Tripp Lite S3M160KXD - Inverter

S3M160KXD - Inverter Tripp Lite - Free user manual and instructions

Find the device manual for free S3M160KXD Tripp Lite in PDF.

📄 356 pages English EN Download 💬 AI Question 10 questions ⚙️ Specs
Notice Tripp Lite S3M160KXD - page 3
View the manual : Français FR Deutsch DE English EN Español ES Русский RU
Pick your language and provide your email: we'll send you a specifically translated version.
Product type Three-phase double conversion online UPS
Brand Tripp Lite
Model S3M160KXD
Capacity 160 kVA / 144 kW
Nominal input voltage 380/400/415 V three-phase (Ph-Ph), 220/230/240 V (Ph-N)
Nominal output voltage 380/400/415 V three-phase (Ph-Ph), 220/230/240 V (Ph-N)
Nominal frequency 50/60 Hz (automatic selection)
Battery type External, VRLA AGM/GEL 12 V, 40 cells (20+20)
Dimensions (H x W x D) 1455 x 567 x 995 mm
Weight (without batteries) 309 kg
Operating temperature 0 °C to 40 °C
Relative humidity 0 to 95 % (non-condensing)
Audible noise < 73 dBA at 1 m
Display 10-inch LCD touch screen
Communication interfaces RS-232, USB, SNMP slot (WEBCARDLX), dry contacts, emergency shutdown REPO
Dual AC input Yes (KXD model)
Line mode efficiency 94% at 100% resistive load
Battery mode efficiency 93% at 100% resistive load
Warranty 2 years (with start-up by authorized service)
Safety standards IEC 62040-1, EN 62040-2, CE, RoHS
Maintenance and cleaning Check fans and battery; dust the exterior with a dry cloth

Frequently Asked Questions - S3M160KXD Tripp Lite

How to start the S3M160KXD UPS?
Ensure that the input breakers (Q1) and battery are in the ON position. Press the On/Off button on the front panel for 2 seconds or use the LCD display in the Control menu.
What to do in case of low battery alarm?
The alarm sounds every 0.5 seconds. Reduce the load or turn off the UPS via the Control menu. Recharge the batteries by restoring mains power.
How to replace the external batteries?
Replacement must be carried out by qualified personnel. Use the same number (40) and type of VRLA 12 V batteries. Turn off the UPS, disconnect the battery cables, and follow safety precautions.
Can I connect two UPS units in parallel?
Yes, up to 2 units. Use the parallel kit P100200KIT, wire the inputs and outputs with equal lengths, configure the parallel function in the SETUP menu, and connect the parallel cables.
How to configure emergency shutdown (REPO)?
Connect a normally closed switch to port X2. In the GENERAL menu, set EPO Function to Normal Open or Normal Close according to your switch.
What is the transfer time in battery mode?
Transfer from line to battery is 0 ms (zero time). Transfer from inverter to synchronous bypass is 0 ms, asynchronous < 1 cycle.
What does the red FAULT light mean?
It indicates a UPS fault. Check the LCD display for the error code. Refer to the Troubleshooting chapter in the manual or contact technical support.
How to perform a manual battery test?
From the Control screen, select Cancel Battery Test to start a test. The test stops automatically according to the duration, voltage, or capacity parameters set in the BATTERY menu.
What is the heat dissipation at full load?
For the S3M160KXD model, the heat dissipation is 31343 BTU/h at 100% load and 14731 BTU/h at 50% load.
Can I use a different external battery cabinet?
Use only the recommended Tripp Lite cabinets: BP480V100, BP480V65, BP480V40 or their NIB versions. Respect the nominal voltage of ±240 V DC and the number of 40 batteries.

User questions about S3M160KXD Tripp Lite

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Inverter in PDF format for free! Find your manual S3M160KXD - Tripp Lite and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. S3M160KXD by Tripp Lite.

USER MANUAL S3M160KXD Tripp Lite

Models: S3M100KX, S3M100KXD, S3M120KX, S3M120KXD, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

Input: 220/230/240V (Ph-N), 380/400/415V (Ph-Ph), 3∅ 4-Wire + PE

Two black rectangular electronic equipment units with perforated bases and control panel displays, no visible text or symbols on the surfaces.

TRIPP·LITE

Tripp Lite S3M160KXD - 3

Table of Contents

1. Introduction 3

2. Important Safety Warnings 4

2.1 UPS Location Warnings 4
2.2 Equipment Connection Warnings 4
2.3 Battery Warnings 4
2.4 Transportation and Storage 5
2.5 Preparation 5
2.6 Installation 5
2.7 Connection Warnings 5
2.8 Operation 6
2.9 Standards 6

3. Installation and Setup 7

3.1. Unpacking and Inspection 7
3.2. Open Front Panel View 9

3.2.1 Interface and Communication 10

3.2.2 Power Stage/Module 10

3.3 Rear Panel View 11
3.4 Wiring Terminal Views 12
3.5 Single UPS Installation 13
3.6 UPS Installation for Parallel Systems 15

3.6.1 Input and Output Wiring 15
3.6.2 Parallel Board Setting 17
3.6.3 Parallel Function Setting 19
3.6.4 Parallel Cable Connection 19
3.6.5 Parallel System Turn On Procedure 20

3.7 Dual AC Input Installation 20

4. Control Panel and LCD Operation

4.1 Control Panel Description 21
4.2 LCD Screen Description 22

4.2.1 Initial Screen 22
4.2.2 Main Screen 22
4.2.3 Control Screen 23
4.2.4 Measurement Screen 24
4.2.5 Setup Screen 26
4.2.6 Information Screen 37
4.2.7 Event Screen 38

4.3 Alarm List 40
4.4 History Record 41

5. Interface and Communication 42

5.1 X1 – Temperature Detection Port for External Battery Pack 42
5.2 X2 - Remote EPO Input Port 43
5.3 Other Communication Interfaces 43

