Soler & Palau

ILHB-ILHT ECOWATT - Ventilateur domestique Soler & Palau - Free user manual and instructions

Find the device manual for free ILHB-ILHT ECOWATT Soler & Palau in PDF.

📄 36 pages English EN Download 💬 AI Question
Notice Soler & Palau ILHB-ILHT ECOWATT - page 31
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about ILHB-ILHT ECOWATT Soler & Palau

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Ventilateur domestique in PDF format for free! Find your manual ILHB-ILHT ECOWATT - Soler & Palau and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. ILHB-ILHT ECOWATT by Soler & Palau.

USER MANUAL ILHB-ILHT ECOWATT Soler & Palau

natural_image Exterior view of a stainless steel industrial machine with open doors and internal components (no visible text or symbols)

Soler & Palau ILHB-ILHT ECOWATT - 1

natural_image 3D rendering of an electronic device with cooling unit and mounting base (no visible text or symbols)

INDICE

1. GENERAL....3

1.1 Disclaimers....3
1.2 Safety instructions 3
1.3 Storage.... 3
1.4 Warranty 4

2. PRODUCT PRESENTATION......4

3. INSTALLATION 5

3.1 Dimensions and weight (mm) 5
3.2 Summary charts of assembly and accessories 6
3.3 Accessories (dimensions in mm)....7
3.4 Handling 8
3.5 Casing assembly 9

4. ELECTRICAL CONNECTION 9

4.1 Preliminary precautions....9
4.2 Electrical characteristics.... 10
4.3 Wiring of INTZ safety switch.... 10

5. COMMISSIONING AND SETTING....11

5.1 Preliminary precautions....11
5.2 Controllers....11
5.3 Operation for smoke extraction 14
5.4 Ventilation fault indication 14
5.5 ILHB/T-ECOWATT Single-phase - VAV variable flow rate control 15
5.6 ILHB/T-ECOWATT Single-phase - CAV constant flow rate control.... 19
5.7 ILHB/T-ECOWATT Single-phase - COP constant pressure control 22
5.8 ILHB/T-ECOWATT 3-phases - VAV variable flow rate control 24
5.9 ILHB/T-ECOWATT 3-phases - CAV constant flow rate control....28
5.10 ILHB/T-ECOWATT 3-phases - COP constant pressure control 31

6. MAINTENANCE....34

7. WASTE MANAGEMENT 35

7.1 Treatment of Packagings and non dangerous wastes 35
7.2 Treatment of a Professional WEEE 35

1. GENERAL

1.1 Disclaimers

This product has been manufactured according to rigorous technical rules of safety in conformity with EC standards. The EC declaration may be downloaded from the Internet site (address given on the last page). Before installing and using this product, carefully read these instructions, which contain important indications for your safety and the user's safety during the installation, commissioning and maintenance of this product. Once the installation is achieved, keep this manual handy nearby the machine for future consultation.

This product must be installed (installation, connections, commissioning, maintenance) and all other interventions performed by a professional applying recognized good practice procedures, and respecting the standards and safety regulations in force. The installation must be made in accordance with the prescriptions indicated in the Electromagnetic Compatibility (EMC) and Low Voltage (LV) Directives.

We advise all people exposed to risks to scrupulously respect the accident prevention standards. The manufacturer may not be held liable for any human injury and/or material damage resulting from the non-respect of the safety instructions or from a change made on the product.

Smoke extract unit ILHB/T-ECOWATT are intended for smoke extraction and ventilation applications in residential buildings, tertiary buildings, industrial buildings and professional kitchens:

• Outdoor installation
• Environmental temperature range: -10^ / +45^
- Max temperature of extracted air in permanent operation: 120^
• Relative humidity: max 95% non-condensing
• Atmosphere not potentially explosive
- Low salinity atmosphere, with no corrosive chemical agents

1.2 Safety instructions

  • Wear suitable PPE (Personal Protective Equipment) before any intervention.
  • Before installing the roof fan and its accessories, make sure that the support and the location are sufficiently resistant to withstand the unit's weight and the accessories, if any.
  • Do not remove mesh grilles to access the impeller before cutting off the electric power supply with the safety switch.
  • If the work is to be done inside the device, cut off the electric power supply with the main circuit breaker and make sure that nobody can accidentally switch it back on.
    • Make sure that moving parts are stopped.
  • Make sure that the impeller is not accessible from connection tappings (connection duct or mesh protection).

Before starting, check the following points:

• Make sure that the device does not contain any foreign body.
- Make sure that all the components are attached to their original locations.
- Check manually that the impeller does not rub or is not blocked.
- Make sure that the mesh protection are in place.
• Make sure that the ground connection is connected.

1.3 Storage

The product must be stored protected from the weather, shocks and dirt due to splashings or splatterings of any kind during transport from the supplier to the end customer, and onto the worksite before installation.

1.4 Warranty

The equipment is warranted for twelve (12) months – Parts only – from date of manufacture.

S&P agrees to replace parts or the equipment whose operation is recognised defective by our departments, excluding all damages or penalties, such as operating losses, commercial prejudice, or other intangible or indirect losses.

Our warranty does not cover: (1) defects resulting from an abnormal use or an use not conforming to the recommendations indicated in our manuals; (2) defects observed following normal wear; (3) inc caused by negligence, lack of monitoring or maintenance; (4) defects due to the inappropriate installation of the devices or unsuitable pre-installation storage conditions.

In any case, S&P may not be held liable for transformed or repaired equipment even partially.

2. PRODUCT PRESENTATION

EC Certifi cate F400 -120 N° 1812-CPR-0040, according to European Standard EN 12101-3 Approved F400 120 (400°C 120 min)

Soler & Palau ILHB-ILHT ECOWATT - PRODUCT PRESENTATION - 1• ILHB/T-ECOWATT: complete unit with multi-directional suction plenum, with horizontal or vertical axis motor.
Soler & Palau ILHB-ILHT ECOWATT - PRODUCT PRESENTATION - 2• ILHB/T-ECOWATT: single ventilation unit, with horizontal or vertical axis motor.

• 6 sizes : 355 / 400 / 450 / 500 / 630 / 710.
• Flowrates from 500 to 24 000 m ^3 /h.

Construction

  • Detachable galvanised steel sheet panels.
  • Modular structure of aluminium sections.
  • High performance galvanised steel reaction turbine, mounted by direct coupling with the motor.

Motor

- ECOWATT® motor, F class, 3 phases with remote IP55 controller :

-1 phase 230V 50/60Hz controller input for sizes 355 up to 450.
-3 phases 400V 50/60Hz controller input for sizes 500 up to 710.
• Thermal protection fitted within the controller.

Kitchen Option

The kitchen option includes a reinforced seal of the casing and a drain to dispose of wash water. The drain should be installed at the bottom of the casing to allow the wash water to be effectively discharged.

3. INSTALLATION

3.1 Dimensions and weight (mm)

ILHB/T-ECOWATT MV
Assembly with horizontal motor axis
Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 1

text_image A BH F

Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 2

text_image C D J F K

Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 3
Tipping risk during handling operations

Assembly with vertical motor axis
Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 4

text_image A L BV 56

Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 5

text_image A C G D

ILHB/T-ECOWATTCC

Assembly with horizontal motor axis
Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 6

text_image A BH F

Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 7

text_image C D J EC KC

Assembly with vertical motor axis

Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 8

text_image A L C H BVC C G 55

Soler & Palau ILHB-ILHT ECOWATT - Dimensions and weight (mm) - 9

text_image A C D
SeizeABHBVBVCCDEECFGGCHJKKCLWeight MV (Kg)Weight CC (Kg)
NakedInsulatedNakedInsulated
3556276953276452635596067906603150315102826110332145486571
4006997673616782976316068647323150349102860117032156607987
45077984739273832671160699081231503781028921230321737898108
50085892542478433876870010398904262402112954129435194100121132
6301066113348891240397770011831098426246611210181422351133140177195
710119412615511032462110490613251226426252611210701533446159168279303

3.2 Summary charts of assembly and accessories

Soler & Palau ILHB-ILHT ECOWATT - Summary charts of assembly and accessories - 1

text_image CC ILBR ICOL ACOPEL F400 N ILAR ILRC ILSH ILVV MV ILBC ILVH ILBC ILSH ILVV

The TNHB/T-ECOWATT accessories on the diagram below can be used with the ILHB/T-ECOWATT MV with a vertical axis motor: (example below)

Soler & Palau ILHB-ILHT ECOWATT - Summary charts of assembly and accessories - 2

text_image ILHV ILPL

3.3 Accessories (dimensions in mm)

Circular fl exible spool pieceRectangular fl exible spool piece
ACOPEL F400 N ILARSoler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 1Soler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 2
ILSHSoler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 3Standard support for horizontal axis motor:This support means that the casing can be attached fl oor with the motor in a horizontal position (horizontal axis). The 2 support arms are attached to the casing by the 4 M8 x 15 screws which are supplied, and the 4 stands are attached to the arms by the 16 self-drilling 4.8 x 12 screws which are supplied.
ILBRSoler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 4Connecting fl angeThis connecting fl ange is attached to the plain fl ange at its 4 corners for the purpose of attaching a sheath.
ILBCSoler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 5Circular connection to the MV suction, horizontal axis motor:This connection is used with the ILHB/T-ECOWATT MV for a sheath connection which does not have an upstand and which does not bear the weight of the casing.
ILRCSoler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 6Rigid circular connection
ISI Soler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 7Soler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 8Vibration isolating devices4 vibration isolating devices supplied with 4 screws to attach them to the casing.
ILVVSoler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 9Soler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 10Rain guard with bird guardThese guards are attached after the supplied plain fl ange has been detached from the casing.

ILPL

Soler & Palau ILHB-ILHT ECOWATT - Accessories (dimensions in mm) - 11

text_image A A C ØD 75 B 75 Ø12 E

Double suction plenum

To be bolted under the casing, without any accessory between the ILPL and the casing.

DRAIN (KITCHEN OPTION)

To install the drain at the bottom of the casing, make a 22 mm hole, position the drain with its seal and attach it with 2 3.5 x 19 screws (recommendation, screws not supplied).

Dimensions (mm) and weight (kg)

ACOPEL F400 N / ILAR / ILBR / ILBC / ILRC / ISA-SLHT / ILVV / ILVH
ModelABCDE∅FHJ
35555926319719416040067080
40063129721621316045067080
45071132623323416050067080
50076833824024916056067080
63097740327830516071067080
710110446231134016080067080
natural_image Technical line drawing of a mechanical assembly with a crane lifting a component (no text or symbols present)

To keep people safe or prevent damage to property use compliant handling equipment that is in a good condition.

The casing must be lifted at the 4 lifting lugs.

Use slings with a length that is at least double the height of the casing. Make sure that the slings do not rub against the motor cowl or the electrical accessories.

If in doubt, detach it to avoid any damage.

3.5 Casing assembly

The support surface that will support the base of the casing must be as flat at as possible (sealing frame or upstand supplied on demand). A seal of foam or similar material (not supplied) is recommended between the support surface and the base of the casing. A maximum incline of 2.5^ is tolerated between the motor axis and the vertical axis (see diagram below).

Soler & Palau ILHB-ILHT ECOWATT - Casing assembly - 1

text_image 2,5°

Make sure that the support is adapted to the weight of the whole machine and its various accessories. Attach the casing at the ∅20 holes provided for this purpose. You are advised to use a LL washer. Any screws that are not properly tightened may make noises and cause harmful vibrations. Once the machine has been correctly set up, make sure that the motor turbine is able to rotate freely without any friction or noise. Vibration isolating devices are available: ISA - ILHT.

Soler & Palau ILHB-ILHT ECOWATT - Casing assembly - 2

natural_image Technical line drawing of a mechanical assembly with no visible text or symbols

Detaching and re-assembling casing panels The smooth side panels are easy to detach by loosening their screws. They are repositioned in the same way.

4. ELECTRICAL CONNECTION

4.1 Preliminary precautions

Electrical connections must be set up by qualified staff. Electrical connections will be set up in accordance with applicable International, National and Local regulations. Do not forget the earthing connection.

In case of smoke extraction purpose, use high-temperature and protected against UV radiation cables. Please note that cables and electrical accessories must be dimensioned according to HF 384 European Standards (CENELEC). In this cases, no thermal protection device is permitted on the smoke extraction circuit.

Furthermore, the cables must be protected against any mechanical stress when they are routed if the connection is established on the terminal box of the motor or on the proximity switch of the casing. In case of comfort purpose, the motor must be protected by an adapted magnetothermal protection mechanism.

WARNING: use a voltage tester before you undertake any operation.

4.2 Electrical characteristics

ModelP. Nom (kW)I. Nom. (A) 230VI. Nom. (A) 400VINTZElectrical protection necessary
3550,70 3,05INTZ 1V15 10 A
4000,72 3,05INTZ 1V15 10 A
4501.24 5,40INTZ 1V15 10 A
5001,70 3,52INTZ 1V15 16 A
6303,16 6,99INTZ 1V15 16 A
7105,91 12,43INTZ 1V22 16 A

4.3 Wiring of INTZ safety switch

Safety switch delivered factory wired and mounted.

Note: the safety switch is sized to be used in smoke extract application for a 400V three-phases or 230V single-phase 50/60Hz power supply.

Soler & Palau ILHB-ILHT ECOWATT - Wiring of INTZ safety switch - 1

natural_image Technical line drawing of an industrial machine with cooling unit and mounting base (no text or symbols)

Safety switch access : is located next to tl controller.

Wiring of version with INTZ safety switch 1V15

Unit size 355 / 400 / 450with compacto controllerUnit size 500 / 630with Invento S controller
Soler & Palau ILHB-ILHT ECOWATT - Wiring of version with INTZ safety switch 1V15 - 1Soler & Palau ILHB-ILHT ECOWATT - Wiring of version with INTZ safety switch 1V15 - 2

Wiring of version with INTZ safety switch 1V22

Unit size 710 with Invento S controller
Soler & Palau ILHB-ILHT ECOWATT - Wiring of version with INTZ safety switch 1V22 - 1

5. COMMISSIONING AND SETTING

5.1 Preliminary precautions

Before starting fan, make sure that the electric motor and impeller assembly rotate freely and that there is no object likely to be ejected by the turbine. The protection housings must be fastened to roof fan to prevent any accidental contact with rotating parts.

The machine should be attached to its support before power is applied.

Switch on just an instant to check the turbine's rotating direction.

WARNING: The impeller rotating direction must correspond to each speed in the direction indicated by the arrow on the product. A centrifugal backward fan unit with an impeller that does not rotate in the right direction still creates a flowrate and a low pressure in the duct. An incorrect rotating direction can lead to an abnormal overheating of the motor, resulting in its destruction and cancelling our manufacturer's warranty.

