DANFOSS HMC-211 - Remote control

HMC-211 - Remote control DANFOSS - Free user manual and instructions

Find the device manual for free HMC-211 DANFOSS in PDF.

📄 31 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice DANFOSS HMC-211 - page 4
Pick your language and provide your email: we'll send you a specifically translated version.
Product TypePLUS+1® Controller Module (HMC-211)
Model NumberHMC-211-010/112
Supply Voltage (Nominal)9 to 36 Vdc
Maximum Supply Voltage36 Vdc
Digital InputsMultifunction: DIN/AIN/FreqIN/Rheo
Analog Input Resolution12-bit (4096 counts)
Analog Input Ranges0-5.25 V (low), 0-36 V (high)
Input Impedance (Analog)206–236 kΩ (low range, no pull-up)
Digital Output TypesDOUT (3 A), HDOUT (6 A), PWMOUT/DOUT/PVGOUT (3 A), HPWMOUT/DOUT (6/10 A)
PWM Frequency Range33 to 4000 Hz
CAN BusCAN 2.0B, one port
Protection RatingIP67 (with mating connector)
Operating Temperature-40 to 70 °C
Storage Temperature-40 to 85 °C
Connector TypeDEUTSCH (bag assembly)
MountingPanel mounting only
Dimensions (approximate)160 x 80 x 35 mm
Weight (approximate)200 g
Programming SoftwarePLUS+1® GUIDE
Sleep Mode Current0.14 mA at 12 Vdc, 0.28 mA at 24 Vdc
Safety FeatureEmergency stop required (OEM responsibility)
Spare PartsMating connector kits, crimp tools (e.g., HDT48-00)

Frequently Asked Questions - HMC-211 DANFOSS

What is the supply voltage range for the HMC-211?
The nominal supply voltage range is 9 to 36 Vdc. The module can survive up to 36 Vdc without damage. For MC050-055/05B variants, the maximum is limited to 16 Vdc.
Can the input pins be configured as digital, analog, or frequency?
Yes, multifunction pins (e.g., DIN/AIN/FreqIN) are user-configurable via PLUS+1® GUIDE templates. They can operate as digital inputs, analog inputs, frequency inputs, or rheostat inputs.
How do I program the HMC-211 controller?
Programming is done using PLUS+1® GUIDE software. The application is downloaded via the CAN bus using a USB/CAN gateway (e.g., CG150-2). Refer to the PLUS+1® GUIDE User Manual for details.
What is the maximum output current for digital outputs?
Standard digital outputs (DOUT) can source up to 3 A per pin. High-current outputs (HDOUT) can source up to 6 A. Pair limitations apply; check the data sheet for derating.
Does the HMC-211 support CAN bus communication?
Yes, it has a CAN 2.0B compliant CAN port. The module communicates over a machine CAN network. Proper termination (120 Ω resistor) at each end of the bus is required.
What is the IP rating of the HMC-211?
The module has an IP67 rating when the mating connector is properly installed and unused pins are sealed. This ensures protection against dust and temporary immersion.
How should I mount the HMC-211 controller?
The HMC-211 is designed for panel mounting only. Use fasteners with 6.0 mm outer diameter and tighten to 2.26 N·m. Ensure the connector is positioned to allow moisture drainage.
Is the HMC-211 field serviceable?
No, the module is not field serviceable. The housing is ultrasonically welded and tamper-proof. Do not open the device; warranty will be voided.
Where can I find the data sheet for the HMC-211?
Data sheets for HMC-211 and other PLUS+1® modules are available at www.danfoss.com. Search for the specific model number (e.g., HMC-211-010) to download the PDF.
What tools are needed for the DEUTSCH connectors?
Typical tools include HDT48-00 crimp tool for solid contacts (20-24 AWG) and extraction tool DEUTSCH 0411-240-2005. Refer to the manual for complete tool and contact part numbers.

User questions about HMC-211 DANFOSS

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Remote control in PDF format for free! Find your manual HMC-211 - DANFOSS and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. HMC-211 by DANFOSS.

USER MANUAL HMC-211 DANFOSS

Technical Information

PLUS+1® Controllers

MC0XX-0XX Controller Family

DANFOSS HMC-211 - MC0XX-0XX Controller Family - 1

natural_image Stacked gray plastic electronic device modules with visible internal connectors (no text or symbols)

Revision history Table of revisions

Date Changed Rev
May 2021 Added torque information 1908
Changed document number from 'BC00000034' and '520L0719' to 'BC152886484710'XX
October 2019 Resolved link under General ratings, table MC controllers general ratings. 1804
October 2019 Corrected table Danfoss crimp extraction tool part information, last row, Description: Extraction tool DEUTSCH 0411-240-2005; 16 to 20, 20 to 24 AW.1803
March 2017 Changed module name, HMC-211-010/112; Changed name of manual, from PLUS+1 Controller Family to PLUS+1 MC0XX-0XX Controller Family.1802
December 2016 Added input impedance for analog inputs 1801
July 2016 Updated DIN/AIN/FreqIN; Din/AIN/FreqIN/Rheo Specifications table; Din/AIN/FreqIN Specifications table; added link to MC038-010 sleep mode in first bullet under MC038-010 power supply; updated to Engineering Tomorrow design1701
May 2015 Revised note regarding pin C1p26 QA
February 2014 MC050-055/05B input voltage maximum is limited to 16 Vdc PB
January 2014 Converted to Danfoss layout PA
June 2005 to September 2013Various updatesBA through OA
March 2004 First editionAA

Contents

MC0XX-0XX Controller Family literature references

Technical Information (TI)....4

Module product Data Sheet (DS)....4

API specifications (API)....4

PLUS+1 ^® GUIDE User Manual....4

User liability and safety statements

OEM responsibility....5

Overview

MC0XX-0XX Controller Family....6

CAN

Input types....7

DIN....7

AIN....8

High range input impedance for analog inputs....9

AIN offset....10

A/D refresh rate....10

AIN/Temp/Rheo; DIN/AIN/FreqIN/Rheo....10

DIN/AIN/FreqIN; DIN/AIN/FreqIN/Rheo....11

DIN/AIN/FreqIN....13

DIN/AIN/4-20 mA IN....14

Output types....15

DOUT and DOUT/PVEpwr....16

HDOUT....17

PWMOUT/DOUT/PVGOUT....17

HPWMOUT/DOUT....19

MC038-010, MC088-XXX output pin power supply....19

Controller Area Network (CAN)

CAN system design....20

Specifications for terminating resistor....20

Notes on CAN Bus installation....20

Expansion module CAN Bus loading....20

Product ratings

Module supply voltage/maximum current ratings.... 22

MC038-010 power supply....22

MC038-010 sleep mode....22

Sensor power supply ratings....23

PVG valve power supply ratings....24

EEPROM write/erase ratings....24

Vault memory....24

FRAM memory....24

Environmental testing criteria....25

General ratings....26

Modules housing....26

Product installation and start-up

Connectors....27

Mounting....28

Machine diagnostic connector....29

Grounding....29

Hot plugging....29

Machine wiring guidelines....29

Machine welding guidelines....30

PLUS+1 ^° USB/CAN Gateway....30

MC0XX-0XX Controller Family literature references

Literature title Document type Literature ID
MC0XX-0XX Controller Family Technical InformationUser GuideBC152886484710
MC0XX-0XX Controllers Data Sheets Data Sheet*
PLUS+1*GUIDE Software User Manual Operation Guide AQ152886483724

* Data Sheets for 12, 18, 24, 38, 50, and 88 pin models, go to https://www.danfoss.com/en/products/electronic-controls/?sort=default_sort.

