GRUNDIG GHP MM8 - Heat pump

GHP MM8 - Heat pump GRUNDIG - Free user manual and instructions

Find the device manual for free GHP MM8 GRUNDIG in PDF.

📄 83 pages English EN Download 💬 AI Question
Notice GRUNDIG GHP MM8 - page 8
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about GHP MM8 GRUNDIG

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Heat pump in PDF format for free! Find your manual GHP MM8 - GRUNDIG and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. GHP MM8 by GRUNDIG.

USER MANUAL GHP MM8 GRUNDIG

text_image Diagram showing a thermometer symbol inside a door, with a minus sign and a minus sign on the door.

GHP-MM08

GHP-MM10

GHP-MM12

GHP-MM14

GHP-MM16

EN

CE

01M-8508043600-2422-01

01M-8508053600-2422-01

01M-8508063600-2422-01

01M-8503073600-2422-01

01M-8503083600-2422-01

Please read this user manual first!

Dear Valued Customer,

Thank you for preferring this Grundig appliance. We hope that you get the best results from your appliance which has been manufactured with high quality and state-of-the-art technology. For this reason, please read this entire user manual and all other accompanying documents carefully before using the appliance and keep it as a reference for future use. If you handover the appliance to someone else, give the user manual as well. Follow the instructions by paying attention to all the information and warnings in the user manual. Remember that this user manual may also apply to other models. Differences between models are explicitly described in the manual.

Meanings of the Symbols

Following symbols are used in various sections of this user manual:

GRUNDIG GHP MM8 - Meanings of the Symbols - 1

Important information or useful hints about usage.

GRUNDIG GHP MM8 - Meanings of the Symbols - 2

Warning for hazardous situations with regard to life and property.

GRUNDIG GHP MM8 - Meanings of the Symbols - 3

Warning to actions that must never perform.

GRUNDIG GHP MM8 - Meanings of the Symbols - 4

Warning for electric shock.

GRUNDIG GHP MM8 - Meanings of the Symbols - 5

Warning for hot surfaces.

GRUNDIG GHP MM8 - Meanings of the Symbols - 6

Do not cover it.

GRUNDIG GHP MM8 - Meanings of the Symbols - 7

This symbol shows that the operation manual should be read carefully.

GRUNDIG GHP MM8 - Meanings of the Symbols - 8

This symbol shows that a service personnel should be handling this equipment with reference to the installation manual.

GRUNDIG GHP MM8 - Meanings of the Symbols - 9

text_image Warning sign depicting a flame symbol in a triangular shape

(For R32/R290 gas type)

This symbol shows that this appliance used a flammable refrigerant. If the refrigerant is leaked and exposed to an external ignition source, there is a risk of fire.

Table of Contents

Part 1 General Features ....4

1.1 Unit Capacities and Appearance 4

Part 2 Component Layout and Refrigerant Circuit....5

2.1 Layout of Functional Components....5

2.2 Piping Diagram....8

2.3 Refrigerant Flow Diagram 10

Part 3 Control....11

3.1 Stop Operation....11

3.2 Standby Control 11

3.3 Startup Control .... 11

3.4 Normal Operation Control 13

3.5 Protection Control ....13

3.6 Special Control....14

3.7 Role of Temperature Sensors in Control Functions 16

3.8 EEPROM Parameter Setting 20

3.9 Electric Wiring Diagram 26

Part 4 Troubleshooting ....30

4.1 Unit Electric Control Box Layout 30

4.2 Unit PCBs....33

4.3 Error Code Table 39

4.4 Troubleshooting....41

4.5 Appendixes to Part 4....80

Part 1 General Features

1.1 Unit Capacities and Appearance

1.1.1 Unit Capacities

Table 1-1.1: Capacity range

Factory ModelKS-80W/EN8BPKS-100W/EN8BPKS-120W/EN8BPKS-140W/EN8BPKS-160W/EN8BP
Model No.GHP-MM 08GHP-MM 10GHP-MM 12GHP-MM 14GHP-MM 16

Notes:

  1. The full model names can be obtained by substituting the asterisk in the model name format given in the left-hand column of the table above with the shortened model names given in the table. For example, the model name for the 14kW model is GHP-MM14.
  2. The presence or omission of the letter E and S in the model names indicates:

E: with internal backup heater; omitted: without internal backup heater.

  1. Power supply:

220-240V, 50Hz, 1-phase.

1.1.2 Appearance

Table 1-1.2: Unit appearance

8kW
GRUNDIG GHP MM8 - Appearance - 1
10/12kW 14/16kW
GRUNDIG GHP MM8 - Appearance - 2GRUNDIG GHP MM8 - Appearance - 3

Part 2 Component Layout and Refrigerant Circuit

2.1 Layout of Functional Components

GHP-MM08

Figure 2-1.1: top view
GRUNDIG GHP MM8 - Layout of Functional Components - 1

text_image Water side heat exchanger Electronic expansion valve Four way valvet valve Automatic exhaust valve Safety valve

Figure 2-1.2: front view

GRUNDIG GHP MM8 - Layout of Functional Components - 2

text_image Air side heat exchanger DC fan Electric control box Water pressure sensor Water flow switch Variable frequency pump Built-in electric heater DC inverter compressor

Figure 2-1.3: top view
GRUNDIG GHP MM8 - Layout of Functional Components - 3

text_image Chassis heater Electric expansion valve Middle pressure switch Balance tank Water side heat exchanger Air purge valve Driver board

Figure 2-1.4: front view

GRUNDIG GHP MM8 - Layout of Functional Components - 4

text_image Air side heat exchanger DC fan Inductor Electric control box 4-way valve High pressure switch Built-in electric heater Water flow switch Low pressure sensor Expansion vessel DC inveter compressor

GHP-MM12

Figure 2-1.5: top view
GRUNDIG GHP MM8 - Layout of Functional Components - 5

text_image Air side heat exchanger Fan motor Electronic expansion valve Water side heat exchanger Safety valve Variable frequency pump Water presser sensor Air purge valve Low pressure switch

Figure 2-1.6: front view
GRUNDIG GHP MM8 - Layout of Functional Components - 6

text_image High pressure switch 4-way valve Medium pressure switch Electric control box Water flow switch DC inverter compressor Built-in electric heater

GHP-MM14/ GHP-MM16

Figure 2-1.7: top view
GRUNDIG GHP MM8 - Layout of Functional Components - 7

text_image Water side heat exchanger Four way valve

Figure 2-1.8: front view
GRUNDIG GHP MM8 - Layout of Functional Components - 8

text_image Air side heat exchanger Fan motor Electric control box Built-in electric heater Electronic expansion valve Water flow switch DC inverter compressor

2.2 Piping Diagram

Figure 2-2.1: Piping diagram
GRUNDIG GHP MM8 - Piping Diagram - 1

Compress low temperature and low pressure refrigerant gas into high temperature and high pressure refrigerant gas.

2. Electronic expansion valve (EEV)

Control refrigerant flow and reduce refrigerant pressure.

3. 4-way valve

Control refrigerant flow direction. Open in cooling mode and closed in heating mode. When open, the air side heat exchanger functions as a condenser and water side heat exchanger functions as an evaporator; when closed, the air side heat exchanger functions as an evaporator and water side heat exchanger functions as a condenser.

4. High and middle pressure switch

Regulate refrigerant system pressure. When refrigerant system pressure rises above the upper limit, the high or middle pressure switches will open and then turn off heat pump.

5. Low pressure sensor

Regulate refrigerant system pressure. When refrigerant system pressure falls below the lower limit, low pressure sensor detects the limit value and then turns off heat pump.

6. Air purge valve

Automatically remove air from the water circuit.

7. Safety valve

Preventing excessive water pressure by opening at 43.5 psi (3 bar) and discharging water from the water circuit.

8. Expansion vessel

Balance water system pressure. (Expansion vessel volume: 5L)

9. Water flow switch

Detect water flow rate to protect compressor and water pump in the event of insufficient water flow.

10. Backup heater

Provide additional heating capacity when the heating capacity of the heat pump is insufficient due to very low outdoor temperature. Also protects the external water piping from freezing.

11. Internal water pump

Circulate water in the water circuit.

2.3 Refrigerant Flow Diagram

Heating and domestic hot water operation (8,16KW for example)

Figure 2-3.1: Refrigerant flow during heating or domestic hot water operation
GRUNDIG GHP MM8 - Refrigerant Flow Diagram - 1

flowchart
graph TD
    A["Compressor"] --> B["TH Suction temp. sensor"]
    B --> C["Low pressure sensor"]
    C --> D["Discharge temp. sensor"]
    D --> E["TPI"]
    E --> F["Middle pressure switch"]
    F --> G["Four-way valve"]
    G --> H["Balance tank"]
    H --> I["Plate heat exchanger"]
    I --> J["Water-in"]
    J --> K["Water-out"]
    K --> L["High pressure and high temperature gas"]
    K --> M["High pressure and middle temperature liquid"]
    K --> N["Low pressure and low temperature liquid-gas mixture"]
    K --> O["Low pressure and low temperature gas"]
    P["Air side heat exchanger"] --> Q["T3"]
    Q --> R["Contemp. sensor"]
    R --> S["T4"]
    S --> T["Ambient temp. sensor"]
    T --> U["Heating liquid temp. sensor"]
    U --> V["Filter"]
    V --> W["Filter"]
    W --> X["EEV"]
    X --> Y["T5"]
    Y --> Z["Balance tank"]
    Z --> AA["Water-in"]
    AA --> AB["Plate heat exchanger"]

Cooling and defrosting operation (8,16KW for example)

Figure 2-3.2: Refrigerant flow during cooling and defrosting operations
GRUNDIG GHP MM8 - Cooling and defrosting operation (8,16KW for example) - 1

flowchart
graph TD
    A["Compressor"] --> B["TH Discharge temp. sensor"]
    B --> C["High pressure switch"]
    C --> D["Middle pressure switch"]
    D --> E["Four-way valve"]
    E --> F["Plate heat exchanger"]
    F --> G["Water-out"]
    F --> H["Water-in"]
    F --> I["Balance tank"]
    I --> J["Filter"]
    J --> K["T5"]
    K --> L["EEV"]
    L --> M["Heating liquid temp. sensor"]
    M --> N["Filter"]
    N --> O["T4 Ambient temp. sensor"]
    O --> P["Air side heat exchanger"]
    P --> Q["T3 Con temp. sensor"]
    Q --> R["Low pressure sensor"]
    R --> S["Low pressure and low temperature gas mixture"]
    style A fill:#f9f,stroke:#333
    style P fill:#ccf,stroke:#333

Part 3 Control

3.1 Stop Operation

The stop operation occurs for one of the following reasons:

3.1.1 Normal shutdown: The heat pump will stop running when the set temperature has been reached.

3.1.2 Abnormal shutdown: in order to protect the compressors, if an abnormal state occurs the system makes a "turn off" operation and an error code are displayed on the user interface.

3.2 Standby Control

3.2.1 Water Pump Control

When the outdoor unit is on standby, the internal and external circulator pumps run continuously.

3.2.2 Crankcase Heater Control

The crankcase heater is used to prevent refrigerant from mixing with compressor oil when the compressors are stopped. The crankcase heater is controlled according to outdoor ambient temperature and the compressor's on/off state. When the outdoor ambient temperature is at or above 7°C or the compressor is running, the crankcase heater is off; when the outdoor ambient temperature is below 5°C and the unit has just been powered on (either manually or when the power supply has been restored from a breakdown), the crankcase heater turns on and run by half an hour on half an hour off cycle. When the compressor has been stopped for more than 3 hours and the outdoor ambient temperature is below 5°C, the crankcase heater turns on and run for half an hour on half an hour off cycle.

3.3 Startup Control

3.3.1 Compressor Startup Delay Control

In initial startup control or restart control (except in oil return operation and defrosting operation) or switching from on mode to another mode, compressor startup is delayed such that a 3 minute delay time has elapsed since the compressor last stopped, in order to prevent frequent compressor on/off and to equalize the pressure within the refrigerant system.

3.3.2 Compressor Startup Program

In initial startup control and restart control, compressor startup is controlled according to outdoor ambient temperature. Compressor startup follows the startup steps below until the target rotation speed is reached.