6. Operation Principles 44

6.1 UPS Block Diagram 44
6.2 Operation Modes 45

6.2.1 Standby Mode 45
6.2.2 Line Mode 46
6.2.3 Battery Mode 47
6.2.4 Frequency Conversion Mode 48
6.2.5 Bypass Mode 49
6.2.6 ECO Mode 50
6.2.7 Shutdown Mode 51
6.2.8 Maintenance Bypass Mode 52

7. UPS Operation 53

7.1 AC Startup 53
7.2 Cold Start Startup 55

7.3 Maintenance Bypass Operation 57

7.3.1 Transfer Critical Load from Line Mode to Maintenance Bypass 57
7.3.2 Transfer Critical Load from Maintenance Bypass to Line Mode 59

7.4 Turn Off Operation 61

7.4.1 Turn Off Operation in Line Mode 61
7.4.2 Turn Off Operation in Battery Mode 62

8. Troubleshooting 64

9. Storage and Service 66

9.1 Storage 66
9.2 Service 66
9.3 Batteries 66
9.4 Fans 66

10. Specifications 67

Warranty 70

Español 71

Français 142

Русский 212

Deutsch 283

1. Introduction

Tripp Lite's SmartOnline S3MX-Series Uninterruptible Power Supply (UPS) is a Voltage and Frequency Independent (VFI) true on-line, double-conversion 3-phase UPS system. This UPS continuously conditions the incoming electrical power supply, eliminating power disturbances that will otherwise damage sensitive electronic devices and minimising system downtime from power fluctuations and interruptions.

S3MX-Series UPS systems are designed to the highest quality and performance standards and offer the following features:

Model Agency Number Capacity
S3M100KX, S3M100KXD* AG-6100 100kVA
S3M120KX, S3M120KXD* AG-6120 120kVA
S3M160KX, S3M160KXD* AG-6160 160kVA
S3M200KX, S3M200KXD* AG-6200 200kVA

* "KXD" models are dual-AC input capable.
- True on-line UPS – the highest level of UPS protection, fully regulates the incoming power with zero transfer time to battery in the event of an extended mains failure, so critical loads remain continuously supported
- Paralleling for redundancy and capacity for up to two UPS systems
- High-efficiency performance in AC On-line and Battery Standby Modes to minimise energy consumption
• Market-leading small size and footprint
- ECO Mode allows the UPS to operate on bypass in stable utility conditions and immediately transfers to inverter to support the load when the utility input drops below tolerance
- High output power factor – more actual power allows more equipment to be supported
• Automatic and manual bypass increase system reliability and allow for maintenance without removing power from the attached load
- Wide input voltage window – the UPS system regulates even poor-quality incoming power without reverting to battery, maximising system uptime and protecting battery life
- Matching external battery cabinets allow for increased battery autonomy
• Emergency shutdown via REPO
- SNMP Network Monitoring and volt-free contact options provide optimum configurability
- Optional dual-AC input "KXD" models available

SmartOnline S3MX-Series UPS systems are ideally suited for protecting 4-wire loads in the following mission-critical electrical applications:

• IT infrastructure and data centres
• Telecommunications
• Networks (LAN/WAN)
• Corporate infrastructure
• Security and emergency systems
• Financial institutions
• Healthcare and hospitals

2. Important Safety Warnings

SAVE THESE INSTRUCTIONS

This manual contains important instructions and warnings that should be followed during the installation and maintenance of all Tripp Lite SmartOnline S3MX 3-Phase 100kVA, 120kVA, 160kVA and 200kVA UPS Systems and their batteries. Failure to heed these warnings may affect your warranty.

2.1 UPS Location Warnings

• Install the UPS indoors, away from heat, direct sunlight, dust, and excess moisture or other conductive contaminants.
• Install the UPS in a structurally sound area. The UPS is extremely heavy; take care when moving and lifting the unit.
- Only operate the UPS at indoor temperatures between 0°C and 40°C .
- Optimum UPS performance and maximum battery life is obtained when the operating temperature is maintained between 17°C and 25°C .
- Ensure the installation area has sufficient space for maintenance and ventilation of the UPS system. Maintain a minimum clearance of 50 cm from the front and rear of the UPS for maintenance and ventilation.
- Do not install the UPS near magnetic storage media, as this may result in data corruption.

2.2 Equipment Connection Warnings

  • Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
  • The UPS system contains its own energy source (battery). The output terminals may be live, even when the UPS is not connected to an AC supply.
  • The UPS models covered in this manual are not compatible with loads that do not have a Neutral Reference or Delta load.

2.3 Battery Warnings

This UPS contains LETHAL VOLTAGES. The UPS is designed to supply power, even when disconnected from utility power. Only AUTHORISED SERVICE PERSONNEL should access the interior of the UPS after disconnecting utility and DC power.

⚠ Batteries present a risk of electrical shock and burns from high short-circuit current. Battery connection or replacement should be performed by only qualified service personnel observing proper precautions. Turn off the UPS before connecting or disconnecting internal batteries. Use tools with insulated handles. Do not open the batteries. Do not short or bridge the battery terminals with any object.

  • The batteries are recyclable. Refer to local codes for disposal requirements or visit tripplite.com/support/recycling-program for recycling information.
  • Do not dispose of the batteries in a fire, mutilate the batteries or open the battery coverings. Escaping electrolytes may be toxic and cause injury to skin and eyes.
  • Do not disconnect the batteries while the UPS is in Battery Mode.
  • Disconnect the charging source prior to connecting or disconnecting terminals.

- The following precautions should be observed:

1) Remove watches, rings and other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries or battery cabinets.
5) Determine whether the battery supply (+, -, N) is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded battery can result in electric shock. The likelihood of an electric shock is reduced if such grounds are removed during installation and maintenance.

- Battery replacement should be performed only by authorised service personnel, using the same number and type of batteries (sealed lead acid).

Tripp Lite S3M160KXD - Battery Warnings - 1

WARNING: In order to avoid any hazardous conditions during UPS installation and maintenance, these tasks may be performed only by qualified and experienced electricians.