Comprehensive technical literature is online at www.danfoss.com

Technical Information (TI)

A TI is comprehensive information for engineering and service personnel to reference.

Module product Data Sheet (DS)

A module product DS contains summarized information and parameters that are unique to an individual PLUS+1 ^* module, including:

• Numbers and types of inputs and outputs
• Module connector pin assignments
• Module maximum current capacity
• Module sensor power supply (if present) current capacity
• Module installation drawing
- Module weights
• Product ordering information

API specifications (API)

Module API specifications contain detailed information about the module BIOS. PLUS+1 ^® BIOS functionality is pin dependent. Pins are defined in module data sheets as C (connector number) p (pin number).

API specifications include:

  • Variable name
  • Variable data type
    • Variable direction (read/write)
    • Variable function and scaling

Module API specifications are the definitive source of information regarding PLUS+1 ^® module pin characteristics.

PLUS+1\* GUIDE User Manual

The Operation Manual (OM) details information regarding the PLUS+1 ^ GUIDE tool used in building PLUS +1 ^ applications. This OM covers the following broad topics:

  • How to use the PLUS+1* GUIDE graphical application development tool to create machine applications
    • How to configure module input and output parameters
    • How to download PLUS+1 ^® GUIDE applications to target PLUS+1 ^® hardware modules
    • How to upload and download tuning parameters
    • How to use the PLUS+1 ^® Service Tool

User liability and safety statements

OEM responsibility

The OEM of a machine or vehicle in which Danfoss products are installed has the full responsibility for all consequences that might occur. Danfoss has no responsibility for any consequences, direct or indirect, caused by failures or malfunctions.

  • Danfoss has no responsibility for any accidents caused by incorrectly mounted or maintained equipment.
  • Danfoss does not assume any responsibility for Danfoss products being incorrectly applied or the system being programmed in a manner that jeopardizes safety.
  • All safety critical systems shall include an emergency stop to switch off the main supply voltage for the outputs of the electronic control system. All safety critical components shall be installed in such a way that the main supply voltage can be switched off at any time. The emergency stop must be easily accessible to the operator.

Overview

MCOXX-0XX Controller Family

PLUS+1 ^* Mobile Machine Modules are designed to provide flexible, expandable, powerful and cost effective total machine management systems for a wide variety of vehicle applications.

These modules communicate with one another and other intelligent systems over a machine Controller Area Network (CAN) data bus.

PLUS+1 ^® controller products utilize modular designs wherever possible. This modularity extends to product housings, connectors and control circuitry.

PLUS+1 ^® hardware products are designed to be equally effective in a distributed CAN system, with intelligence in every node, or as stand-alone control for smaller machine systems.

PLUS+1* Compliant systems are incrementally expandable: additional modules can be easily added to the machine CAN bus to increase system capabilities or computational power.

Six standard housings, 12, 18, 24, 38, 50, and 88 pin, cover this product line.

CAN

Input types

  • Digital (DIN)
    • Digital or Analog (DIN/AIN)
    • Analog or Temperature or Rheostat (AIN/Temp/Rheo)
    • Multifunction: Digital or Analog or Frequency (DIN/AIN/FreqIN)
    • Multifunction: Digital or Analog or Frequency or Rheostat (DIN/AIN/FreqIN/Rheo)
    • Fixed Range Analog or CAN shield (AIN/CAN shield)
    • Digital or Analog or Current (DIN/AIN/4-20 mA IN)

Each PLUS+1 ^9 module input pin supports one of the above functional types. For pins with multiple functions, input configurations are user programmable using PLUS+1 ^6 GUIDE templates.

DIN

Digital inputs (DIN) connected to PLUS+1 ^® dedicated digital input pins are debounced in software. Digital input debounce is defined as an input being in a given state for three samples before a state change is reported. The sample time is a function of application loop time.

Multifunction pins that are configured to be Digital input (DIN) are subject to the same update rates as the Analog input (AIN) function for that pin. Debounce is not used, as hysteresis is built into the function. The time to recognize a transition is dependent on the timing of the switch activation and the sample rate.

General response to input time

Description Comment
Response to input below minimum voltageNon-damaging, non-latching; reading saturates to the low limit.
Response to input above maximum voltageNon-damaging, non-latching; reading saturates to the high limit.
Response to input openPin configuration dependent: No pull up/ no pull down = floating Pull up to 5 Vdc = 5 Vdc Pull down = 0 Vdc Pull up/ pull down = 2.5 Vdc
Voltage working rangesProgrammable (see specific data sheets for ranges).

DIN characteristics

Description Units MinimumMaximumComment
Allowed voltage at pin Vdc 036*Modules will survive with full functionality if input voltage does not exceed 36 Vdc.
Rising voltage threshold Vdc2.80 4.15A digital input is guaranteed to beread as high if the voltage is greater than 4.15 Vdc.
Falling voltage threshold Vdc1.01 2.77A digital input is guaranteed to beread as low if the voltage is less than 1.01 Vdc.
Time to change state in response to step inputms 1.5Input change from maximum tominimum—add to debounce time.
Input impedance
Input voltage < 5.7 Vdc kΩ 233 nominal—no pull up or pull down pin configuration.
Input impedance
Input voltage < 5.7 Vdc kΩ 14.1 nominal—pull up or pull down pin configuration.

CAN

DIN characteristics (continued)

Description Units MinimumMaximumComment
Input impedance
Input voltage ≥ 5.7 Vdc kΩ14.1 nominal—all pin configurations.

MC050-055/05B input voltage maximum is limited to 16 Vdc.

AIN

Analog inputs (AIN) specifications

Description Units MinimumMaximumComment
Allowed voltage at pin*Vdc 0 36**
0 to 5 Vdc range maximum discernible voltageVdc 5.215.30 5.26 is typical.
0 to 36 Vdc range maximum discernible voltageVdc 31.70
Precision mV 1.28
Input impedance kΩ 206 236Dependson pin configuration.

* Maximum allowed voltage on fixed range analog input pins (CAN shield) is 25 Vdc.
** MC050-055/05B input voltage maximum is limited to 16 Vdc.

For voltages > 5.7 V, see High range input impedance for analog inputs on page 9.

In high range the input impedance decreases as the input voltage increases.

CAN
DANFOSS HMC-211 - AIN - 1

CAN

AIN offset

Module analog input offset error can be 80 counts out of 4096 (12 bit resolution). Therefore, the minimum voltage that a module will read at the 0 to 5.25 V DC range is 105 mV. The minimum voltage that a module will read at the 0 to 36 V DC range is 703 mV.

The input offset error is a function of component tolerances and can vary from one module to the next. When an input value is used in an algorithm where the offset error could impact the control strategy, the way the signal is acquired and the need to calibrate should be considered.

A/D refresh rate

Analog to Digital (A/D) refresh rates for individual PLUS+1* MC0XX-0XX family modules and expansion modules are listed in the following table.

