1.0 CYPEDOMATE POWERA OPTIZIONALE 1 2 3 10 A 1 2 3 10 B

Model D

5 Installation

L1 L2 L3 L4 L5 L6 OP-OUTRANGE FOTINZA TO A TO B

Model E

L1 L2 TOA TOA TOB POTENTIAL TOA TOB TOA TOB T0 A T0 B

Model F

W L N LT LTM NO. SHA LTM NO. SHA ALMENADOKE T0 A Y/G

Model G

graph TD A["ALIMENTATION"] --> B["L1A"] A --> C["L2B"] A --> D["TO A"] B --> E["OPZONALE"] C --> E D --> E E --> F["TO B"] F --> G["Y/G"] H["W"] --> I["L1A"] H --> J["L2B"] H --> K["TO B"] L["N"] --> M["L1A"] L --> N["L2B"] L --> O["TO B"] P["I"] --> Q["L1A"] P --> R["L2B"] P --> S["TO B"]

Model H

L1 L2 L1A L2A L3A L1B L2B SBI OCTRNDIAL PULENA OCTRNDIAL L N S Q T0 A L N S Q T0 B

5 Installation

L1 L2 L1A L2A S1A L1B L2B S3B OPTIONAL POTENZA OPTIONAL OPTIONAL 1 2 3 TO A TO B

I1 I2 I10 I20 S0 I18 I28 S0 OPTIONAL OPTIONAL OPTIONAL OPTIONAL POTENZA TO A TO B

1 2 1A 2A 1A 1B 2B 1B OPTIONAL POTENZA 1 2 3 TO A 1 2 3 TO B OPTIONAL OPTIONAL TO A TO B

Model P Model Q Model RL1 L2 1(A) 2(A) 3(A) 1(B) 2(B) 3(B) OPTIONAL ALIMENTAZIONE 1 2 3 TO A 1 2 3 TO B OPTIONAL OPTIONAL

L1 L2 L1(A) L2(A) S(A) L1(B) L2(B) S(B) OPTIONAL ALIMENTAZIONE L1(A) L2(A) S(A) L1(B) L2(B) S(B) OPTIONAL 1 2 3 TO A 1 2 3 TO B

Model T Model S

graph TD A["Power Supply"] --> B["POTENZA"] B --> C["Component 1: L N L(A) N(S) L(B)"] B --> D["Component 2: L N S"] C --> E["Verso l'unità interna A"] D --> F["Verso l'unità interna B"] G["External Component"] --> H["Component 3: L N S"] G --> I["Component 4: L N S"] G --> J["Component 5: L N S"] s…

Model U

LAY N/A1 S/N LAY N/A1 S/N OPTIONAL L N S OR ON L N S or or or W To-Indoor Interna A W To-Indoor Interna B OPTIONAL

Model W

5 Installation

Models One-Three:graph TD subgraph Power Supply A["TONICANALI"] --> B["POWER"] B --> C["TO A"] D["TONICANALI"] --> E["POWER"] E --> F["TO B"] G["TONICANALI"] --> H["POWER"] H --> I["TO C"] end subgraph Circuit Breakers J["TONICANALI"] --> K["POWER"] K --> L["TO A"] M["TONICANALI"] --> N["POWER"] N --> O["TO B"] P["T…

Model A

graph TD A["Power Source"] --> B["Tower"] B --> C["Transformer"] C --> D["Terminal Block 1"] C --> E["Terminal Block 2"] C --> F["Terminal Block 3"] C --> G["Terminal Block 4"] C --> H["Terminal Block 5"] C --> I["Terminal Block 6"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C…