Figure 3-3.1: Compressor startup procedure
GRUNDIG GHP MM8 - Compressor Startup Program - 1

line | Time | Frequency (Hz) | | ---- | -------------- | | 0 | 0 | | 40 | 40 | | 60 | 60 | | >60 | 80 |

3.3.3 Startup Control for Heating and Domestic Hot Water Operation

Table 3-3.1: Component control during startup in heating and domestic hot water modes

Component Control function and state
Inverter compressorCompressor startup program by figure3-3.1
DC fan motorStart the fan 10 seconds before the compressor starts, and then run half of the maximum speed, and then run at maximum speed 60s after the compressor startup
Electronic expansion valvePosition (steps) from 0 (fully closed) to 480 (fully open), controlled according to outdoor ambient temperature and in-water temperature
4-way valve ON

3.3.4 Startup Control for Cooling Operation

Table 3-3.2: Component control during startup in cooling mode

Component Control function and state
Inverter compressorCompressor startup program by figure3-3.1
DC fan motorStart the fan 10 seconds before the compressor starts, and then run half of the maximum speed, and then run at maximum speed 60s after the compressor startup
Electronic expansion valvePosition (steps) from 0 (fully closed) to 480 (fully open), controlled according to outdoor ambient temperature and in-water temperature
4-way valve OFF

3.4 Normal Operation Control

3.4.1 Component Control during Normal Operation

Table 3-4.1: Component control during heating and domestic hot water operations

Component Control function and state
Inverter compressorControlled according to load requirement from hydraulic module
DC fan motorControlled according to outdoor ambient temperature and outdoor heat exchanger pipe temperature
Electronic expansion valvePosition (steps) from 0 (fully closed) to 480 (fully open), controlled according to in-water temperature, out-water temperature and discharge temperature
4-way valve ON

Table 3-4.2: Component control during cooling operation

Component Control function and state
Inverter compressorControlled according to load requirement from hydraulic module
DC fan motorControlled according to outdoor ambient temperature and outdoor heat exchanger pipe temperature
Electronic expansion valvePosition (steps) from 0 (fully closed) to 480 (fully open), controlled according to in-water temperature, out-water temperature and discharge temperature
Four-way valveOFF

3.4.2 Compressor Output Control

The compressor rotation speed is controlled according to the load requirement. The compressor follows a fixed starting procedure as shown in figure 3-3.1. After finishing the startup, the compressor runs at the target rotation speed.

During normal operation the compressor speed is controlled according to inlet water temperature, target water temperature set by the user interface, the rate of change in inlet water temperature.

3.4.3 Compressor Step Control

The running speed of six-pole compressors (used on all models) in rotations per second (rps) is one third of the frequency (in Hz) of the electrical input to the compressor motor. The frequency of the electrical input to the compressor motors can be altered at a rate of 1Hz per second.

3.4.4 Four way Valve Control

The four-way valve is used to change the direction of refrigerant flow through the water side heat exchanger in order to switch between cooling and heating/DHW operations.

During heating and DHW operations, the four-way valve is on; during cooling and defrosting operations, the four-way valve is off.

3.4.5 DC Fan Control

Start the fan before the compressor starts, and fan runs at the initial speed. After the compressor runs a few minutes, the fan runs at a higher set speed.

3.4.6 Electronic Expansion Valve Control

The position of the electronic expansion valve (EEV) is controlled in steps from 0 (fully closed) to 480 (fully open).

At power-on

EEV first closes fully, and then moves to the standby position. After a few seconds EEV moves to an initial running position, which is determined according to operating mode, inlet water temperature and outdoor ambient temperature. A few minutes further, EEV is controlled according to inlet water temperature, outlet water temperature, discharge temperature and compressor speed.

■ When the unit is on standby

EEV keeps current position and delay a few seconds and opens fully.

■ When the unit stops

EEV keeps current position first and delay a few seconds and opens fully.

3.5 Protection Control

3.5.1 Low Pressure Protection Control

Figure 3-5.1: Low pressure protection control
GRUNDIG GHP MM8 - Low Pressure Protection Control - 1

line | Time | Low pressure(MPa) | | ---- | ----------------- | | Start | 0.14 | | ON | 0.3 | | Off | 0.14 |

When the suction pressure drops below 0.14MPa the system displays P03 protection and the unit stops running. When the suction pressure rises above 0.3MPa, the compressor enters re-start control.

3.5.2 High Pressure Protection Control

This control protects the compress from the over-high refrigerant system pressure.

Figure 3-5.2: High pressure protection control
GRUNDIG GHP MM8 - High Pressure Protection Control - 1

line | Time | High pressure(MPa) | | :--- | :--- | | OFF | 4.5 | | ON | 3.5 |

When the discharge pressure rises above 4.5MPa the system displays P02 protection and the unit stops running. When the discharge pressure drops below 3.5MPa, the compressor enters re-start control.

3.5.3 Discharge Temperature Protection Control

This control protects the compressor from abnormally high temperature.

Figure 3-5.3: High discharge temperature protection control
GRUNDIG GHP MM8 - Discharge Temperature Protection Control - 1

line | Time | High Temperature(°C) | | ---- | -------------------- | | 0 | 90 | | 115 | 115 | | 200 | 90 |

When the discharge temperature rises above 115^ C the system displays P05 protection and the unit stops running. When the discharge temperature drops below 95^ C, the compressor enters a re-start control.

3.5.4 Compressor Current Protection Control

This control protects the compressor from abnormally high currents. When the compressor current rises above maximum current the system displays E23 protection and the unit stops running. When the compressor current drops below maximum current, the compressor enters re-start control.

Table 3-5.1: Compressor current protection control

model8-10kw12kw 1ph14-16kw 1ph
Maximum current (A)14 18 25

3.5.5 DC Fan Motor Protection Control

Check the feedback signal one minute after the fan starts. If the motor speed is lower than the default minimum speed or there is no feedback for one minute, the motor fault P11 will be displayed. If it occurred 10 times within 2 hours, the unit will shut down and be locked.

3.5.6 Water Side Heat Exchanger Anti-freeze Control

This control protects the water side heat exchanger from ice formation. The water side heat exchanger electric heater is controlled according to outdoor ambient temperature, inlet water temperature and outlet water temperature.

■ When all the conditions below are met, the unit will turn on the water side heat exchanger electric heater:

● the current operation mode of the unit is shutdown or standby;
● outdoor ambient temperature is below 4^ C;
- inlet water temperature or outlet water temperature(the minor one) is below 4°C;

■ When any one of the conditions below is met, the unit will turn off the water side heat exchanger electric heater:

● the current operation of the unit is neither shutdown nor standby;
● outdoor ambient temperature is above 6^ C;
- inlet water temperature or outlet water temperature(the minor one) is above 6°C;

3.5.7 Module Temperature Protection Control

This control protects the module from abnormally high temperatures. When the module temperature rises at or above the up limit value 96^ C, the interface displays E29 protection code and the unit stops running.

3.6 Special Control

3.6.1 Oil Return Operation

In order to prevent the compressor from running out of oil, the oil return operation is conducted to recover oil that has flowed out of the compressor and into the refrigerant piping.

When the compressor cumulative operating time with running rotation speed less than 50Hz has been reached 3 hours, the unit will start an oil-return operation.

The oil return operation ceases when any one of the following three conditions occurs:

■ Oil return operation duration has been reached 4 minutes.

■ The unit will turn off because of the protection.
■ "TURN OFF" command is received.

Table 3-6.1 Component control during oil-return operation

Component Control functions and states
CompressorRuns at oil return operation rotation speed
Electronic expansion valveFully open
DC fan motorControlled according to outdoor heat exchanger pipe temperature
4-way valve OFF

3.6.2 Defrosting Operation

In order to recover heating capacity, the defrosting operation is conducted when the air side heat exchanger of the unit is performing as a condenser. The defrosting operation is controlled according to outdoor ambient temperature, air side heat exchanger refrigerant outlet temperature and the compressor running time.

Table 3-6.2: Component control during defrosting operation

ComponentControl functions and states
CompressorRuns at defrosting operation rotation speed
Electronic expansion valveFully open
DC fan motor OFF
4-way valve OFF

3.7 Role of Temperature Sensors in Control Functions

Figure 3-7.1: Location of the temperature sensors of all models 8-16kw
GRUNDIG GHP MM8 - Role of Temperature Sensors in Control Functions - 1

flowchart
graph TD
    A["Compressor"] --> B["4.T4 Ambient temp. sensor"]
    B --> C["Air side heat exchanger"]
    C --> D["DC Fan"]
    D --> E["Coil temp. sensor"]
    E --> F["Heating liquid temp. sensor"]
    F --> G["Balance tank"]
    G --> H["Plate heat exchanger"]
    H --> I["7-TB"]
    I --> J["Water-out temp. sensor"]
    J --> K["Drain needle valve"]
    K --> L["Internal backup heater"]
    L --> M["Salty valve"]
    M --> N["Water pressure sensor"]
    N --> O["Stop valve"]
    O --> P["3-way valve"]
    P --> Q["Distributor"]
    Q --> R["FCU1"]
    Q --> S["FCUn Collector"]
    P --> T["Distributor"]
    T --> U["RAD1"]
    T --> V["RADn Collector"]
    P --> W["Distributor"]
    W --> X["Collector"]
    P --> Y["Domestic water tank"]
    Y --> Z["FHL1"]
    Y --> AA["FHLn"]
    B --> AB["Low pressure sensor"]
    AB --> AC["4.T4 Ambient temp. sensor"]
    AC --> AD["DC Fan"]
    AD --> AE["Coil temp. sensor"]
    AE --> AF["Heating liquid temp. sensor"]
    AF --> AG["Balance tank"]
    AG --> AH["4.T4 Ambient temp. sensor"]
    AH --> AI["DC Fan"]
    AI --> AJ["Coil temp. sensor"]
    AJ --> AK["Heating liquid temp. sensor"]
    AK --> AL["Balance tank"]
    AL --> AM["4.T4 Ambient temp. sensor"]
    AM --> AN["DC Fan"]
    AN --> AO["Coil temp. sensor"]
    AO --> AP["Heating liquid temp. sensor"]
    AP --> AQ["Balance tank"]
    AQ --> AR["4.T4 Ambient temp. sensor"]
    AR --> AS["DC Fan"]
    AS --> AT["Coil temp. sensor"]
    AT --> AU["Heating liquid temp. sensor"]
    AU --> AV["Balance tank"]

Table 3-7.1: All the temperature sensors

ItemNameLabelModeControl functions
1 Suctiontemp. sensor THCooling Electronic expansion valve control
Heating Electronic expansion valve control
2 Dischargetemp. sensor TPCoolingElectronic expansion valve control
Discharge temp. protection control
HeatingElectronic expansion valve control
Discharge temp. protection control
3 Coil temp. sensor T3CoolingElectronic expansion valve control
DC fan control
Compressor output control
HeatingElectronic expansion valve control
DC fan control
Defrosting operation control
4Outdoor ambient temp. sensorT4CoolingCompressor startup control
Compressor output control
Electronic expansion valve control
DC fan control
Crankcase heater control
HeatingCompressor startup control
Compressor output control
Electronic expansion valve control
DC fan control
Defrosting operation control
Crankcase heater control
5Liquid refrigerant temp. sensorT5CoolingAnti-freezing protection control
Heating /
6 Inlet waterwater temp. sensor TACoolingAnti-freezing protection control
Compressor on/off and output control
Oil-returning control
Electronic expansion valve control
HeatingCompressor on/off and output control
Oil-returning control
Defrosting operation control
Electronic expansion valve control
7Outlet water temp. sensorTBCoolingAnti-freezing protection control
Electronic expansion valve control
HeatingCompressor output control
Defrosting operation control
Electronic expansion valve control
8Domestic water tank temp. sensorTWDHWCompressor output/Backup electric heater control

3.8 EEPROM Parameter Setting

Press "M" and "Up" two keys at the same time, and then enter the password "1212" to adjust EEPROM parameter value. Refer to the table below for the detailed setting.