A/D channels are sampled at 25 kHz and 64 samples are taken to build an average value. This results in a refresh rate of 2.56 ms for channels directly measured. All internal current feedback channels are refreshed at the 2.56 ms rate.

Some PLUS+1* MC0XX-0XX family modules A/D channels are shared. Each of the shared channels have eight multiplexed analog inputs. Each multiplexed input is serviced every 20.48 ms. Update rates for specific analog input pins are found in the following table. Update rates for input expander modules are dependent on the CAN message frequency selected in the application program.

A/D refresh rates for PLUS+1 ^® MC0XX-0XX family modules

PLUS+1* module A/D refresh rate
MC012-010/012 All: 2.56 ms
MC012-026/029 All: 2.56 ms
HMC-211-010/012 All: 2.56 ms
MC024-010/011/012/014 All: 2.56 ms
MC024-020/021/022/024 C1p10 to C1p12: 7.68 msRemaining pins: 2.56 ms
MC024-500 All: 2.56 ms
MC038-010 C1p08, C1p14, C1p17 to C1p20, C1p24 to C1p27, C1p36 to C1p38: 20.48 msC1p05, C1p10 to C1p12: 2.56 ms
MC050-010/012 C1p05, C1p08, C1p14 to C1p19, C1p22 to C1p30, C1p34 to C1p36: 20.48 msC1p02: 2.56 ms
MC050-020/022 C1p05, C1p22, C1p25 to C1p32, C1p39, C1p40: 20.48 msC1p02, C1p08, C1p18, C1p19, C1p23, C1p24: 2.56 ms
MC050-055/05B C1p05, C1p13 to C1p29, C1p31 to C1p39, C1p41 to C1p45: 20.48 msC1p46 to C1p49: 2.56 ms
MC088-015/01B/315 C1p05, C1p08, C1p14 to C1p19, C1p22 to C1p30, C1p34 to C1p36, C1p47 to C1p50 , C2p09 to C2p11, C2p35 to C2p38: 20.48 ms
IOX012-010 Refresh rate is a function of CAN message frequency
IOX024-020 Refresh rate is a function of CAN message frequency
IX012-010 Refresh rate is a function of CAN message frequency
IX024-010 Refresh rate is a function of CAN message frequency

AIN/Temp/Rheo; DIN/AIN/FreqIN/Rheo

Analog/Temperature/Rheostat (AIN/Temp/Rheo); Digital/Analog/Frequency/Rheostat (DIN/AIN/FreqIN/Rheo).

When a PLUS+1 ^ module input pin is configured in the temperature/rheostat mode, the input has a 1.33 kΩ pull up resistor to +5 Vdc. It will source up to 3.75 mA current to an external load (RL) which then can be measured. The equation for relating AD counts to a given load is: AD counts = (4096*RL) / (RL + 1330).

CAN

This calculation is solved internally and the ohms value is available for the programmer. The following chart shows the relationship between AD counts and load resistance in ohms.

Rheostat inputs
DANFOSS HMC-211 - CAN - 1

line | Load Resistance (Ω) | AD Counts | | ------------------- | --------- | | 0 | 0 | | 10000 | 1500 | | 2000 | 2500 | | 5000 | 3000 | | 8000 | 3500 | | 10000 | 3600 |

Specifications

Description Units MinimumMaximumComment
Allowed voltage at pin Vdc 036
Measured resistance Ω 0 10000

DIN/AIN/FreqIN; DIN/AIN/FreqIN/Rheo

All modules except IX012-010, IX024-010.

The characteristics of Digital/Analog/Frequency (DIN/AIN/FreqIN) pins are PLUS+1* GUIDE software controlled. The input can be digital, analog or frequency.

Inputs can be pulled to 5 Vdc, pulled to ground, pulled to 2.5 Vdc, or no pull-up/pull-down.

DIN/AIN/FreqIN general information

Description Comment
Response to input below minimum voltageNon-damaging, non-latching; reading saturates to the low limit.
Response to input above maximum voltageNon-damaging, non-latching; reading saturates to the high limit.
Expected measurement Frequency (Hz)
Period (0.1 μsec)
Channel to channel phase shift (paired inputs . . . ) (0.1 ms).
PWM duty cycle (0.01%)—Duty cycle measurement only valid up to 5 kHz (FreqIN).
Edge count.
Quadrature count (paired inputs driven from a quadrature encoder).
Pull up/pull down configurationNo pull down/ pull up is standard with pull up or pull down programmable; failure modes are detectable.

As with analog input pins, values in the following table assume software compensation for AD converter offset errors.

Specifications

Description Units MinimumMaximumComment
Allowed voltage at pin Vdc 036
Frequency range Hz 0 10000In steps of 1 Hz.

CAN

Specifications (continued)

Description Units MinimumMaximum Comment
Maximum discernible voltage (high range)Vdc 34.62 35.91 35.3 Vdc is typical.
Maximum discernible voltage (middle range)Vdc 5.18 5.33 5.26 Vdc is typical.
Maximum discernible voltage (low range)Vdc 0.360 0.375 0.368 Vdc is typical.
Precision (high range) mV – - 8.62
Worst case error (high range)mV – - 614
Precision (middle range) mV – - 1.28
Worst case error (middle range)mV – - 75
Precision (low range) μV – - 89.7
Worst case error (low range)mV – - 7.39
Input impedance (pulled to 5 Vdc or ground, middle and low range)kΩ 13.9 14.3
Input impedance (pulled to 2.5 Vdc middle and low range)kΩ 7.17 7.37
Input impedance (no pull ups, middle and low range)kΩ 230 236
Input impedance (pulled to 5 Vdc or ground, high range)kΩ 13.0 13.4
Input impedance (pulled to 2.5 Vdc high range)kΩ 6.92 7.12
Input impedance (no pull ups, high range)kΩ 108 112
Rising voltage threshold (high range)Vdc 27.6 It is inadvisable to use the high rangeoption when configuring the input as a digital or frequency input.
Falling voltage threshold (high range)Vdc 6.8It is inadvisable to use the high range option when configuring the input as a digital or frequency input.
Rising voltage threshold (middle range)Vdc 4.27 Voltage required for frequency inputto read high.
Falling voltage threshold (middle range)Vdc 0.96Voltage required for frequency input to read low.
Rising voltage threshold (low range)Vdc 0.298 Voltage required for frequency inputto read high.
Falling voltage threshold (low range)Vdc 0.07Voltage required for frequency input to read low.

MC050-010 and MC050-018 pin C1p26 should not be configured as a FreqIN.

Recommendation is to not use pin C1p26 as a frequency input. If used, recommendation is to disable internal filtering and use filter inside the application instead.

CAN

DIN/AIN/FreqIN

The characteristics of Digital/Analog/Frequency (DIN/AIN/FreqIN) pins are PLUS+1* GUIDE software controlled. The input can be digital, analog or frequency.

Inputs can be pulled to 5 Vdc, pulled to ground, pulled to 2.5 Vdc, or no pull-up/pull-down.

Analog to digital resolution is 10 bits.

As with analog input pins, values in the following table assume software compensation for the errors in the AD converter.