Please read this Owner's Manual and safety instructions carefully before installing or using the unit.

2. Important Safety Warnings

2.4 Transportation and Storage

⚠️ To protect against shock and impact, transport the UPS system using only its original packaging.
The UPS must be stored in a room that is dry and ventilated.

2.5 Preparation

⚠️ Condensation may occur if the UPS system is moved directly from a cold to warm environment. The UPS system must be completely dry before being installed. Please allow at least two hours for the UPS system to adjust to the environment.
⚠️ Do not install the UPS system near water or in moist environments.
⚠️ Do not install the UPS system in direct sunlight or near heat sources.
Do not block the ventilation holes on the UPS system's housing.

2.6 Installation

Do not connect appliances or devices that could overload the UPS (i.e., equipment with large electrical motors) to the UPS output sockets or terminal.
⚠️ Carefully arrange cables so no one can step on or trip over them.
Do not block the UPS system's air vents. The UPS must be installed in a location with good ventilation. Ensure adequate ventilation space on each side of the unit.
The UPS contains an earthed terminal. In the final installed system configuration, ensure equipotential earth grounding to the external UPS battery cabinet by connecting the earth terminals of both cabinets together.
⚠ The UPS should only be installed by qualified service personnel.
⚠ An appropriate disconnect device such as short-circuit backup protection must be provided in the building wiring installation.
⚠ An integral single-emergency switching device should be included in the building wiring installation.
⚠️ Connect the earth ground before connecting to the building wiring terminal.
⚠️ Installation and wiring must be performed in accordance with local electrical codes and regulations.

2.7 Connection Warnings

- The UPS system does not contain standard backfeed protection inside. Isolate the UPS before working on this circuit. The isolation device must be able to carry the UPS input current.

Input R S T N UPS «Automatic backfeed protection system» input, external to the UPS (EN-IEC 62040-1)

  • This UPS should be connected with TN earthing system.
  • The power supply for this unit must be 3-phase rated in accordance with the equipment nameplate. It also must be suitably grounded.
  • The input power to 3-phase UPS models require a 3-pole breaker.
  • Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended.
  • Connect the UPS power module's grounding terminal to a grounding electrode conductor.
  • The UPS is connected to a DC energy source (battery). The output terminals may still be live, even when the UPS is not connected to an AC supply.

2. Important Safety Warnings

  • When installing the unit, verify that any maintenance bypass panel used is configured correctly before applying power to the unit.
  • Be sure to place a warning label on all primary power isolators installed remotely from the UPS area and on any external access points between such isolators and the UPS. The warning label shall carry the following wording or equivalent.

Before working on this circuit

- Isolate Uninterruptible Power System (UPS)

- Then check for Hazardous Voltage between all terminals

including the protective earth.

Tripp Lite S3M160KXD - Before working on this circuit - 1

Risk of Voltage Backfeed

2.8 Operation

Do not disconnect the earth conductor cable on the UPS or the building wiring terminals at any time, as this will cancel the protective earth of the UPS system.
⚠ In order to fully disconnect the UPS system, first press the "OFF" button, then disconnect the mains.
⚠ Ensure no liquid or other foreign objects can enter into the UPS system.

2.9 Standards

*Safety
IEC 62040-1: 2008+A1:2013
*EMI
Conducted Emission......EN 62040-2: 2006 Category C3
Radiated Emission ...... EN 62040-2: 2006 Category C3
*EMS
ESD...... EN 61000-4-2 Level4
RS ...... EN 61000-4-3Level 3
EFT ...... EN 61000-4-4Level 4
SURGE ...... EN 61000-4-5Level 4
CS ...... EN 61000-4-6Level 3
Power-Frequency Magnetic Field......EN 61000-4-8 Level4
Low-Frequency Signals ...... EN 61000-2-2
Warning: This is a product for commercial applications. Installation restrictions or additional precautions may be needed to prevent disturbances.

3. Installation and Setup

3.1 Unpacking and Inspection

Unpack the unit and inspect its contents. Packaging may include additional accessories and components, depending on specific customer orders.

  • One (1) UPS
    • One (1) Owner's Manual
    • One (1) RS-232 Cable
    • One (1) paralleling cable for every set of UPS units being paralleled: P100200KIT

Other Accessory or Component Options Available Upon Request

• One (1) Battery Charger Temperature Compensation Thermostat: TEMPC100200

Note: Do not turn on the unit. Make sure to inspect the unit prior to installation. Ensure nothing inside the package was damaged during transportation. Notify the carrier and dealer immediately if there is any damage or missing parts. Please keep the original packaging in a safe place for future use.

  1. Use a forklift to move the product to the installed area. Make sure the bearing capacity of forklift is sufficient. Refer to Figure 3.1.
  2. Follow the unpacking order in Figure 3.2 to remove carton (1, 2) and foams (3).
  3. Remove two fixing plates located on the two sides of the unit (1, 2 and 3) in Figure 3.3. Loosen leveling feet (4) by rotating them counterclockwise. Once loosened, move the cabinet from the pallet.
  4. To fix the cabinet into position, simply rotate leveling feet clockwise. Refer to Figure 3.4.

S3M100KX, S3M100KXD and S3M120KX, S3M120KXD Models

Technical diagram of a server rack system with numbered components for identification

Figure 3.1A
Figure 3.2A Figure 3.3A

Simple line drawing of a mechanical component with a downward arrow indicating force or direction (no text or symbols)

1175 mm 1125 mm

705 mm

Figure 3.4A Figure 3.5A

3. Installation and Setup

S3M160KX, S3M160KXD, and S3M200KX, S3M200KXD Models

Tripp Lite S3M160KXD - Installation and Setup - 1

Simple line drawing of a mechanical component with a downward arrow indicating force or direction (no text or symbols)

1610 mm 1125 mm

705 mm

Figure 3.4B Figure 3.5B

3. Installation and Setup

Remove the accessory package and inspect the package contents. The standard shipping package should contain an Owner's Manual and RS-232 cable. The key to the UPS is attached to the front door with a cable tie. Packaging may also include additional accessories and components, depending on specific customer orders.

