USER MANUAL DP3213 IFM
Operating instructions
Converter IO-Link / 2 x 4...20 mA (IP 69K)
DP3213
Contents
1 Preliminary note 3
1.1 Symbols used 3
1.2 Warnings used 3
1.3 Safety symbol on the device 3
2 Safety instructions.... 4
3 Intended use.... 5
4 Function 6
4.1 Application as an IO-Link device 6
4.1.1 General information.... 6
4.1.1.1 Application example 6
4.1.2 IO Device Description (IODD) 6
5 Installation.... 7
6 Electrical connection.... 8
6.1 Input side 8
6.2 Connecting the device.... 8
6.2.1 Mounting the connector.... 9
6.2.1.1 Maximum cable length 9
7 Operating and display elements 10
7.1 LEDs.... 10
7.2 Diagram of the current value at the output 11
8 Parameter setting 12
8.1 Parameters adjustable via IO-Link 12
8.1.1 Application-specific tag 12
9 Operation 13
10 Troubleshooting 14
11 Maintenance, repair and disposal 15
1 Preliminary note
You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at documentation.ifm.com.
1.1 Symbols used
√ Requirement
Instructions
Reaction, result
[...] Designation of keys, buttons or indications
→ Cross-reference

Important note
Non-compliance may result in malfunction or interference.

Information
Supplementary note
1.2 Warnings used
ATTENTION
Warning of damage to property

CAUTION
Warning of personal injury
▷ Slight reversible injuries may result.
1.3 Safety symbol on the device

Safety symbol on the device:
▶ Adhere to the operating instructions for the safe operation of the unit.
2 Safety instructions
- The unit described is a subcomponent for integration into a system.
- The system architect is responsible for the safety of the system.
-
The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the architect of the system.
-
Read this document before setting up the product and keep it during the entire service life.
- The product must be suitable for the corresponding applications and environmental conditions without any restrictions.
- Only use the product for its intended purpose (→ Intended use).
- If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur.
- The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator.
- Installation, electrical connection, set-up, operation and maintenance of the product must be carried out by qualified personnel authorised by the machine operator.
- Protect units and cables against damage.
- Replace damaged units, otherwise the technical data and safety will be impaired.
- Observe applicable documents.
3 Intended use
The device is used for the control of a connected actuator or another device with analogue input (4...20 mA). The device has two analogue current outputs. It operates as an "IO-Link / analogue converter".

Fig. 1: Inputs/outputs of the device
The device is suited for wet environments. Observe instructions in chapters "Installation" and "Electrical connection".
The unit is not suited for environments with particular requirements on mechanical stability (e.g. shock/vibration).
The unit is intended for indoor use only.
▶ Observe the operating conditions ( → Technical data at www.ifm.com).
4 Function
The device converts IO-Link signals into analogue current values (4...20 mA).
The current values to be provided can be set via IO-Link communication using IO-Link tools or a PLC.
4.1 Application as an IO-Link device
4.1.1 General information
The unit has an IO-Link communication interface which requires an IO-Link capable module (IO-Link master).
The IO-Link interface allows direct access to the process and diagnostic data and enables setting of the parameters of the unit during operation.
You will find further information about IO-Link and all the necessary information about the required IO-Link hardware and software at:
www.io-link.ifm
4.1.1.1 Application example

Fig. 2: Application example with IO-Link master
1: Analogue actuator
2: Converter IO-Link / 2 x 4...20 mA
3: Fully bidirectional IO-Link communication
Remote parameter setting:
reading and changing the parameter setting
4: IO-Link master
5: Fieldbus (e.g. Profibus, Profinet etc.)
6: PLC
4.1.2 IO Device Description (IODD)
You will find the IODDs required for configuration of the IO-Link device as well as detailed information about the process data structure, diagnostic information and parameter addresses at documentation.ifm.com
5 Installation
ATTENTION
Higher shock ≥ IK06
▷ Damage possible
▷ Protection rating and, in wet environments, electrical protection might be impaired
▶ If necessary, the system creator must take external measures to protect the device depending on the requirements of the corresponding application.
▶ Replace damaged devices, otherwise the technical data and safety will be impaired.
The IP rating of the overall system depends on the protection ratings of the individual devices, the applied connection elements and the corresponding protective caps.
ATTENTION
No protection rating / no protection of the contacts without mounted connectors / protective caps.
▷ Inadmissible soiling / moisture possible.
▷ Disconnection of circuits / safety possibly impaired.
▷ Before installation / when replacing the device, maintain pollution degree 2.
▶ Disconnection / safety guaranteed.
▶ Connect the M12 connectors of the device ( → Electrical connection).
▶ Install the device so that the M12 connection parts and the device are protected from mechanical stress such as shock and vibration.
▶ If necessary, fix the device with cable ties.

The following applies to all types of mounting:
The responsibility for the compliance with the requirements concerning mounting of the device in the application with regard to shock, vibration, acceleration and weight lies with the system architect.
6 Electrical connection

The unit must be connected by a qualified electrician.
▶ Observe the national and international regulations for the installation of electrical equipment.