Specifications

Description Units MinimumMaximumComment
Allowed voltage at pin Vdc 036
Frequency range Hz 0 10000In steps of 1 Hz.
Maximum discernible voltage (high range)Vdc 35.336 36 Vdc is typical.
Maximum discernible voltage (middle range)Vdc 5.675.83 5.75 Vdc is typical.
Maximum discernible voltage (low range)Vdc 0.4400.456 0.448 Vdc is typical.
Minimum discernible voltageVdc 0 0.08
Precision (high range) mV - -36.5
Worst case error (high range)mV - - 614
Precision (middle range)mV - - 5.62
Worst case error (middle range)mV - - 75
Precision (low range)μV- - 438
Worst case error (low range)mV - - 7.39
Input impedance (pulled to 5 Vdc or ground, middle and low range)kΩ 13.94.3
Input impedance (pulled to 2.5 Vdc middle and low range)kΩ 7.177.37
Input impedance (no pull ups, middle and low range)kΩ 230236
Input impedance (pulled to 5 Vdc or ground, high range)kΩ 10.310.7
Input impedance (pulled to 2.5 Vdc high range)kΩ 6.076.27
Input impedance (no pull ups, high range)kΩ 36.438.4
Rising voltage threshold (high range)Vdc - - 277.6 It is inadvisable to use the high rangeoption when configuring the input as a digital or frequency input.
Falling voltage threshold (high range)Vdc 6.8- - It is inadvisable to use the high rangeoption when configuring the input as a digital or frequency input.

CAN

Specifications (continued)

Description Units MinimumMaximumComment
Rising voltage threshold (middle range)Vdc 4.27Voltage required for frequency inputto read high.
Falling voltage threshold (middle range)Vdc 0.96Voltage required for frequency inputto read low.
Rising voltage threshold (low range)Vdc 0.298Voltage required for frequency inputto read high.
Falling voltage threshold (low range)Vdc 0.071Voltage required for frequency inputto read low.

Potential for IX modules to not go online. If voltage is applied to an IX module input pin prior to the module being powered on, there is a possibility that the module CPU will not power up. The module is not damaged and will power up and operate normally once power is removed from the input pins. It is recommended that either the IX module's 5 Vdc sensor power be used to power sensors or that power is removed from the input pins until the module is powered up.

If the frequency goes to zero, the data will not decay over time, it will be updated once a new pulse is seen, or times out. It is possible to monitor the count of pulses to know when the frequency reading is updated.

DIN/AIN/4-20 mA IN

Digital/Analog/4-20 mA (DIN/AIN/4-20 mA IN).

Refer to DIN/AIN/FreqIN on page 13, for input properties when pins are configured as digital, analog or frequency. If the pin is configured to read current, the table below applies. When interfacing with sensors that transmit a 4 to 20 mA current signal, the positive lead of the transmitter is connected to battery voltage and the negative lead is connected to the PLUS+1* module pin. The current measuring configuration relies on the application program to provide over current protection.

The current measuring configuration is only available on MC088-XXX modules.

Specifications

Description Units MinimumMaximumComment
Allowed voltage at pin Vdc 036
Minimum input current mA34
Maximum input current mA2024
PrecisionμA5.86

CAN

Output types

  • Digital (DOUT)
    • Digital/PVG valve reference power (DOUT/PVGpwr)
    • High current digital (HDOUT)
    • Pulse width modulated (PWM/DOUT/PVGOUT)
    • High current (6 A) pulse width modulated (HPWMOUT/DOUT)
  • High current (10 A) pulse width modulated (HPWMOUT/DOUT)

Output pins available on PLUS+1° Controller Family

PLUS+1* moduleDOUT (2A)DOUT (3 A)HDOUT (6 A)DOUT/PVGpwr (3 A)PWMOUT/ DOUT/PVGOUT (3 A)HPWMOUT/ DOUT (6 A)HPWMOUT/ DOUT (10 A)
MC012-010/012 2
MC012-026/029 2
HMC-211-010/01 242
MC024-010/011/ 012/0144
MC024-020/021/ 022/0248
MC038-010 2 3 3 5
MC050-010/0123 3 10
MC050-020/022 62 6
MC050-055/05B 12
MC088-015/01B 136 3 10
IOX012-010 2
IOX024-020 8
OX012-010 6
OX024-010 4 2 10

PLUS+1 ^® modules feature user-configurable output pin parameters. Output pin parameters are configured using PLUS+1 ^® GUIDE templates.

Refer to module data sheets for maximum output current ratings of individual modules and MC038-010 and MC088-015/01B power planes. The total output current for any PLUS+1* module must not exceed the maximum allowable current specified in the module data sheet. In the case of MC038-010 and MC088-015/01B modules, both the total output current for an individual power plane and the total output for the module must not exceed the limits specified on the module data sheets.

DANFOSS HMC-211 - Output types - 1

Warning

Unintended movement of the machine or mechanism may cause injury to the technician or bystanders. The module will be powered up if battery voltage is applied to the module's output pin. To protect against unintended movement, secure the machine.

DANFOSS HMC-211 - Warning - 1

Caution

Warranty will be voided if module is damaged. Avoid significant current driven back through an output pin.

CAN

DOUT and DOUT/PVEpwr

Digital (DOUT) and Digital/PVG Reference Power (DOUT/PVEpwr).

Digital outputs can source up to 3 A. The exception is MC038-010 controller, DOUT pins are limited to 2 A.

• Current outputs for MC050-010, MC050-020, MC088-015, and OX024-010 module
• DOUT and DOUT/PVG Pwr pins are pair limited and a function of temperature.
Output per pair is: 6 A maximum at 25 C [77 F]. Output per pair is 4 A maximum at 70°C [158°F]
• MC050-010 pairs are: C1p31 and C1p32, C1p33 and C1p34, C1p35 and C1p36
• MC050-020 pairs are: C1p33 and C1p34, C1p35 and C1p36, C1p37 and C1p38, C1p39 and C1p40
• MC088-015 pairs are:

Power plane C2p35: C1p31 and C1p32, C1p33 and C1p34

Power plane C2p36: C1p35 and C1p36

Power plane C2p37: C2p1 and C2p7, C2p2 and C2p3, C2p4 and C2p5, C2p30 and C2p33

Power plane C2p38: C2p6 and C2p12

- OX024-010 pairs are: C1p6 and C1p7, C1p8 and C1p9, C1p10 and C1p11

• Example: at a module temperature of 70^ C [158°F], if C1p31 is sourcing 2.5 A, the most current that can be sourced on its paired pin C1p32 is 1.5 A

General

Description Comment
Configuration Sourcing only.
Type Linear switching.
Short circuit to ground protection Non-damage, current/thermal limit with status indication; automatic latch off /resume.
Open circuit detection Fault indication provided. The GUIDE Pin Status requires a load of 500 mA to be connected or an open fault will be declared.
Parallel operation Digital outputs from the same module are capable of being connected together such that the net current rating is the sum of the individual ratings; timing is resolved by the operating system; diagnostic capability is maintained.
Shut off Processor control with hardware WatchDog override.