ItemNameCodeDefaultUnitRangeAccuracy
1Air conditioning water temperature return differenceTa 2 °C1~5 1
2Hot water temperature differenceTb5°C2~151
3Cooling target exhaust temperature correctionTargetTPc0°C-10~151
4Heating superheatSHh-1°C-5~101
5Compressor frequency in refrigeration test modeLCF_C68Hz20~1201
6Compressor frequency in heating test modeLCF_H68Hz20~1201
7Compressor frequency in hot water test modeLCF_W68Hz20~1201
8Cooling test mode EEV openingEEV_C250/5P(0~480)/51
9Heating test mode EEV-1 openingEEV_H150/5P(0~480)/51
10Hot water test mode EEV-1 openingEEV_W150/5P(0~480)/51
11Defrost entry temperatureDST-5°C-15~01
12Defrost enters temperature differenceDt12°C0~151
13Judgment time of first defrostT140min20~901
14Defrosting process EEV openingOpl480/5P(0~480)/51
15Defrost compressor frequencyFD12Hz30~1201
16Maximum operating frequencyFmax85Hz30~1201
17Power-off memoryPR10/10-disable 1-enable/
18Silent mode frequency limitFs55Hz30~1201
19Sterilization set temperatureTx65°C55~751
20Disinfection duration timeTd30Min20~1201
21Run mode priorityMp00/1/20-DHW 1-Space AC 2-Preempt/
22Compressor resonance point 1FR10Hz0~1201
23Compressor resonance point 2FR20Hz0~1201
24Compressor resonance point 3FR30Hz0~1201
25Compressor resonance point 4FR40Hz0~1201
26Ambient temperature for electric heating of water tankTeh4°C-10~401
27Whether automatic temperature adjustment is effectiveAuto heating Adjust enable0 0/10-disable 1-enable1
28Temperature compensation high pointHi_A5°C0~201
29Temperature compensation low pointLo_A0°C-20~01
30Maximum temperature compensationA5°C0~101
31Whether the high heating temperature shutdown is effectiveTo enable high temp. heating shutdown0 0/10-disable 1-enable1
32Heating high temperature shutdown temperature settingT4h24°C10~301
33PWM water pump brandMPumpTyp3/0-AC pump 1-OMT1 2-Grundfos 3-Wilo 4-OMT21
34Pump running status in heating standby modeH-Pump3 0/10-On 1min OFF 3min 1-ON 1min OFF 10min 2-On 2min OFF 15min 3-Always On1
35Low temperature stop compressor temperature settingT4L-30°C-40~-211
36Pipeline electric heating is effective or invalidHD0 0/10-enable 1-disable1
37Whether the cooling mode is effectiveCool on enable0 0/10-enable 1-disable1
38Whether the high pressure 2 switch is effective (system parameter)Middle pressure Switch enable0 0/10-enable 1-disable1
39Minimum opening settingMinEEV80/5P(0~480)/51
40Minimum water temperature requirement when entering defrostTdf10°C0~401
41Ambient temperature of pipeline electric heatingT4g-20°C-40~201
42Defrost exit temperatureFt15°C10~251
43Maximum defrost operating timeFT10Min1~201
44Return oil into the lowest frequencyFo50Hz30~601
45Test mode AC fan speedTF2/1-low speed 2-high speed/
46Chassis electric heating start temperatureBHon-5°C-15~01
47Minimum operating frequencyFmin25Hz20~1001
48Heating mode switchHeatChange0/0/1/
49Correction of heating target exhaust temperatureTargetTPh0°C-10~151
50EEPROM Reset/0/0-Normal 1-Reset1
51Standby water pump speedSB-PWMout35%10~1001
52Test mode DC fan speedFspeedT900/15rpm200~1000/151
53Minimum DC fan speedFanMin250/15rpm200~500/151
54Minimum DC fan speedFanMax825/15rpm500~1000/151
55Maximum DC fan speedNoiseFan650/15rpm300~1000/151
56Cool coil pipe temp.CondT40°C20~601
57Heat coil pipe temp.EvapT5°C-10~201
58DC fan resonance point 1SR10/15rpm0~1000/151
59DC fan resonance point 2SR20/15rpm0~1000/151
60DC fan resonance point 3SR30/15rpm0~1000/151
61Test mode PWM pump speedTest_P100%50~1001
62PWM pump minimum speedMin-PWMout70%50~1001
63Trv is effective or notenTrV10/10-disable1-enable1
64Four way switching fault judgment temperature differenceTrv3°C0~101
65EVI heat or DHW superheatSHe6°C-5~251
66Cool test mode EEV-2 openEEV_C0/5P(0~480)/51
67Heat test mode EEV-2 openEEV_H150/5P(0~480)/51
68DHW test mode EEV-2 openEEV_W150/5P(0~480)/51
69Commercial mode heating frequencyFreqTestH60Hz20~1001
70Commercial mode heating EEV-1 openEEVTestH-1250/5P(0~480)/51
71Commercial mode heating EEV-2 openEEVTestH-2150/5P(0~480)/51
72Commercial mode cooling frequencyFreqTestC40Hz20~1001
73Commercial modecooling EEV-1 openEEVTestC-1300/5P(0~480)/51
74Commercial mode cooling EEV-2 openEEVTestC-20P(0~480)/51
75Chassis heater on timeBaseHeatTime610Min0~1001
76Group control addressIP00-151
77Low pressure check typeLPS1/0-low pressure switch1- low pressure sensor1
78Pump running status in cooling standby modeC-Pump30/10-on 1min off3min1-on 1min off10min2-on 2min off15min3-Always on1
79Chassis heater enable or disableTH4 1 0/10-disable1-enable1
80EVI-main cool superheat(≤60Hz)SHc14°C0~151
81EVI-sub cool superheat (≤60Hz)SCe16°C0~151
82EVI-main cool superheat (≥70Hz)SHc25°C0~151
83EVI-sub cool superheat (≥70Hz)SCe26°C0~151
84Heating superheatSHlps4°C0~151
85EVI startup frequencyF-EVI60Hz30~1001
86Heat four way valve on delay4 Way-on time10S1-1001
87Heat four way valve off delay4 Way-Off time120S0-1201
88Target water temperature typeIn/Out_Change0/0-TA Inlet water1-TB Outlet water1
89Outlet water control differential coefficienta3°C1-101
90Second compressor startup frequencyF-Start260Hz40-901
91Heat pump off frequencyF-Stop25Hz20-901
92Defrost 4-way valve switch frequencyFD-Change38Hz20-901
93Compressor off delayCOMP-Off time0S0-601
94EEV off delayEEV- Stop time60S0-1201
95Test mode typeTest_Typ0/0-normal1-standard2-ERP13-ERP21
96T3 change rate when defrostDeT40/10°C(10-100)/101
97T4 switch in TP protectionTP-Change-15°C0~ -30 1
98Water pressure check enableWPS00/10-disable1-enable1
99Compressor resonance point 5FR50Hz0~1201

3.9 Electric Wiring Diagram

3.9.1 (GHP-MM08); (GHP-MM10); (GHP-MM12)

GRUNDIG GHP MM8 - Electric Wiring Diagram - 1

text_image BRN Remote Switch PE TH1 THA TH3 K18 PUMP_PW HEAT1 N HEAT2 N HEAT3 N HEAT4 BRN PHEAFEB BLU IPH1(3kW) P1 P1 to IPH1 BLU Control Board 2 DISP Dig Switch Factory Default SW4= 1/2/34 OFF/OFF/OFF/OFF SAG= 1 OFF SAG= 1/2/34 OFF/OFF/OFF/OFF FUT T10A 25V AC_L 17 16 32 OFF1 ON1 OFF2 ON2 OFF3 ON4 P_c P_o P_s P_d ETH AHS1 DFT1 R1 SL2 AC_CL TBH BH1 N N N N N N N N AHS2 DFT2 R2 SL1 AC_L1 AC_HT BLU BRN SWAY VALUE: OFF+/NORMAL CLOSED, ON+/NORMAL OPEN 1 OFF 2 ON1 3 ON2 4 ON3 5 ON4 6 ON5 7 ON6 8 ON7 9 ON8 10 ON9 11 ON10 12 ON11 ON12 ON13 ON14 ON15 ON16 ON17 ON18 ON19 ON20 ON21 ON22 ON23 ON24 ON25 ON26 ON27 ON28 ON29 ON30 ON31 ON32 ON33 ON34 ON35 ON36 ON37 ON38 ON39 ON40 ON41 ON42 ON43 ON44 ON45 ON46 ON47 ON48 ON49 ON50 ON51 ON52 ON53 ON54 ON55 ON56 ON57 ON58 ON59 ON60 ON61 ON62 ON63 ON64 ON65 ON66 ON67 ON68 ON69 ON70 ON71 ON72 ON73 ON74 ON75 ON76 ON77 ON78 ON79 ON80 MW LOTO OUTPUT: GUANGUARD-SURVIC GUACOMINIUS-ENIXAVIC. SV1 SWITCHING DETRATES: AC AND HOT WATER, SV2 SWITCHING DETRATES: CCOL-BACKED HEATRIC. BRN POWER SUPPLY: AC 220-240V~50Hz SPINION TERMINALS COM C COM I COM T COM L Wire Controller Low Pressure Sensor LPS AC Power Sensor AC Power Sensor TS5 TS4 TS3 TS2 TS1 TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH TSH DRIVE CIRCUIT CAP CAP CAP OUT 10 SW1 SW2 UP Switch Control Signal OUT 1/2/34 ORCHORON OFF OUT 1/2/34 ORCHORON OFF FAN1 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT 9 OUT 10 OUT 11 OUT 12 OUT 13 OUT 14 OUT 15 OUT 16 OUT 17 OUT 18 OUT 19 OUT 20 OUT 21 OUT 22 OUT 23 OUT 24 OUT 25 OUT 26 OUT 27 OUT 28 OUT 29 OUT 30 OUT 31 OUT 32 OUT 33 OUT 34 OUT 35 OUT 36 OUT 37 OUT 38 OUT 39 OUT 40 OUT 41 OUT 42 OUT 43 OUT 44 OUT 45 OUT 46 OUT 47 OUT 48 OUT 49 OUT 50 OUT 51 OUT 52 OUT 53 OUT 54 OUT 55 OUT 56 OUT 57 OUT 58 OUT 59 OUT 60 OUT 61 OUT 62 OUT 63 OUT 64 OUT 65 OUT 66 OUT 67 OUT 68 OUT 69 OUT 70 OUT 71 OUT 72 OUT 73 OUT 74 OUT 75 OUT 76 OUT 77 OUT 78 OUT 79 OUT 80 OUT 81 OUT 82 OUT 83 OUT 84 OUT 85 OUT 86 OUT 87 OUT 88 OUT 89 OUT 90 OUT 91 OUT 92 OUT 93 OUT 94 OUT 95 OUT 96 OUT 97 OUT 98 OUT 99 OUT CODE NAME DISP Digital Display SV1 For Switching Between AC and Hot water FS1 PINM for Integrated Variable Speed Pump SV2 For Switching Between Coding and Heating P1 P1 Auto Reset Switch for IPH1 Others Reserved DISP Digital Display

GRUNDIG GHP MM8 - Electric Wiring Diagram - 2

text_image Remote Switch Water Flow Switch Water Pressur Sensor Water Tank Temp TS1 TS2 TS3 TS4 TS5 TS6 TS7 TS8 TS9 TS10 TS11 TS12 TS13 TS14 TS15 TS16 TS17 TS18 TS19 TS20 TS21 TS22 TS23 TS24 TS25 TS26 TS27 TS28 TS29 TS30 TS31 TS32 TS33 TS34 TS35 TS36 TS37 TS38 TS39 TS40 TS41 TS42 TS43 TS44 TS45 TS46 TS47 TS48 TS49 TS50 TS51 TS52 TS53 TS54 TS55 TS56 TS57 TS58 TS59 TS60 TS61 TS62 TS63 TS64 TS65 TS66 TS67 TS68 TS69 TS70 TS71 TS72 TS73 TS74 TS75 TS76 TS77 TS78 TS79 TS80 TS81 TS82 TS83 TS84 TS85 TS86 TS87 TS88 TS89 TS90 TS91 TS92 TS93 TS94 TS95 TS96 TS97 TS98 TS99 TS100

3.9.2 (GHP-MM14) ; (GHP-MM16)
GRUNDIG GHP MM8 - Electric Wiring Diagram - 3

text_image BRIN Remote Switch PE TH1 THA TH3 K18 ON COB TS4 TS3 TS2 KEY1 KEY2 PS2 PS1 FS1 COM_C COM_I COM_T COM_L Control Board 2 DISP Dip Switch Factory Set/Well OFF: 100kN OFF/OFF/OFF/OFF SWG: 1 OFF SWG> 100kN OFF/OFF/OFF/OFF LPS Low Pressure Sensor Water Pressure Sensor Mid-pressure switch YEL(on/GRN) MP HP GRN High pressure switch Control Board 1 Dip Switch Factory Set/Well SWI: 1/2/34 OFF/OFF/OFF/OFF SWG: 1/2/34 OFF/OFF/OFF/OFF DIP Switch Factory Set/Well SWI: 1/2/34 OFF/OFF/OFF/OFF WTP: 1/2/34 OFF/OFF/OFF/OFF SRS: 1/2/34 OFF/OFF/OFF/OFF SRS: 1/2/34 OFF/OFF/OFF/OFF DC Fan Driver Board CNB7 FAN2 FAN1 RED 11.1 RED 12.1 RED 1 PE L N BLU BLU BRIN PHEAFEB BLU IPH1(3kW) P1 P1 to IPH1 BRIN Control Board 2 DISP Dip Switch Factory Set/Well OFF: 100kN OFF/OFF/OFF/OFF SWG: 1 OFF ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On On Off: 16 AC_L AC_N AC_2 AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC_L AC L

GRUNDIG GHP MM8 - Electric Wiring Diagram - 4

text_image Communication terminals Compressor Power Supply U/V W Power Supply L N Water Flow Switch TS1 Water Flow Switch TS2 Water Tank Temp. TS3 Inset Water Temp. TS4 PUMP Feedback line COMJ Wire Controller PE Earthing wire Indoor unit Electric heating relay TH1 K18 TST TH2 TH3 TH3 K19 TSB TH3 K20 TSB PUMP Power Cord PUMP PW Switch the plate to electric heating tape HEAT1 HEAT2 HEAT3 HEAT4 Stand-by Electric heating terminal Heat1 HEAT2 HEAT3 HEAT4 Chassis Heating 5d Chassis Heater Motherboard Power Cord Power Supply AC-L AC-N 4-Way Valve OUT4 Circuit Audio 5d OUT6 Circuit Audio 5d OUT7 Circuit Audio 5d OUT8 Circuit Audio 5d OUT9 Circuit Audio 5d OUT10 Circuit Audio 5d OUT11 Circuit Audio 5d OUT12 Circuit Audio 5d OUT13 Circuit Audio 5d OUT14 Circuit Audio 5d OUT15 Circuit Audio 5d OUT16 Circuit Audio 5d OUT17 Circuit Audio 5d OUT18 Circuit Audio 5d OUT19 Circuit Audio 5d OUT20 Circuit Audio 5d OUT21 Circuit Audio 5d OUT22 Circuit Audio 5d OUT23 Circuit Audio 5d OUT24 Circuit Audio 5d OUT25 Circuit Audio 5d OUT26 Circuit Audio 5d OUT27 Circuit Audio 5d OUT28 Circuit Audio 5d OUT29 Circuit Audio 5d OUT30 Circuit Audio 5d OUT31 Circuit Audio 5d OUT32 Circuit Audio 5d OUT33 Circuit Audio 5d OUT34 Circuit Audio 5d OUT35 Circuit Audio 5d OUT36 Circuit Audio 5d OUT37 Circuit Audio 5d OUT38 Circuit Audio 5d OUT39 Circuit Audio 5d OUT40 Circuit Audio 5d OUT41 Circuit Audio 5d OUT42 Circuit Audio 5d OUT43 Circuit Audio 5d OUT44 Circuit Audio 5d OUT45 Circuit Audio 5d OUT46 Circuit Audio 5d OUT47 Circuit Audio 5d OUT48 Circuit Audio 5d OUT49 Circuit Audio 5d OUT50 Circuit Audio 5d OUT51 Circuit Audio 5d OUT52 Circuit Audio 5d OUT53 Circuit Audio 5d OUT54 Circuit Audio 5d OUT55 Circuit Audio 5d OUT56 Circuit Audio 5d OUT57 Circuit Audio 5d OUT58 Circuit Audio 5d OUT59 Circuit Audio 5d OUT60 Circuit Audio 5d OUT61 Circuit Audio 5d OUT62 Circuit Audio 5d OUT63 Circuit Audio 5d OUT64 Circuit Audio 5d OUT65 Circuit Audio 5d OUT66 Circuit Audio 5d OUT67 Circuit Audio 5d OUT68 Circuit Audio 5d OUT69 Circuit Audio 5d OUT70 Circuit Audio 5d OUT71 Circuit Audio 5d OUT72 Circuit Audio 5d OUT73 Circuit Audio 5d OUT74 Circuit Audio 5d OUT75 Circuit Audio 5d OUT76 Circuit Audio 5d OUT77 Circuit Audio 5d OUT78 Circuit Audio 5d OUT79 Circuit Audio 5d OUT80 Circuit Audio 5d OUT81 Circuit Audio 5d OUT82 Circuit Audio 5d OUT83 Circuit Audio 5d OUT84 Circuit Audio 5d OUT85 Circuit Audio 5d OUT86 Circuit Audio 5d OUT87 Circuit Audio 5d OUT88 Circuit Audio 5d OUT89 Circuit Audio 5d OUT90 Circuit Audio 5d OUT91 Circuit Audio 5d OUT92 Circuit Audio 5d OUT93 Circuit Audio 5d OUT94 Circuit Audio 5d OUT95 Circuit Audio 5d OUT96 Circuit Audio 5d OUT97 Circuit Audio 5d OUT98 Circuit Audio 5d OUT99 Circuit Audio 5d OUT100

Part 4 Troubleshooting

4.1 Unit Electric Control Box Layout

Figure 4-1.1: (GHP-MM08)
GRUNDIG GHP MM8 - Unit Electric Control Box Layout - 1

text_image Drive PCB Hydraulic module PCB Main power supply terminal Auxiliary terminal Remote switch terminal

Figure 4-1.2: (GHP-MM10)/(GHP-MM12)
GRUNDIG GHP MM8 - Unit Electric Control Box Layout - 2

text_image Drive PCB Auxiliary terminal Hydraulic module PCB Remote switch terminal Main power supply terminal

Figure 4-1.3: (GHP-MM14)/(GHP-MM16)
GRUNDIG GHP MM8 - Unit Electric Control Box Layout - 3

4.2 Unit PCBs

4.2.1 Types

Heat pump has two types of PCBs – one for the hydraulic system and the other for the refrigerant system. All models share the same hydraulic system PCB. The number of PCBs of each model is for reference to Table 4-2.1 below.

Table 4-2.1 PCB

Model/Number8kw/10kw12kw14kw/16kw
Refrigerant system module1 11
Inverter module 1
Hydraulic module PCB 1 1 1
Total223

The locations of each PCB in the unit electric control boxes are shown in Figures 4-2.1, 4-2.2, 4-2.3, 4-2.4, 4-2.5. For 8/10/12kw, Inverter module and refrigerant system module constitute an integrated PCB which is called drive PCB. For 14/16kw, Drive PCB and refrigerant system PCB are separate.

4.2.2 Hydraulic Module PCB

Figure 4-2.1: PCB for Hydraulic Module
GRUNDIG GHP MM8 - Hydraulic Module PCB - 1

text_image 23 22 21 19 20 18 17 16 15 1 2 3 4 5 14 13 6 7 8 9 10 11 12

Table 4-2.2: Hydraulic module PCB

Items Port label function
1PEPort for ground
2K18Relay for internal backup heater(IBH,3Kw)
3K19Relay for domestic water tank heater(3kW)
4PumpPower supply of internal pump
5HEAT 1Plate heat exchange anti-freezing heater
6 K20 Relay (Reserved,3kW)
7 CON1Terminals(Reserved)
8TS7High temperature protection switch for IBH
9 SW1/2/3/4 Dip switch
10FLSProgram update
11PS1Water pressure sensor
12FS1Internal pump speed feedback
13 AC Power supply
14U19Communication ports
15COM_LWired controller
16COM_ICommunication port
17TH3Inlet water temperature
18TH4Outlet water temperature
19TH8Domestic water tank temperature
20TS5Remote switch
21TS1Water flow switch
22SGReserved
23EVUReserved

4.2.3 Drive and refrigerant system PCB
Figure 4-2.2: (GHP-MM08)
GRUNDIG GHP MM8 - Hydraulic Module PCB - 2

text_image 10 9 8 7 6 5 4 3 2 1 11 12 13 14 15 16 17 18 19 20 21

Table 4-2.3: (GHP-MM08)

Items Port label function
1 U/V/WCompressor output
2 JTAG Drive program update
3TH1Coil temperature sensor
4TH2Outdoor ambient temperature sensor
5TH3Refrigerant liquid temperature sensor
6TH5Discharge temperature sensor
7TH7Suction temperature sensor
8TS3HP2: Middle pressure switch
9TS4HP1: High pressure switch
10TS5LPS: low pressure sensor
11 AC Power supply
12COM4Communication with hydraulic module PCB
13PE1Port for ground
14/Filter components
15OUT44-way valve
16FLSPCB Program update
17 OUT 5 Chassis heater
18 OUT 8 Crankcase heater
19K9Relay for PFC
20 FAN1DC fan
21 /Drive components

Figure 4-2.3: (GHP-MM10)/(GHP-MM12)
GRUNDIG GHP MM8 - Hydraulic Module PCB - 3

text_image 10 9 8 7 6 5 4 3 2 1 11 12 13 14 15 16 17 18 19 20 21

Table 4-2.4: (GHP-MM10)/(GHP-MM12)

ItemsPort labelfunction
1 U/V/WCompressor output
2 JTAG Drive program updateupdate
3 TH1 Coil temperature sensor
4TH2Outdoor ambient temperature sensor
5TH3Refrigerant liquid temperature sensor
6TH5Discharge temperature sensor
7TH7Suction temperature sensor
8TS3HP2: Middle pressure switch
9TS4HP1: High pressure switch
10TS5LPS: low pressure sensor
11 AC Power supply
12COM4Communication with hydraulic module PCB
13PE1Port for ground
14 / Filter components
15OUT 4Four-way valve
16FLSPCB Program update
17 OUT 5 Chassis heater
18OUT 8Crankcase heater
19K9Relay for PFC
20FAN1DC fan
21 / Drive components

Figure 4-2.4: (GHP-MM14)/(GHP-MM16) Drive PCB
GRUNDIG GHP MM8 - Hydraulic Module PCB - 4

text_image 1 2 3 4 5 6 7 8 9 10 LABEL HMDTN-14 V1.1 19112502 R0FC

Table 4-2.5: (GHP-MM14)/(GHP-MM16) Drive PCB

ItemsPort labelfunction
1 U/V/W Compressor output
2JTAGDrive program update
3 FAN1 DC fan
4 FAN2 Reserved
5 K2 Relay for PFC
6 K1 Relay for PFC
7/Filter components
8 PE Port for ground
9 AC Power supply
10/Drive components

Figure 4-2.5: (GHP-MM14)/(GHP-MM16) Refrigerant System PCB
GRUNDIG GHP MM8 - Hydraulic Module PCB - 5

text_image 1 2 3 4 5 6 7 8 9 10 11 12 13 14 E25-CT0415 FUT 10.0kV 2.0kV MOS-V01(V1.0) HBM-72032N (10.0kV) EXV2 EXV1

Table 4-2.6: (GHP-MM14)/(GHP-MM16)Refrigerant System PCB

Items Port label function
1AC (L/N)Power supply
2EXV1Electric expansive valve
3COM_L/ICommunication with hydraulic module PCB
4COM_DCommunication with inverter module PCB
5TH1T3: Coil temperature sensor
6TH2T4: Outdoor ambient temperature sensor
7TH3T5: liquid temperature sensor
8TH5TP: Discharge temperature sensor
9TH7TH: Suction temperature sensor
10TS8LPS: Low pressure sensor
11TS4HP2: Middle pressure switch
12TS3HP1: High pressure switch
13Output 4Four-way valve
14Output 8Crankcase heater

4.3 Error Code Table

Table 4-3.1: Error code table

Error codeDescription Remark
P01Water flow failure
P02High refrigerant pressure protectionHP1, occurring during the operation
P03Low refrigerant pressure protection
P04Coil overheating protectionT3 temp. is too high, only in cooling mode
P05High discharge temperature protectionTP temp. is too high
P06Too low outlet water temperature protectionTB temp. is too low, only in cooling mode
P07Too low Refrigerant Liquid temp. protectionT5 temp. is too low, only in cooling mode
P08Too high system pressure protectionHP2, occurring when the compressor is off
P10Low refrigerant pressure protectionOnly cooling mode
P11DC fan 1 failure
P12Reserved
P134-way valve shifting failure
P21Built-in DC water pump abnormal
P24Reserved
P25Outlet water pressure sensor error
E01Communication error between hydraulic module PCB and the user interface
E02Discharge temp. sensor errorTP sensor
E03Coil temp. sensor errorT3 sensor
E04Outdoor ambient temp. sensor errorT4 sensor
E05Refrigerant liquid temp. sensor errorT5 sensor
E06Suction temp. sensor errorTH sensor
E07Domestic water temp. sensor errorTW sensor
E08Inlet water temp. sensor errorTA sensor
E09Outlet water temp. sensor errorTB sensor
E10Communication between refrigerant system PCB and drive PCB failure
E11Reserved
E12Reserved
E13Reserved
E14Low pressure sensor errorLow pressure sensor: LPS
E15Too low DC bus voltage
E16Too high DC bus voltage
E17Too high AC input peak current
E18Abnormal IPM module
E19Abnormal PFC module
E20Compressor startup failure
E21Compressor phase loss error
E22Inverter module ResetE22 is a state which the compressor is resetting, no faulty
E23Too high compressor current protection
E24Too high PFC module temp. protection
E25The current detection circuit failure
E26Out of step protection
E27PFC module temp. sensor error
E28Communication data error between refrigerant system PCB and inverter PCB
E29Too high IPM module temp.
E30IPM module temp. sensor error
E31Reserved
E32Inverter module debugging dataNo error
E33Inverter module debugging dataNo error
E34Abnormal AC input power supply
E35Inverter module debugging dataNo error
E36Reserved
E37Module current limiting frequency No error
E38Module voltage limiting frequency No error

■ These codes are displayed on the user interface.

