USER MANUAL MELLIZO Soler & Palau

natural_image Exterior view of a large industrial air duct or fan unit with a control panel and circular vent (no visible text or symbols)

INDEX

  1. RECOMMENDATIONS......5
  2. GENERAL....5

2.1. Speed Control Inputs....5
2.2. Installer-defined Fixed Speed Control 5
2.3. Remote Switching....5
2.4. Fan-Fail Detection by Fault Sensing....5
2.5. Outputs .... 5
2.6. Analog Switch Outputs....5

  1. TRANSPORT AND HANDLING....6
  2. SAFETY RULES 6

4.1. ON INSTALLATION....6
4.2. AT START UP 6

  1. MECHANICAL INSTALLATION....7
  2. MELLIZO POWER CONNECTIONS....8
  3. CONTROL WIRING....9

7.1. REMOTE ENABLE (VOLT-FREE CONTACT) 9
7.2. REMOTE ENABLE (230V)....10
7.3. 0-10V (1 SIGNAL)....11
7.4. 0-10V (2 SIGNALS)....12
7.5. REB-CVF 13
7.6. REB-ECOWATT....14
7.7. PREP/COOK SWITCH....15
7.8. 3-SET SPEEDS (VOLT-FREE CONTACT)....16
7.9. 3-SET SPEEDS (230V)....17
7.10. AIRSENS (0-10V)....18
7.11. AIRSENS (TRICKLE/BOOST)....19
7.12. AIRSENS (REMOTE ENABLE)....20
7.13. EXTERNAL FAULT....21
7.14. RELAY OUTPUT....22
7.15. TIMER FUNCTION....23

  1. MAINTAINENCE 24
  2. Warranty....24
  3. RECYCLING....24
  4. EC DECLARATION OF CONFORMITY....25
  5. DESIGNATION OF EQUIPMENT 25

  6. GUARANTEE......25

1. RECOMMENDATIONS

You have purchased a MELLIZO twin fan designed specifically by Soler & Palau to perform the functions described in the table of contents.

Before you install and start up this product, please read this instruction book carefully because it contains important information for your safety and the safety of users during installation, use and maintenance. Once installation is complete, please pass the instruction book on to the end user. Please check that the equipment is in perfect condition when you unpack it since any factory defect is covered under the S&P guarantee. Please also check that the equipment is the one that you have ordered and that the information on the instruction plate meets your requirements.

2. GENERAL

The Mellizo range comprises of two inline centrifugal fans in an acoustically lined cabinet; each fan works independently for run and standby plus 3 to 24 hours duty-share function with the display indicating the status of the unit.

2.1. Speed Control Inputs

• Variable Speed Control
• Manual variable speed control via an optional secondary S&P REB ECOWATT or REB-CVF controller, or
- Automated variable speed control via a 0-10V signal from an external source.

2.2. Installer-defined Fixed Speed Control

  • An upon-installation defined duty either continuous or on-demand (triggered by an external switch), or
  • One, two or three speeds defined during installation to provide a minimum/middle/maximum speed ventilation system, the middle and maximum speeds being selected by an external switch/sensor (either Volt-free and/or 230V).
  • Note that there is a 3-Volt minimum output to the fan to ensure start-up momentum.

2.3. Remote Switching

  • The switching between the (up to) three speeds can be activated by either:
    • (Up to) Three Volt-free contacts, or
    • (Up to) Three 230V supply inputs
  • On/Off – Volt-Free Contact and/or 230V
  • External Fire Fan Shut-Off Switch – An external “Fire” switch (Volt-Free) can be connected, If the switch opens signifying that the fire alarm has been activated, then the MULTI-REG Controller will automatically stop the fan.

2.4. Fan-Fail Detection by Fault Sensing

• Automatic monitoring of the impeller rotation via the Tacho pulse (frequency generator) signal.
- Low current sensing to indicate a connection open circuit problem.
- Sixty seconds time-delay of fault detection on start-up to allow input levels to normalise.
- Facility to connect an Airflow Switch or Differential Pressure Switch (DPS), for use on fans where other options are not practical. There is approximately a 60 seconds delay in the operation of the airflow switch monitoring system, to allow full airflow to develop.