Specifications

Description Units Minimum Maximum Comment
Allowed voltage at pin Vdc 0 36 Reference warningstatement in topicHDOUTon page 17.
Output voltage, energized state Vdc Vbatt-1.0 VbattOver all load conditions.
Output voltage, off stateVdc 0 0.1AtRload=200 Ω
Output current range for a status bit to read OKA0.53 Refer to the noteaboveregarding pair.

Do not connect a digital output to battery+ (back drive) without a series diode.

CAN

HDOUT

High Current Digital (HDOUT)

High current digital outputs can source up to 6 A.

General

Description Comment
Configuration Sourcing only.
Type Linear switching.
Short circuit to ground protection Non-damage, current/thermal limit with status indication; automatic latch off/resume.
Open circuit detection Status indicationprovided. The GUIDE pin status requires a load of 1000 mA to be connected or an open status will be declared.
Parallel operation Digital outputs fromthe same module are capable of being connected together such that the net current rating is the sum of the individual ratings: timing is resolved by the operating system and diagnostic capability is maintained.
Shut off Processor control with hardwareWatchdog override.

Specifications

Description Units MinimumMaximumComment
Allowed voltage at pin Vdc 036 See caution statement below.
Output voltage, energized stateVdc Vbatt-1.0 VbattOver all load conditions.
Output voltage, off stateVdc 0 0.1AtRload=200 Ω
Output current range for status bit to read OKA1 6 See pair comment above.

DANFOSS HMC-211 - HDOUT - 1

Warning

Unintended movement of the machine or mechanism may cause injury to the technician or bystanders. DOUT and HDOUT digital outputs do not have an internal feedback to the PLUS+1* module kernel. To protect against unintended movement, if the application requires fault detection, an external feedback using an AIN configured pin must be used.

External feedback is required if the actual output is to be read by the PLUS+1 ^® Service Tool.

All other output types have internal feedback to the PLUS+1 ^® module kernel that provide pin fault and status information that can be read directly by the application and the PLUS+1 ^® Service Tool.

PWMOUT/DOUT/PVGOUT

All PLUS+1 ^® module proportional outputs are Pulse Width Modulated (PWM). PWM frequency is software adjustable using PLUS+1 ^® GUIDE. A low frequency dither may also be added with software to some outputs (see individual module API specifications for PWM outputs that support dither). There are two modes of PWM operation: open loop and closed loop (current control).

In open loop mode, current can be sourced or sunk (all modules are limited to 8 amps sinking), but the output is a PWM duty cycle. Current feedback may be monitored in open loop mode, but the output is a constant voltage, not a constant current. PVG valves may be driven with open loop PWM.

In closed loop mode, current is sourced and a constant current is maintained by the module's operating system using internal current feedback. Load impedance must not exceed 65 ohms.

CAN

In closed loop mode, the maximum current is limited by measuring the feedback current. There is no thermal protection. If the maximum current is exceeded, the controller kernel will shut down the output and latch it. The kernel also limits how quickly the output can be repowered (250 ms). The output cannot be reset until the command goes to 0 or False (if configured as a digital output).

Proportional outputs that are used as a digital sinking output have a potential for a leakage current of up to 5 mA when off.

Refer to individual module data sheets for the maximum allowable output current for each PLUS+1 ^® module.

General

Description Comment
Configuration Sourcing or sinking
Type (Linear vs. PWM) PWM
Operating modes Programmable: closed loop current or open loop voltage (duty cycle)
Dual coil PCPs Compensated for induced currents in a non-driven coil (closed loop mode)
Short circuit to ground Output fully protected against damage and fault detected
Mode selection (current or voltage) and full scale current rangesProgrammable

Do not connect a digital output to battery+ (back drive) without a series diode.

PLUS+1 ^® PWM output circuits are not designed to be used as inputs. Output current feedback readings should be used for fault checking only.

DANFOSS HMC-211 - CAN - 1

Warning

Unintended movement of the machine or mechanism may cause injury to the technician or bystanders. The module will be powered up if battery voltage is applied to the module's output pin. To protect against unintended movement, secure the machine.

DANFOSS HMC-211 - Warning - 1

Caution

Warranty will be voided if module is damaged.

Avoid significant current driven back through an output pin.

Specifications

Description Units Minimum MaximumComment
Full scale proportional current outputmA 10 3000The current may accidentally be exceeded inopen loop mode. If the current exceeds the trip point, the output will be latched off.
Output voltage, 100% duty cycle Vdc0 Vbatt-1
Output resolution of 3 AmA0.25
Repeatability of full range% of full scale0.5
Absolute accuracy of full range% of full scale3.0
Output settling timems100Depends on load characteristics.
PWM frequencyHz33 4000 Some pins have a fixed frequency, consultmodule application program interface (API).
Dither frequencyHz33250Increased in steps, see module API.

CAN

Specifications (continued)

Description Units Minimum Maximum Comment
Dither amplitude A 0 0.5 Increased in steps, see module API.
Over-current trip point A 5 5.25 There is over-current protection built into eachoutput driver. If the instantaneous current exceeds the trip point, the driver is latched off. GUIDE application software can reset the latch and attempt to drive current again.

HPWMOUT/DOUT

High Current Pulse Width Modulated (HPWMOUT/DOUT).

High current proportional outputs are unique to the MCO38-010 controller. These outputs are PWM, with PWM frequency user-configurable using PLUS+1 ^® GUIDE.

The MC038-010 has two types of high current PWM outputs:

• Paired bi-directional PWMs (10 A) that can be configured as either H bridges or independent outputs.
• Sourcing only PWMs (one 10 A and six 6 A).

See the product data sheet and API documents for pair assignments.

All high current proportional outputs are operated as open loop. The controller kernel does, however, monitor current for circuit protection, but there is no current feedback to the application. The output is a constant voltage and not a constant current. PWM outputs are hardware protected from short or over current.

Specifications

Description Units MinimumMaximumComment
Over-current trip point, 6 A A12Temperature dependent.
Over-current trip point, 10 AA 18Temperature dependent.
PWM frequencyHz334000

MC038-010, MC088-XXX output pin power supply

The output pin power supply design of the MC038-010 and MC088-XXX controllers is different from that of other PLUS+1 ^® modules. MC038-010 and MC088-XXX controllers have discrete power supply planes for output pins and a separate dedicated power supply for the DSP. Each output pin is associated with a specific power supply plane. Refer to the controller data sheets for a map of outputs and their associated power plane.

The controller DSP will be powered if power is supplied to any one of the controller's power planes.

Controller Area Network (CAN)

CAN system design

All PLUS+1 ^® modules have CAN ports that conform to CAN 2.0B specifications, including CAN shield. CAN1 port and CAN2 port on MC050-155/15B controllers cannot be used to download PLUS+1 ^® GUIDE application programs.

Specifications for terminating resistor

Each end of the main backbone of the CAN bus must be terminated with an appropriate resistance to provide correct termination of the CAN_H and CAN_L conductors. This termination resistance should be connected between the CAN_H and CAN_L conductors.

Specifications

Description Units Minimum MaximumNominal Comment
Resistance Ω 110 130 120 Minimum power dissipation400 mW(assumes a short of 16 Vdc to CAN_H).
Inductance μH 1

Notes on CAN Bus installation

Total bus impedance should be 60 Ω.

The CAN transceiver will be damaged by any voltage outside of allowable range, (-7 to +36 Vdc), even with a very short pulse.