Note: Before installing, please inspect the unit. Ensure there is no physical damage to the unit. Do not turn on the unit. Notify the carrier and dealer immediately if there is any damage or missing parts and accessories. Keep the original packaging for future use. It is recommended you keep each equipment and battery set in their original packaging, as it is designed to provide maximum protection during transportation and storage.

Owner's Manual SmartOnline® S3MX 3-Phase UPS Systems RS-232 Cable Owner's Manual P100200KIT Paralleling Cable

3.2 Open Front Panel View

Each UPS comes equipped with a front door key. The key can be found attached to the front door with a cable tie. Upon opening the front door, you will see the communication area and several power stages/modules inside. From each power stage/module you can easily identify its ID.

Table 3.1 Power Stage ID

Power Rating 100K 120K 160K 200K
Stage ID—Individual Unit OperationTripp Lite S3M160KXD - Open Front Panel View - 1Tripp Lite S3M160KXD - Open Front Panel View - 2Tripp Lite S3M160KXD - Open Front Panel View - 3Tripp Lite S3M160KXD - Open Front Panel View - 4
Stage ID—For Parallel UPSTripp Lite S3M160KXD - Open Front Panel View - 5Tripp Lite S3M160KXD - Open Front Panel View - 6Tripp Lite S3M160KXD - Open Front Panel View - 7Tripp Lite S3M160KXD - Open Front Panel View - 8

3. Installation and Setup

3.2.1 Interface and Communication

These UPS systems come equipped with various communication devices. Please refer to section 5. Interface and Communication for further details.

Diagram showing a device layout with labeled ports and connectors, including a grid and control panel.

1 Dry Contact Port X1 (Optional battery temperature compensation thermostat)
2 Dry Contact Port X2 (EPO)
3 SNMP Slot (Optional WEBCARDLX or RELAYCARDSV card)
4 RS-232 Port
5 USB Port

3.2.2 Power Stage/Module

Each power stage/module includes a power factor correction rectifier, a battery charger, an inverter and control circuit.

1 2 3 4 5

No.Item Description
1FanAir enters the power stage through the front grills and is exhausted through the rear of the module. Do not block the ventilation vent.
2Stage Address DIP SwitchesThere are three DIP switches for Power Stage address setting. In the same cabinet, each Power Stage ID MUST be exclusive. Refer to Table 3.1 Power Stage ID for more information.
3Battery Start Button When AC input is not available, use this button to start UPS battery power.
4FAULT LEDON The power stage is in fault condition.
ON/OFF 0.5 sec The power stage IDs are in conflict.
5RUN LEDON The power stage normally works as a secondary stage.
ON/OFF 0.5 sec The power stage normally works as a primary stage.
ON/OFF 0.15 sec The CAN Bus communication does not work.

3. Installation and Setup

3.3 Rear Panel View

Several breakers are located on the rear panel of the UPS. Models with a second AC input (Q2) are also available. The breakers shown are Q1 input 1, Q2 input 2*, Q3 output and Q4 maintenance bypass.

Tripp Lite S3M160KXD - Rear Panel View - 1
100KVA / 120KVA 160KVA / 200KVA
*Second AC circuit breaker (Q2) only applicable on second AC-input models with "KXD" suffix.

3. Installation and Setup

3.4 Wiring Terminal Views

1 2 3 4 5* 6 OUTPUT R S T R S N INPUT2 N INPUT1 BAT N OUTPUT S N INPUT2 OUTPUT 3 3

100KVA / 120KVA

2 5* 1 4 3

160KVA / 200KVA

No.Item Function Description
1Output Block Connects to the critical loads Includes R, S, T and Neutral terminals.
2Main Input Block Connects to main AC source Includes R, S, T and Neutral terminals.
3Ground Connection For UPS grounding Includes one grounding terminal.
4Battery Input Block Connects to an external battery cabinetIncludes:Positive (+), Negative (-) and Neutral (N) terminals.
5*Second Input Block Connect to second AC source Includes R, S, T and Neutral terminals.

*Second AC input block only applicable on second AC-input models with "KXD" suffix.

3. Installation and Setup

graph TD A["100kVA / 120KVA"] --> B["External Battery Input/Output Breaker"] C["160KVA / 200KVA"] --> B B --> D["+BATTERY"] B --> E["-BATTERY"] style A fill:#f9f,stroke:#333 style C fill:#f9f,stroke:#333 style D fill:#ccf,stroke:#333 style E fill:#ccf,stroke:#333

3.5 Single UPS Installation

Installation and wiring must conform with the local electric laws/regulations. The following procedures must be performed by a professional electrician:

1) Make sure the mains wire and breakers in the building provide adequate power for the rated UPS capacity so as to avoid electrical shock or fire hazards.

Note: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS system's maximum input current. Otherwise, the receptacle may be shorted and destroyed.

2) Switch off the mains in the building before installation.
3) Turn off all connected devices before connecting to the UPS.
4) Prepare the power cables according to Table 3.2. Refer to Table 3.3 for UPS Input Breaker sizes and Table 3.4 for Battery Cabinet Batteries and Breaker sizes.

Tripp Lite S3M160KXD - Single UPS Installation - 1

Warning:

- Before connecting any wires, make sure the AC input and battery power are completely shut off.