2.5. Outputs

  • Digital Display
  • Running, Stopped and/or fault condition.
  • Fan speed percentage and 0-10V output condition.
  • Countdown to fault status monitoring condition (allows fan to gain speed).
  • Diagnostic – Reasons for fan stop/fail.

2.6. Analog Switch Outputs

- Output to BMS of fan run and fault indicated by an individual set of contacts capable of controlling a maximum load of up to 230 Volts at 8 Amps.

3. TRANSPORT AND HANDLING

  • The equipment packaging has been designed to withstand normal transport conditions. The equipment must not be transported without its original packaging as it could become damaged.
  • The product must be stored in its original packaging and in a dry and clean place until it is installed. Do not accept any equipment that is not supplied in its original packaging or that shows signs of having been tampered with.
  • Prevent the packaging from falling or being knocked
  • Do not place heavy loads on top of it.
  • When handling heavy products, adequate lifting equipment techniques and equipment should be used to avoid injury.
  • Do not lift a product by pulling the wires, terminal/control enclosure, shutter or impeller to avoid damaging the product.

4. SAFETY RULES

4.1. ON INSTALLATION

• Installation and commissioning must be done by a qualified professional specialist.
- Ensure that installation complies with mechanical and electrical regulations in each country.
- Once commissioned, the equipment must comply with the following Directives:
- Standard for Low Pressure Instalments 2006/95/CE
- Machinery Standard 2006/42/CE
- Standard for Electromagnetic Compatibility 2004/108/CE

- Do not use this equipment in explosive or corrosive atmospheres.

4.2. AT START UP

  • Make sure there are no loose elements near the ventilator, as they could run the risk of being sucked up by it. If it is going to be installed in a duct, check that it is clean of any element that could be sucked up by the ventilator.
  • When installing an apparatus, make sure that all the fittings are in place and that the structure which supports it is resistant enough to bear its weight at full functioning power.
  • Before you handle this equipment, ensure it is disconnected from the mains power supply.
  • Check that the mains voltage and frequency are the same as specified on the name plate.
  • Follow the wiring diagram to make the electrical connections.
  • Check that the earthing, if any, is correct and that the thermal and surge protection has been connected and are within the relevant limits.
  • If a ventilator is installed in a duct, the duct must be exclusively for the ventilation system.

5. MECHANICAL INSTALLATION

The product should only have the airflow going vertically up and horizontally. In this orientation it is suitable for fitment onto a suitable supportive structure and secured through the 4 fixing holes provided.

Soler & Palau MELLIZO - MECHANICAL INSTALLATION - 1

  • Leave an air space of not less than 150mm around the edges control enclosure to allow cooling air to flow freely.
  • Leave an additional gap in front of the control enclosure lid to allow for access during installation/wiring/maintenance.
  • Do not install in close proximity to other heat sources.
    • The maximum ambient temperature for the control board must not exceed 40°C.

The 2 fans integrated into the product are separately wired into a MELLIZO control panel located in an enclosure box positioned on the external casing.

6. MELLIZO POWER CONNECTIONS

This basic wiring must be followed for every installation!!!