If using shielded cable, the shield must be grounded to the machine ground at one point only; preferably at the mid-point of the CAN bus. Each PLUS+1° module CAN shield pin must be connected to the cable shield.

Expansion module CAN Bus loading

System designers incorporating PLUS+1 ^ expansion modules in their applications should be aware of PLUS+1 ^ CAN bus loading and controller memory usage during system design. Each expansion module is associated with a PLUS+1 ^* controller and uses part of the controller's memory resources for inter-module communications. The following table can be used to estimate system CAN bus loading and the memory impact of I/O modules on their associated controller.

Estimated usage of memory and communication resources

Description IX012-010 IX024-010OX012-010 OOX024-010 IOX0112-010 IOX024-20
Estimated module bus load (using default update and 250K bus speed)4% 10% 11% 27%11% 27%
Estimated module bus load (using 70 ms updates and 250K bus speed)2% 5% 3% 8% 4%8%
RAM usage on MC012-XXX9% 12% 9% 14%9% 17%
RAM usage on MC024-0109% 12% 9% 14%9% 17%

Controller Area Network (CAN)

Estimated usage of memory and communication resources (continued)

Description IX012-010 IX024-0110 OX012-010 OX024-010 IOX0112-010 IOX024-20
RAM usage on MC050-010, MC050-0201% 1% 1% 2% 1% 2%
RAM usage on MC050-0551% 1% 1% 2% 1% 0%
ROM usage on MC012-XXX8% 11% 12% 18% 10% 19%
ROM usage on MC024-0108% 11% 12% 18% 10% 20%
ROM usage on MC050-010, MC050-0203% 4% 4% 6% 3% 8%
ROM usage on MC050-0553% 4% 4% 6% 3% 8%

Product ratings

Module supply voltage/maximum current ratings

PLUS+1 ^* modules are designed to operate with a nominal 9 to 36 Vdc power supply.

The modules will survive with full functionality if the supply voltage remains below 36 Vdc.

Specifications

Description Units Minimum MaximumComment
Allowed voltage at pin V 0 36
Allowed module current A 0 120

DANFOSS HMC-211 - Module supply voltage/maximum current ratings - 1

Caution

PCB damage may occur.

To prevent damage to the module all module power supply + pins must be connected to the vehicle power supply to support advertised module maximum output current capacity. DO NOT use module power supply + pins to supply power to other modules on a machine.

MC038-010 power supply

The MC038-010 controller's power supply design recommendations must be followed:

  • Power supply to MC038-010 controller's output power planes (C1-p36 to C1-p38) must be wired directly to the vehicle battery (see MC038-010 sleep mode on page 22) and the wiring runs must be kept as short as possible.
  • Power supply to the controller's DSP (C1-p2) must be wired separately from the power supply to the controller's output power planes.
  • Do not connect any other PLUS+1 ^* controllers to the power supply to MC038-010 controller's output power planes.

MC038-010 sleep mode

Sleep mode is unique to the MC038-010 controller. This feature gives OEM designers the ability to implement automotive-like features in their machine control system design. If the sleep mode feature is not implemented, this controller has the same operating characteristics as any other PLUS+1 ^® controller.

When used as a sleep mode controller, supply power to the MC038-010 is connected directly to the battery. Sleep mode initiation is defined by the controller's application software: PLUS+1 ^® GUIDE programmers define the conditions under which the controller is to put to sleep. When in sleep mode, controller outputs are set to zero, sensor power supply is off and the controller consumes a small amount of current.

Controller sleep mode current consumption

Supply voltage Sleep mode current consumption
12 Vdc 0.14 mA
24 Vdc 0.28 mA

Battery power must be supplied to designated wake-up digital inputs, since the controller's 5 Vdc regulated power supply is not available when the controller is in sleep mode.

Either of two conditions will wake up the controller:

  • Switching any of the designated wake-up digital inputs (DIN) in the PLUS+1 ^9 GUIDE application, to high
    • Cycling all input power to the controller

The following input pins may be designated as wake-up digital inputs:

Product ratings

• DIN (C1p06, C1p07)
• DIN/AIN (C1p14, C1p17 to C1p20, C1p24 to C1p27

Specifications

Description Units MinimumMaximumComment
Wake-up pin threshold Vdc 236 To wake up by cycling input power.
Wake-up pin threshold Vdc 45 36 To wake up by digital input.
Wake-up time delay ms 250500

Sensor power supply ratings

PLUS+1 ^® modules that support sensor inputs are provided with dedicated, software adjustable, regulated sensor power supply and ground pins. Refer to individual product data sheets for sensor power supply current ratings.

The sensor power is nominally 5 Vdc, unless otherwise noted on the product data sheet.

General

Description Comment
Short circuit to groundOutput is not damaged and fault is detected.
Short circuit to battery +Output is not damaged and fault is detected.

Specifications (all modules except MC050-055/05B)

Description Units Minimum MaximumComment
Output short circuit voltageV36
Output voltage (actual)V4.885.12
Output voltage (internally measured)V4.64 5.32
Output currentmARefer to individual data sheets for sensor power supply ratings.
Output Load CapacitanceμF10
Hold up time after power lossms515

MC050-055/05B controllers feature two additional levels of regulated power: 1.6 Vdc and 3.3 Vdc. The PLUS+1 ^® GUIDE application developer can detect open and short digital inputs, when these power supplies are used in conjunction with DIN/AIN inputs.

Specifications (MC050-055/05B)

Description Units MinimumMaximumComment
Output short circuit voltageVdc36
Output voltage, sensorsVdc4.885.12Sensor power supply drops below minimum if controller power supply is less than 9 Vdc.
Output voltage, DIN diagnosticsVdc 1.541.66Nominal 1.6
Output voltage, DIN diagnosticsVdc 3.003.60Nominal 3.3

Product ratings

PVG valve power supply ratings

DOUT/PVGpwr pins can provide the battery supply voltage required by Danfoss PVG valve electronics for those control strategies requiring application software control of the valve power source.

When enabled, the DOUT/PVGpwr pin passes battery (reference) voltage to the PVG valve electronics. One DOUT/PVGpwr pin can power up to 3 PVG valves. Refer to individual module API documents for PVG power pin characteristics.

EEPROM write/erase ratings

To prevent unexpected memory writes, care must be taken to ensure memory with a high number of read/write cycles is either U32 or S32 data types.

Write/erase cycles

Description Minimum Maximum Comment
EEPROM write/erase cycles 1 millionMinimum valid over entire operating temperature range.

EEPROM used in MC050-055/05B controllers is rated for 1 million read/write cycles per sector. Sector size is 32 bits. When a value is written to EEPROM, all 32 bits in a particular sector are always written, regardless of the size of the size of the saved value. If the value being saved in a sector is less than 32 bits (such as U8, S16, BOOL) adjacent bits in the same EEPROM sector are rewritten with their previous value. The implication of this memory property is that if two values are being written to the same memory sector, the useful life of the sector is determined by the value being written most frequently. If that value exceeds 1 million read/write cycles, all values in the sector may be compromised if the useful life is exceeded.

Vault memory

Some variants of PLUS+1 ^* modules have 2 Mbyte of serial flash vault memory (also referred to as application logging memory).

