IFM SBM613 - Flow sensor

SBM613 - Flow sensor IFM - Free user manual and instructions

Find the device manual for free SBM613 IFM in PDF.

📄 10 pages English EN Download 💬 AI Question
Notice IFM SBM613 - page 1
View the manual : Français FR Deutsch DE English EN 中文 ZH
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about SBM613 IFM

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Flow sensor in PDF format for free! Find your manual SBM613 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. SBM613 by IFM.

USER MANUAL SBM613 IFM

Operating instructions Mechatronic flow sensor

SBM6xx

Contents

1 Preliminary note 3

1.1 Symbols used 3
1.2 Warnings.... 3

2 Safety instructions.... 4

3 Intended use.... 5

3.1 Application area 5

4 Function 6

4.1 Analogue output 6

5 Mounting 7

5.1 Process connection.... 7
5.1.1 Installation drawing 8
5.2 Interference.... 8
5.3 Installation in case of water containing dirt 8

6 Electrical connection.... 9
7 Maintenance, repair and disposal 10

1 Preliminary note

You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at documentation.ifm.com.

1.1 Symbols used

√ Requirement
Instructions
Reaction, result

[...] Designation of keys, buttons or indications

→ Cross-reference

IFM SBM613 - Symbols used - 1

Important note

Non-compliance may result in malfunction or interference.

IFM SBM613 - Symbols used - 2

Information

Supplementary note

1.2 Warnings

Warnings indicate the possibility of personal injury and damage to property. This enables safe product handling. Warnings are graded as follows:

IFM SBM613 - Warnings - 1

WARNING

Warning of serious personal injury

▷ If the warning is not observed, fatal and serious injuries are possible.

IFM SBM613 - Warnings - 2

CAUTION

Warning of minor to moderate personal injury

▷ If the warning is not observed, minor to moderate injuries are possible.

ATTENTION

Warning of damage to property

▷ If the warning is not observed, damage to property is possible.

2 Safety instructions

- The unit described is a subcomponent for integration into a system.

  • The system architect is responsible for the safety of the system.
  • The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the architect of the system.

  • Read this document before setting up the product and keep it during the entire service life.

  • The product must be suitable for the corresponding applications and environmental conditions without any restrictions.
  • Only use the product for its intended purpose (→ Intended use).
  • Only use the product for permissible media.
  • If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur.
  • The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator.
  • Installation, electrical connection, set-up, operation and maintenance of the product must be carried out by qualified personnel authorised by the machine operator.
  • Protect units and cables against damage.
    • Store the product in its original packaging.

3 Intended use

The unit monitors liquid media.

The device detects the volume flow (flow rate/time) and outputs an analogue signal that is proportional to the process value.

3.1 Application area

  • Water
  • Glycol solutions
  • Industrial oils
  • Coolants

IFM SBM613 - Application area - 1

If the cable length exceeds 30 m or if used outside buildings, there is a risk of overvoltage pulses from external sources. We recommend to use the unit in protected operating environments and to limit overvoltage pulses to max. 500 V.

ATTENTION

Frost formation of the medium.

▷ The sensor may be damaged.

▶ Ensure that the medium in the sensor does not freeze during operation and transport.

4 Function

The unit detects the flow according to the principle of differential pressure by means of a permanent magnet and a measuring cell.

4.1 Analogue output

IFM SBM613 - Analogue output - 1

Fig. 1: Analogue output (water 20 °C)

The analogue signal for water is linear from 4 mA (= no flow) to 20 mA (= final value of the measuring range, VMR).

If the measured value is above the final value of the measuring range, a current signal of > 20 mA is output.

5 Mounting

IFM SBM613 - Mounting - 1

CAUTION

During installation or in case of a fault (e.g. housing damage) media under high pressure or hot media can leak from the system.

▷ Risk of injury caused by pressure or burns.
▶ Ensure that the system is free of pressure during installation.
▶ Ensure that no media can leak at the mounting location during installation.
▶ Equip the unit with suitable protection (e.g. cover) to avoid hazard to personnel from leaking media.

IFM SBM613 - Mounting - 2

CAUTION

If the medium temperature is above 50\ °C ( 122\ °F ), parts of the housing can increase in temperature to over 65\ °C ( 149\ °F ).

▷ Risk of burns.
▶ Protect the housing against contact with flammable substances and unintentional contact.

5.1 Process connection

▶ Avoid major changes of cross section on the inlet side.
▶ Screw the unit into a pipe section or a valve with a G3/4 process connection until the measurement insert rests on the pipe section or the valve.
▶ Tighten firmly. Tightening torque: 10 Nm.

Preferred installation position: vertical.

IFM SBM613 - Process connection - 1

Fig. 2: Process connection

IN: inlet

OUT: outlet

IFM SBM613 - Process connection - 2

Calming sections on the sensor's inlet or outlet side are not necessary.

IFM SBM613 - Process connection - 3

The sensor can also prevent backflow.

5.1.1 Installation drawing

IFM SBM613 - Installation drawing - 1

Fig. 3: Dimensions for installation in pipe section or valve

5.2 Interference

▶ The following minimum distances must be adhered to:

Distance between the sensor and ferromagnetic materials≥ 30 mm *
Distance between the sensor and constant / alternating fields≥ 500 mm
Distance between the sensor axes for side-by-side installation≥ 50 mm

* The pipe may consist of ferromagnetic material.

5.3 Installation in case of water containing dirt

▶ Use a 200-micron filter in front of the inlet (IN).
▶ Install sensor horizontally.

In clean medium, installation in vertical pipes is also possible.

6 Electrical connection

IFM SBM613 - Electrical connection - 1

The unit must be connected by a qualified electrician.

Observe the national and international regulations for the installation of electrical equipment.

Voltage supply according to SELV, PELV.

▶ Disconnect power.
▶ Connect the unit as follows:

IFM SBM613 - Electrical connection - 2

Fig. 4: Wiring diagram (colours in accordance with DIN EN60947-5-2)

BN: Brown

WH: White

BU: Blue

IFM SBM613 - Electrical connection - 3

Information on available sockets see: www.ifm.com.

7 Maintenance, repair and disposal

The operation of the unit is maintenance-free.

Only the manufacturer is allowed to repair the unit.

▶ After use dispose of the device in an environmentally friendly way in accordance with the applicable national regulations.