L - Live

N - Neutral

E - Earth

Soler & Palau MELLIZO - MELLIZO POWER CONNECTIONS - 1

text_image FAN A N/N + D/N O/N C/N O/N Fault B/654321 Fan trip current under current off on Display 7/n1 add 7 pt ic 24v 0v c/o Remote TX Transformer Fuse B CT3 + REMOTE ON/OFF 230V INPUTS I/P1 I/P2 I/P3 High Mid High 230V OUT/PUTS MIN SPEED MID SPEED MID SPEED HIGH SPEED Changeover Button Tacho B off FIRE n/c n/o Switch1 OFF n/c n/o Tacho A off 24 21 18 15 12 9 6 3 RED Fuse A RET3 RT2 RT1 L N E Fan A L2 L3 N1 Fan B L/N 230V AC SUPPLY POWER L N I/P3 I/P2 I/P1 MID I/p MID I/P2 MID I/P3 MID I/P4 MID I/P5 MID I/P6 MID I/P7 MID I/P8 MID I/P9 MID I/P10 MID I/P11 MID I/P12 MID I/P13 MID I/P14 MID I/P15 MID I/P16 MID I/P17 MID I/P18 MID I/P19 MID I/P20 MID I/P21 MID I/P22 MID I/P23 MID I/P24 MID I/P25 MID I/P26 MID I/P27 MID I/P28 MID I/P29 MID I/P30 MID I/P31 MID I/P32 MID I/P33 MID I/P34 MID I/P35 MID I/P36 MID I/P37 MID I/P38 MID I/P39 MID I/P40 MID I/P41 MID I/P42 MID I/P43 MID I/P44 MID I/P45 MID I/P46 MID I/P47 MID I/P48 MID I/P49 MID I/P50 MID I/P51 MID I/P52 MID I/P53 MID I/P54 MID I/P55 MID I/P56 MID I/P57 MID I/P58 MID I/P59 MID I/P60 MID I/P61 MID I/P62 MID I/P63 MID I/P64 MID I/P65 MID I/P66 MID I/P67 MID I/P68 MID I/P69 MID I/P70 MID I/P71 MID I/P72 MID I/P73 MID I/P74 MID I/P75 MID I/P76 MID I/P77 MID I/P78 MID I/P79 MID I/P80 MID I/P81 MID I/P82 MID I/P83 MID I/P84 MID I/P85 MID I/P86 MID I/P87 MID I/P88 MID I/P89 MID I/P90 MID I/P91 MID I/P92 MID I/P93 MID I/P94 MID I/P95 MID I/P96 MID I/P97 MID I/P98 MID I/P99 MID I /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p / p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /p /m A C S U P P L Y P O W P E R

7.1. REMOTE ENABLE (VOLT-FREE CONTACT)

Soler & Palau MELLIZO - REMOTE ENABLE (VOLT-FREE CONTACT) - 1

text_image FAN A D/N O N + FAN B D/N O N Fault D/N O N - 7654321 Fan (rip current) under current off on Display v1s1 add r g1 ic 24v c/o Remote 0v TX Transformer 230V INPUTS 230V OUTPUT I/P1 I/P2 I/P3 Mid High High Tacho B OFF FIREn/c n/o Switch1 OFF n/c n/o Tacho on off Tacho on A 24 21 18 15 12 9 6 3 RED Fuse A Fuse B RT3 RT2 RT1 230V S MIN SPEED MID SPEED MID SPEED HIGH SPEED Changeover Button Add Pull up Register Yes No L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N I/PI2 230V Remote Enable HIOH 0v SM1 FIRE +10 HIOH 0v Tsc 0v Tsc B I/PI2 230V MID i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/p i/mo/FF VIA EXTERNAL VOLT-FREE SWITCH E.G. PIR SENSOR CLOSED CIRCUIT = RUN

Fan speed set-point (Min Speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan.

7.2. REMOTE ENABLE (230V)

Soler & Palau MELLIZO - REMOTE ENABLE (230V) - 1

text_image REMOTE ENABLE JUMPER JUMPER LINK ON "REMOTE ON/OFF" NO JUMPER LINK ON "/P1" Transformer RED Fuse A RED L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N I/P2 I/P3 I/P1 RT3 RT2 RT1 FAN A FAN B FAN C C/D C/D C/D C/D Fault C/D C/D C/D 7/6 5/3 2/1 Fan trip current under current off on Display v/n/s sec F st lc 24v c/o Remote 8v TX 0switch2 off FIRE n/c n/o 8switch1 Tacho B on off Tacho A off HIGH SPEED Changeover Button Add Pull up Register Yes No MIN SPEED MID SPEED MID SPEED HIGH SPEED MIN SPEED MID SPEED HIGH SPEED REMOTE ENABLE HIGH I/p SM1 FIRE +10 o/p HIGH o/p Fan o/p Fan o/p Remote Enable HIOH i/p Mid i/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD o/p MHD O/P U/S WITCHABLE 230V AC SUPPLY E.G. LIGHT SWITCH

Fan speed set-point (Min Speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan.