Application developers can use this memory to log machine event data and use the PLUS+1° Service Tool to extract the logged data. As there is no real time clock on PLUS+1° modules, vault memory is not time stamped.

Accessing non-volatile or application log memory can delay the service tool scan.

FRAM memory

Write/erase cycles

Description Minimum Maximum Comment
FRAM write/erase cycles 100 trillionMinimum valid over entire operating temperature range.

FRAM used in the MC050-055/05B controller, is rated for 100 trillion read/write cycles per sector. Sector size is 32 bits. When a value is written to FRAM, all 32 bits in a particular sector are always written, regardless of the size of the saved value. If the value being saved in a sector is less than 32 bits (such as U8, S16, BOOL, etc) adjacent bits in the same FRAM sector are rewritten with their previous value. The implication of this memory property is that if two values are being written to the same memory sector, the useful life of the sector is determined by the value being written most frequently. If that value exceeds 100 trillion read/write cycles, all values in the sector may be compromised if the useful life is exceeded.

Product ratings

Environmental testing criteria

Climate environment

Description Applicable standardComment
Storage temperature IEC 60068-2-1test Ab, IEC60068-2-2 test Bb
Operating temperature IEC 60068-2-1, test Ab, IEC60068-2-2 test Bd
Thermal cycle IEC 60068-2-2, test NaIEC60068-2-38 (partial)
Humidity IEC 60068-2-78, IEC60068-2-30 test DbDamp heat steady state and cyclic.
Degree of protection IEC 60529

Chemical environment

Description Applicable standardComment
Salt mist IEC 60068-2-58 test Kb
Chemical resistance ISO 16750-5

Mechanical environment

Description Applicable standardComment
Vibration IEC 60068-2-6 test Fc, IEC6008-2-64 test Fh
Bump IEC 60068-2-29 test Eb
Shock IEC 60068-2-27 test Ea
Free fall IEC 60068-2-32 test Ed

Electrical/electromagnetic

Description ApplicablestandardComment
EMC emission ISO 13766, SAEJ1113-13Electromagnetic compatibility for earth moving machinery.
EMC immunity ISO 13766 Electromagnetic compatibility for earth moving machinery.
Electrostatic discharge EN 60-1 000-4-2
Auto electrical transientsISO 7637-2, ISO 7637-3
Short circuit protectionDanfoss testInputs and outputs survive continuous short circuit.Normal function resumes when short is removed.
Reversed polarity protectionDanfoss testSurvives reverse polarity at supply voltage for at least five minutes.

Product ratings

General ratings

MC controllers general ratings

Description Units MinimumMaximumComment
Operating temperature °C [°F]-40 [-40]70 [158] Maximumoperating temperatureure for MC012-026/029 modules is 105°C (221°F).
Storage temperature °C [°F]-40 [-40]85 [185] Maximum storage temperature forMC012-026/029 modules is 105°C (221°F).
Allowable module supply voltageVdc 9 36*Minimum allowable supply voltage for the MC038-010 module CPU power pin is 6 Vdc.
Module sensor supply voltageVdc 4.8 52 Sensor voltage drops below theminimum value if module supply voltage < 9 Vdc. Exception for MC050-055/05B and MC024-01A, see Sensor power supply ratings on page 23.
Analog input voltage levelsVdc 36*
Allowable output load current (per pin)A See individual module data sheets.
Module allowable total output currentA See individual module data sheets.
All modules Ingress Protection (IP) rating**IP 67
All modules CE rating CE compliant.

* MC050-055/05B input voltage maximum is limited to 16 Vdc.
** The PLUS+1* modules IP 67 rating is only valid when the module mating connector is in place and unused connector pin positions have sealing plugs installed.

Modules housing

MC050-055/05B module housing features are ultrasonically welded together with an assembly that is tamper-proof. Once assembled at the factory, the housing cannot be opened for service.

DANFOSS HMC-211 - Modules housing - 1

Caution

Warranty will be voided if device is opened.

Device is not field serviceable. Do not open the device.

Product installation and start-up

Connectors

PLUS+1 ^9 modules use DEUTSCH connectors. Danfoss assembles mating connector kits, referred to as a bag assembly.

Mating connector bag assembly ordering information is found in module product data sheets.

DEUTSCH mating connector part information

Description 12pin module18 pin module24 pin module38 pin module50 pin module88 pin module
Crimp tool HDT448-00(solid contacts)(20 to 24 AWG)HDT48-00(solid contacts)(16 to 20 AWG)HDT48-00(solid contacts)(20 to 24 AWG)— — HDT48-00solid contacts)(20 to 24 AWG)HDT48-00(solid contacts)(20 to 24 AWG, 12 to 14 AWG)
DTT20-00(stamped contacts)(16 to 20 AWG)DTT20-00(stamped contacts)(16 to 20 AWG)DTT20-00(stamped contacts)(16 to 20 AWG)DTT20-00(stamped contacts)(16 to 20 AWG)
Contacts Solid:0462-201-2031(20 to 24 AWG)Solid:0462-201-1631(16 to 20 AWG)Solid:0462-201-2031(20 to 24 AWG)Stamped:0462-203-12141(10 to 14 AWG)1062-20-0144(16 to 20 AWG)Solid:0462-201-2031(20 to 24 AWG)Solid:0462-201-2031(20 to 24 AWG)
Stamped:1062-20-0144(16 to 20 AWG)Stamped:1062-20-0144(16 to 20 AWG)Stamped:1062-20-0144(16 to 20 AWG)Solid:0462-201-12141(12 to 14 AWG)
Stamped:1062-20-0144(16 to 20 AWG)
Connector plugGray A-Key DTM 06-12SADT16-185B-K004Gray A-KeyDTM06-12SA Black B-Key DTM06-12SBDRC26-38S01-P017DRC26-50S01 DRC26-50S01DRC26-38S01-P017
Wedge WM-12SNot required WM-12S Not requiredNot required Not required
Strip length 3.96to 5.54mm[0.156 to 0.218 in]6.35 to 0.792mm[0.250 to 0.312 in]3.96 to 5.54mm[0.156 to 0.218 in]6.43 to 0.79mm[0.253 to 0.031 in]3.96 to 5.54mm[0.156 to 0.218 in]20 to 24 AWG:3.96 to 5.54mm[0.156 to 0.218 in]
12 to 14 AWG:6.43 to 0.79mm[0.253 to 0.031 in]
Rear seal maximum insulation OD3.05 mm[0.120 in]3.05 mm[0.120 in]3.05 mm[0.120 in]4.32 mm [0.17 in]2.41 mm[0.095 in]20 to 24 AWG:2.41 mm[0.095 in]
12 to 14 AWG:4.32 mm [0.17 in]
Sealing plugs 0413-204-2005 114017 0413-204-2005 114017 0413-204-2005 0413-2004-2005, 114017

Product installation and start-up

Danfoss mating connector part information

Description 12pin module18 pin module24 pin module38 pin module50 pin module88 pin module
Mating connector bag assembly (20 to 24 AWG)10100944 — —10100945 — —10100946 10105649
Mating connector bag assembly (16 to 20 AWG)10102025 1010202510102023 10279191010202411071844

Danfoss crimp extraction tool part information

Description Part number
Crimp tool for 20 to 24 AWG 10100745
Crimp tool for 16 to 20 AWG 10102028
Extraction tool DEUTSCH 114010; 12 AWG 11068808
Extraction tool DEUTSCH 0411-240-2005; 16 to 20, 20 to 24 AWG 10100744

Controller mounting

Recommended outer diameter (OD) Recommended torque
6.0 mm (0.25 in) 2.26 N•m (20 in•lbs)

Mounting

PLUS+1*MC0XX-0XX 12, 24, 38, and 50 pin modules can be mounted in one of three ways:

• End (bulkhead) installation
• Up to 3 units stacked on one another
• Individually side mounted

HMC-211-0XX modules are designed for panel mounting only.