Table 3.2 Power Cables

ModelPower cable (mm2 and AWG)
Input(Ph) Output(Ph) Neutral BatteryGround
100KVA70 mm2(2/0 AWG)70 mm2(2/0 AWG)70 mm2(2/0 AWG)150 mm2(300 MCM)70 mm2(2/0 AWG)
120KVA95 mm2(3/0 AWG)95 mm2(3/0 AWG)95 mm2(3/0 AWG)240 mm2(500 MCM)95 mm2(3/0 AWG)
160KVA150 mm2(300 MCM)150 mm2(300 MCM)150 mm2(300 MCM)120 mm2 x 2(4/0 AWG x 2)150 mm2(300 MCM)
200KVA185 mm2(400 MCM)185 mm2(400 MCM)185 mm2(400 MCM)185 mm2 x 2(400 MCM x 2)185 mm2(400 MCM)

3. Installation and Setup

Table 3.3 UPS Input Breakers

Model (Series Number) Breaker Size
S3M100KX, S3M100KXD (AG-6100) 200A,3-Pole
S3M120KX, S3M120KXD (AG-6120) 250A,3-Pole
S3M160KX, S3M160KXD (AG-6160) 400A,3-Pole
S3M200KX, S3M200KXD (AG-6200) 400A,3-Pole

Table 3.4 Battery Cabinet Batteries and Breakers

Model Batteries Included Battery Size and Qty. Breaker Size
BP480V100300A, 3-Pole200A, 3-Pole100Ah x 40 400A, 3-Pole
BP480V65 65Ah x 40
BP480V40 40Ah x 40
BP480V100-NIB(Designed For) 100Ah x 40 400A, 3-Pole
BP480V65-NIB (Designed For) 65Ah x 40 300A, 3-Pole
BP480V40-NIB (Designed For) 40Ah x 40 200A, 3-Pole

Tripp Lite S3M160KXD - Installation and Setup - 1

Warning:

  • Before connecting any wires, make sure the AC input and battery power are completely shut off.
  • Make sure the breakers, input1 breaker (Q1), input2 breaker (input2, Q2 on dual input models only), output breaker (Q3 @120K/160K/200K) maintenance breaker (Q4 @ 120K/160K/200K) and battery breaker are all in the "OFF" position. For further reference, review the UPS rear panel images in section 3.3.
  • Make sure the maintenance bypass switch is in "UPS" position (@ 100K).

5) Remove the terminal block cover on the rear panel of the UPS. Connect the input1, (input2 @ dual input UPS models), output and battery wires according to the function indicated on terminal block. Make sure to connect the grounding/earth wires first when establishing a wire connection. Disconnect the grounding/earth wire last when performing wire disconnection.

Notes:

  • Ensure the wires are tightly and securely connected to the terminals.
  • This breaker must have leakage current protective function.
  • Be sure to also add an equipotential bonding wire between the UPS and the External Battery Cabinets.

6) Reattach the terminal block cover to the rear panel of the UPS.

Tripp Lite S3M160KXD - Notes: - 1

Warning:

  • Make sure a DC breaker or other protection device is installed between the UPS and external battery pack. Switch off the battery breaker before installation.
    Note: Set the battery pack breaker to the "OFF" position before installing the battery pack.
  • Pay special attention to the rated battery voltage marked on the label. If you want to change the numbers of the battery pack, make sure to modify the setting accordingly. The connection with the wrong battery voltage may cause permanent damage to the UPS.
  • Make sure the protective grounding/earth wiring is correct. The current spec, colour, position, connection and conductance reliability of the wires must be checked carefully.
  • Make sure the utility input and output wiring is correct. The current spec, colour, position, connection and conductance reliability of the wires must be checked carefully. Make sure the L/N is correct, not reversed or short-circuited.

3. Installation and Setup

3.6 UPS Installation for Parallel Systems

Tripp Lite S3M160KXD - UPS Installation for Parallel Systems - 1

Warning:

  • The input harmonic current distortion will be between 3% and 4.5% in parallel UPS operations.
    • One parallel kit is needed for every two UPS systems.

3.6.1 Input and Output Wiring

  1. When installing the parallel system, the length of input wires (R, S, T, N) in one UPS must be equal to the input wires of the other UPS. Likewise, the length of output wires (R, S, T, N) must also be in equal length. If not, it will cause unbalanced current on the output load.

graph TD subgraph_AC_IP1["AC I/P 1"] A["Input Breaker"] --> B["Static Switch"] C["Bat Module"] --> B D["Input Breaker"] --> B B --> E["UPS Module"] E --> F["Output Breaker"] G["Charge"] --> E end subgraph_Load["Load"] H["Parallel Cable"] --> I["Output Breaker"] J["Input Breaker"] --> K["Static Switc…

Figure 3.6 Single Input Wiring In Parallel System

3. Installation and Setup

graph TD subgraph AC_I/P_1["AC_I/P 1"] A["Input Breaker"] --> B["Static Switch"] C["Bat Module"] --> B D["Bar Module"] --> B end subgraph AC_I/P_2["AC_I/P 2"] E["Input Breaker"] --> F["Static Switch"] G["Bat Module"] --> F H["Bar Module"] --> F end B --> I["UPS Module"] F --> J["UPS Module"] F --> K…

Figure 3.7 For Dual Input Models Wiring models In Parallel System

3. Installation and Setup

3.6.2 Parallel Board Setting

3.6.2.1 Configure Parallel Board of UPS 1

  1. Set SW2 on the parallel board of the UPS 1 to the right side.

SW1 SW2 CN10 CN9 CN7 CN8 OUTPUT T] [ R E T ] N INPUT2 BAT N INPUT1 SW1 SW2 CN10 CN9 CN7 CN8

Figure 3.8 SW2 Position on UPS 1 (Default Setting)

3. Installation and Setup

3.6.2.2 Configure Parallel Board of UPS 2

  1. Set SW2 on the parallel board of the UPS 2 to the left side.

SW1 SW2 OUTPUT DIPUTS INPUTT

SW1 SW2 CN10 CN9 CN7 CN8

Figure 3.9 SW2 Position on UPS 2

3. Installation and Setup

3.6.3 Parallel Function Setting

  1. For input and output wiring, make sure to follow the instructions in section 3.6.1.
  2. For the parallel board setting, make sure to follow the instructions in section 3.6.2.

Confirm no power is applied to either UPS at this time.

Once the two steps above and the battery configuration have been completed correctly, proceed with the following steps:

1. Do not connect Parallel Cable until informed.

  1. Set the input breakers (Q1) of two UPS systems to the "ON" position. Make sure to keep the output breakers (Q3) of two UPS systems set to the "OFF" position.
  2. Turn on the battery breaker.
  3. Turn on the external AC source breaker to apply the AC input source to both UPS systems.
  4. Wait for the the power-cycles to complete. Proceed to set UPS 1.
  5. Use the LCD panel on UPS 1 to set up the parallel function. Enter the "PARALLEL" menu in the "SETUP" page (refer to section 4.2.5.5 Setup-Parallel Screen for more information).
  6. Enable "UPS Parallel" function of UPS 1 (ignore the "Parallel UPS Cable Loose" warning).
  7. Choose the battery configuration as "independent" or "common" battery, depending on your preference.
  8. To save your settings, select the "Save Setting" icon in the "General" screen of the "SETUP" page.
  9. Proceed to set up UPS 2.
  10. Set up the parallel function through the LCD panel on UPS 2. Enter the "PARALLEL" menu in the "SETUP" page (refer to section 4.2.5.5 Setup-Parallel Screen for more information).
  11. Enable the "UPS Parallel" function of UPS 2 (ignore the "Parallel UPS Cable Loose" warning).
  12. Choose the battery configuration as "independent" or "common" battery, depending on your preference.
  13. To save your settings, select the "Save Setting" icon in the "General" screen of the "SETUP" page.
  14. Turn off the external AC source breaker and wait for complete shutdown of both UPS systems.
  15. Turn off the battery breakers.

3.6.4 Parallel Cable Connection

There are three connectors at the end of each parallel cable: one 16-pin connector and two 2-pin connectors.

Short 2-Pin Long 2-Pin 16-Pin

Notes:

  • For 100K and 120K UPS with One Parallel Board: Connect the 16-pin connector and the short 2-pin connector.
  • For 160K and 200K UPS with Two Parallel Boards: Connect the 16-pin connector and the short 2-pin connector to the bottom board. Then, connect the long 2-pin connector to the top board.
  • If the 2-pin connector is disconnected by accident, the UPS will prompt a fault: "Warning! Parallel UPS Cable Loose". Insert the 16-pin connector into CN7 and the 2-pin connector into CN10 of the Parallel Board of UPS 1. Connect the other end of the parallel cable into the Parallel Board of UPS 2, again connecting the 16-pin connector into CN7 and the 2-pin connector into CN10.

SW1 SW2 CN10 CN9 CN7 CN8

SW1 SW2 CN10 CN9 CN7 CN8

Figure 3.10 UPS 1 Parallel Board Figure 3.11 UPS 2 Parallel Board

3. Installation and Setup

Tripp Lite S3M160KXD - Installation and Setup - 1

Warning:

Improper parallel cable connections will result in abnormal operations. Verify each step while connecting the parallel cables on each UPS.

Confirm no power is applied to either UPS at this time.

3.6.5 Parallel System Turn On Procedure

  1. Make sure to follow sections 3.6.1 to 3.6.4 correctly.
  2. Confirm the input breaker and output breakers of each UPS have been turned "ON".
  3. Turn ON the battery breaker.
  4. Turn ON the external AC source breaker to apply AC input source to both UPS systems.
  5. Watch for abnormal event messages on the LCD display (refer to section 4.2.7 Event Screen for more information).
  6. Switch ON the UPS by pressing the power button on the UPS front panel or through the control page on the LCD panel (refer to section 4.2.3 Control Screen for more information).

3.7 Dual AC Input Installation

Dual AC Input UPS (or suffix "KXD") models are defaulted to a Single AC Input configuration via the placement of three shorting jumpers between AC Input 1 and AC Input 2. If you desire to operate the "KXD" models in a dual AC configuration, remove these three jumpers, and wire AC input 1 and AC Input 2 accordingly.

Technical line drawing of an electrical control cabinet with internal wiring and mounting hardware (no text or labels)

Jumpers on "KXD" dual-AC input models.

4. Control Panel and LCD Operations

4.1 Control Panel Description

The control panel and display screen are located on the UPS front panel. This interface monitors all measured parameters, UPS status, battery status and alarms. The control interface is divided into four sections: (1) LCD panel, (2) LED indicators, (3) Power Button and (4) Audible Alarm. Refer to Figure 4.1.

graph TD A["1"] --> B["BYPASS"] B --> C["INV"] C --> D["LOAD"] D --> E["BATT"] E --> F["FAULT"] E --> G["ALARM"] H["3"] --> I["POWER"]

1 LCD Panel: Graphic display and all measured parameters.
2 LED Indicators: Refer to Table 4.1.
3 Power Button: Refer to Table 4.2.
4 Audible Alarm: Refer to Table 4.3.

Table 4.1: LED Indicators

LED Colour Status Definition
LINE GreenOn Input source is normal.
Flashing Input source is abnormal.
Off No input source
BYPASS YellowOn Load on Bypass.
Flashing Input source is abnormal.
Off Bypass not operating.
LOAD GreenOn There is power output for the load.
Off There is no power output for the load.
INV GreenOn Load on inverters.
Off Inverters not operating (unless in ECO Mode).
BATTERY RedOn Load on Battery.
Flashing Low battery
Off Battery converter is normal and battery is charging.
FAULT/ALARM RedOn UPS fault.
Flashing UPS alarm.
Off Normal.

Table 4.2: Power Button

Control KeyDescription
Power On/OffTurn on UPS or Turn off UPS (hold 2 seconds).

Table 4.3: Audible Alarm

UPS ConditionDescription
Power On/OffBuzzer sounds every 2 seconds.
Bypass ModeBuzzer sounds once every minute.
Battery ModeBuzzer sounds every 2 seconds.
Low BatteryBuzzer sounds every 0.5 seconds.
UPS AlarmBuzzer sounds every 1 second.
UPS FaultBuzzer sounds continuously.

4. Control Panel and LCD Operations

4.2 LCD Screen Description

4.2.1 Initial Screen

Upon powering on, the UPS will execute POST (Power-On Self-Test). The initial screen (shown below) will display for approximately 5 seconds.

Online UPS

Figure 4.2 Initial Screen

4.2.2 Main Screen

After initialization, the main screen will display.

graph TD A["1 SYSTEM ON Line Model"] --> B["2"] B --> C["3 AC/DC"] C --> D["4 KVA"] D --> E["5 LOAD"] E --> F["6 85%"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333 style E fill:#cff,stroke:#333 style F fill:#ffc,stroke:#333

Figure 4.3 Main Screen

The Main Screen is divided into six sections:

1 UPS Operation Mode: Shows UPS current operation mode and status.
2 UPS Flow Chart: Shows current flow chart and measurement data.
3 Main Menu: Touch each icon to enter submenu. Refer to Figure 4.4 for menu tree.

graph TD A["Main"] --> B["HOME CONTROL"] A --> C["MEASUREMENT SETUP"] A --> D["INFORMATION EVENTS"] A --> E["SETUP"] A --> F["INFORMATION"] A --> G["EVENT"]

Figure 4.4 Menu Tree

4 UPS Power Rating: Shows UPS power rating.
5 Date and Time: Shows current date and time.

4. Control Panel and LCD Operations

6 UPS Status: The descriptions of each icon and its status are listed as:

Icon UPS StatusLED Status
Tripp Lite S3M160KXD - Control Panel and LCD Operations - 1UPS operating in Standby Mode or Shutdown Mode. LOAD – Off
Tripp Lite S3M160KXD - Control Panel and LCD Operations - 2UPS operating in Line Mode or Converter Mode. LINE, INV and LOAD – On
Tripp Lite S3M160KXD - Control Panel and LCD Operations - 3UPS operating in Bypass Mode or ECO Mode. LINE, BYPASS and LOAD – On
Tripp Lite S3M160KXD - Control Panel and LCD Operations - 4UPS operating in Battery Mode or Battery Test Mode. BATT, INV and LOAD – On
Tripp Lite S3M160KXD - Control Panel and LCD Operations - 5UPS operating in Fault Mode. FAULT – On or Flashing (Alarm)

4.2.3 Control Screen

Touch to enter into the submenu (as shown in Figures 4.5 and 4.6).

graph TD A["CONTROL Yes or No"] --> B["System Turn On"] A --> C["System Turn Off"] A --> D["Manual Battery Test"] A --> E["Cancel Battery Test"] A --> F["Turn to Bypass"] A --> G["Shutdown Restore"] A --> H["Cancel Shutdown"] A --> I["Charger Turn On"] A --> J["Charger Turn Off"] B --> K["End"] C --…

Figure 4.5 Control Screen

SYSTEM ON Standby Mode System Turn On System Turn Off Manual Battery Test Cancel Battery Test Turn To Bypass Shutdown Restore Cancel Shutdown Charger Turn On Charger Turn Off L1 0% 0% 0% 0% HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 15:30 2018/01/01

Figure 4.6 Control Menu

4. Control Panel and LCD Operations

Touch any option directly. The confirmation screen will pop up. Touch Yes to confirm command or No to cancel command.

SYSTEM ON Standby Mode System Turn On System Turn Off Manual Battery Test Cancel Battery Test Turn To Bypass Shutdown Restore Cancel Shutdown Charger Turn On Charger Turn Off ESC Yes No 15:30 2018/01/01

Figure 4.7 Confirmation Screen

4.2.4. Measurement Screen

Touch to enter into the Measurement submenu. You may choose Input, Output, Bypass, Load or Battery to monitor each detailed status. Refer to Figures 4.8 and 4.9.

graph TD A["MEASUREMENT"] --> B["Input"] A --> C["Output"] A --> D["Bypass"] A --> E["Load"] A --> F["Battery"]

Figure 4.8 Measurement Menu

4. Control Panel and LCD Operations

SYSTEM ON Standby Mode L1 L2 L3 VOL 1Hz 230.0V VOL 1Hz 230.0V VOL 1Hz 230.0V FRESQUENCY 50.0Hz FRESQUENCY 50.0Hz FRESQUENCY 50.0Hz INPUT OUTPUT BYPASS LOAD BATTERY HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 12:00 2018/01/01

SYSTEM ON Standby Mode L1 L2 L3 VOLTAGE 230.0V VOLTAGE 230.0V VOLTAGE 230.0V CURRENT 10.0A CURRENT 10.0A CURRENT 10.0A FREQUENCY 50.0Hz FREQUENCY 50.0Hz FREQUENCY 50.0Hz POWER FACTORY 0.99 POWER FACTORY 0.99 POWER FACTORY 0.99 INPUT OUTPUT BYPASS LOAD BATTERY HOME CONTROL MEASUREMENT SERIES INFORMAT…

SYSTEM ON Standby Mode L1 L2 L3 0% VOLTAGE 230.0V VOLTAGE 230.0V VOLTAGE 230.0V CURRENT 10.0A CURRENT 10.0A CURRENT 10.0A POWER FACTORY 0.99 POWER FACTORY 0.99 POWER FACTORY 0.99 INPUT OUTPUT EV/ASS LOAD BATTERY HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 12:00 2018/01/01

SYSTEM ON Standby Mode L1 L2 L3 0% LOAD 0% LOAD 0% LOAD 0% S OUT OKVA S OUT OKVA S OUT OKVA P OUT OKW P OUT OKW P OUT OKW INPUT OUTPUT BYPASS LOAD BATTERY HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 12:00 2018/01/01

POSTIVE NEFATIVE CAPACITY SYSTEM ON Standby Mode 0% VOLTAGE 216.0V VOLTAGE 216.0V REMAIN TIME 1Min CURRENT 10.0A CURRENT 10.0A TEST RESULT Passed TEMPERATURE 01 35.0C TEMPERATURE 02 37.0C CHARGING STATUS Float TEMPERATURE 03 34.0C TEMPERATURE 04 38.0C TEMPERATURE 05 34.0C INPUT OUTPUT BYPASS LOAD BA…