7.3. 0-10V (1 SIGNAL)

Soler & Palau MELLIZO - 0-10V (1 SIGNAL) - 1

text_image FAN A C/N C/N + FAN B C/N C/N Fault C/N C/N - 87654321 Fan trip current under current off on Display v/mb sec.7 pt.1c 24v 0v Remote TX Transformer Fuse B CTA 238V INPUTS I/P1 I/P2 I/P3 +10 Mid High High REMOTE ON/OFF 238V OUT/PUTS HIOH I/P1 MIN SPEED MID SPEED HIOH SPEED MID SPEED HIGH SPEED HIGH SPEED Changeover Button Techo B off Techo on A off 24 21 18 15 12 9 6 3 RED Fuse A RT3 RT2 RT1 L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N N/1/238V 238V Remote Enable HIGH 0v SW1 FIRE +10 0v HIGH 0v Fan Tac 0v Tac B MID i/p MID o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid O-10V INPUT SIGNAL FROM EXTERNAL DEVICE

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed (0-10V)

The speed is defined by the voltage from the 0 - 10V signals from the external devices; the minimum output is 3V.

7.4. 0-10V (2 SIGNALS)

Soler & Palau MELLIZO - 0-10V (2 SIGNALS) - 1

text_image FAN A N N O + FAN B N N O Fault N D N O 8 7 6 5 +3 2 1 Fan trip current under current off on Display y/n3 add r pt lc 24v c/o Remote 0v TX Transformer Fuse B CTS 230V INPUTS 1/P1 1/P2 1/P3 Mid +18 High High REMOTE ON/OFF 230V OUT/PUTS H10H MIN SPEED MID SPEED H10H SPEED TACHO ON OFF Tacho A OFF 24 21 18 15 12 9 6 3 RED Fuse A RET3 RT2 RT1 MIN SPEED MID SPEED H10H SPEED Changeover Button Add Pull up Register Yes No L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N N I/PE 230V Remote Enable HIGH o/v SM1 FIRE +10 o/p SM2 +10 o/p MID o/p MHD o/p Fan A o/p Fan B o/p D-10V INPUT SIGNAL FROM EXTERNAL DEVICE O-10V INPUT SIGNAL FROM EXTERNAL DEVICE 0-10V 0V 0-10V 0V

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed (0-10V)

The speed is defined by the highest voltage from the two 0 - 10V signals from external devices; the minimum output is 3V.

7.5. REB-CVF

Soler & Palau MELLIZO - REB-CVF - 1

text_image FAN A FAN B Fault 230V INPUTS I/P1 I/P2 I/P3 +18 Mid High High REMOTE ON/OFF 230V OUT/PUTS H10H MID MIN SPEED MID SPEED MID SPEED HIGH SPEED UNDER CURRENT OFF ON Display +/- TX 16 24v c/o Remote TX 24 21 18 15 12 9 6 3 Transformer Techo B on off Tacho on A OFF Changeover Button SH Add Pull Register Yes No RED Fuse A RED L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N N 230V Remote Enable H10H I/p 0v SH1 FIRE +10 o/p H10H o/p Mid o/p Fan A Fan B o/p REC-CVF Mid i/p SW1 FIRE +10 o/p H10H o/p Mid o/p Fan A Fan B o/p

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed

The speed is defined by rotating the dial on the REB-CVF.

7.6. REB-ECOWATT

Soler & Palau MELLIZO - REB-ECOWATT - 1

text_image FAN A N N O N + FAN B N N O N Fault 8 7 6 5 + 3 2 1 Fan (r) p current under current off on Display v in1 add r gt lc 24v c/o Remote 0v TX Transformer 230V INPUTS I/P1 I/P2 I/P3 +18 Mid High High 230V OUT/PUTS I/P1 I/P2 HIGH MID MIN SPEED MID SPEED HIGH SPEED Tacho on off Tacho on A OFF Changeover Button 24 21 18 15 12 9 6 3 RED Fuse A Fuse B RT3 RT2 RT1 L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N I/I I/2 230V I/I1 I/I2 Remote Enable HIGH 0v SW1 FIRE +18 +o/p HIGH 0v Tsc 0v Tsc B Mid i/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o /250VAC REB-ECOWATT

PRIOR TO ENERGISING THE MULTI-REG, THE INSTALLER MUST SET ALL THREE OF THE SPEED POTENTIOMETERS TO THEIR MINIMUM (FULLY ANTI-CLOCKWISE)!!!

Fan speed

The speed is defined by rotating the dial on the REB-ECOWATT.

7.7. PREP/COOK SWITCH

Soler & Palau MELLIZO - PREP/COOK SWITCH - 1

text_image FAN A FAN B Fault under current 24v c/o Remote 0v TX 87654321 off on Display v/n1 sec r pt lc Transformer FUSE B 230V INPUTS 1/P1 I/P2 I/P3 Mid High REMOTE ON/OFF 230V OUT/PUT S MIN SPEED MID SPEED HIOH HIGH HIGH MID HIGH SPEED CHANGEover I/P1 I/P2 HIGH M D MID SPEED MHD I/P3 I/P4 HIGH M D HIGH SPEED Changeover RT3 RT2 RT1 L N E L N L2 L3 NI L N Fan B Remote Enable HIGH 0v SW1 FIRE +10 o/p HIGH 0v Tsc 0v Fan A Fan B SUPPLY L N Fan A ACTUATOR L N Fan B Mid i/p MW1 FIRE 0v 0v Tsc 0v Fan B PREP/COOK SWITCH PREP/COOK OFF COM COM 2 WAY 1 WAY 2 WAY 1 WAY

Prep speed set-point (Min speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Cook speed set-point (High speed)

The speed is defined by the 'High speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

7.8. 3-SET SPEEDS (VOLT-FREE CONTACT)

Soler & Palau MELLIZO - 3-SET SPEEDS (VOLT-FREE CONTACT) - 1

text_image FAN A FAN B Fault 87654321 under current off on Display 24v c/o Remote 0v TX Transformer Fuse B CTS Fan trip current 230V INPUTS I/P1 I/P2 I/P3 +10 High Mid High 230V OUT/PUT H10H I/P1 I/P2 H10H M D MIN SPEED MID SPEED HIGH SPEED Changeover I/P3 H10H M D MIN SPEED MID SPEED HIGH SPEED Button L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N 230V Remote Enable HIGH 0v SW1 FIRE +10 H10V 0v TAC 0v Tac A o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /o /n REMOTE ENABLE ON/OFF VIA EXTERNAL VOLT-FREE SWITCH E.G. FIR SENSOR CLOSED CIRCUIT = RUN OPTIONAL SECOND SPEED VIA EXTERNAL VOLT-FREE CONTACT OPTIONAL THIRD SPEED VIA EXTERNAL VOLT-FREE CONTACT OPTIONAL SECOND SPEED VIA EXTERNAL VOLT-FREE CONTACT

Trickle speed set-point (Min speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Second speed set-point (Mid speed)

The speed is defined by the 'Mid speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Third speed set-point (High speed)

The speed is defined by the 'High speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

7.9. 3-SET SPEEDS (230V)

Soler & Palau MELLIZO - 3-SET SPEEDS (230V) - 1

text_image REMOTE ENABLE JUMPER JUMPER LINK ON "REMOTE ON/OFF" NO JUMPER LINK ON "/P1" FAN A D/N O/N o+ FAN B D/N O/N o- Fault D/N O/N o- 8 7 6 5 4 3 2 1 Fan trip current under current off on Display v/n1 add F st ic 24v c/o Remote 8v TX Transformer 230V INPUTS SWITCH2 off FIREn/c n/o Switch1 Tacho on OFF Tacho on A 24 21 18 15 12 9 6 3 Fuse B CTB +10 High I/P1 I/P2 I/P3 Mid High REMOTE ON/OFF 230V OUT/PUT S MIN SPEED MID SPEED HIGH SPEED Changeover Button Add Pull Up Yes No RT3 I/P1 D MIN SPEED MID SPEED HIGH SPEED Register Yes No RT2 I/P2 H10H M D I/P3 H10W N D MIN SPEED MID SPEED HIGH SPEED Register Yes No L N E L N Fan A L2 L3 N1 L N Fan B N N I/P2 I/P1 I/P2 I/P1 Remote Enable H10H 0v SW1 FIRE +18 o/p H10H 0v Tsc 0v Tac B MID i/p MID o/p MID o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid o/p Mid O P U P REMOTE ENABLE L ON/OFF VIA SWITCHABLE 230V AC SUPPLY E.G. LIGHT SWITCH OPTIONAL SECOND SPEED L SECOND SPEED VIA SWITCHABLE 230V AC SUPPLY N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N-N Potential Second Speed OPTIONAL THIRD SPEED L THIRD SPEED VIA SWITCHABLE 230V AC SUPPLY

Trickle speed set-point (Min speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Second speed set-point (Mid speed)

The speed is defined by the 'Mid speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Third speed set-point (High speed)

The speed is defined by the 'High speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

The speed is defined by the AIRSENS sensor, which will proportionally increase its control voltage depending on the pollutants or humidity in the air.