MC088-XXX modules are designed for bulkhead mounting only.

Care must be taken to insure that the module connector is positioned so that moisture drains away from the connector.

If the module is side or stack mounted, provide a drip loop in the harness. If the module is mounted vertically, the connector should be on the bottom of the module.

Provide strain relief for mating connector wires.

DANFOSS HMC-211 - Mounting - 1

Caution

Module damage may occur.

Use caution when installing modules. Due to the size of the mating connector wire bundle, it is possible to twist off the end cap of the module if excessive pressure is applied during the installation of harness strain relief.

Fasteners

Recommended outer diameter (OD) Recommended torque
6.0 mm (0.25 in) 2.26 N·m (20 in·lbs)

Product installation and start-up

Machine diagnostic connector

It is recommended that a diagnostic connector be installed on machines that are controlled by PLUS+1 ^9 modules. The connector should be located in the operator's cabin or in the area where machine operations are controlled and should be easily accessible.

Communication (software uploads and downloads and service and diagnostic tool interaction) between PLUS+1 ^® modules and personal computers is accomplished over the vehicle CAN network. The diagnostic connector should tee into the vehicle CAN bus and have the following elements:

• CAN +
CAN-
• CAN shield

Grounding

Proper operation of any electronic control system requires that all control modules including displays, microcontrollers and expansion modules be connected to a common ground. A dedicated ground wire of appropriate size connected to the machine battery is recommended.

Hot plugging

Machine power should be off when connecting MC050-055/05B modules to mating connectors.

Machine wiring guidelines

W Warning

Unintended movement of the machine or mechanism may cause injury to the technician or bystanders. Improperly protected power input lines against over current conditions may cause damage to the hardware. Properly protect all power input lines against over-current conditions. To protect against unintended movement, secure the machine.

C Caution

Unused pins on mating connectors may cause intermittent product performance or premature failure. Plug all pins on mating connectors.

  • Protect wires from mechanical abuse, run wires in flexible metal or plastic conduits.
  • Use 85^ (185°F) wire with abrasion resistant insulation and 105^ (221°F) wire should be considered near hot surfaces.
  • Use a wire size that is appropriate for the module connector.
  • Separate high current wires such as solenoids, lights, alternators or fuel pumps from sensor and other noise-sensitive input wires.
  • Run wires along the inside of, or close to, metal machine surfaces where possible, this simulates a shield which will minimize the effects of EMI/RFI radiation.
  • Do not run wires near sharp metal corners, consider running wires through a grommet when rounding a corner.
    • Do not run wires near hot machine members.
  • Provide strain relief for all wires.
  • Avoid running wires near moving or vibrating components.
  • Avoid long, unsupported wire spans.
  • Ground electronic modules to a dedicated conductor of sufficient size that is connected to the battery (-).

Product installation and start-up

• Power the sensors and valve drive circuits by their dedicated wired power sources and ground returns.
• Twist sensor lines about one turn every 10 cm (4 in).
- Use wire harness anchors that will allow wires to float with respect to the machine rather than rigid anchors.

Machine welding guidelines

DANFOSS HMC-211 - Machine welding guidelines - 1

Warning

High voltage from power and signal cables may cause fire or electrical shock, and cause an explosion if flammable gasses or chemicals are present.

Disconnect all power and signal cables connected to the electronic component before performing any electrical welding on a machine.

The following is recommended when welding on a machine equipped with electronic components:

  • Turn the engine off.
  • Remove electronic components from the machine before any arc welding.
    • Disconnect the negative battery cable from the battery.
    • Do not use electrical components to ground the welder.
  • Clamp the ground cable for the welder to the component that will be welded as close as possible to the weld.

PLUS+1" USB/CAN Gateway

Communication (software uploads and downloads and service and diagnostic tool interaction) between PLUS+1 ^® modules and a personal computer (PC) is accomplished using the vehicle's PLUS+1 ^® CAN network.

The PLUS+1 ^® CG150-2 USB/CAN gateway provides the communication interface between a PC USB port and the vehicle CAN bus. When connected to a PC, the gateway acts as a USB slave. In this configuration, all required electrical power is supplied by the upstream PC host. No other power source is required.

Refer to the PLUS+1 ^® GUIDE Software User Manual, AQ152886483724, for gateway set-up information. Refer to the CG150-2 USB/CAN Gateway Data Sheet, AI152986480800, for electrical specifications and connector pin details.

Products we offer:

  • Cartridge valves
    • DCV directional control valves
    • Electric converters
    Electric machines
    Electric motors
  • Gear motors
  • Gear pumps
    • Hydraulic integrated circuits (HICs)
    • Hydrostatic motors
    • Hydrostatic pumps
  • Orbital motors
  • PLUS+1 ^® controllers
  • PLUS+1 ^ displays
    • PLUS+1° joysticks and pedals
    • PLUS+1 ^® operator interfaces
  • PLUS+1 ^ sensors
  • PLUS+1* software
    • PLUS+1 ^® software services, support and training
    • Position controls and sensors
    • PVG proportional valves
    • Steering components and systems
  • Telematics

Danfoss Power Solutions is a global manufacturer and supplier of high-quality hydraulic and electric components. We specialize in providing state-of-the-art technology and solutions that excel in the harsh operating conditions of the mobile off-highway market as well as the marine sector. Building on our extensive applications expertise, we work closely with you to ensure exceptional performance for a broad range of applications. We help you and other customers around the world speed up system development, reduce costs and bring vehicles and vessels to market faster.

Danfoss Power Solutions – your strongest partner in mobile hydraulics and mobile electrification.

Go to www.danfoss.com for further product information.

We offer you expert worldwide support for ensuring the best possible solutions for outstanding performance. And with an extensive network of Global Service Partners, we also provide you with comprehensive global service for all of our components.

Local address:

Hydro-Gear

www.hydro-gear.com

Daikin-Sauer-Danfoss

www.daikin-sauer-danfoss.com

Danfoss

Power Solutions (US) Company

2800 East 13th Street

Ames, IA 50010, USA

D-24539 Neumünster, Germany

Phone: +49 4321 871 0

Danfoss

Power Solutions ApS

Nordborgvej 81

DK-6430 Nordborg, Denmark

Phone: +45 7488 2222

Danfoss

Power Solutions Trading

(Shanghai) Co., Ltd.

Building #22, No. 1000 Jin Hai Rd

Jin Qiao, Pudong New District

Shanghai, China 201206

Phone: +86 21 2080 6201

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/5. All rights reserved.

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : DANFOSS

Model : HMC-211

Category : Remote control