CAUTION
Use in wet environments
▷ Electric shock possible.
▶ Voltage derating required ( → Technical data).
The input and output circuits are insulated from each other and from device surfaces that could be touched with basic insulation according to IEC 61010-1 (secondary circuit with max. 32 V DC, supplied from the mains circuit up to 300 V of overvoltage category II).
The external wiring has to be carried out in a way that ensures the required separation from other circuits.
6.1 Input side
Operating voltage (SELV/PELV)

CAUTION
The input current of the operating voltage is not limited.
▷ No fire protection.
▶ Protect the circuit.
▶ Protect the sensor supply via the same fuse.
| Potential | M12 connector 1 | Fuse |
| L+ / supply voltage | Pin 1 | ≤ 2 A |
| C/Q IO-Link (if not protected via IO-Link master) | Pin 4 | ≤ 2 A |
Required tripping characteristic of the fuses:
Tfuse ≤ 120 s at max. 6.25 A (fire protection)
▶ Alternatively supply the device via a limited energy circuit according to IEC 61010-1 or class 2 according to UL1310.
6.2 Connecting the device
▶ Disconnect power.
▶ Connect the unit as follows:

Fig. 3: Electrical connection
1: 4-pole M12 connector
(Input side)
• Pin 1: L+ / supply voltage
• Pin 2: not connected
• Pin 3: L- / supply voltage
- Pin 4: C/Q IO-Link
2: 5-pole M12 socket
(Output side)
- Pin 1: L+
• Pin 2: 4...20 mA analogue output 2 - Pin 3: L-
• Pin 4: 4...20 mA analogue output 1 - Pin 5: not connected
The device must not be externally supplied via the 5-pole M12 output socket ②.
Always use the provided connection cables to connect other devices.
See also application examples ( → Function)
6.2.1 Mounting the connector
The threaded connections in the device correspond to the M12 standard. To ensure compliance with the specified protection rating, only cables that comply with this standard may be used. In the case of self-assembled cables, the system manufacturer is responsible for the protection rating.
▶ Use connectors with gold-plated contacts.
▶ During installation, place the connectors vertically so that the coupling nut will not damage the thread.
▶ Observe the coding of the connectors during installation.
If connector in the device:
▶ Tighten the cable sockets according to the torque specifications indicated by the cable vendor. Maximum permissible tightening torque: 1.8 Nm
If sockets in the device:
▶ Tighten the cable plug using 1.3 ± 0.1 Nm.
▶ Provide all outgoing cables with suitable strain relief after a maximum of 200 mm. Observe the minimum bending radius of the cables ( → information from the cable manufacturer).
6.2.1.1 Maximum cable length
• Without IO-Link communication: 30 m on each side
• With IO-Link communication: 20 m on the master side
7 Operating and display elements

1: LED I
2: LED Power
3: LED II
7.1 LEDs
| LED | Colour | Status | Designation | |
| I | OUT1 | yellow | on | Analogue value in the standard range:0...100 % (4...20 mA) |
| flashing (2 Hz) | Analogue value in the range:-10...0 %, 100...110 % (2...4 mA, 20...22 mA) | |||
| flashing (5 Hz) | Interruption of the current loop | |||
| off | Analogue value off:< -10 % (< 2 mA) | |||
| Power | green | on | Voltage supply OK. Device in operating mode. | |
| flashing (5 Hz) | Device supply undervoltage | |||
| off | No voltage supply. Device switched off. | |||
| II | OUT2 | yellow | on | Analogue value in the standard range:0...100 % (4...20 mA) |
| flashing (2 Hz) | Analogue value in the range:-10...0 %, 100...110 % (2...4 mA, 20...22 mA) | |||
| flashing (5 Hz) | Interruption of the current loop | |||
| off | Analogue value off:< -10 % (< 2 mA) | |||
Error signals and diagnostics: → Troubleshooting
7.2 Diagram of the current value at the output

8 Parameter setting
During parameter setting the unit remains in the operating mode. It continues its monitoring functions with the existing parameters until the parameter setting has been completed.
8.1 Parameters adjustable via IO-Link
8.1.1 Application-specific tag
Customer-specific application description, max. 32 characters long.
Default value: “ *** ” / can be freely defined by the customer
9 Operation
The device provides the analogue output signals according to the process data set via IO-Link.
10 Troubleshooting
| LED | Status | Error | Troubleshooting |
| I | flashing (5 Hz) | Interruption of the current loop | Check/correct connection cables and connections at the output. → Electrical connection |
| Power | flashing (5 Hz) | Supply voltage too low | Check/correct the supply voltage. → Electrical connection |
| off | No supply voltage | Check/correct the supply voltage. → Electrical connection | |
| II | flashing (5 Hz) | Interruption of the current loop | Check/correct connection cables and connections at the output. → Electrical connection |
11 Maintenance, repair and disposal
The unit is maintenance-free.
▶ Carry out cleaning considering the technical data (protection rating) and the connection technology used.
▶ Cleaning agents must be checked by the system manufacturer / operator for their suitability for the device materials ( → Technical data) and the connection technology used.
▶ The cleaning agents must not damage the device materials.
▶ It is not possible to repair the unit.
▶ After use, dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations.