EV3M-D - Multimeter Vemer - Free user manual and instructions
Find the device manual for free EV3M-D Vemer in PDF.
| Brand | Vemer |
| Model | EV3M-D |
| Product Type | TRMS Digital Multimeter (3 or 4-wire three-phase) |
| Power Supply | 230 V AC (-15%/+10%), 50/60Hz |
| Voltage Input | Phase-Neutral: 300 V max; Phase-Phase: 300 V max (chained) |
| Current Input | Nominal 5 A, Max 6 A (via external CT) |
| Accuracy | Voltage & Current: ±0.5% F.S. +1 digit; Frequency: 47-63 Hz (±1 Hz) |
| Display | Triple 3-digit 7-segment LED (auto-ranging with k/M indicators) |
| Measurements | Phase voltages (L-N), line voltages (L-L), phase currents, active/ apparent/reactive power, power factor (cos φ), frequency, neutral current |
| CT Setting | Primary: 5 to 10000 A (step 5 up to 1000A, then step 50); Secondary fixed 5A |
| Wire System | Selectable 3 or 4 wires (default 4 wires) |
| Operating Temperature | -10°C to +45°C |
| Storage Temperature | -20°C to +60°C |
| Humidity | 10% to 80% non-condensing |
| Insulation Voltage | 4 kV between front panel and terminals |
| Protection Degree | IP20 (enclosure), IP51 (front panel) |
| Overvoltage Category | CAT III, Pollution Degree 2 (per EN 61010-1) |
| Wire Cross-Section | Max 6 mm² (power), 2.5 mm² (72x72 mode) |
| Standards Compliance | EN 61010-1, EN 61000-6-2, EN 61000-6-4; 2016/95/EC (LVD), 2014/30/EU (EMC) |
Frequently Asked Questions - EV3M-D Vemer
User questions about EV3M-D Vemer
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Multimeter in PDF format for free! Find your manual EV3M-D - Vemer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. EV3M-D by Vemer.
USER MANUAL EV3M-D Vemer
Read all instructions carefully
■ The measurement instruments in the EV3M series are TRMS electronic digital multimeters to view the
main electric measurements of 3 or 4 wire three-phase systems
■ The electric measurements: voltage, current, power, power factor, frequency and neutral current are shown on three LED displays with three digits
SAFETY WARNINGS
During the installation and operation of the instrument, comply with the following instructions:
1) The product must be installed by a qualified expert.
2) Do not power or connect the instrument if it is damaged.
2) The appliance must be installed and operated in compliance with current electric systems
standards.
2) After installation, inaccessibility to the connection terminals without appropriate tools may
3) After installation, inaccessibility to the connection terminals without appropriate tools must be guaranteed.
5) Before accessing the connection terminals, verify that the leads are not live.
6) The instrument is destined for use in environments with overvoltage category ill and pollution
level 2, according to the CEI EN 61010-1 standard.
7) There must be a bipolar cut-off in the power supply network.
8) A device to protect against overloads must be installed in the electrical system under fire.
6) A device to protect against overloads must be installed in the electrical system upside from the instrument.
Code
Model Description
VE333100 EV3M-D 4 DIN digital multimeter
TECHNICAL CHARACTERISTICS
• Power supply: 230 V AC (-15%/+10%), 50/60Hz
- Input voltage: Vmax = 300V (phase-neutral)
• Maximum own consumption: voltage circuits: < 2.5 VA;
current circuits: < 2.5 VA; Input current: In = FA (nominal) max = FA (maximum).
- Input current: IN = 3A (nominal) max = 6A (maximum)
- Accuracy: Alternating voltage: +0.5% F.S. +1 digit
Alternating current: ±0.5% F.S. ± 1 digit
• Frequency 47-63Hz (±1Hz)
• Alternating voltage: resolution 1V
• Alternating current: resolution 10mA
minimum display: 150mA with TA 5/5A
- Selectable TA: x/5A type (up to 10000/5A)
• Measurements taken: phase voltages (L-N); chained voltages (L-L); phase currents; phase active power
phase apparent power, phase reactive power, power factor (cosφ), frequency, neutral current
• Cross-section of leads: max 6mm² pm
max 2.5mm² on 72x72 mode
• Display: 7-segment LED display
- Operating temperature: -10 ÷ +45 °C
- Operating humidity: 10 ÷ 90% noncond
• Storage temperature: -20 ÷ +60
• Insulation voltage: 4kV between accessible parts (front) and all terminals
• Degree of Protection: IP20 / IP51 on the Front Panel
INSTALLATION
• The instrument must be installed exactly as shown in the figure.
- Connection for the voltage inputs is always direct, whereas an external amperometric transformer (TA) is used for the current inputs.
Attention! The current transformer secondary circuits CANNOT be earthed.
OPERATION
- Once the instrument has been installed, the pages of the various electric measurements monitored can be viewed by pressing the ▼ key to move on to the next page, ▲ to go back to the previous page, in the following order:
Page 1: PHASE VOLTAGE (L-N)
LED V(L-N) is on
| Example | ||
| field 1 | 230 | 230_u |
| field 2 | 230 | 238_u |
| field 3 | 230 | 230_u |
Page 2: CHAINED VOLTAGES (L-L)
LED W(L-L) is on.
| Example | ||
| field 1 | 300 | 300 |
| field 2 | 300 | 300 |
| field 3 | 300 | 300 |
Page 3: PHASE CURRENTS
LED (A) is
| Example | ||
| field 1 | 10.8 | 10.8_u |
| field 2 | 0.53 | 0.53_u |
| field 3 | 3.00 | 3.00_u |
Page 4: PHASE ACTIVE POWER
LED (W) is
| Example | ||
| field 1 | 100 | 100 |
| field 2 | 170 | 170 |
| field 3 | 120 | 120 |
| Press | the | "OK" key to view the system power as follows: |
Example
| field 1 | P | |
| field 2 | SYS | 545 |
| field 3 | 390 (calculated value) | 390 |
| Press | "OK" again to go back to the phase measurement. |
Page 5: PHASE APPARENT POWER
LED (VA) i
Example
| field 1 | 100 | 100 |
| field 2 | 170 | 170 |
| field 3 | 120 | 120 |
| Press | the | "OK" key to view the system power as follows: |
Example
| field 1 | PA | PA |
| field 2 | SYS | SYS |
| field 3 | 390 (calculated value) | 390 |
| Press | “OK” again to go back to the phase measurement. |
Page 6: PHASE REACTIVE POWER
LED (var)
| Example | ||
| field 1 | 38.0 | 38.0 |
| field 2 | 16.0 | 16.0 |
| field 3 | 24.0 | 24.0 |
| Press | the | “OK” key to view the system power as follows: |
Example
| field 1 | Pr | Pr |
| field 2 | SYS | SYS |
| field 3 | 78.0 (calculated value) | 78.0 |
| Press | "OK" again to go back to the phase measurement. |
Page 7: POWER FACTOR (cosφ)
No LEDs on and the displays show the value of cosφ measured on each phase.
Example
| field 1 | L.86 | L = inductive phase shift | L.86 |
| field 2 | C.94 | C = capacity phase shift | C.94 |
| field 3 | L.82 | L = inductive phase shift | L.82 |
| If you want to display the system power factor (PF), press the "OK" key; |
Example
| field 1 | PF | |
| field 2 | SYS | |
| field 3 | 0.80 (calculated value) | 0.80 |
| Press | “OK” again to go back to the phase measurement. |
Page 8: FREQUENCY
No LEDs on and information displayed as follows
| Example | ||
| field 1 | F | F |
| field 2 | 50.0 | 50.0 |
| field 3 | (empty) | |
Page 9: NEUTRAL CURRENT
LED (A) is
| field 1 | In | In |
| field 2 | 1.4 | 14 |
| field 3 | (empty) |
Measurement unit management
The "k" and "M" measurement units are associated with two LEDs which come on automatically
depending on the value of the measurement taken
Example (with TA 5000/5A)
I1=160A; I2=1000A; I3=2500A, the information displayed will be as follows:
L1 0.16
0.16
100
1.00
2.50
LEDs "A" and "k" are on.
PARAMETER SETTING: TA AND 3 OR 4 WIRE SYSTEM
TA setting
The value of the TA secondary is 5A and cannot be modified
To set the capacity of the primary, proceed as follows.
With the instrument turned off, hold down the "PRG" key, then power the instrument. After
approximate

field 1 Pr
field 2 ct
NOTE 2
field 3 05 (flashing)
To modify field 3 use the ▲ key (increase) or ▼ key (decrease). The value can be modified in steps
of 5 up to 10
Once you have selected your chosen capacity, press "OK" to confirm.
3 or 4 wire system setting (4 wires by default)
This second setting is used by the instrument to determine the neutral current (4 wire system).
Getting page display.

field 1 Pr
field 2 SV
(1) 2017年1月1日
field 3 04 (flashing)
To modify field 3 use the ▲ o ▼ keys. The selectable values are 3 or 4.
If you set the value 3 (three wire system), pages 1 (three-phase voltage) and 9 (neutral current) are
Not display you Press 160K11
Monitor the system. If you do not press "OK", the instrument leaves the programming mode after 30
seconds with
Subsequently, to view the TA setting, use the ▲ or ▼ arrows on page 3 (phase currents, LED "A" on)
and press "PRG" (the parameters cannot be modified on this page). To exit press "PRG" again or
(No text)
Note: THE TA MUST NOT BE EARTHED.
Incorrect TA connection
In case of incorrect connection of one or more TA, the display relating to the phase concerned by the incorrect connection flashes on the active powers page (LED (W) on).
ERROR MESSAGES
Error messages
If message EEE is shown (flashing)
please contact Vemer technical support.
If message Err Par is shown (flashing)
repeat the parameter setting procedure:
•
Out of scale message
HHH (flashing)
Means the current and/or voltage values are beyond the full scale value.
Voltage overload V>Vmax + 6%
Current overload I>In + 20% for connection via 5/5A TA (for different TAs, multiply by the
If the page displayed is not related to the measurement in overload (out of scale), phase or chained voltage or phase current, the message is nonetheless shown by flashing the value of the overall measurement (if the page displayed concerns the system) or the measurements related to the phases in overload (if the page displays the phase measurements).
Note. If at least one of the phase currents is out of scale, three dashes are displayed on the neutral current page:
(Hooking)
REFERENCE STANDARDS
ompliance with Community Directives
16/95/EC (Low Voltage)
44.10d/LS (Electromagnetic Compatibility) declared with reference to the following bar
N 61010-1, EN 61000-6-2 and EN 61000-6-4