If the rotating direction is incorrect, cut off the electrical power supply, make sure no power is present, Contact after-sales service. Do not modify wirings, as this might seriously damages the unit.

While running, make sure that the motor's absorbed current is not more than 10% above the name plate indicated current.

Once the roof fan is installed and the tests successfully completed, present the main points of the operation and maintenance manual to the user, and explain:

• How to start up and shut down.
• How to change the operating modes.

Then hand over to the user the technical manual of the roof fan and the mounted accessories so that he can keep it handy to consult it at any time.

5.2 Controllers

The ECM motor controller controls this motor according to an adjusting potentiometer on the controller, an external 0-10V signal or a set point given by Modbus BMS.

The Modbus BMS connection, present as standard, allows you to adjust the flow rate set point or pressure, and to read the controller registers to find out the state of the roof fan.

5.2.1 Controller terminal block

Soler & Palau ILHB-ILHT ECOWATT - Controller terminal block - 1

natural_image 3D rendering of a black industrial electronic component with ventilation slots and mounting holes (no text or symbols visible)

Unscrew the plate on the front of the controller (Torx T20 screwdriver).

5.2.2 Adjustment potentiometer

Soler & Palau ILHB-ILHT ECOWATT - Adjustment potentiometer - 1

text_image Terminal strip 1 Terminal strip 2 Terminal strip 3 Terminal strip 4 Terminal strip 5 Adjustment potentiometer Gland 1 Gland 2 Gland 3 Gland 4 Sealing insert

5.2.3 Fault correction

In the event of a fault, restarting operation after switching off the power for 5 minutes may allow the controller to reset. A fault relay allows us to identify the main causes of faults on the controller.

Connection of the relay:

For sizes 355/400/450: Controller - Terminals 4, 5, 6.

For sizes 500/630/710: Controller - Terminals 17, 18, 19.

Regardless of the principle of operation of the roof fan, the relay operates in the following manner:

STATE OF THE UNITState of the relay**CompactoInvento
"Normal" operation (COP, CAV, VAV)=NO=5-6=18-19
Supply cut off =NC=4-5=17-18
On / Off switch open - the wheel is stationary but power is on to the controller.NC4-517-18
Loss of phases* - possibility that during a loss of phase the wheel continues to turn.NC4-517-18

*If the control unit detects a fault more than once, notably a phase problem twice, the roof fan will not restart automatically. (**) NO.: normally open, NC: normally closed.

Switch off the power supply for 5 min and restart the roof fan. If the problem persists, it is possible to identify the nature of the problem in the registers of the Modbus. The controller operating manual is available for more information on www.solerpalau.com.

For sizes 355/400/450

The "Inputs" table allows you to read the following information:

RegisterFaultValueDescription
0Power on0-11 = Voltage too low to operate
1Over voltage0-11 = Voltage too high to operate
2IGBT over current0-11 = Over current protection triggered
3Temperature0-11 = Thermal protection triggered, power reduced
4Phase loss0-11 = loss of phase or motor synchronism
5PFC over current0-11 = PFC protection (Power Factor Correction) FET triggered
6CRC settings0-11 = Monitoring of parameters has failed (TBD)
7Circuit fault0-11 = Error detected during checking of the internal circuits.
8Motor fault0-11 = Abnormal motor behaviour
9On temperature0-11 = Converter too hot to operate
10I2R IGBT fault0-11 = IGBT programme protection triggered
14Restart fault0-11 = Fault condition repeated more than once in a short time. The power converter must be restarted or reset.
RegisterFault Value Description
15=Fire mode=0-1=1 = Fire mode enabled
16=Operation Active =0-1=1 = Operation Active
17=Relay Active =0-1=1 = relay output enabled
18=Awaiting shut-down=0-1=1 = The engine should stop, but is still running.
24=Speed regulation=0-1=Speed regulator enabled
25=Power regulation=0-1=Power limit regulator enabled
26=Current regulation=0-1=Line current regulator enabled
27Over modulation regulation 0-1Over modulation reached. The converter can no longer provide the voltage required for the motor.
28=Regeneration regulation=0-1Motor in regeneration. Increased speed to prevent over voltage at the DC connection.
29=Phase current regulation=0-1=Motor phase RMS current limit
30Synchronisation regulation 0-1=Motor still in synchronous mode

For sizes 500/630/710

The "Inputs" table allows you to read the following information:

RegisterFault ValueDescription
0Power on0-1=1 = Voltage too low to operate
1Over voltage0-1=1 = Voltage too high to operate
2SW over current0-1=1 = current protection of the IGBT software
3On temperature0-1=1 = Converter too hot to operate
4Phase loss0-1=1 = Loss of phase or of main supply
5Earth current fault0-1 1 = asymmetrical load (sum of all currents >3 A)
6CRC settings0-1 1 = Monitoring of parameters has failed (TBD)
7Driver fault0-1 1 = Transistor driver initialization fault
8ADC fault0-1=1 = ADC conversion error
9SPI communication fault=0-1=1 = No communication between the processors
10Reduction in power0-1 1 = Reduction in the power of the controller.
11Stoppage of the reduction in power0-1=1 = Stop (motor stop) temperature of the controller reached
12=HW over current0-1=1 = IGBT software current protection
13FLW enabled0-1 1 = Weakening of the active field
14=System error0-1=1= Machine error

Refer to the controller operating manual (available on www.solerpalau.com).

5.2.4 Modbus connection - Connection to a BMS

In the case of a connection to a BMS, the Modbus connection, present in standard, allows:

  • ILHB/T-ECOWATT Single phase or 3-phase - Control of the VAV variable flow rate:
  • On / Off
  • Speed adjustment
  • reading of registers (state of the casing).
  • ILHB/T-ECOWATT Single phase or 3-phase - Adjustment to CAV constant flow rate:
  • On / Off
  • adjustment of the flow rate set point,
  • reading of registers (state of the casing).
  • ILHB/T-ECOWATT Single or 3-phase - Adjustment to COP constant pressure:
  • On / Off
  • adjustment of the pressure set point,
  • reading of registers (state of the casing).

Refer to the corresponding paragraph below for the connection and the setting of your casing.

5.2.5 Default configuration settings

A USB converter with RS 485 is necessary for you to connect to the registers via a PC, as well as an interface of the same type as ModBus Doctor.

Single-phase model*3-phase model*
MODBUS address180
Baut rate19200
START Bit1
STOP Bit1
ParityNONE

* For additional information refer to the roof fan controller manual (available on www.solerpalau.com).

5.2.6 Input register table

The "Input Register" table allows you to read the following information:

RegisterFonctionResolutionDescription
Single-phase model
4Speed 1 rpm
8Power 0,1W
9An1 input0,01V
10An2 input0,01V
11Pot input0,01V
RegisterFonctionResolutionDescription
3-phase model
0Speed 1 rpm
2Power 1W
9An1 input0,01V
10An2 input0,01V

For all other information on the setting of Modbus, contact the After-Sales service department.

5.3 Operation for smoke extraction

The ILHB/T-ECOWATT is approved for extraction of hot gases and smoke in the event of a fire. This mode of operation is automatic and does not require any setting: In the case of extraction of gas at a temperature >200^ , the roof fan will automatically switch to high speed with its internal thermal protections inhibited. The smoke extraction mode must be triggered manually with a BDRA type control unit.

The CAV/VAV/COP modes are no longer accepted.

5.4 Ventilation fault indication

Replaces the use of a PRESOSTATO DPS type pressure switch

Ventilation fault
ILHB/T-ECOWATT single phaseILHB/T-ECOWATT 3-phase
Soler & Palau ILHB-ILHT ECOWATT - Ventilation fault indication - 1Soler & Palau ILHB-ILHT ECOWATT - Ventilation fault indication - 2
Stop ventilation inc lightVentilation defect in cator light

5.5 ILHB/T-ECOWATT Single-phase - VAV variable flow rate control

VAV - Slaving to an external signal

In variable speed operation, the controller pilots the speed of the roof fan linearly. The controller will vary the speed of the roof fan between 200 rpm (min. speed), and its maximum speed in proportion to the signal sent by the external sensor. If the display is present on the roof fan, it will show you the flow rate in m³/h.

The speed adjustment can be done in different ways:

• by the potentiometer integrated in the controller,
- by an ON/OFF + variation remote control (CVF or REB-ECOWATT),
• by an external 0-10V output,
- by a VRPZ voltage variator (allowing operation 0 / LS / HS with adjustable LS and HS),
• by flow rate control by Modbus BMS.

VAV - Regulation according to the deviation between the set point / external measurement

During operation at variable speed, the controller regulates the speed of the roof fan according to the set point-measurement deviation. The set point is adjusted with the potentiometer built into the controller or a CVF/REB-ECOWATT external control. If the display is present on the roof fan, it will show you the flow rate in m^3/h .

Example of slaving and VAV regulation according to measurement of the outside temperature:

VAV slaved according to measurement of the outside temperatureVAV with regulation according to the deviation between the set point / external measurement
Soler & Palau ILHB-ILHT ECOWATT - VAV - Regulation according to the deviation between the set point / external measurement - 1Soler & Palau ILHB-ILHT ECOWATT - VAV - Regulation according to the deviation between the set point / external measurement - 2

5.5.1 Connection

VAV type factory assembly and wiring, with or without display. Connection of the power supply to the INTZ switch to be done by the customer.

Soler & Palau ILHB-ILHT ECOWATT - Connection - 1

text_image 230V Power supply Phase Neutral INTZ 15A Green/ Yellow Blue Brown Controller Relay fault PE N L NC COM NO An1 GND Pot +5V An2 GND +24V GND Speed-Output +24V Fire Start/Stop A B PE U V W 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Black Blue Red Green Brown Shunt Green/Yellow U V W CASING TDPD Display only on ILHB/T with display types Thermo switch N/F M 1 2 3 4 SW1 3 On 2 On 1 Off

Wiring for accessories not supplied
Soler & Palau ILHB-ILHT ECOWATT - Connection - 2

text_image MODBUS Controller Controller A B 20 21 RS + 485 RS - 485 BDRA +24V Fire 16 17 Thermo switch N/F Factory fitted and wired ON / OFF ControllerController Start/ Stop +24V 18 19 Instead of the shunt ON / OFF command Relay fault NC COM NO 4 5 6 Gas actuator output contact 5A/250VAC breaking capacity

Wiring for manual adjustment and slaving to an external signal

When the speed adjustment is done by the CVF/REB-ECOWATT type remote control, the 0-10V output or the Modbus BMS, the factory-fi tted potentiometer in the controller must be disconnected.

Soler & Palau ILHB-ILHT ECOWATT - Wiring for manual adjustment and slaving to an external signal - 1
*0-10V output examples: temperature sensor, humidity sensor.

0-LS-HS installation diagram, with adjustable LS and HS

The LS and the HS are adjusted by a VRPZ voltage variator (accessory not supplied). 0-LS-HS choice with the VRPZ.

Soler & Palau ILHB-ILHT ECOWATT - 0-LS-HS installation diagram, with adjustable LS and HS - 1

text_image VRPZ 888 INPUT relay230V Output L N Motor L N Light L N EVGAS OUT 0-10V S Gnd OUT ME24V +24Gnd SP E Speed MAXI E M/A E GndGndGnd Controller AN1 GND 7 8 Start/Stop +24V 18 19 230V Power supply

Wiring for regulation according to the deviation between the set point / external measurement

Soler & Palau ILHB-ILHT ECOWATT - 0-LS-HS installation diagram, with adjustable LS and HS - 2

flowchart
graph TD
    A["Controller"] --> B["An1 7 GND +5V"]
    A --> C["Start/Stop 18 +24V"]
    D["CVF/REB-ECOWATT"] --> E["On/ OFF Power supply (V) Output signal"]
    F["Instead of the shunt"] --> E
    G["Instead of the potentiometer"] --> H["GND"]
    I["P"] --> J["Output signal"]
    K["Power supply (V)"] --> L["Ground"]

Soler & Palau ILHB-ILHT ECOWATT - 0-LS-HS installation diagram, with adjustable LS and HS - 3

flowchart
graph TD
    A["0 - 10V OUTPUT"] --> B["Controller"]
    B --> C["An2 11"]
    B --> D["GND 12"]
    B --> E["+24V* 13"]
    B --> F["GND 14"]
    B --> G["Speed-Output 15"]
    B --> H["*24Vdc - 40mA Maxi"]
    H --> I["Shunt"]
    I --> J["12VDC Maxi output signal"]
    I --> K["GND"]
    K --> L["0 - 10V Output"]
    L --> M["Sensor power supply"]

5.5.2 Speed adjustment (unregulated VAV)

By potentiometer, or CVF/REB-ECOWATT type remote control.

By default the roof fan is set to its maximum speed, in bold in the table below.

The potentiometer in the controller allows you to change the speed of the turbine to adjust the flow rate.

The adjustment can be done with a CVF/REB-ECOWATT type remote control.

Correspondence table between the graduation of the internal potentiometer, the voltage applied on terminal 9 and the speed.

Graduation potentiometerVoltage (V) at terminal 9ILHB/T-ECOWATT 355ILHB/T-ECOWATT 400/450
0 0 200 rpm 200 rpm
2 1 530 rpm 460 rpm
4 2 850 rpm 720 rpm
6 3 1 180 rpm 980 rpm
8 4 1 500 rpm 1 240 rpm
10 5 1 830 rpm 1 500 rpm

For information: The flow rate is proportional to the speed of rotation.

$$ Q _ {v 2} = Q _ {v 1} \times \left(\frac {N _ {2}}{N _ {1}}\right) N \text { is the speed of rotation. } $$

By 0-10V output

Correspondence table between the voltage applied on terminal 7 and the speed.

Voltage (V)at terminal 7ILHB/T-ECOWATT355ILHB/T-ECOWATT400/450
0 200 rpm 200 rpm
2 530 rpm 460 rpm
4 850 rpm 720 rpm
61 180 rpm980 rpm
81 500 rpm1 240 rpm
101 830 rpm1 500 rpm

Speed adjustment 0 / LS / HS (adjustable LS and HS)

The adjustment can be done with a VRPZ voltage variator.

The low speed and the high speed are adjusted with the VRPZ, see VRPZ operating instructions.

Speed adjustment by the Modbus BMS

The adjustment can be done with a Modbus BMS. To know the parameters of the Modbus connection, refer to § "5.2.4 Modbus connection - Connection to a BMS".

After you wired your Modbus Link:

Turn on the power to connect yourself to the controller. The fan wheel must be stopped.

StepsRegister numbersValue to be entered
1 - Access to Level 151
2 - Change in the operating mode of the controller62
3 - Saving of changes510000
4 - Changing the set point0Between 1000 and 10,000 to set the desired speed of the roof fan, see the table below
Fan stop00
Register set point 0ILHB/T-ECOWATT355ILHB/T-ECOWATT400/450
1000200 rpm200 rpm
2000380 rpm345 rpm
3000560 rpm490 rpm
4000740 rpm630 rpm
5000920 rpm780 rpm
60001 110 rpm920 rpm
70001 290 rpm1 070 rpm
80001 470 rpm1 210 rpm
90001 650 rpm1 360 rpm
100001 830 rpm1 500 rpm

5.6 ILHB/T-ECOWATT Single-phase - CAV constant flow rate control

During operation at constant flow rate, the controller regulates the speed of the roof fan to obtain the set point flow rate. A display installed under the cap indicates the flow rate measured in m/h. The flow rate set point can be adjusted by the potentiometer in the controller, by ON/OFF + variation remote control, by an external 0-10V output or by Modbus BMS.

5.6.1 Wiring

CAV type factory assembly and wiring. Connection of the power supply to the INTZ switch to be done by the customer.

Soler & Palau ILHB-ILHT ECOWATT - Wiring - 1

text_image 230V power supply Phase Neutral INTZ 15A 3 1 2 4 Brown Controller Relay fault PE N L NC COM NO An1 GND Pot +5V An2 GND +24V GND Speed-Output +24V Fire Start/Stop +24V A B PE U V W 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 Blue Black Red Shunt Shunt Green/Yellow Green/W CASING TDPD display 1 2 3 4 SW1 3 Off 2 On 1 Off Green Grey Brown Thermo switch N/F M

Wiring for accessories not supplied

When the flow rate set point adjustment is given by the CVF/REB-ECOWATT type remote control or the 0-10V output, the factory-fi tted potentiometer in the controller must be disconnected.

When the speed set point setting is given by the MODBUS BMS the factory-fi tted potentiometer in the controller must be disconnected, as well as the shunt between terminals 13 and 15.

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 1

flowchart
graph TD
    subgraph_Remote_Control["REMOTE CONTROL"]
        A["Controller"] --> B["An1 7 GND +5V Start/Stop +24V"]
        B --> C["CVF/REB-ECOWATT"]
        C --> D["On/OFF Power supply (V) Output signal GND"]
        D --> E["Instead of the shunt"]
        E --> F["1 2 3 4 5 P"]
        F --> G["Output Signal"]
        H["0-10V OUTPUT"] --> I["Controller"]
        I --> J["An1 7 GND +24V* 13 *24Vdc - 40mA Maxi"]
        J --> K["Sensor power supply"]
        K --> L["0-10V Output"]
        M["MODBUS"] --> N["Controller"]
        N --> O["A 20 RS +485 B"]
        N --> P["B -485 RS"]
        Q["BDRA"] --> R["Controller"]
        R --> S["+24V Fire"]
        T["Factory fitted and wired"] --> U["Thermo switch N/F"]
    end

    subgraph_Control_Control["Control"]
        V["Controller"] --> W["Relay fault NC COM NO"]
        W --> X["Gas actuator output contact 5A/250VAC breaking capacity"]
        X --> Y["P"]
    end

    style Remote_Control fill:#f9f,stroke:#333
    style Remote_Control fill:#ccf,stroke:#333
    style Control_Control fill:#cfc,stroke:#333
    style Control_Control fill:#fcc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#fcc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#fcc,stroke:#333
    style Control_Control fill:#cff,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc, stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#�33
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333
    style Control_Control fill:#ffc,stroke:#333

5.6.2 Adjusting the flow rate set point,

By potentiometer, CVF/REB-ECOWATT type remote control or 0-10V output.

Adjustment of the flow rate set point by potentiometer, CVF/REB-ECOWATT type remote control or 0-10V output.

The potentiometer in the controller allows you to change the flow rate set point.

The display under the cap shows the calculated flow rate.

For Sizes 355 / 400 / 450 : the display shows m³/h.

Graduation potentiometerFlow rate (m3/h)
355400450
000
1204030503340
2288043204720
3353052905780
4408061006680
5N/A
Graduation potentiometerFlow rate (m3/h)
355400450
06N/AN/A8170
7N/AN/AN/A
8N/AN/AN/A
9N/AN/AN/A
10N/AN/AN/A
N/A : max. flow rate already reached7

Note: After each adjustment wait 1 minute for the fan speed to stabilize.

By Modbus BMS

The flow rate set point can be given by a Modbus BMS set point. To find the settings of the Modbus connection, refer to § "5.2.4 Modbus connection - Connection to a BMS".

After you wired your Modbus link:

Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.

StepsRegister numbersValue to be entered
1 - Access to Level 151
2 - Change in the operating mode of the controller69
3 - Saving of changes510000
4 - Changing the set point16Between 0 and 1,000 to defi ne the desired flow rate set point, see the table below
Register set point 16ILHB/T-ECOWATT355ILHB/T-ECOWATT400ILHB/T-ECOWATT450
100 2 040 m ^3/h 3 050 m ^3/h 3 340 m ^3/h
200 2 880 m ^3/h 4 320 m ^3/h 4 720 m ^3/h
300 3 530 m ^3/h 5 290 m ^3/h 5 780 m ^3/h
400 4 080 m ^3/h 6 100 m ^3/h 6 680 m ^3/h
500N/AN/A7 460 m^3/h
600N/AN/A8 170 m^3/h
700N/AN/AN/A
800N/AN/AN/A
900N/AN/AN/A
1000N/AN/AN/A

For information: Calculation of the flow rate according to the set point

$$ Q _ {v} = K x \sqrt {2 , 5 x s e t p o i n t} $$

Size of ILHB/T-ECOWATTCoeff. K
355129
400193
450211

5.7 ILHB/T-ECOWATT Single-phase - COP constant pressure control

During operation at constant pressure, the controller regulates the speed of the roof fan to obtain the set pressure. If the display is present on the roof fan, it will show you the pressure in Pa. The pressure set point can be adjusted by the potentiometer in the controller, by a CVF/REB-ECOWATT ON/OFF + variation remote control, by an external 0-10V output or by Modbus BMS.

5.7.1 Wiring

COP type factory assembly and wiring. Connection of the power supply to the INTZ switch to be done by the customer.

Soler & Palau ILHB-ILHT ECOWATT - Wiring - 1

text_image 230V Power supply Phase Neutral INTZ 15A Green/ Yellow Blue Brown Controller Relay fault PE N NC COM NO An1 GND Pot +5V An2 GND +24V GND Speed-Output +24V Fire Start/Stop A B PE U V W Blue Black Red Shunt Shunt Green/ Yellow U V W CASING SPRD pressure sensor Only on ILHB/T types without display Thermo switch N/F SW1 3.0ff 2.0n 1.0ff Green Grey Brown TDPD Display only on ILHB/T with display types

Wiring for accessories not supplied

When the pressure set point is given by the CVF/REB-ECOWATT type remote control or the 0-10V output, the factory-fi tted potentiometer in the controller must be disconnected.

When the speed set point is given by the MODBUS BMS the factory-fi tted potentiometer in the controller must be disconnected, as well as the shunt between terminals 13 and 15.

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 1

text_image REMOTE CONTROL Controller An1 GND +5V Start/Stop +24V 7 8 10 18 19 CVF/REB-ECOWATT Instead of the shunt Power supply (V) Output signal GND Instead of the potentiometer ON/OFF 1 2 3 4 5 P Controller Relay fault NC COM NO 4 5 6 Gas actuator output contact 5A/250VAC breaking capacity

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 2

flowchart
graph TD
    A["0-10V Output Signal"] --> B["12VDC Maxi Output Signal"]
    B --> C["An1 7 GND"]
    B --> D["An1 8"]
    B --> E["+24V* 13"]
    C --> F["GND"]
    D --> F
    E --> F
    F --> G["Sensor power supply"]
    H["Controller"] --> I["*24Vdc - 40mA Maxi"]

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 3

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 4

text_image ON / OFF Controller Start/ Stop +24V 18 19 Instead of the shunt ON / OFF command

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 5

flowchart
graph TD
    A["Thermo switch N/F"] --> B["+24V Fire"]
    B --> C["Controller 16 17"]
    C --> D["Factory fitted and wired"]
    D --> E["11 21 33"]
    D --> F["12 22 34"]

5.7.2 Adjusting the pressure set point

By potentiometer, CVF/REB ECOWATT type remote control or 0-10V output.

By default the roof fan is set to obtain the pressure in bold in the table.

The potentiometer in the controller allows you to change the pressure set point.

The set point can be given by a CVF/REB ECOWATT type remote control or a 0-10V output.

Correspondence table between the potentiometer graduation, the voltage applied on terminal 7 and the pressure set point.

Note: After each adjustment wait 1 minute for the fan speed to stabilize.

Potentiometer graduationVoltage (in V) at terminal 7Without displayVoltage (in V) at terminal 7With display*
000
1 0,5 0 Pa 0,5 80 Pa
2 1 100 Pa 1 160 Pa
3 1,5 200 Pa 1,5 240 Pa
4 2 300 Pa 2 320 Pa
5 2,5 400 Pa 2,5 400 Pa
6 3 500 Pa 3 480 Pa
7 3,5 600 Pa 3,5 560 Pa
8 4 700 Pa 4 640 Pa
9 4,5 800 Pa 4,5 720 Pa
10 5** 800 Pa 5** 800 Pa

*If the roof fan has a display, the display will show you the pressure measured at the roof fan plate (see diagram below).
**If 0-10V source, 5 to 10V: 800Pa.

Soler & Palau ILHB-ILHT ECOWATT - By potentiometer, CVF/REB ECOWATT type remote control or 0-10V output. - 1

text_image Pressure measurement

By Modbus BMS

The pressure set point can be given by a Modbus BMS set point. To find the Modbus connection settings, refer to § "5.2.4 Modbus connection - Connection to a BMS".

After you have wired your Modbus link:

Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.

Modbus register table:

StepsRegister numbersValue to be entered
1 - Access to Level 151
2 - Change in the operating mode of the controller69
3 - Saving of changes510000
4 - Changing the set point16Between 0 and 1000 to define the desired pressure set point, see the table below
Without display With display
Register set point 16Pressure (Pa)Register set point 16Pressure (Pa)
100 100 100 160
200 300 200 320
300 500 300 480
400 700 400 640
450 800 500 800
450 à 1000 800 600 960
700 1 120
800 1 280
900 1 440
1000 1 600

5.8 ILHB/T-ECOWATT 3-phases - VAV variable flow rate control

VAV - Slaving to an external signal

In variable speed operation, the controller pilots the speed of the roof fan linearly. The controller will vary the speed of the roof fan between 200 rpm (min. speed), and its maximum speed in proportion to the signal sent by the external sensor. If the display is present on the roof fan, it will show you the flow rate in m³/h.

The speed adjustment can be done in different ways:

• control by a potentiometer in the controller,
• control by a CVF ON/OFF + variation remote control,
• control by an external 0-10V output,
- by a VRPZ voltage variator (allowing 0 / LS / HS operation with adjustable LS and HS),
• flow rate control by Modbus BMS.

VAV - Regulation according to the deviation between the set point / external measurement

During operation at variable speed, the controller regulates the speed of the roof fan according to the set point-measurement deviation. The set point is adjusted with the potentiometer built into the controller or a CVF/REB-ECOWATT type external control. If the display is present on the roof fan, it will show you the flow rate in m^3/h .

Example of slaving and VAV regulation according to measurement of the outside temperature:

VAV slaved according to the temperature sensorVAV with regulation according to the deviation between the set point / external measurement
Soler & Palau ILHB-ILHT ECOWATT - VAV - Regulation according to the deviation between the set point / external measurement - 1Soler & Palau ILHB-ILHT ECOWATT - VAV - Regulation according to the deviation between the set point / external measurement - 2

5.8.1 Wiring

VAV type factory assembly and wiring, with or without display. Connection of the power supply to the INTZ switch to be done by the customer.

INTZ 15 A
Soler & Palau ILHB-ILHT ECOWATT - Wiring - 1

text_image Controller Relay fault +24V Fire Start/Stop A B GND An1 +10V An2 GND +24V GND Speed-Output NO COM NC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 PE U V W PE L1 L2 L3 Shunt Black Blue Red Green Brown Green/Yellow U V W CASING Thermo switch N/F TDPD Display only onLHB/T-ECOWATT with display types 1 2 3 4 SW1 3 On 2 On 1 Off 400V Power supply L1 L2 L3 INTZ 15A TOP/HAUT Grey Brown Black Green/Yeloow 4 2 6

INTZ 22 A for ILHB/T-ECOWATT 710
Soler & Palau ILHB-ILHT ECOWATT - Wiring - 2

text_image Controller +24V Fire Start/Stop +24V A B GND An1 +10V An2 GND +24V GND Speed-Output NO COM NC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Shunt Black Blue Red Green Brown Green/Yellow U V W W PE L1 L2 L3 CASING Thermo switch N/F TDPD Display only on ILHB/T with display types SW1 3 On 2 On 1 Off M Power supply 400V INTZ 22A Grey Brown Black Green/Yellow 1 2 3 4

Wiring for accessories not supplied

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 1

Wiring for manual adjustment and slaving to an external signal.

When the speed set point adjustment is given by the CVF/REB-ECOWATT type remote control, the 0-10V output or the Modbus BMS, the factory-fi tted potentiometer in the controller must be disconnected.

Soler & Palau ILHB-ILHT ECOWATT - Wiring for manual adjustment and slaving to an external signal. - 1

flowchart
graph TD
    A["Controller"] --> B["GND An1 +10V 11910"]
    A --> C["Start/Stop +24V 3 4"]
    D["CVF/REB-ECOWATT"] --> E["Power supply (V)"]
    F["Instead of the shunt"] --> G["OFF/ ON 1 2 3"]
    F --> H["Output signal P"]
    I["Instead of the potentiometer"] --> J["GND 5"]
    style A fill:#f9f,stroke:#333
    style D fill:#ccf,stroke:#333
    style F fill:#cfc,stroke:#333
    style I fill:#fcc,stroke:#333

Soler & Palau ILHB-ILHT ECOWATT - Wiring for manual adjustment and slaving to an external signal. - 2

flowchart
graph TD
    A["0 - 10V OUTPUT"] --> B["Controller"]
    B --> C["GND An1 9 10 14"]
    B --> D["GND An1 +24V*"]
    C --> E["12VDC Maxi Output signal"]
    D --> F["*24Vdc - 40mA Maxi"]
    G["0-10V output"] --> H["GND Sensor power supply"]
    H --> I["Sensor power supply"]

0-LS-HS installation diagram, with adjustable LS and HS

The PV and the GV are adjusted by a VRPZ VOLTAGE variator (accessory not supplied). 0-LS-HS choice with the VRPZ.