7.11. AIRSENS (TRICKLE/BOOST)

Soler & Palau MELLIZO - AIRSENS (TRICKLE/BOOST) - 1

text_image FAN A FAN B Fault under current 24v c/o Remote off on Display out 7 pt to 230V INPUTS SWITCH2 OFF FIREn/c n/o Switch1 Tacho B off n/c n/o 230V OUT/PU S MIN SPEED MID SPEED HIGH SPEED Changeover Button I/P1 I/P2 I/P3 Mid Speed D MIN SPEED MID SPEED HIOH M D HIGH SPEED RT3 RT2 RT1 L N E L N L2 L3 N1 FAN B SUPPLY Fan A ACTUATOR L N Fan B Remote Enable HIGH 0v SW1 FIRE +18 o/p HIOH o/p Fan A Fan B 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 1/PS 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236V 236S AIRSENS 100-240V 50/60Hz power supply L N ON RV DO DI RV J9 D17 DRE DUE NO C NC SW Operation modes 3-LED intensity Set point

Trickle speed set-point (Min speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

Boost speed set-point (High speed)

The speed is defined by the 'High speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan between 3-10V.

7.12. AIRSENS (REMOTE ENABLE)

Soler & Palau MELLIZO - AIRSENS (REMOTE ENABLE) - 1

text_image FAN A D/N O/N + - Transformer RED Fuse A L N E SUPPLY L N Fan A L2 L3 N1 ACTUATOR L N Fan B N 1/2/2 230V 1/P3 1/P2 RT1 RET3 I/P1 I/P2 HIGH M I/P3 HIGH M 230V INPUTS +10 High 230V OUT/PUT HIGH S MIN SPEED MIN SPEED MID SPEED MID SPEED HIGH SPEED HOLD SPEED HOLD SPEED Changeover Button Add Pull Up Register Yes No Remote Enable HIGH I/p Remote Enable MID I/p SW1 FIRE SW2 +10 o/p HIGH o/p Fan A o/p Tac A Fan B o/p AIRSENS 100-240V 50/80Hz power supply LN J9 D17 D16 D18 NO C NC SW Operation modes 3-LED intensity under current off on Display v/n1 add r st ic 24v c/o Remote TX Switch2 off FIREn/c n/o Switch1 off n/c n/o Techo B on off Tacho A off 24 21 18 15 12 9 6 3

Fan speed set-point (Min Speed)

The speed is defined by the 'Min speed' Potentiometer, by rotating the potentiometer dial it will change the set speed of the fan.

7.13. EXTERNAL FAULT

Soler & Palau MELLIZO - EXTERNAL FAULT - 1

text_image FAN A FAN B Fault 8 6 5 4 3 2 1 Fan trip current under current off on Display vin1 add r pt ic 24v c/o Remote 0v TX Transformer 230V INPUTS I/P1 I/P2 I/P3 +10 Mid High High 230V OUT/PUTS MIN SPEED MHD SPEED MHD SPEED HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H100 HIGH MHD HIGH SPEED H1O H Speed Changeover Button Tacho B off off Tacho A off off Tacho B 24 21 18 15 12 9 6 3 24 21 18 15 12 9 6 3 24 21 18 15 12 9 6 3 24 21 18 15 12 9 6 3 24 21 18 15 12 9 6 3 24 21 18 15 12

External fault (SW1)

When the fan is in normal running conditions the switch should be in the closed position. If additional switches are required then can be connected in series. During start-up there is a 60 seconds delay to allow the airflow to increase. When the fault switch opens signifying loss of airflow, the controller will automatically stop the fan and display "EXTERNAL SW1 FAULT".

Following an "EXTERNAL SW1 FAULT", a manual re-start will be required.