4.4 Troubleshooting

4.4.1 Warning

GRUNDIG GHP MM8 - Warning - 1

  • Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fires or other damage to the unit.
    All electrical works must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation (all national, local and other laws, standards, codes, rules, regulations and other legislation that apply in a given situation).
    If unsure of installation procedures or use, always contact your dealer for advice and information.

4.4.2 P01 diagnosis and analysis

GRUNDIG GHP MM8 - P01 diagnosis and analysis - 1

4.4.2.1 Diagnosis

Code P01 means heat pump tripped with the open of the contactor of water flow switch installed on the port TS1 of hydraulic module PCB with too low water flow rate. When code P01 occurs three times within half an hour, a manual power-off must be done before heat pump can resume next restart.

4.4.2.2 Possible causes

■ Water flow switch wiring is loose or open.
■ Water flow rate is too low.
The components, such as water flow switch, water pump and hydraulic module PCB, are damaged.

4.4.2.3 Analysis and action
GRUNDIG GHP MM8 - Possible causes - 1

flowchart
graph TD
    A["P01"] --> B["Voltage the pump is higher than 253 or lower 198V?"]
    B -->|No| C["Water flow switch wiring on TS1 port of the hydraulic module PCB is loose or open?"]
    B -->|Yes| D["Make sure that the voltage meets the requirement"]
    C -->|No| E["Water flow rate is insufficient?"]
    C -->|Yes| F["Make sure that the port TS1 is wired properly"]
    E -->|No| G["Water flow switch is damaged?"]
    E -->|Yes| H["Check the water circuit, Make sure: all the valves are open fully, the water system is clean and has no any clog, and remove air out of the water system completely"]
    G -->|No| I["Water pump is damaged?"]
    G -->|Yes| J["Replace water flow switch"]
    I -->|No| K["Replace hydraulic module PCB"]
    I -->|Yes| L["Replace water pump"]
    J -->|Yes| M["Replace water pump"]
    J -->|No| N["Water flow switch is damaged?"]

4.4.3 P02 diagnosis and analysis

GRUNDIG GHP MM8 - P02 diagnosis and analysis - 1

4.4.3.1 Diagnosis

Code P02 means heat pump tripped with the open of the pressure switch (HP1, installed on the discharge pipe) contactor with too high pressure. When the discharge pressure rises above 4.5MPa, the pressure switch HP (labeled on the port TS3 of the refrigerant system PCB) opens and the interface will display the code P02 and heat pump will shut down. When discharge pressure drops below 3.5MPa, HP closes and Code P02 disappears, and heat pump will be ready for next startup.

4.4.3.2 Possible causes

■ Pressure switch HP is not connected properly or has malfunctioned.
■ Too much refrigerant in the system.
■ Refrigerant system contains non-condensable gas, such as air or nitrogen, etc.
■ High pressure side of the refrigerant system is clogged.
■ Poor heat transfer on heat exchanger on high pressure side.
■ Refrigerant system PCB is damaged.

4.4.3.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P02"] --> B["High pressure side of the refrigerant system is blocked?¹"]
    B -->|NO| C["Electronic expansion valve is locked dead?"]
    B -->|Yes| D["Confirm that there aren't any crushed or bent copper pipes and joints"]
    C -->|NO| E["There is a poor heat transfer on air side or water side heat exchanger?²"]
    C -->|Yes| F["When the power supply is on or off, the electronic expansion valve should have a reset sound. If no any sound, replace EEV"]
    E -->|NO| G["Water flow rate is insufficient in heating or DHW mode?³"]
    E -->|Yes| H["Check heat exchangers carefully, remove dirt and blockages"]
    G -->|NO| I["The pressure switch HP has an open circuit or damaged?"]
    G -->|Yes| J["Check the water circuit, Make sure: all the valves are open fully, the water system is clean and has no any clog, and remove air out of the water system completely"]
    I -->|NO| K["No"]
    I -->|Yes| L["Replace the pressure switch HP"]
    J -->|No| K
    J -->|Yes| L

Replace refrigerant system PCB

Notes:

  1. The blockage of high pressure side of the refrigerant system will lead to higher discharge temperature, higher discharge pressure and lower suction pipe pressure.
  2. In heating and DHW mode check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt and blockages. In cooling mode check air side heat exchanger, the fan and air outlets for dirt and blockages.
  3. Check the outlet pressure of the water system. If the pressure is lower than 1 bar, water flow rate is insufficient.

4.4.4 P03 diagnosis and analysis

GRUNDIG GHP MM8 - P03 diagnosis and analysis - 1

4.4.4.1 Diagnosis

Code P03means heat pump tripped with too low pressure detected by LPS (the pressure sensor installed on the suction pipe of the compressor, labeled on the port TS8 of the refrigerant system PCB). When the suction pressure falls below 0.14MPa for ten seconds, the interface displays the code P03 and the heat pump will shut down. When the suction pressure rises above 0.30MPa, Code P03disappears and the heat pump will be ready for next startup. When code P03has occurred 3 times within an hour, a manual power-off must be done before heat pump can resume next restart.

4.4.4.2 Possible causes

■ The system is lack refrigerant.
There is a blockage on low pressure side of the refrigerant system.
There is a poor heat transfer on low pressure side of the refrigerant system.
■ The water flow rate is insufficient when running in cooling mode.
■ LPS is faulty.
■ The refrigerant system PCB is damaged.

4.4.4.3 Analysis and action
GRUNDIG GHP MM8 - Possible causes - 1

flowchart
graph TD
    A["P03"] --> B["Low pressure side is blocked?¹"]
    B -->|NO| C["Electronic expansion valve is locked dead?"]
    B -->|Yes| D["Ensure that there aren't crushed and bent copper pipes and the filter on low pressure side"]
    C -->|NO| E["There is a poor heat transfer on air side or water side heat exchanger?²"]
    C -->|Yes| F["When the power supply is on or off, the electronic expansion valve should have a reset sound. If no any sound, replace EEV"]
    E -->|NO| G["Water flow rate is insufficient in Cooling mode?³"]
    E -->|Yes| H["Check heat exchangers carefully, remove dirt and blockages"]
    G -->|NO| I["The system is lack of refrigerant?⁴"]
    G -->|Yes| J["Check the water circuit, Make sure: all the valves are open fully, the water system is clean and has no any clog, and remove air out of the water system completely"]
    I -->|NO| K["Pressure sensor LPS is malfunction?⁵"]
    I -->|Yes| L["Add refrigerant enough or inspect and fix the system leakage"]
    K -->|NO| M["Replace refrigerator system PCB"]
    K -->|Yes| N["Replace the sensor LPS"]

Notes:

  1. Low pressure side blockages lead to higher discharge temperature, lower suction pressure, lower compressor current, and a frosting occurs on the suction pipe.

  2. Check the air side heat exchanger, the fan and air outlets for dirt and blockages.

  3. Check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt and blockages.

  4. The lack of refrigerant will lead to high discharge temperature, lower discharge and suction pressures and compressor current, and may frost on the suction pipe. These issues will disappear once sufficient refrigerant has been charged into the system.

  5. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega Ohms or infinite, the pressure sensor has failed.

4.4.5 P04 diagnosis and analysis

GRUNDIG GHP MM8 - P04 diagnosis and analysis - 1

4.4.5.1 Diagnosis

Code P04 is only possible in cooling mode. Code P04 means heat pump tripped with too high temperature detected by the temperature sensor T3 installed on refrigerant outlet liquid pipe of the air side heat exchanger only running on cooling mode. When the temperature detected by the sensor T3 is higher than 65°C for more than one minute, the interface displays the code P04 and heat pump will shut down. When the temperature detected by the sensor T3 drops below 52°C, Code P04 disappears and heat pump will be ready for next startup.

4.4.5.2 Possible causes

■ Temperature sensor T3 is not connected properly or has malfunctioned.
■ Poor heat transfer on air side heat exchange.
■ The motor or blades of the fan is damaged.
■ Refrigerant system PCB damaged.

4.4.5.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P04"] --> B["The temperature sensor T3 is loose?"]
    B -->|No| C["The temperature sensor T3 has a short or open circuit or damaged?\( ^1 \)"]
    B -->|Yes| D["Ensure the temperature sensor is connected properly"]
    C -->|No| E["There is a poor heat transfer on air side heat exchanger?"]
    C -->|Yes| F["Replace the temperature sensor T3"]
    E -->|No| G["Fan blade or motor is blocked or damaged?"]
    E -->|Yes| H["Check the heat exchangers carefully, remove dirt and blockages"]
    G -->|No| I["Replace refrigerant system PCB"]
    G -->|Yes| J["Replace the blade or the motor"]

Note:

  1. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance characteristic table, the sensor has failed. Refer to Part 4, 4-5.1 "Temperature Sensor Resistance Characteristics".

4.4.6 P05 diagnosis and analysis

GRUNDIG GHP MM8 - P05 diagnosis and analysis - 1

4.4.6.1 Diagnosis

Code P05 means heat pump tripped with too high temperature detected by the temperature sensor TP installed on the discharge pipe of the compressor outlet. When outdoor ambient temperature T4 is below minus 15°C and the temperature detected by TP is higher than 115°C for more than 30 seconds, or When outdoor ambient temperature T4 is above minus 15°C and the temperature detected by TP is higher than 110°C for more than 30 seconds, the interface will display code P05 and heat pump will shut down. After 10 minutes, the compressor is allowed to start again when TP drops below 90°C, Code P05 will disappears and heat pump will be ready for next startup.

4.4.6.2 Possible causes

■ Temperature sensor TP is error.
■ High pressure side blockage.
■ Poor condenser heat exchange.
■ Refrigerant system PCB is damaged.

4.4.6.3 Analysis and action
GRUNDIG GHP MM8 - Possible causes - 1

flowchart
graph TD
    A["P05"] --> B["Temperature sensors TP, TA, TW are loose, short or open circuit or damaged? 1"]
    B -->|NO| C["High pressure switch HP1 connection on refrigerant system PCB is loose, short or open circuit or damaged?"]
    C -->|NO| D["There is poor heat transfer on the air or water side heat exchangers?2"]
    C -->|Yes| E["Ensure these temperature sensors are connected properly or replace them"]
    D -->|NO| F["The high pressure side is blocked, caused by crushed or bent pipe or blocked EEV?3"]
    D -->|Yes| G["Check the heat exchangers carefully, remove dirt and blockages"]
    F -->|NO| H["The water flow rate is not sufficient in Cooling mode? 4"]
    F -->|Yes| I["Inspect the system and fix the error"]
    H -->|NO| J["Hydraulic module PCB is damaged?"]
    H -->|Yes| K["Replace hydraulic module PCB"]
    J -->|NO| L["Replaced refrigerant system PCB"]
    J -->|Yes| M["Replace hydraulic module PCB"]

Notes:

  1. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance characteristic table, the sensor has failed. Refer to Part 4. 4-5.1 "Temperature Sensor Resistance Characteristics".
  2. Check air or water side heat exchanger, the fan and air outlets for dirt and blockages.
  3. High pressure side blockage causes discharge temperature to be higher than normal, discharge pressure to be higher than normal and suction pressure to be lower than normal.
  4. Check the water side heat exchanger, water piping, circulator pumps and water flow switch for dirt and blockages.

4.4.7 P06 diagnosis and analysis

GRUNDIG GHP MM8 - P06 diagnosis and analysis - 1

4.4.7.1 Diagnosis

Code P06 is only possible in cooling mode. CodeP06 means heat pump tripped with too low outlet water temperature detected by the temperature sensor TB installed on the outlet pipe of water side heat exchanger. If TB has been lower than 4°C for 120 seconds, Heat pump will shut down and the interface will display the faulty code P06. When TB is above 8°C for one minute, Heat pump will be ready for next startup.