Model B Model C

graph TD subgraph Operational Amplifier 1 A["TO A"] --> B["POWER"] C["TO B"] --> D["POWER"] E["TO C"] --> F["POWER"] end subgraph Operational Amplifier 2 G["TO A"] --> H["POWER"] I["TO B"] --> J["POWER"] K["TO C"] --> L["POWER"] end A --> M["POTENZA"] C --> N["POWER"] E --> O["POWER"] G --> P["POWER…

graph TD A["Terminal L1"] --> B["Component"] C["Terminal L2"] --> B D["Terminal L3"] --> B E["Terminal L4"] --> B F["Terminal L5"] --> B G["Terminal L6"] --> B H["Terminal L7"] --> B I["Terminal L8"] --> B J["Terminal L9"] --> B K["Terminal L10"] --> B L["Terminal L11"] --> B M["Terminal L12"] --> B…

POWER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 POWER 1 TO A POWER 1 TO B POWER 1 TO C

L N L A M A S A T0 10A PULN/A T0 10A T0 10B T0 10C T0 10D T0 10E T0 10F T0 10G T0 10H T0 10I T0 10J T0 10K T0 10L T0 10M T0 10N T0 10O T0 10P T0 10Q T0 10R T0 10S T0 10T T0 10U T0 10V T0 10W T0 10X T0 10Y T0 10Z T0 10A T0 10B T0 10C

Model D Model E Model FPOWER N/A TO A TO B TO C

Model G

1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 POWER/AC 1.2 1.3 TO A (2)PZ000000000000000000000000000000000000000000000000000000000000000000000000 1.2 1.3 TO B 1.2 1.3 TO C

L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L10 L11 L12 L13 L14 L15 L16 L17 L18 L19 L20 L20 L21 L22 L23 L24 L25 L26 L27 L28 L29 L30 L30 L31 L32 L33 L34 L35 L36 L37 L38 L39 L40 L40 L41 L42 L43 L44 L45 L46 L47 L48 L49 L50 L50 L51 L52 L53 L54 L55 L56 L57 L58 L59 L60 L60 L61 L62 L63 L64 L65 L66 L67 L68 L69 L70 L71 L…

Model I Model H Model G

graph TD subgraph Power Unit L1["L"] --> L2["L(A)"] L3["L"] --> L4["N(A)"] L4 --> L5["S(A)"] L5 --> L6["L"] L6 --> L7["B"] L7 --> L8["N(B)"] L8 --> L9["S(B)"] end subgraph Power Unit L10["L"] --> L11["N"] L12["L"] --> L13["S"] L13 --> L14["OR"] L14 --> L15["OR"] L15 --> L16["OR"] L16 --> L17["OR"] L…

Model J

Models One-Four:L1 L2 OPTIONAL ALIMENTAZIONE TO A TO B TO C TO D

Model H

5 Installation

L1 L2 L1A L2A S1V OPR0N4E POTR0A OPR0N4E L1B L2B S1B L1C L2C S1C L1D L2D S1D T0 A T0 B T0 C T0 D

Model L

L N L(A) N(A) S(A) L(B) N(B) S(B) L(C) N(C) S(C) L(D) N(D) S(D) ORANGE FOR BHA L N S O R 10Ω 20Hz E 10Ω 20Hz E W 10Ω 20Hz S ORANGE FOR C L N S O R 10Ω 20Hz E 10Ω 20Hz E W 10Ω 20Hz S ORANGE FOR D L N S O R 10Ω 20Hz E 10Ω 20Hz E W 10Ω 20Hz S ORANGE FOR E L N S O R 10Ω 20Hz E 10Ω 20Hz E W 10Ω 20Hz S OR…

Model M

Models One-Five:N LONAM R1 R2 POTTA OPTZIONALE LNS LNS DT TO A TO B OPTZIONALE LNS LNS DT TO C TO D TO E

Model A

L N L A N A S A L B R S E 120 NC 32M 120 M1 32M 120 M1 32M OPTINZA OPTINZA OPTINZA OPTINZA OPTINZA TO A TO B TO C TO D TO E

Model B

Symbol of a trash bin crossed with no text or numbers, representing environmental restriction (no text present)

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : BEKO

Model : BGMPI 090

Category : Air conditioner