Fire shut-off (SW2)

When the fan is in normal running conditions the switch should be in the closed position. When the fault switch opens signifying the fire alarm has been activated, the controller will automatically stop the fan and display "FIRE ALARM ACTIVATED".

Following an "FIRE ALARM ACTIVATED", a manual re-start will be required

7.14. RELAY OUTPUT

Soler & Palau MELLIZO - RELAY OUTPUT - 1

text_image FAN A FAN B Fault 8 6 5 4 3 2 1 Fan trip current under current off on Display add / add to 24v c/o Remote 0v TX Transformer 230V INPUTS OFF FIRE n/c n/o Switch2 SWITCH1 TIMER Tacho B on off Tacho A off 24 21 18 15 12 9 6 3 RED Fuse A Fuse B RT3 RET2 RT1 REMOTE ON/OFF 230V OUT/PUTS HIGH MIN SPEED MID SPEED MID SPEED HIGH SPEED Changeover Button Add Pull up up register Yes No L N E SUPPLY L N Fan A L2 L3 N1 Actuator L N Fan B N 1/1/230V Remote Enable HIGH 0v SW1 FIRE +10 SM2 +10 o/p HIOH 0v HIOH o/p Fan A Fan B MID i/p MID i/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p o/p O

Fan A (Maximum current load 8A)

Fan A is a run relay that will activate when Fan A is operating, below is the operation:

Fan Running – Continuity between COM and NO

Fan Stopped – Continuity between COM and NC

Fan B (Maximum current load 8A)

Fan B is a run relay that will activate when Fan B is operating, below is the operation:

Fan Running – Continuity between COM and NO

Fan Stopped – Continuity between COM and NC

Fault (Maximum current load 8A)

Fault is a fault relay that will activate when either fan is in fault condition, below is the operation:

Fan Running/Stopped – Continuity between COM and NC

Fault with Fan – Continuity between COM and NO

7.15. TIMER FUNCTION

Soler & Palau MELLIZO - TIMER FUNCTION - 1

text_image FAN A D/N O/N + FAN B D/N O/N Fault D/N O/N Fan trip current under current off on Display 24v c/o Remote 0v TX add r st lc Transformer 230V INPUTS I/P1 I/P2 I/P3 +18 Mid High REMOTE ON/OFF 230V OUT/PUTS HIOH I/P1 I/P2 HIGH MID I/P3 HIGH MID MIN SPEED MID SPEED MID SPEED HIGH SPEED Add Pull up Register Yes No L N E SUPPLY L N Fan A L2 L3 NI ACTUATOR L N Fan B N I/P5 230V Remote Enable HIGH 0v SW1 FIRE +18 +18 0v Tsc 0v Tac MID i/p Mid o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p a o/p ao p Trencher Switch2 off FIREn/c n/o Switch1 Tacho B on off Tacho on A 24 21 18 15 12 9 6 3 TIMER HIGH Speed Changeover Button X B RT3 RT2 RT1

Timer function

The over-run timer works when you alter the 'Timer' potentiometer, this will allow you to add an over-run of 0 to 15 minutes; the over-run function will operate for both remote enable and boost functions.

If a 10-minute over-run is set then the remote enable will over-run for 10 minutes and the boost will over-run for 10 minutes.

8. MAINTAINENCE

Before manipulate the device, make sure that it is disconnected from the mains and that no one can turn it on during the intervention.

The apparatus must be regularly inspected. These inspections should be carried out bearing in mind the ventilator's working conditions, in order to avoid dirt or dust accumulating on the impeller, motor or back-draught shutter. This could be dangerous and perceptibly shorten the working life of the ventilator unit.

While cleaning, great care should be taken not to unbalance the impeller or motor.

In all maintenance and repair work, the safety regulations in force in each country must be observed.

9. Warranty

S&P Limited Warranty

24 (TWENTY-FOUR) MONTH PRODUCT WARRANTY

S&P UK Ventilation Systems Limited warrants that the MULTI-REG Control will be free from defective materials and workmanship for the period of 24 (twenty-four) months from the date of original purchase. In the event that we find any part is defective the product will be repaired or at the company's discretion, replaced without charge provided that the product has been installed in accordance with the enclosed instructions and all applicable standards and national and local building standards.

IF CLAIMING UNDER WARRANTY

Please return the completed product, carriage paid, to your local authorized distributor. All returns must be accompanied by a valid Invoice of Sale. All returns must be clearly marked "Warranty Claim", with an accompanying description stating the nature of the fault.

THE FOLLOWING WARRANTIES DO NOT APPLY

  • Damages resulting from improper wiring or installation.
  • Damages resulting when using the fan/control with fans/motors/controls/sensors other than those supplied and manufactured by the S&P Group of Companies.
  • Removal or alteration of the S&P data plate label.

WARRANTY VALIDATION

- The end user must keep a copy of the Invoice of Sale to verify a purchase date.

10. RECYCLING

Dismantling and recycling must be carried out by qualified personnel and in compliance with local and international regulations.

Disconnect the electrical equipment from the power supply making sure that no one can start it during the operation.

Disassemble and eliminate the parts to be replaced according to current national and international standards.

Soler & Palau MELLIZO - RECYCLING - 1

EEC legislation and our consideration of future generations mean that we should always recycle materials where possible; please do not forget to deposit all packaging in the appropriate recycling bins. If your device is also labelled with this symbol, please take it to the nearest Waste Management Plant at the end of its serviceable life.

11. EC DECLARATION OF CONFORMITY

Herewith we declare that the fan/control designated below, on the basis of its design and construction in the form brought onto the market by us is, in accordance with the relevant EC Council Directives on Electromagnetic Compatibility. If alterations are made to the apparatus without prior consultations with us, this declaration becomes invalid. We further declare that the equipment identified below may be intended to be assembled with other equipment/machines to constitute machinery, which shall not be put into service until the assembled machinery has been declared in conformity with the provisions of these relevant EC Council Directives.

12. DESIGNATION OF EQUIPMENT

EMC Directive 2014/30/EU based on conformity to the requirements of: -

BS EN IEC 61000-6-3:2021 // BS EN 61000-4-4:2012 // BS EN IEC 61000-4-11:2020 // BS EN 61000-4-2:2009 // BS EN 61000-4-8:2010 // BS EN IEC 61000-4-3:2020 // BS EN 61000-4-6:2014 // BS EN 61000-4-5:2014+A1:2017

EN 60204-1:2018 // EN 61000-3-2:2014 // EN 61000-3-3:2013 // EN 61000-6-2: 2005 + AC:2005//EN 61000-6-3:2007+A1:2011+AC:2012 // //EN62311:2008 // EN ISO 12100:2010 // EN ISO 12499:2008 //EN ISO 13857:2019

13. GUARANTEE

S&P Limited Warranty

24 (TWENTY-FOUR) MONTH PRODUCT WARRANTY

S&P UK Ventilation Systems Limited warrants that the CAB TWIN ECOWATT N /ACODS fan control will be free from defective materials and workmanship for the period of 24 (twenty-four) months from the date of original purchase. In the event that we find any part is defective the product will be repaired or at the company's discretion, replaced without charge provided that the product has been installed in accordance with the enclosed instructions and all applicable standards and national and local building standards.

IF CLAIMING UNDER WARRANTY

Please return the completed product, carriage paid, to your local authorized distributor. All returns must be accompanied by a valid Invoice of Sale. All returns must be clearly marked "Warranty Claim", with an accompanying description stating the nature of the fault.

THE FOLLOWING WARRANTIES DO NOT APPLY

  • Damages resulting from improper wiring or installation.
  • Damages resulting when using the fan/control with fans/motors/controls/sensors other than those supplied and manufactured by the S&P Group of Companies.
  • Removal or alteration of the S&P data plate label.

WARRANTY VALIDATION

The end user must keep a copy of the Invoice of Sale to verify a purchase date.

Soler & Palau MELLIZO - GUARANTEE - 1

text_image S&P

S&P UK VENTILATION SYSTEMS LTD

S&P HOUSE

WENTWORTH ROAD

RANSOMES EUROPARK

IPSWICH

SUFFOLK

TEL. 01473 276890

WWW.SOLERPALAU.CO.UK

Soler & Palau MELLIZO - S&P UK VENTILATION SYSTEMS LTD - 1

Soler & Palau MELLIZO - S&P UK VENTILATION SYSTEMS LTD - 2