Soler & Palau ILHB-ILHT ECOWATT - 0-LS-HS installation diagram, with adjustable LS and HS - 1

text_image VRPZ INPUT relay230V Sortie Light Speed 230V Power supply 230V Power supply OUTPUT 0-10V OUT 24V MES SP MAX M/A S Gnd +24Gnd 1 Gnd 2 E E GndGndGnd Controller GND AN1 Start/Stop +24V 9 10 3 4

Wiring for regulation according to the deviation between the set point / external measurement
Soler & Palau ILHB-ILHT ECOWATT - 0-LS-HS installation diagram, with adjustable LS and HS - 2

flowchart
graph TD
    A["Controller"] --> B["CVF/REB-ECOWATT"]
    B --> C["Instead of the shunt"]
    C --> D["Output signal GND"]
    D --> E["Power supply (V)"]
    E --> F["On/OFF"]
    F --> G["1 2 3 4 5"]
    G --> H["P"]
    H --> I["Start/Stop +24V"]
    I --> J["9 10 11"]
    J --> K["GND An1 +10V"]
    K --> L["Instead of the potentiometer"]

Soler & Palau ILHB-ILHT ECOWATT - 0-LS-HS installation diagram, with adjustable LS and HS - 3

flowchart
graph TD
    A["0 - 10V OUTPUT"] --> B["Controller"]
    B --> C["An2 12"]
    B --> D["GND 13"]
    B --> E["+24V* 14"]
    B --> F["GND 15"]
    B --> G["Speed-Output 16"]
    B --> H["*24Vdc - 40mA Maxi"]
    I["12VDC Maxi Output signal"] --> J["GND"]
    J --> K["0 - 10V Output"]
    L["Sensor power supply"] --> M["Shunt"]
    M --> N["GND"]

5.8.2 Speed adjustment

By potentiometer, CVF/REB-ECOWATT type remote control or 0-10V signal.

By default the roof fan is set to its maximum speed, in bold in the table below.

The potentiometer in the controller allows you to change the speed of the turbine to adjust the flow rate.

The adjustment can be given by the CVF/REB-ECOWATT type remote control or a 0-10V signal.

Correspondence table between the potentiometer graduation, the voltage applied on terminal 10 and the speed.

Graduation potentiometerVoltage (V) at terminal 10ILHB/T-ECOWATT 500ILHB/T-ECOWATT 630ILHB/T-ECOWATT 710
00200 rpm200 rpm200 rpm
22460 rpm400 rpm410 rpm
44720 rpm600 rpm620 rpm
66980 rpm790 rpm830 rpm
881 240 rpm980 rpm1 040 rpm
10101 500 rpm1 180 rpm1 250 rpm

For information: The flow rate is proportional to the speed of rotation.

$$ Q _ {v 2} = Q _ {v 1} \times \left(\frac {N _ {2}}{N _ {1}}\right) \text { Where } N \text { is the speed of rotation. } $$

Speed adjustment 0 / LS / HS (adjustable LS and HS)

The adjustment can be done with a VRPZ voltage variator.

The low speed and the high speed are adjusted with the VRPZ, see VRPZ operating instructions.

Speed adjustment by Modbus BMS

The adjustment can be done with a Modbus BMS. For the Modbus connection settings, refer to § "5.2.4 Modbus connection - Connection to a BMS".

After you have wired your Modbus link:

Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.

StepsRegister numbersValue to be entered
1 - Access to Level 181
2 - Change in the operating mode of the controller102
3 - Enabling of the on/off in Modbus131
4 - Saving of changes810000
5 - Changing the set point0
Fan stop130
Register set point 0ILHB/T-ECOWATT500ILHB/T-ECOWATT630ILHB/T-ECOWATT710
1000150 rpm120 rpm125 rpm
2000300 rpm240 rpm250 rpm
3000450 rpm350 rpm375 rpm
4000600 rpm470 rpm500 rpm
5000750 rpm590 rpm625 rpm
6000900 rpm710 rpm750 rpm
70001 050 rpm830 rpm875 rpm
80001 200 rpm940 rpm1 000 rpm
90001 350 rpm1 060 rpm1 125 rpm
100001 500 rpm1 180 rpm1 250 rpm

5.9 ILHB/T-ECOWATT 3-phases - CAV constant flow rate control

During constant flow rate operation, the controller regulates the speed of the roof fan to obtain the flow rate. A display installed under the cap indicates the flow rate measured in m³/h. The flow rate set point can be adjusted by the potentiometer in the controller, by a CVF/REB-ECOWATT ON/OFF + variation remote control, by an external 0-10V output or by Modbus BMS.

5.9.1 Wiring

CAV type factory assembly and wiring, with or without display. Connection of the power supply to the INTZ switch to be done by the customer.

Soler & Palau ILHB-ILHT ECOWATT - Wiring - 1

text_image Controller Relay fault +24V Fire Start/Stop A B GND An1 +10V An2 GND +24V GND Speed-Output NO COM NC PE L1 L2 L3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Shunt Black Blue Red Shunt Green/Yellow U V W M U V W Thermo switch N/F TDPD Display only on ILHB/T with display types Green Grey Brown SW1 3 Off 2 On 1 Off 400V Power supply INTZ 15A L1 L2 L3 3 1 5 4 2 6 Grey Brown Black Green/Yellow

Wiring for accessories not supplied

When the flow rate set point is given by the CVF/REB-ECOWATT type remote control or the 0-10V output, the factory-fi tted potentiometer in the controller must be disconnected.

When the speed set point is given by the MODBUS BMS the factory-fi tted potentiometer in the controller must be disconnected, as well as the shunt between terminals 14 and 16.

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 1

text_image REMOTE CONTROL Controller GND An1 +10V 9 10 11 Start/Stop +24V 3 4 CVF/REB-ECOWATT Instead of the shunt ON/OFF Power supply (V) Output signal P 0 - 10V OUTPUT Controller GND An1 +24V* 9 10 14 *24Vdc - 40mA Maxi 12VDC Maxi Output signal GND Sensor power supply 0-10V output MODBUS Controller A B 5 6 RS + 485 RS - 485 BDRA Controller +24V Fire 1 2 ON / OFF Control Start/Stop +24V 3 4 Instead of the shunt ON / OFF command Gas actuator output contact 5A/250VAC breaking capacity Controller Relay fault NC COM NO 17 18 19

5.9.2 Adjusting the flow rate set point

By potentiometer, CVF/REB-ECOWATT type remote control or 0-10V output.

The potentiometer in the controller allows you to change the flow rate set point.

The set point can be given by the CVF/REB-ECOWATT type remote control or a 0-10V output. The display shows you the measured flow rate.

For sizes 500 / 630 / 710 : the display shows m³/h x 1000.

Graduation potentiometerFlow rate (m3/h)
500630710
0000
1395067707480
25590957010580
368501172012950
479101353014960
588401513016720
69680N/A18320
710460N/A19790
8N/AN/A21150
9N/AN/A22440
10N/AN/A23650

N/A : max. flow rate already reached

Note: After each adjustment wait 1 minute for the fan speed to stabilize.

By Modbus BMS

The flow rate set point can be given by a Modbus BMS set point. For the Modbus connection settings, refer to § "5.2.4 Modbus connection - Connection to a BMS".

After you have wired your Modbus link:

Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.

StepsRegister numbersValue to be entered
1 - Access to Level 181
2 - Change in the operating mode of the controller102
3 - Enabling of the on/off in Modbus131
4 - Saving of changes810000
5 - Changing the set point0Between 0 and 10,000 to defi ne the desired fl ow rate set point, see the table below
Fan stop130
Register set point 0ILHB/T-ECOWATT500ILHB/T-ECOWATT630ILHB/T-ECOWATT710
1000 3 950 m^3/h 6 770 m^3/h 7480 m^3/h
2000 5 590 m^3/h 9 570 m^3/h 10 580 m^3/h
3000 6 850 m^3/h 11 720 m^3/h 12 950 m^3/h
4000 7 910 m^3/h 13 530 m^3/h 14 960 m^3/h
5000 8 840 m^3/h 15 130 m^3/h 16 720 m^3/h
6000 9 680 m^3/h N/A 18 320 m^3/h
7000 10 460 m^3/h N/A 19 790 m^3/h
8000 N/A N/A 21 150 m ^3/h
9000 N/A N/A 22 440 m ^3/h
10000N/A N/A 23 650 m ^3/h

5.10 ILHB/T-ECOWATT 3-phases - COP constant pressure control

During operation at constant pressure, the controller regulates the speed of the roof fan to obtain the set pressure. If the display is present on the roof fan, it will show you the pressure in Pa. The pressure set point can be adjusted by the potentiometer in the controller, by a CVF/REB-ECOWATT ON/OFF + variation remote control, by an external 0-10V output or by Modbus BMS.

5.10.1 Wiring

COP type factory assembly and wiring, with or without display. Connection of the power supply to the INTZ switch to be done by the customer.

Soler & Palau ILHB-ILHT ECOWATT - Wiring - 1

text_image INTZ 15 A Controller Relay fault +24V Fire Start/Stop +24V A B GND An1 +10V An2 GND +24V GND Speed-Output NO COM NC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 PE U V W PE L1 L2 L3 Shunt Black Blue Red P Shunt Green/Yellow U V W M Thermo switch N/F Yellow TDPD Display only on ILHB/T with display types pressure sensor Green Grey Brown SW1 3 Off 2 On 1 Off 400V power supply L1 L2 L3 4 2 6 INTZ 15A TOP/HAUT Grey Brown Black Green/Yellow

INTZ 22 A
Soler & Palau ILHB-ILHT ECOWATT - Wiring - 2

text_image Controller +24V Fire Start/Stop +24V A B GND An1 +10V An2 GND +24V GND Speed-Output NO COM NC Relay fault Shunt Black Blue Red Shunt Green/Yellow U V W W PE L1 L2 L3 Thermo switch N/F Yellow TDPD Display only on ILHB/T with display types pressure sensor Green Grey Brown SW1 3 Off 2 On 1 Off 400V Power supply INTZ 22A Grey Brown Black Green/Yellow

Wiring for accessories not supplied

When the pressure set point is given by the CVF/REB-ECOWATT type remote control or the 0-10V output, the factory-fi tted potentiometer in the controller must be disconnected.

When the speed set point is given by the MODBUS BMS the factory-fi tted potentiometer in the controller must be disconnected, as well as the shunt between terminals 14 and 16.

Soler & Palau ILHB-ILHT ECOWATT - Wiring for accessories not supplied - 1

text_image REMOTE CONTROL Controller GND An1 +10V Start/Stop +24V 11910 3 4 CVF/REB-ECOWATT Instead of the shunt ON/ OFF Power supply (V) Output signal GND Instead of the potentiometer 0-10V OUTPUT Controller GND An1 +24V* 9 10 14 *24Vdc - 40mA Maxi 12VDC Maxi Output signal GND Sensor power supply 0-10V Output MODBUS Controller A B RS + 485 RS - 485 Controller Relay fault NC COM NO 17 18 19 Gas actuator output contact 5A/250VAC breaking capacity ON / OFF Controller Start/Stop +24V 3 4 ON / OFF command Instead of the shunt Thermo switch N/F Factory fitted and wired

5.10.2 Adjusting the pressure set point

By potentiometer, CVF/REB-ECOWATT type remote control or 0-10V output.

By default the roof fan is set to obtain the pressure in bold in the table.

The potentiometer in the controller allows you to change the pressure set point.

The set point can be given by the CVF/REB-ECOWATT type remote control or a 0-10V output.

Correspondence table between the potentiometer graduation, the voltage applied on terminal 10 and the pressure set point.

Graduation potentiometerVoltage (V) at terminal 10Without displayWith display
1 1 100 Pa 160 Pa
2 2 300 Pa 320 Pa
3 3 500 Pa 480 Pa
4 4 700 Pa 640 Pa
5 5 800 Pa 800 Pa
6 6 800 Pa 960 Pa
7 7 800 Pa 1 120 Pa
8 8 800 Pa 1 280 Pa
9 9 800 Pa 1 440 Pa
10 10 800 Pa 1 600 Pa

If the roof fan has a display, the display will show you the pressure measured at the roof fan plate (see diagram below).

Soler & Palau ILHB-ILHT ECOWATT - By potentiometer, CVF/REB-ECOWATT type remote control or 0-10V output. - 1

text_image Pressure measurement

Note: After each adjustment wait 1 minute for the fan speed to stabilize.

By Modbus BMS

The pressure set point can be given by a Modbus BMS set point. For the Modbus connection settings, refer to §"5.2.4 Modbus connection - Connection to a BMS".

After you have wired your Modbus link:

Turn on the power to connect yourself to the controller. The roof fan wheel must be stopped.

Modbus register table:

Steps Register numbers Value to be entered
1 - Access to Level 181
2 - Change in the operating mode of the controller 102
3 - Enabling of the on/off in Modbus131
4 - Saving of changes810000
5 - Changing the set point0Between 0 and 10,000 to define the desired pressure set point, see the table below
Fan stop130
Without display With display
Register set point 0 Pressure (Pa) Register set point 0 Pressure (Pa)
1 000 100 100 160
2 000 300 200 320
3 000 500 300 480
4 000 700 400 640
4 500 800 500 800
4 500 à 10 000 800 600 960
700 1 120
800 1 280
900 1 440
1000 1 600

6. MAINTENANCE

The maintenance frequency depends on the operating conditions. If the air is highly loaded with impurities, the duration between two visits must be shortened.

WARNING: Before any maintenance operation, cut off the power supply upstream of the casing and make sure that it cannot be re-established during the intervention (lockout).

The motors used do not require any particular maintenance. They are fitted with sealed greased-for-life ball bearings.

Perform a periodical check based on the following indications:

Unit/Item At commissioningEvery 6 months minimum
TurbineCheck the direction of rotation and the absence of friction between the moving parts and the fixed partsClean if necessary, check the absence of friction between the moving parts and the fixed parts
ControllerCheck the connections, especially those to earthRetighten the terminals if necessary, check the rated current
SwitchCheck the connections, especially those to earthTighten the terminals if necessary
Protective grillesCheck the presenceClean if necessary
Duct networksCheck the sealingClean if necessary
FasteningsCheck the tightnessTighten the screws if necessary
Pressure tappingCheck the aeraulic connectionsCheck the operation

7. WASTE MANAGEMENT

7.1 Treatment of Packagings and non dangerous wastes

The packagings (unconsigned pallets, cartons, fi lms, wooden boxes) and other non dangerous wastes must be made reusable by an approved service provider. It is strictly prohibited to burn, bury or dump them in nature.

7.2 Treatment of a Professional WEEE

This product must not be dumped or treated with household refuse, but must be deposited in an appropriate collection point for waste electrical and electronic equipment (WEEE).

Soler & Palau ILHB-ILHT ECOWATT - Treatment of a Professional WEEE - 1

text_image S&P

Ref. NT-51907601-ILHB-ILHT-ECOWATT-AN-170711

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Soler & Palau

Model : ILHB-ILHT ECOWATT

Category : Ventilateur domestique