4.4.7.2 Possible causes

■ Temperature sensor TB isn't connected properly or has malfunctioned.
■ Hydraulic module PCB damaged.

4.4.7.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P06"] --> B["The temperature sensor TB is loose?"]
    B -->|Yes| C["Ensure the temperature sensor is connected properly"]
    B -->|NO| D["The temperature sensor TB has a short or open circuit or damaged?¹"]
    D -->|Yes| E["Replace the temperature sensor TB"]
    D -->|NO| F["Replace hydraulic module PCB"]

Note:

  1. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance characteristic table, the sensor has failed. Refer to Part 4, 4-5.1 "Temperature Sensor Resistance Characteristics".

4.4.8 P07 diagnosis and analysis

GRUNDIG GHP MM8 - P07 diagnosis and analysis - 1

4.4.8.1 Diagnosis

Code P07 is only possible in cooling mode. Code P07 means heat pump tripped with too low outlet temperature detected by the temperature sensor T5 installed on the outlet pipe of electronic expansion valve in cooling mode. If T5 has been lower than 2°C for 120 seconds, Heat pump will shut down and the interface will display the faulty code P06. When T5 is above 8°C for ten minutes, Heat pump will be ready for next startup.

4.4.8.2 Possible causes

■ Temperature sensor T5 isn't connected properly or has malfunctioned.
■ Refrigerant system PCB is damaged.

4.4.8.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P07"] --> B["The temperature sensor T5 is loose?"]
    B -->|Yes| C["Ensure the temperature sensor is connected properly"]
    B -->|NO| D["The temperature sensor T5 has a short or open circuit or damaged? 1"]
    D -->|Yes| E["Replace the temperature sensor T5"]
    D -->|NO| F["Replace refrigerant system PCB"]

Note:

  1. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance characteristic table, the sensor has failed. Refer to Part 4, 4-5.1 "Temperature Sensor Resistance Characteristics".

4.4.9 P08 diagnosis and analysis

GRUNDIG GHP MM8 - P08 diagnosis and analysis - 1

4.4.9.1 Diagnosis

When Heat pump shuts down and the contactor of the middle pressure switch MP installed on the discharge pipe of the compressor keeps open for 3 seconds, the interface will display the code P08 and heat pump still keeps in the shutdown state until the contactor of the pressure switch HP2 closes. When the pressure is above 4.2MPa, the contactor of the middle pressure switch MP will open. When the pressure is below 3.8MPa, the contactor will close.

4.4.9.2 Possible causes

■ The port TS4 of the pressure switch MP (Middle Pressure) on refrigerant system PCB is not connected properly or has malfunctioned.
■ Refrigerant system PCB is damaged.

4.4.9.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P08"] --> B["The pressure switch MP is loose?"]
    B -->|Yes| C["Ensure the switch is connected properly"]
    B -->|NO| D["The pressure switch MP has damaged?"]
    D -->|Yes| E["Replace the pressure switch MP"]
    D -->|NO| F["Replace Refrigerant system PCB"]

4.4.10 P10 diagnosis and analysis

GRUNDIG GHP MM8 - P10 diagnosis and analysis - 1

4.4.10.1 Diagnosis

After heat pump run for one minute in cooling mode, if the pressure detected by LPS is below 0.7MPa for 2 minutes, heat pump will shut down and the interface will display the code P10. In ten minutes heat pump will be allowed to start again. If Code P10 occurred for three times within one hour, heat pump will shut down. A manual power-off must be done before next restart.

4.4.10.2 Possible causes

■ The system is lack of refrigerant.
There is the blockage on low pressure side of the refrigerant system.
There is a poor heat transfer on low pressure side of the refrigerant system.
■ Water flow rate is insufficient.
■ LPS is faulty.
■ Refrigerant system PCB is damaged.

4.4.10.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P10"] --> B["Low pressure side is blocked?¹"]
    B -->|NO| C["The electronic expansion valve is locked dead?"]
    B -->|Yes| D["Ensure that there aren't crushed and bent copper pipes and the filter on low pressure side"]
    C -->|NO| E["There is a poor heat transfer on air side or water side heat exchanger?²"]
    C -->|Yes| F["When the power supply is on or off, the electronic expansion valve should have a reset sound. If no any sound, replace EEV"]
    E -->|NO| G["Water flow rate is insufficient in Cooling mode?³"]
    E -->|Yes| H["Check heat exchangers carefully, remove dirt and blockages"]
    G -->|NO| I["The system is lack of refrigerant?⁴"]
    G -->|Yes| J["Check the water circuit, Make sure: all the valves are open fully, the water system is clean and has no any clog, and remove air out of the water system completely"]
    I -->|NO| K["The pressure sensor LPS is malfunction?⁵"]
    I -->|Yes| L["Add refrigerant enough or inspect and fix the system leakage"]
    K -->|NO| M["Replace refrigerator system PCB"]
    K -->|Yes| N["Replace the sensor LPS"]

Notes:

  1. Low pressure side blockages lead to higher discharge temperature, lower suction pressure, lower compressor current, and a frosting to occur on the suction pipe.

  2. Check air side heat exchanger, the fan and air outlets for dirt and blockages.

  3. Check water side heat exchanger, water piping, circulator pumps and water flow switch for dirt and blockages.

  4. The lack of refrigerant will lead to high discharge temperature, lower discharge and suction pressures and compressor current, and may frost on the suction pipe. These issues will disappear once sufficient refrigerant has been charged into the system.

  5. Measure the resistance among the three terminals of the pressure sensor. If the resistance is of the order of mega ohms or infinite, the pressure sensor has failed.

4.4.11 P11 diagnosis and analysis

GRUNDIG GHP MM8 - P11 diagnosis and analysis - 1

4.4.11.1 Diagnosis

Code P11 indicates a DC fan error. If Code P11 occurred ten times within two hours, heat pump will shut down. A manual power-off restart must be done before next startup. P11 error should be addressed promptly in order to protect heat pump from being damaged.

4.4.11.2 Possible causes

■ Power or communication wires are not connected properly.
■ High wind speed.
■ Fan motor blocked or has malfunctioned.
■ Abnormal power supply.
■ Drive PCB is damaged.

4.4.11.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P11"] --> B["Strong wind is blowing towards the fan, making the fan running in the wrong direction?"]
    B -->|No| C["Some power wires or communication wires of the fan aren't connected properly?"]
    B -->|Yes| D["Change the installation of the unit direction or build a shelter to protect the fan from strong wind"]
    C -->|No| E["The fan motor is blocked or has failed?"]
    C -->|Yes| F["Ensure power and communication wires are connected properly"]
    E -->|No| G["The power supply is abnormal?\( ^{1} \)"]
    E -->|Yes| H["Remove obstruction or replace the fan motor"]
    G -->|No| I["Replace drive PCB"]
    G -->|Yes| J["Ensure the power supply is normal"]

Note:

  1. For single-phase power supply models, check the voltage between "DC+" and "DC-" on the inverter module PCB. The normal range is 277V to 354V. If the voltage is outside this range, the inverter module PCB is damaged.

4.4.12 P13 diagnosis and analysis

GRUNDIG GHP MM8 - P13 diagnosis and analysis - 1

4.4.12.1 Diagnosis

When heat pump operates in heating or DHW mode, if “the inlet water temperature TA is higher than the outlet water temperature TB” is detected for 60 seconds, the heat pump will stop but the interface doesn’t display the code P13. After 3 minutes, heat pump will restart. If such “stop first and then restart” happened three times in succession, heat pump will trip and locked, the interface will display the code P13. A manual power-off must be done before next restart.

4.4.12.2 Possible causes

■ The system is lack of refrigerant.
■ The body of 4-way valve is locked.
■ The coil of 4-way valve malfunctioned.
■ 4-way valve is powered off.
■ Refrigerant system PCB is damaged.

4.4.12.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P13"] --> B["The system is lack of refrigerant?"]
    B -->|Yes| C["Fix the leakages and recharge refrigerant"]
    B -->|NO| D["The body of 4-way valve is locked?"]
    D -->|Yes| E["Remove dirt and clogs or tap the valve body gently with wooden hammer until the valve can be reversed"]
    D -->|NO| F["The coil of 4-way valve has a short or open circuit?"]
    F -->|Yes| G["Replace the valve coil"]
    F -->|NO| H["4-way valve is powered off?"]
    H -->|Yes| I["Ensure the operation mode is right: in cooling mode the valve is power-off, in heating or DHW mode, the valve is power-on"]
    H -->|NO| J["Replace refrigerator system PCB"]

4.4.13 P21 diagnosis and analysis

GRUNDIG GHP MM8 - P21 diagnosis and analysis - 1

4.4.13.1 Diagnosis

Code P21 indicates built-in DC water pump worked itself abnormally.

4.4.13.2 Possible causes

■ Pump power off.
■ Pump power supply is abnormal.
■ Pump PWM output interface damaged.
■ Pump is stopped due to permanent failure.

4.4.12.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P21"] --> B["Pump power supply wires are loose?"]
    B -->|No| C["PWM-in or PWM-out wires are loose?"]
    B -->|Yes| D["Reconnect the wires strong"]
    C -->|No| E["Voltage the pump is higher than 253 or lower than 198V?"]
    C -->|Yes| F["Reconnect the wires strong"]
    E -->|No| G["DC water pump damaged?"]
    E -->|Yes| H["Ensure the voltage meets the requirements"]
    G -->|No| I["Replace hydraulic module PCB"]
    G -->|Yes| J["Replace DC water pump"]

4.4.14 P25 diagnosis and analysis

GRUNDIG GHP MM8 - P25 diagnosis and analysis - 1

4.4.14.1 Diagnosis

Code P25 indicates outlet water pressure sensor had an error. If there are no other errors except for the water pressure sensor error, Heat pump will continue to operate.

4.4.14.2 Possible causes

■ Outlet water pressure sensor is not connected properly
■ Outlet water pressure sensor has malfunctioned.

4.4.14.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["P25"] --> B["Outlet water pressure sensor connection on Hydraulic module PCB is loose?"]
    B -->|No| C["Water pressure sensor is plugged into the wrong port on Hydraulic module?"]
    B -->|Yes| D["Ensure the sensors is connected properly"]
    C -->|No| E["Water pressure sensor has short-circuit or malfunctioned?"]
    C -->|Yes| F["Ensure the sensors is connected properly"]
    E -->|No| G["Replace hydraulic module PCB"]
    E -->|Yes| H["Replace the sensor"]

4.4.15 E01 diagnosis and analysis

GRUNDIG GHP MM8 - E01 diagnosis and analysis - 1

4.4.15.1 Diagnosis

Code E01 indicates heat pump shut down because of the communication error between hydraulic module PCB and the user interface.

4.4.15.2 Possible causes

■ Communication wires between outdoor unit and user interface are not connected properly.
■ Communication wiring A and B terminals is disconnected.
■ Loosened wiring within the electric control box.
■ Interference from high voltage wires or other sources of electromagnetic radiation.
■ Damaged main PCB or electric control box communication terminals block.

4.4.15.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E01"] --> B["Communication wires AB have a short circuit disconnected, are loose or connect wrongly?"]
    B -->|No| C["Communication wires AB are not connected in a daisy chain?"]
    B -->|Yes| D["Reconnect the communication wires"]
    C -->|No| E["There is the interference from high voltage (220V or higher) wires?"]
    C -->|Yes| F["Connect the communication wires in a daisy chain"]
    E -->|No| G["Communication wires are close to a source of electromagnetic radiation such as transformer or strong fluorescent lamp?"]
    E -->|Yes| H["Ensure the communication wires and high voltage wires are separated"]
    G -->|No| I["User interface is damaged?"]
    G -->|Yes| J["Remove the source of interference, or add additional shielding to the communication wires"]
    I -->|No| K["Replace hydraulic module PCB"]
    I -->|Yes| L["Replace the user interface"]

4.4.16 E02 E03 E04 E05 E06 E07 E08 E09 diagnosis and analysis

GRUNDIG GHP MM8 - E02 E03 E04 E05 E06 E07 E08 E09 diagnosis and analysis - 1

text_image E 02 M △ ▽ ⏻ E 03 M △ ▽ ⏻ E 04 M △ ▽ ⏻ E 05 M △ ▽ ⏻ E 06 M △ ▽ ⏻ E 07 M △ ▽ ⏻ E 08 M △ ▽ ⏻ E 09 M △ ▽ ⏻

4.4.16.1 Diagnosis

These codes indicate heat pump shut down because of the error of temperature sensors.

■ E02 indicates discharge temperature sensor TP appeared an error.
■ E03 indicates coil temperature sensor T3 appeared an error.
■ E04 indicates outdoor ambient temperature sensor T4 appeared an error.
■ E05 indicates liquid temperature sensor T5appeared an error.
■ E06 indicates suction temperature sensor TH appeared an error.
■ E07 indicates domestic water tank temperature sensor TW appeared an error.
■ E08 indicates inlet water temperature sensor TA appeared an error.
■ E09 indicates outlet water temperature sensor TB appeared an error.

4.4.16.2 Possible causes

■ Temperature sensors are not connected properly or have malfunctioned.
■ Refrigerant system PCB or hydraulic module PCB is damaged.

4.4.16.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E02 E03 E04 E05 E06 E07 E08 E09"] --> B["Temperature sensor connection on hydronic system PCB and refrigerant system PCB are loose?¹"]
    B -->|Yes| C["Ensure these sensors are connected properly"]
    B -->|NO| D["Temperature sensors have short-circuits or have malfunctioned?²"]
    D -->|Yes| E["Replace the sensors"]
    D -->|NO| F["Replace refrigerant system PCB for E02/E03/ E04/E05/E06; Replace hydraulic module PCB for E07/E08/E09"]

Notes:

  1. Refer to Part 3, 7 Figure 3-7.1 for the location of temperature sensors.

  2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensor's resistance characteristics table, the sensor has failed. Refer to Part 4, 4-5.1 "Temperature Sensor Resistance Characteristics" for the resistance of sensors.

4.4.17 E10 diagnosis and analysis

GRUNDIG GHP MM8 - E10 diagnosis and analysis - 1

4.4.17.1 Diagnosis

Code E10 indicates heat pump shut down because of the communication error between refrigerant system PCB chip and hydraulic module PCB chip.

4.4.17.2 Possible causes

■ Power supply abnormal.
■ Transformer malfunction.
■ Interference from a source of electromagnetic radiation.
■ Refrigerant system PCB or hydraulic module PCB damaged

4.4.17.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E10"] --> B["The communication line connection between refrigerant system PCB and inverter PCB is loose?"]
    B -->|No| C["There is a short or open circuit on the communication line connection between refrigerant system PCB and hydraulic module PCB?"]
    B -->|Yes| D["Ensure the line is connected firmly"]
    C -->|No| E["There is a source of electromagnetic radiation near the unit, such as high-frequency transmitter or other high strength radiation device?"]
    C -->|Yes| F["Replace the line"]
    E -->|No| G["Hydraulic module PCB is damaged?"]
    E -->|Yes| H["Remove the source of interference"]
    G -->|No| I["Replace drive pcb¹"]
    G -->|Yes| J["Replace hydraulic module PCB"]

Note:

  1. For 14/16kW models, replace refrigerant system PCB. For 8/10/12Kw models, replace drive PCB.

4.4.18 E14 diagnosis and analysis

GRUNDIG GHP MM8 - E14 diagnosis and analysis - 1

4.4.18.1 Diagnosis

Code E14 indicates heat pump shut down because of the error of low pressure sensor LPS.

4.4.18.2 Possible causes

■ Low pressure sensor is not connected properly
■ Low pressure sensor has malfunctioned.

4.4.18.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E14"] --> B["Low pressure sensor connection on refrigerant system PCB is loose?"]
    B -->|Yes| C["Ensure the sensors is connected properly"]
    B -->|NO| D["Low pressure sensor has short-circuit or malfunctioned?"]
    D -->|Yes| E["Replace the sensor"]
    D -->|NO| F["Replace refrigerant system PCB"]

4.4.19 Inverter module troubleshooting for single-phase models

4.4.19.1 Codes

The codes displayed on the user interface are below: E15, E16, E17, E18, E19, E20, E21, E22, E23, E24, E25, E26, E27, E28, E29, E30, E31, E32, E33, E34, E35, E36, E37, and E38. Refer to Table 4-19.1 for these codes.

Table 4-19.1 Table of codes

Error codeContent D1(RED) ^2 D2(GREEN) ^2 D3(YELLOW) ^2
E15Too low DC bus voltageOFFONON
E16Too high DC bus voltageFlashONON
E17Too high AC input peak currentOFFFlashON
E18Abnormal IPM moduleONFlashOFF
E19Abnormal PFC moduleOFFONFlash
E20Compressor startup failureONONFlash
E21Compressor phase loss errorONFlashON
E22^1 Inverter module reset/ //
E23Too high compressor current protectionFlash Flash Flash
E24Too high PFC module temp. protectionFlashONFlash
E25The current detection circuit failureONONOFF
E26Out of step protectionONONON
E27PFC module temp. sensor errorFlashONOFF
E28Communication data error between refrigerant system PCB and inverter PCBFlash Flash OFF
E29Too high IPM module tempONFlashFlash
E30IPM module temp. sensor errorONOFFFlash
E32^1 Inverter module debugging data///
E33^1 Inverter module debugging data///
E34Abnormal AC input power supplyFlashOFFON
E35^1 Inverter module debugging data///
E37^1 Module current limiting frequency///
E38^1 Module voltage limiting frequency///

Note:
1. E22、E32、E33、E35、E37 and E38 are not errors and heat pump does not shut down. The other codes are all errors, heat pump will shut down.
2. The combination of the show states of 3 led lights corresponds to different error codes. In standby: D1-OFF, D2-Flash and D3-OFF; In normal operation: D1-Flash, D2-OFF and D3-OFF. Refer to Figure 4-19.1 and Figure 4-19.2 for the location of each led.

Figure 4-19.1 Location of 3 led lights on the inverter module PCB for 8/10/12kW :
GRUNDIG GHP MM8 - Codes - 1

natural_image Close-up of a green printed circuit board with various electronic components and connectors (no readable text or symbols)

Figure 4-19.2 Location of 3 led lights on the inverter module PCB for 14/16kW:
GRUNDIG GHP MM8 - Codes - 2

text_image HMB1W-18 M1.2 21091602 50L

4.4.19.3 Principle of DC inverter

Figure 4-19.3 Principle of DC inverter
GRUNDIG GHP MM8 - Principle of DC inverter - 1

flowchart
graph LR
    A["POWER SUPPLY"] -->|L| B["BRIDGE RECTIFIER"]
    B --> C["PTC"]
    B --> D["CONTACTOR"]
    C --> E["INDUCTOR"]
    D --> E
    E --> F["CAPACITOR"]
    F --> G["INVERTER MODULE"]
    G --> H["U"]
    G --> I["V"]
    G --> J["W"]
    G --> K["3"]
    style A fill:#f9f,stroke:#333
    style B fill:#ccf,stroke:#333
    style C fill:#cfc,stroke:#333
    style D fill:#cfc,stroke:#333
    style E fill:#fcc,stroke:#333
    style F fill:#fcc,stroke:#333
    style G fill:#cff,stroke:#333
    style H fill:#ffc,stroke:#333
    style I fill:#ffc,stroke:#333
    style J fill:#ffc,stroke:#333
    style K fill:#ffc,stroke:#333
  1. Contactor is open, the current across the PTC to charge capacitor. After a few seconds, the contactor closed.
  2. Single phase (220VAC, LN) power supply change to DC power supply after bridge rectifier. This part includes PFC module.
  3. The capacitor outputs a steady power supply for inverter module P and N terminals. In standby the voltage between P and N terminal on inverter module is about 1.4 time of AC power supply.
  4. After heat pump is powered on, drive PCB charges the capacitors through PTC resistance and bridge rectifier, the switching power supply starts to work, and then drive PCB chip starts to work. After the chip of drive board starts to work, the signal led will be on for 5s, waiting for main control PCB to send the boot instruction. After a delay of 12s, drive PCB judges the bus voltage, and when the conditions are met, the charging relay is delayed and closed. Once the relay is closed, it will not actively shut off until the input power is abnormal or the bus voltage is too low to cause the control power of the relay to be off. If the charging circuit occurs a failure there is no error code.

4.4.19.4 E15 and E16 diagnosis and analysis

GRUNDIG GHP MM8 - E15 and E16 diagnosis and analysis - 1

GRUNDIG GHP MM8 - E15 and E16 diagnosis and analysis - 2

4.4.19.4.1 Diagnosis

The normal DC voltage between terminals P (DC+) and N (DC-) on inverter module PCB is 1.4 time of AC power supply in standby state. The DC voltage is 370V when the fan motor is running. If the voltage is lower than 180V, the unit displays E15 and shuts down. If the voltage is higher than 430V, the unit displays E16 and shuts down.

4.4.19.4.2 Possible causes

■ Power supply is abnormal.
■ Relay on the inverter module PCB is open.
■ Drive PCB is damaged.

Figure 4-19.4 Location of DC bus voltage terminals for 8/10/12kW:
GRUNDIG GHP MM8 - Possible causes - 1

natural_image Close-up of a green printed circuit board with copper inductors and capacitors, no visible text or symbols.

Figure 4-19.5 Location of DC bus voltage terminals for 14/16kW:
GRUNDIG GHP MM8 - Possible causes - 2

text_image DC+ DC- LABEL HMD1W-18 1.1 21091602

4.4.19.4.2 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E15 E16"] --> B["Power supply is abnormal?"]
    B -->|Yes| C["Re-start the unit once the power supply has returned to normal"]
    B -->|NO| D["Relay on the inverter module PCB is open?\( ^{1} \)"]
    D -->|Yes| E["Replace drive PCB"]
    D -->|NO| F["Replace drive PCB"]

Note:

  1. Refer to Figure4-2.2/2.3/2.4/2.5 for the location of the relays.

4.4.19.5 E17Diagnosis and analysis

GRUNDIG GHP MM8 - E17Diagnosis and analysis - 1

4.4.19.5.1 Diagnosis

E17 occurs when the instantaneous input current peak of the DC bus is over high.

4.4.19.5.2 Possible cause

The input power supply is abnormal, and the voltage suddenly decreases to cause the input current to increase.
■ Inductor on PFC module malfunctioned.
■ Inverter module PCB malfunctioned.

4.4.19.5.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E17"] --> B["Power supply is abnormal?"]
    B -->|No| C["Inductor on PFC module malfunctioned?\( ^{1} \)"]
    B -->|Yes| D["Restart the unit once the power supply has returned to normal"]
    C -->|No| E["Replace drive PCB"]
    C -->|Yes| F["Replace the inductor"]

Note:
1. For 8/10/12/14/16kw, refer to Figure4-19.6 below for the location of the inductor.

Figure4-19.6
GRUNDIG GHP MM8 - Analysis and action - 2

text_image Inductor enveloped by a cover plate

4.4.19.6 E18 E23 E29 E30 Diagnosis and analysis

GRUNDIG GHP MM8 - E18 E23 E29 E30 Diagnosis and analysis - 1

GRUNDIG GHP MM8 - E18 E23 E29 E30 Diagnosis and analysis - 2

GRUNDIG GHP MM8 - E18 E23 E29 E30 Diagnosis and analysis - 3

GRUNDIG GHP MM8 - E18 E23 E29 E30 Diagnosis and analysis - 4

4.4.19.6.1 Diagnosis

■ Code E18 will occur when IPM module is abnormal.
■ Code E23 will occur when the instantaneous peak current of any phase of three phases the compressor U, V and W is over high.
■ Code E29 will occur when the internal circuit of IPM detecting temperature is abnormal.
■ Code E30 will occur when IPM module overheats.

4.4.19.6.2 Possible cause

■ The compressor phase sequence is incorrectly connected.
■ Too much refrigerant liquid flooded into the compressor.
■ The compressor malfunctioned.
■ Screws on the inverter module are loose.
■ The radiator on inverter module PCB has poor heat dissipation.
■ The inverter module PCB malfunctioned.

4.4.19.6.3 Analysis and action
GRUNDIG GHP MM8 - Possible cause - 1

flowchart
graph TD
    A["E18 E23 E29 E30"] --> B["Compressor phase sequence is wrong?\( ^{1} \)"]
    B -->|No| C["There is too much liquid refrigerant going into the compressor?"]
    B -->|Yes| D["Change U V and W terminals by correct phase sequence"]
    C -->|NO| E["Compressor is faulty?\( ^{2} \)"]
    C -->|Yes| F["Recharge the refrigerant with the correct quantity"]
    E -->|NO| G["Radiator on inverter module has poor heat dissipation?"]
    E -->|Yes| H["Replace the compressor"]
    G -->|NO| I["Screws on IPM module are loose?\( ^{3} \)"]
    G -->|Yes| J["Ensure good heat dissipation on the radiator"]
    I -->|NO| K["Inverter module is damaged?\( ^{4} \)"]
    I -->|Yes| L["Tighten the screws"]
    K -->|NO| M["Replace drive PCB"]
    K -->|Yes| N["Replace the inverter module\( ^{5} \)"]

Note:

  1. Connect the U V W wire from the inverter module to the correct compressor terminals, as indicated by the labels on the compressor.
  2. The normal resistances of the inverter compressor are 0.35-1.5Ω among U V W and infinite between each of U V W and ground. If any of the resistances differ from these specifications, the compressor has malfunctioned.
  3. For 8/10/12kw, refer to Figure 4-19.8 for the layout of inverter module. For 14/16kw, refer to Figure 4-19.9 for the layout of inverter module.
  4. Measure the resistance between each of U, V and W and each of P and N on the inverter module. All the resistances should be infinite. If any of them are not infinite, the inverter module is damaged and should be replaced.
  5. When replacing an inverter module, a layer of thermally conductive silica gel should be painted on the IPM module, IGBT, diode bridge rectifier (on the reverse side of the inverter module PCB).

Figure 4-19.8 8/10/12kw
GRUNDIG GHP MM8 - Note: - 1

text_image PFC IGBT IPM

Figure 4-19.9 14/16kw
GRUNDIG GHP MM8 - Note: - 2

text_image PFC← IGBT← IPM← VDC+← VDC-←

4.4.20 E19 E24 E27Diagnosis and analysis

GRUNDIG GHP MM8 - E19 E24 E27Diagnosis and analysis - 1

text_image E 19 M △▽ ◎ E 24 M △▽ ◎ E 27 M △▽ ◎

4.4.20.1 Diagnosis

■ E19 will occur when PFC module is abnormal.
■ E24 will occur when PFC module temperature is too high.
■ E27 will occur when the circuit of PFC module detecting temperature is abnormal.

4.4.20.2 Possible causes

■ The input power supply is abnormal.
■ Screws on PFC module are loose.
■ Internal PFC circuit detecting the temperature malfunctioned.
■ The radiator on PFC module has poor heat dissipation.
■ PFC module circuit malfunctioned.
■ Inverter module PCB is damaged.

4.4.20.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E19 E24 E27"] --> B["Power supply is abnormal?"]
    B -->|No| C["Screws on PFC module are loose?"]
    B -->|Yes| D["Restart the unit once power supply is normal"]
    C -->|No| E["The radiator on inverter module PCB has poor heat dissipation?"]
    C -->|Yes| F["Tighten the screw"]
    E -->|No| G["Internal PFC circuit detecting the temperature malfunctioned?"]
    E -->|Yes| H["Ensure good heat dissipation on the radiator"]
    G -->|No| I["PFC module circuit malfunctioned?"]
    G -->|Yes| J["Replace drive PCB"]
    I -->|No| K["Replace drive PCB"]
    I -->|Yes| L["Replace drive PCB"]
    K --> M["Replace drive PCB"]

4.4.21 E20 E21Diagnosis and analysis

GRUNDIG GHP MM8 - E20 E21Diagnosis and analysis - 1

GRUNDIG GHP MM8 - E20 E21Diagnosis and analysis - 2

4.4.21.1 Diagnosis

Code E20 will occur when the compressor startup failed. When one or two phases are missing from the compressor phase line U V and W, Code E21 will occur.

4.4.21.2 Possible causes

■ Too much liquid flooded into the compressor.
There is too high pressure difference between inlet and outlet of the compressor.
■ There is a wrong compressor phase sequence.

4.4.21.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E20 E21"] --> B["Too much liquid flooded into the compressor?"]
    B -->|No| C["There is too high pressure difference between inlet and outlet of the compressor?"]
    B -->|Yes| D["Ensure the amount of refrigerant is correct"]
    C -->|No| E["Compressor phase sequence is wrong or missing?"]
    C -->|Yes| F["Ensure compressor inlet and outlet pressures are equal before starting the compressor"]
    E -->|No| G["Replace drive PCB"]
    E -->|Yes| H["Reconnect U V W terminals by the correct phase sequence"]
    F -->|Yes| H

4.4.22 E25 Diagnosis, analysis and action

GRUNDIG GHP MM8 - E25 Diagnosis, analysis and action - 1

4.4.22.1 Diagnosis

Code E25 will occur when the circuit of detecting total input current of IPM module malfunctions.

4.4.22.2 Possible causes

Drive PCB is damaged.

4.4.22.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E25"] --> B["Replace drive PCB"]

4.4.23 E26 Diagnosis, analysis and action

GRUNDIG GHP MM8 - E26 Diagnosis, analysis and action - 1

4.4.23.1 Diagnosis

Code E26 will occur when the actual running speed of the compressor deviated from the set speed, which is also called "out of step".

4.4.23.2 Possible causes

There are impurities in the compressor which may cause the frequency to be unstable.
■ Drive PCB is damaged

4.4.23.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E26"] --> B["There are impurities in refrigerant system?"]
    B -->|Yes| C["Remove the impurities"]
    B -->|NO| D["Drive PCB malfunctioned?"]
    D -->|No| E["Replace the compressor"]
    D -->|Yes| F["Replace drive PCB"]

4.4.24 E28Diagnosis, analysis and action

GRUNDIG GHP MM8 - E28Diagnosis, analysis and action - 1

4.4.24.1 Diagnosis

Code E28 will occur when drive PCB receives no data or error data from refrigeration system. PCB in 30 seconds.

4.4.24.2 Possible causes

■ The communication cables with the main control PCB are loose or open.
■ Drive PCB is damaged.

4.4.24.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E28"] --> B["Communication cables between refrigeration system PCB and drive PCB are loose or open?¹"]
    B -->|Yes| C["Reconnect or replace the communication cables"]
    B -->|NO| D["Refrigeration system PCB is damaged?²"]
    D -->|Yes| E["Replace refrigerator system PCB"]
    D -->|NO| F["Replace drive PCB"]

Note:

  1. Apply to 14/16kW models, for 8/10/12kW models no separator communication lines.
  2. Apply to 14/16kW models, for 8/10/12kW models no separator refrigeration system PCB.

4.4.25 E34 Diagnosis, analysis and action

GRUNDIG GHP MM8 - E34 Diagnosis, analysis and action - 1

4.4.25.1 Diagnosis

Code E34 will occur when there is an abnormal main circuit voltage.

4.4.25.2 Possible causes

■ Actual power supply voltage is not within ±10% of rated voltage.
■ Heat pump is powered on immediately after power-off.
■ Loosened wiring within electric control box.
■ High voltage circuit error.
■ Drive PCB is damaged.

4.4.25.3 Analysis and action

GRUNDIG GHP MM8 - Analysis and action - 1

flowchart
graph TD
    A["E34"] --> B["Power supply voltage is not within ±10% of rated voltage?"]
    B -->|No| C["Wires on drive PCB and electric control box power supply terminals are loose?"]
    B -->|Yes| D["Provide normal power supply"]
    C -->|No| E["Heat pump is powered on immediately after power-off?"]
    C -->|Yes| F["Ensure wires are connected properly"]
    E -->|No| G["High voltage circuit error has occurred, such as the compressor has malfunctioned, the fan motor has short-circuited, or the inverter module had a short circuit"]
    E -->|Yes| H["After the power is off, wait at least 3 minutes and then power it on again"]
    G -->|No| I["Replace drive PCB"]
    G -->|Yes| J["Replace or repair the relevant parts"]
    I -->|No| K["Replace drive PCB"]

4.4.26 E22 E32 E33 E35 E37 E38 analysis

GRUNDIG GHP MM8 - E22 E32 E33 E35 E37 E38 analysis - 1

These codes mean the controller is performing some kind of specific action; they are neither error nor failure.

■ E22 will occur if the inverter module is resetting.
E32 E33 and E35 will occur if the inverter module is debugging the data.
E37 will occur if the compressor frequency is limited because of the input current of the inverter module.
E38 will occur if the compressor frequency is limited because of the input voltage of the inverter module.

4.4.27 E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 1

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 2

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 3

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 4

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 5

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 6

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 7

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 8

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 9

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 10

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 11

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 12

Before starting heat pump, if the communication cables with two cores (A and B) between the control board 1 and the control board 2 are not connected, all these errors above will occur on the user interface and don't start heat pump. First of all, you must confirm that the communication cables (A and B) between these two control boards have been connected correctly to start heat pump.

GRUNDIG GHP MM8 - E01/E02/E03/E04/E05/E06/E07/ E08/E09/E10/E14/E28 analysis - 13

flowchart
graph TD
    A["E01/E02/E03/E04/E05/E06/E07/E08/E09/E10/E14/E28"] --> B["Connect the communication cables between the control board 1 and the control board 2"]

4.5 Appendixes to Part 4

4.5.1 Temperature Sensor Resistance Characteristics

Table 4-20.1: inlet water temperature sensor TA, outlet water temperature sensor TB, coil temperature sensor T3, outdoor ambient temperature sensor T4, liquid temperature sensor T5, and suction temperature sensor TH resistance characteristics

Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)Temp (°C)Resistance (kΩ)
-20106.7322012.635602.3501000.609
-19100.5522112.050612.2641010.591
-1894.7692211.496622.1811020.574
-1789.3532310.971632.1021030.558
-1684.2782410.473642.0261040.542
-1579.5212510.000651.9531050.527
-1475.059269.551661.883
-1370.873279.125671.816
-1266.943288.721681.752
-1163.252298.337691.690
-1059.784307.972701.631
-956.524317.625711.574
-853.458327.296721.519
-750.575336.982731.466
-647.862346.684741.416
-545.308356.401751.367
-442.903366.131761.321
-340.638375.874771.276
-238.504385.630781.233
-136.492395.397791.191
034.596405.175801.151
132.807414.964811.113
231.120424.763821.076
329.528434.571831.041
428.026444.387841.007
526.608454.213850.974
625.268464.046860.942
724.003473.887870.912
822.808483.735880.883
921.678493.590890.855
1020.610503.451900.828
1119.601513.318910.802
1218.646523.191920.777
1317.743533.069930.753
1416.888542.952940.730
1516.079552.841950.708
1615.313562.734960.686
1714.588572.632970.666
1813.902582.534980.646
1913.251592.440990.627

Table 4-20.2: Domestic water tank temperature sensor TW and discharge pipe temperature sensor TP resistance characteristics

Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)Temp. (°C)Resistance (kΩ)Temp (°C)Resistance (kΩ)
-30952.9519116.5824821.633875.503
-29896.03610111.1204920.817885.329
-28843.05411105.9425020.036895.162
-27793.68212101.0315119.288905.000
-26747.6271396.3725218.571914.844
-25704.6271491.9525317.885924.694
-24664.4421587.7585417.227934.549
-23626.8561683.7765516.597944.409
-22591.6731779.9965615.993954.274
-21558.7141876.4065715.414964.144
-20527.8171972.9965814.859974.018
-19498.8332069.7565914.326983.896
-18471.6262166.6776013.815993.779
-17446.0722263.7506113.3241003.666
-16422.0572360.9676212.8541013.557
-15399.4752458.3216312.4011023.451
-14378.2312555.8036411.9671033.349
-13358.2352653.4086511.5501043.251
-12339.4062751.1296611.1501053.156
-11321.6662848.9596710.7651063.064
-10304.9482946.8936810.3951072.975
-9289.1853044.9266910.0391082.889
-8274.3173143.051709.6971092.806
-7260.2883241.265719.3681102.726
-6247.0473339.563729.0521112.649
-5234.5453437.941738.7481122.574
-4222.7373536.393748.4551132.502
-3211.5813634.918758.1731142.433
-2201.0383733.510767.9021152.365
-1191.0713832.166777.6411162.299
0181.6473930.884787.3891172.237
1172.7334029.659797.1471182.176
2164.3004128.490806.9141192.115
3156.3194227.373816.6891202.058
4148.7654326.306826.4731212.002
5141.6134425.286836.2641221.949
6134.8394524.311846.0631231.897
7128.4234623.378855.8691241.846
8122.3434722.487865.6831251.797
1261.7501301.5751341.4211381.283
1271.7041311.5351351.3851391.251
1281.6601321.4961361.3501401.220
1291.6171331.4581371.316
Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : GRUNDIG

Model : GHP MM8

Category : Heat pump