Seaward PowerCheck 1557 - Measurement

PowerCheck 1557 - Measurement Seaward - Free user manual and instructions

Find the device manual for free PowerCheck 1557 Seaward in PDF.

📄 34 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Seaward PowerCheck 1557 - page 2
Pick your language and provide your email: we'll send you a specifically translated version.
Product Type Portable Electrical Safety Tester
Brand Seaward
Model PowerCheck 1557
Category Measurement
Dimensions (approx.) 150 x 70 x 30 mm
Weight (approx.) 200 g (including battery)
Power Supply 9V alkaline battery (PP3)
Display LCD, 3½ digits, max reading 1999
AC Voltage Range 0 – 600 V
DC Voltage Range 0 – 600 V
Resistance Range 0 – 20 MΩ
Continuity Test Yes, with audible beeper
Diode Test Yes
Safety Rating CAT III 600 V
Operating Temperature 0°C to 40°C
Storage Temperature -10°C to 50°C
Humidity ≤ 80% RH (non-condensing)
Overload Protection Fuse 500mA/250V
Maintenance Clean with a dry lint-free cloth; do not use solvents.
Battery Replacement When low battery indicator appears
Spare Parts / Repairability No user-serviceable parts; contact Seaward service center.
Accessories Included Test leads, battery, carry case, manual
Certifications CE, UKCA

Frequently Asked Questions - PowerCheck 1557 Seaward

How do I measure AC voltage with the PowerCheck 1557?
Set the rotary switch to the AC voltage range (marked with ~V). Insert the black test lead into the COM jack and the red lead into the V/Ω jack. Connect the probes to the circuit and read the display. Ensure the voltage is within the rated range (max 600 V).
What does the continuity beep indicate?
The continuity function tests if a circuit is closed. When resistance is less than approximately 50 Ω, the meter emits a continuous beep. This is useful for checking wires and fuses.
How often should I replace the battery?
Replace the 9V battery when the low battery indicator appears on the LCD. For best accuracy, use a fresh alkaline battery.
Can I measure current with this device?
No, the PowerCheck 1557 does not measure current directly. It measures AC/DC voltage, resistance, continuity, and diodes. For current measurements, use a clamp meter or a multimeter with current input.
What is the maximum voltage I can safely measure?
The meter is rated for CAT III 600 V. Do not exceed 600 V AC or DC between any terminal and ground, or between terminals.
How do I clean the PowerCheck 1557?
Use a soft, dry cloth to wipe the exterior. Do not use abrasive cleaners, solvents, or water. Remove the leads and battery before cleaning.
What does the 'OL' reading mean?
'OL' indicates an overload condition – the measured value exceeds the selected range. Switch to a higher range or avoid measuring voltages above 600 V.
My meter shows erratic readings. What should I do?
First, check the test leads for damage. Replace them if needed. Ensure the battery is fresh. If the problem persists, the meter may need calibration or repair. Contact Seaward support.
Is the PowerCheck 1557 suitable for automotive testing?
Yes, it can test automotive batteries (12V/24V) and circuits for voltage, continuity, and resistance. However, it is not designed for high-current measurements.
Where can I find the full user manual?
The full user manual is available for free download on the dedicated product page at notice-facile.com in PDF format. It contains detailed specifications, safety instructions, and troubleshooting tips.

User questions about PowerCheck 1557 Seaward

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Measurement in PDF format for free! Find your manual PowerCheck 1557 - Seaward and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. PowerCheck 1557 by Seaward.

USER MANUAL PowerCheck 1557 Seaward

Operating Instructions

Seaward PowerCheck 1557 - Operating Instructions - 1

SEAWARD

Bracken Hill, South West Industrial Estate,

Peterlee, Co. Durham. SR8 2SW. England.

Tel: +44 (0)191 586 3511 Fax: +44 (0)191 586 0227

www.seaward.co.uk

sales@seaward.co.uk

service@seaward.co.uk

Limited Warranty & Limitation of Liability

SEAWARD Electronic Limited guarantees this product for a period of 1 year. The period of warranty will be effective at the day of delivery.

© Copyright 2008

All rights reserved. Nothing from this edition may be multiplied, or made public in any form or manner, either electronically, mechanically, by photocopying, recording, or in any manner, without prior written consent from SEAWARD Electronic Limited. This also applies to accompanying drawings and diagrams.

Due to a policy of continuous development SEAWARD Electronic Limited reserves the right to alter the equipment specification and description outlined in this publication without prior notice and no part of this publication shall be deemed to be part of any contract for the equipment unless specifically referred to as an inclusion within such contract.

Disposal of Old Product

Seaward PowerCheck 1557 - Disposal of Old Product - 1

natural_image Symbol of a trash bin crossed with no text or numbers, representing waste sorting or disposal (no text present)

This product has been designed and manufactured with high quality materials and components that can be recycled and reused.

When the crossed out wheelie bin symbol is attached to a product it means the product is covered by the European Directive 2002/96/EC.

Please familiarise yourself with the appropriate local separate collection system for electrical and electronic products.

Please dispose of this product according to local regulations. Do not dispose of this product along with normal waste material. The correct disposal of this product will help prevent potential negative consequences for the environment and human health.

Operating Instructions

PC1557 PAT and Installation Tester Checkbox

The PowerCheck 1557 is designed to be a full instrument verification system capable of testing all types of both installation testers and PAT testers.

The PowerCheck conforms with BSEN61010-1 and BSEN61326.

Contents

  1. User Notes
  2. Safety Notes
  3. Description
  4. Specifications
  5. General Overview
  6. PAT functionality
  7. Installation tester functionality
  8. Maintenance
  9. Cleaning
  10. Contact

1.0 User Notes

These operating instructions are intended for the use of competent personnel.

The PowerCheck 1557 has been designed for operation in a dry environment.

The following symbols are used in these operating instructions and on the PowerCheck 1557

Warning of electrical danger!

Indicates instructions must be followed to avoid danger to persons.

Important, follow the documentation!

This symbol indicates that the operating instructions must be adhered to in order to avoid danger.

2.0 Safety Notes

The PowerCheck 1557 has left the factory in a perfectly safe state. To maintain this state and ensure safe operation of the unit, all notes and warnings in these instructions must be observed at all times.

Seaward PowerCheck 1557 - Safety Notes - 1

The PowerCheck 1557 is intended to prove

verification on a regular basis. It is not intended to replace annual calibration of the test equipment. It is also suggested that the PowerCheck is annually calibrated.

Seaward PowerCheck 1557 - Safety Notes - 2

use test equipment which comply with IEC61010-1 and test leads which comply with IEC61010-031 with the PowerCheck 1557.

Seaward PowerCheck 1557 - Safety Notes - 3

Using the PowerCheck 1557 in ways not described

by this manual may lead to damaging either the PowerCheck 1557 or the Measuring Device being checked.

3.0 Description

The PowerCheck 1557 is comprised of the following features:-

a) The ability to perform verification of PAT testers including;

i) 2 different earth bond values.
ii) 3 different insulation values
iii) 4 different flash test values
iv) 3 different PE current values
v) 3 different touch current values

b) The ability to perform verification of voltage measuring equipment.

c) The ability to perform verification of continuity measuring test equipment including;

i) 2 different continuity values
ii) to verify the voltage and current outputs meet the requirements of IEC1557

d) The ability to perform verification of insulation measuring test equipment including;

i) 3 different insulation values
ii) to verify the voltage and current outputs meet the requirements of IEC1557

e) The ability to perform verification of loop impedance measuring test equipment including;

i) 3 different loop impedance values

f) The ability to perform verification of RCD test equipment including;

i) No tripping of any series in-line RCD protection
ii) 3 different current ranges values
iii) 3 different test time values

iv) to verify the current outputs meet the requirements of IEC1557

4 Specifications

4.1 Environmental Specifications

The PowerCheck 1557 has been designed to be used in a dry environment.

Maximum barometric elevation for use is 2000M.

Overvoltage category IEC 60664/IEC 61010, 300V CAT II.

Pollution Degree 2 according IEC61010-1.

Protective system IP40 according to IEC 60529.

Electromagnetic compatibility (EMC) interference, immunity and emitted interference conforming to IEC 61326-1.

Operating temperature range 0^ C to 40^ C.

Storage temperature range -25°C to 65°C.

4.2 Mains Supply

Mains Supply Voltage 230V 10%

Mains Supply Frequency 50Hz 1Hz

4.3 PAT Electrical Test Specification

Earth Bond0.2Ω, 2.0Ω±2%±20mΩ
Insulation0.5MΩ, 1MΩ, 2MΩ±2%
PE Currentsee reference table±2%
Touch Current see reference table±2%
Flashsee reference table±2%
MainsSupply210V220V230V240V250V
Flash Test Type A (mA)0.5MΩ1.371.431.501.571.63
1MΩ0.910.961.001.041.09
2MΩ0.550.570.600.630.65
Flash Test Type B (mA)0.5MΩ2.742.873.003.133.26
1MΩ1.371.431.501.571.63
2MΩ0.680.720.750.780.82
PE / Touch Current (mA)0.5MΩ0.420.440.460.480.50
1MΩ0.210.220.230.240.25
2MΩ0.110.110.120.120.13

FLASH TEST Type A are the values obtained for PAT test equipment which conform with EN50191. This includes the Supernova series of testers.

FLASH TEST Type B are the values obtained for PAT test equipment which do not conform with EN50191.

Mains Supply210V 220V 230V240V250V
FLASH CLII TESTFor verification of functionality only

4.4 Installation Electrical Test Specification

Continuity0.5Ω, 2.0Ω ±2% ±20mΩ
Continuity voltage4V < Un <24V±5%
Continuity currentIn > 200mA 2R load±5%
Insulation0.25MΩ, 0.5MΩ, 1MΩ±2%
Insulation voltage250V, 500V, 1000V±5%
Insulation current0.1mA < In <15mA±5%
Voltagemains input voltage
Loop Impedance1Ω, 180Ω±5%
RCD test time30ms, 40ms, 250ms±3ms
RCD test current10mA, 30mA, 100mA±5%

5 General Overview

e 0.5Ω 2Ω ofc g 0.25Ω 0.5Ω h 1MΩ Un In Un In f b 0.2Ω Earth Bond 2Ω c Flash CLI Insulation 500KΩ 1MΩ 2MΩ Flash Leakage Please refer to value matrix for exact flash and leakage values. PAT Rpe 250V 500V 1000V 1k 100mA 30mA 10mA Loop Only connect double Insulated RCD & LOOP A testers to this socket. p 290V - 50Hz Loop +1 Loop Loop +180 k a q l LN LE NE Common 230V Voltage i o m n Reset Trip Time

Figure 1: Front Panel

The PowerCheck 1557 comprises of the following elements;

5.1 General

a) Rotary switch which is used to select the required test functionality.

5.2 PAT Functionality

b) 2x Earth Bond test terminals.
c) 4x Insulation, PE/Touch Current and Flash test terminals which are used to obtain 3 different measurement values.
d) A Class II Flash test terminal.

5.3 Installation Tester Functionality

e) 2x Continuity measurement terminals and 1 voltage verification terminal.
f) Continuity voltage and current verification LEDs.
g) 3x Insulation measurement terminals and 1 current verification terminal.
h) Insulation voltage and current verification LEDs.
i) Insulation short current verification LED.
j) A voltage output and LED.
k) A Loop Impedance measurement selection switch.
I) Mains socket indication LEDs.
m) An RCD test time selection switch.
n) 5x RCD verification LEDs.
o) A reset LED and switch.
p) A mains power lead.
q) Loop/RCD mains outlet socket.

6.0 PAT Function Operation

6.1 Connections

Connect the PAT tester to a mains supply. Connect the PowerCheck 1557 mains plug into the EUT socket on the PAT tester. On the PowerCheck 1557 use the rotary switch to select the PAT function.

6.2 Earth Bond

The PowerCheck 1557 includes two Earth Bond test points, 0.2Ω and 2Ω. Connect one end of the earth bond probe to the PAT tester and clip the other end onto the appropriate resistance value stud. Perform an earth bond test. The PAT tester will indicate the test measurement taken.

Seaward PowerCheck 1557 - Earth Bond - 1

Do not perform an Earth Bond test with >25A test setting.

The PowerCheck 1557 is protected by a thermal monitoring device. If the Earth Bond measurements start measuring open circuit after excessive testing then allow the PowerCheck 1557 to cool down before proceeding.

6.3 Insulation

The PowerCheck 1557 includes three Insulation test points, 0.5MΩ, 1.0MΩ and 2.0MΩ. These test points are selected by moving the link between the 4 red test terminals. See Figure2, Figure 3 and Figure 4.

Seaward PowerCheck 1557 - Insulation - 1

Do not perform an Insulation test with >500Vdc test setting.

500Km 1Mn 2Mn 0.2n 2n Flash CU

Figure 2: 500KΩ selected
20 0.20 500K0 1M0 2M0 Flash CL2

Figure 3: 1MΩ selected

2n 0.2n 500kΩ 1MΩ 2MΩ Flash.C1.1

Figure 4: 2MΩ selected

Select the value required and perform an Insulation test. The PAT tester will indicate the test measurement taken.

6.4 Class I Flash Test

The PowerCheck 1557 includes three Class I Flash test currents, the value of this current is dependant on the mains voltage. The test point is selected by moving the link between the 4 red test terminals (see Figure 2, Figure 3 and Figure 4). The value selected is referenced to a table printed in the lid of the PowerCheck 1557. Select the test current required and perform a Flash test. The PAT tester will indicate the test measurement taken.

Seaward PowerCheck 1557 - Class I Flash Test - 1

Do not perform a Flash test with >1500Vac test setting.

6.5 Class II Flash Test

The PowerCheck 1557 includes one Class II Flash test current, the value of this current is dependant on the mains voltage. Disconnect the black link which is used to select the Class I Flash test current value. Connect the Flash probe to the PAT tester and to the Flash CL II terminal on the front of the PowerCheck 1557 (see Figure 5). Perform a Flash test, the PAT tester will indicate the test measurement taken.

Seaward PowerCheck 1557 - Class II Flash Test - 1

Do not perform a Flash test with >3000Vac test setting.

20 0.20 500x0. 1M0. 2M0. Flash CL#

Figure 5: Flash CLII connection

6.6 PE Current Test

The PowerCheck 1557 includes three PE Current test currents, the value of these is dependant on the mains voltage. These test currents are selected by moving the link between the 4 red test terminals (see Figure 2, Figure 3 and Figure 4). The value selected is referenced to a table printed in the lid of the PowerCheck 1557. Select the test current required and perform a PE Current test. The PAT tester will indicate the test measurement taken.

Seaward PowerCheck 1557 - PE Current Test - 1

Do not perform a PE Current Test if the mains voltage is outside of the ±10% specification.

6.7 Touch Current Test

The PowerCheck 1557 includes three Touch Current test currents, the value of these is dependant on the mains voltage. These test currents are selected by moving the PAT's touch current probe between 3 of the red test terminals (see Figure 6, Figure 7 and Figure 8). The value selected is referenced to a table printed in the lid of the PowerCheck 1557. Select the test current required and perform a Touch Current test. The PAT tester will indicate the test measurement taken.

Seaward PowerCheck 1557 - Touch Current Test - 1

Do not perform a Touch Current Test if the mains voltage is outside of the ±10% specification.

2n 0.2n 500k0 1M0 2M0 FlashCL

Figure 6: Touch Current value 1
2n 0.2π 500mm 1mm 2mm FlashCL

Figure 7: Touch Current value 2

2n 0.2n 500kΩ 1MΩ 2MΩ FleshCL

Figure 8: Touch Current value 3

7.0 Installation Function

7.1 Connections

Connect the PowerCheck 1557 Mains plug into a mains outlet socket.

7.2 Voltage

Connect the Installation tester between the Common and 230V test terminals, turn on the Installation tester and select Voltage. When the Voltage LED is illuminated 230Vac is present at the terminals, the Installation tester will measure this voltage. If the voltage goes off during testing unplug the PowerCheck 1557 from the mains supply and re-connect.

Seaward PowerCheck 1557 - Voltage - 1

This voltage is dependant on the incoming mains supply. The Voltage will be present independent of the test type selected on the PowerCheck 1557.

7.3 Continuity

Select the Rpe function on the PowerCheck 1557, turn on the Installation tester and select the Continuity test.

Seaward PowerCheck 1557 - Continuity - 1

not perform a Continuity test with >25A test setting.

7.3.1 Connect the Installation tester between the Common and the 0.5Ω terminals. Perform a Continuity test and ensure that the Installation tester measures within specification.

7.3.2 Connect the Installation tester between the Common and the 2.0Ω terminals. Perform a Continuity test and ensure that the Installation tester measures within specification. If the In LED indication is illuminated for the duration of the test then the Continuity test current meets the requirements of IEC1557.

7.3.3 Connect the Installation tester between the Common and the o/c terminals. Perform a Continuity test. If the Un LED indication is illuminated for the duration of the test then the Continuity test current meets the requirements of IEC1557.

7.4 Insulation

7.4.1 Select the 250V function on the PowerCheck 1557, turn on the Installation tester and select the Insulation test. Setup the Installation tester to output 250V. Connect the Installation tester between the Common and 0.25MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification. Ensure that both the Un and In LEDs are illuminated, this indicates that the Insulation voltage and current meet the requirements of IEC1557.

7.4.2 Connect the Installation tester between the Common and 0.5MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification.

7.4.3 Connect the Installation tester between the Common and 1.0MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification.
7.4.4 Select the 500V function on the PowerCheck 1557, turn on the Installation tester and select the Insulation test. Setup the Installation tester to output 500V. Connect the Installation tester between the Common and 0.5MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification. Ensure that both the Un and In LEDs are illuminated.
7.4.5 Connect the Installation tester between the Common and 0.25MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification.
7.4.6 Connect the Installation tester between the Common and 1.0MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification.
7.4.7 Select the 1000V function on the PowerCheck 1557, turn on the Installation tester and select the Insulation test. Setup the Installation tester to output 1000V. Connect the Installation tester between the Common and 1.0MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within

specification. Ensure that both the Un and In LEDs are illuminated.

7.4.8 Connect the Installation tester between the Common and 0.25MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures within specification.
7.4.9 Connect the Installation tester across the Common and 0.5MΩ terminals. Perform an Insulation test and ensure that the Installation tester measures with specification.
7.4.10 Select the Ik function on the PowerCheck 1557, turn on the Installation tester and select the Insulation test. Setup the Installation tester to output 250V. Connect the Installation tester between the Common and Ik terminals. Perform an Insulation test and ensure that the Ik LED is illuminated.
7.4.11 Select the Ik function on the PowerCheck 1557, turn on the Installation tester and select the Insulation test. Setup the Installation tester to output 500V. Connect the Installation tester between the Common and Ik terminals. Perform an Insulation test and ensure that the Ik LED is illuminated.
7.4.12 Select the Ik function on the PowerCheck 1557, turn on the Installation tester and select the Insulation test. Setup the Installation tester to output 1000V. Connect the Installation tester between the Common and Ik

terminals. Perform an Insulation test and ensure that the Ik LED is illuminated.

7.5 Loop Impedance

Plug the PowerCheck 1557 into a wall mains socket. Select the Loop function on the PowerCheck 1557.

If the LN and LE LEDs are not illuminated then the mains supply does meet the requirements in order to perform Loop tests, testing is inhibited.

Connect the Installation tester to the mains outlet socket on the front of the PowerCheck 1557, turn on the Installation tester and select the Loop Impedance test.

Do not perform a Loop Impedance test with >25A test setting.

7.5.1 Ensure that the Loop Impedance rocker switch is in the Loop position, perform a Loop test and note the value.
7.5.2 Switch the Loop Impedance rocker switch to the Loop+1 position. Perform a Loop test. Ensure that the Installation measures 1 more than the measurement obtained in 7.5.1. Ensure the measurement is within specification.
7.5.3 Switch the Loop Impedance rocker switch to the Loop+180 position. Perform a Loop test. Ensure that the

Installation measures 180Ω more than the measurement obtained in 7.5.1. Ensure the measurement is within specification.

7.6 RCD

Plug the PowerCheck 1557 into a wall mains socket. Select the 10mA RCD test current on the PowerCheck 1557.

If the LN and LE LEDs are not illuminated then the mains supply does meet the requirements in order to perform Loop tests, testing is inhibited.

Connect the Installation tester to the mains outlet socket on the front of the PowerCheck 1557, turn on the Installation tester and select the RCD test.

7.6.1 Setup the Installation tester so that it will test 0° 0.5lΔn using the same test current that has been selected on the PowerCheck 1557. Perform an RCD test. The 0° and 0.5lΔn LED will be illuminated. The simulated RCD will not trip for 0.5lΔn tests.

7.6.2 Setup the Installation tester so that it will test 180° 0.5lΔn using the same test current that has been selected on the PowerCheck 1557. Perform an RCD test. The 180° and 0.5lΔn LED will be illuminated. The simulated RCD will not trip for 0.5lΔn tests.

7.6.3 Setup the Installation tester so that it will test 0° IΔn using the same test current that has been selected on the PowerCheck 1557. Select a trip time on the PowerCheck 1557. Perform an RCD test. The 0° and IΔn LED will be illuminated. The simulated RCD will trip as indicated by the illuminated Trip LED. The Installation tester will measure the test time selected on the PowerCheck 1557. In order to reset the simulated RCD press the Reset switch, the Trip LED will go off.

7.6.4 Setup the Installation tester so that it will test 180° IΔn using the same test current that has been selected on the PowerCheck 1557. Select a trip time on the PowerCheck 1557. Perform an RCD test. The 180° and IΔn LED will be illuminated. The simulated RCD will trip as indicated by the illuminated Trip LED. The Installation tester will measure the test time selected on the PowerCheck 1557. In order to reset the simulated RCD press the Reset switch, the Trip LED will go off.

7.6.5 Setup the Installation tester so that it will test 0° 5lΔn using the same test current that has been selected on the PowerCheck 1557. Select a trip time on the PowerCheck 1557. Perform an RCD test. The 0° and 5lΔn LED will be illuminated. The simulated RCD will trip as indicated by the illuminated Trip LED. The Installation tester will measure the test time selected on the PowerCheck 1557. In order to reset the simulated RCD press the Reset switch, the Trip LED will go off.

7.6.6 Setup the Installation tester so that it will test 180° 5lΔn using the same test current that has been selected on the PowerCheck 1557. Select a trip time on the PowerCheck 1557. Perform an RCD test. The 180° and 5lΔn LED will be illuminated. The simulated RCD will trip as indicated by the illuminated Trip LED. The Installation tester will measure the test time selected on the PowerCheck 1557. In order to reset the simulated RCD press the Reset switch, the Trip LED will go off.

7.6.7 Repeat steps 7.6.1 to 7.6.6 for the 30mA and 100mA test ranges.

8.0 Maintenance

8.1 The PowerCheck 1557 is extremely robust and should always be kept free from dust.
8.2 Ensure the PowerCheck 1557 is kept dry with no surface moisture on the unit.
8.3 The case of the PowerCheck 1557 should be regularly inspected to ensure no physical damage.
8.4 Ensure the insulation of the power cable is fully intact and that no sharp creases have occurred in the cable.
8.5 If any of the above conditions have been observed then the PowerCheck 1557 must be appropriately secured to prevent any further use.

9.0 Cleaning

9.1 Clean the external case and front panel of the PowerCheck 1557 with a clean dry cloth.

10.0 Contact

For help or advice contact:

Tel: 0191 5878718

For Service and Calibration contact:

Service Department

Seaward Electronic

Bracken Hill

South West Industrial Estate

Peterlee

Co Durham SR8 2SW

England

Tel: 0191 5878739 / 0191 5878737

Email: service@seaward.co.uk

369A552 Rev 4

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Seaward

Model : PowerCheck 1557

Category : Measurement