Figure 4.9 Measurement Screens: INPUT, OUTPUT, BYPASS, LOAD, and BATTERY

4. Control Panel and LCD Operations

Table 4.4: Measurement Items

Submenu ItemExplanation
InputL-N Voltage (V) Input phase voltage (L1, L2, L3). Units: 0.1V.
Frequency (Hz) Input frequency (L1, L2, L3). Units: 0.1 Hz.
OutputL-N Voltage (V) Output phase voltage (L1, L2, L3). Units: 0.1V.
L-N Current (A) Output phase current (L1, L2, L3). Units: 0.1A.*
Frequency (Hz) Output frequency (L1, L2, L3). Units: 0.1 Hz.
Power Factor Output power factor (L1, L2, L3).
BypassL-N Voltage (V) Bypass phase voltage (L1, L2, L3). Units: 0.1V.
Frequency (Hz) Bypass frequency (L1, L2, L3). Units: 0.1 Hz.
Power Factor Bypass power factor (L1, L2, L3).
LoadSout (kVA) Apparent power. Units: 0.1kVA.
Pout (kW) Active power. Units: 0.1kW.
Load Level (%) The percentage of connected load. Units: 1%.
BatteryPositive Voltage (V) Battery positive voltage. Units: 0.1V.
Negative Voltage (V) Battery negative voltage. Units: 0.1V.
Positive Current (A) Battery positive current. Units: 0.1A.
Negative Current (A) Battery negative current. Units: 0.1A.
Remain Time (Sec) Battery remaining runtime. Units: 1 sec.
Capacity (%)The percentage of the battery capacity. Units: 1%.
Test ResultBattery test result.
Charging StatusBattery charging status.
Temperature 01(°C)Temperature of external battery pack. Units: 0.1°C.
Temperature 02(°C)Temperature of external battery pack through extra communication card T1. Units: 0.1°C.
Temperature 03(°C)Temperature of external battery pack through extra communication card T2. Units: 0.1°C.
Temperature 04(°C)Temperature of external battery pack through extra communication card T3. Units: 0.1°C.
Temperature 05(°C)Temperature of external battery pack through extra communication card T4. Units: 0.1°C.

* Output current at zero load or low load may indicate up to 1% current flow on the display due to inverter activity. For load power readings, go to the LOAD submenu on the display.

4.2.5. Setup Screen

Touch the 📄 to enter into the Setup submenu. It requires a password to access the General, SYSTEM, BATTERY and PRE-ALARM submenus (as shown in Figures 4.10 and 4.11). The default password is 0000.

graph TD A["SETUP"] --> B["Enter Password"] B --> C["GENERAL"] B --> D["SYSTEM"] B --> E["BATTERY"] B --> F["PRE-ALARM"] B --> G["PARALLEL"]

Figure 4.10 Setup Menu

4. Control Panel and LCD Operations

Touch the grey column to access the numerical keyboard. Enter a 4-digit password and press to enter the SETUP submenu. If an incorrect password is entered, you may retry.

CAUTION! PLEASE ENTER PASSWORDS SYSTEM ON Standby Mode 1 0% 1.2 0% 1.3 0% 15:30 2018/01/01 HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT SYSTEM ON Standby Mode 1 2 3 4 5 6 7 8 9 0 0% 0% 0% 0% 15:30 2018/01/01

CAUTION! WRONG NUMBER,PLEASE ENTER AGAIN! SYSTEM ON Standby Mode 0% 0% 0% 0% HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 15:30 2018/01/01

Figure 4.11 Enter Password Screens

There are two levels of password protection: user password and administrator password.

The default user password is 0000. It may be changed by the user.

The administrator password is owned by trained service personnel.

Different password levels can access different settings. The setting can be changed in various operation modes. Refer to Table 4.5 for details.

4. Control Panel and LCD Operations

Table 4.5: All Setting Items in Setup Menu

Setting item\Mode\UPS OperationStandby ModeBypass ModeLine ModeBattery ModeBattery Test ModeFault ModeConverter ModeECO ModeAuthorisation
UserMaintainer/Administrator
GeneralModel Name*YYYYYYYY
Language**YYYYYYYY
TIMEYYYYYYYY
Change PasswordYYYYYYYY
Baud RateYYYYYYYY
Audible AlarmYYYYYYYY
Factory Reset Y Y
EEPROM Reset Y Y
EPO Function Y Y
Save SettingYYYY
Startup ScreenYYYYYYYYY
SystemOutput VoltageYYY
Bypass Voltage RangeYYYYYYYYY
Bypass Frequency RangeYYY
Converter ModeYY
ECO Mode Y YYY
Bypass Mode Y YY
Auto-RestartYYYYYYYYY
Cold StartYYYYYYYYY
Battery Mode Delay TimeYYYYYY
System Shutdown TimeYYYYYYYYY
System Restore TimeYYYYYYYYY
Charger TestYYYYY
RedundancyYYYYYYYYY
BatteryBattery Capacity in AhYYYYYY
Maximum Charging CurrentYYY
Battery Low/Shutdown SettingYYYYYY
Periodic Battery TestYYYYYYYYY
Battery Test IntervalYYYYYYYYY
Stop by TimeYYYYYY
Stop by Battery VoltageYYYYYY
Stop by Battery CapacityYYYYYY
Battery Age AlertYYYYYYYYY
Temperature CompensationYYYYYYYYY
Charging VoltageYYY
Auto-Restart Battery VoltageYYYYYYYYY
Pre-AlarmLine Voltage RangeYYYYYYYYY
Line Frequency RangeYYYYYYYYY
Load YYYYYYYYYY
ParallelUPS ParallelYYY
Independent BatteryYYY

"Y" indicates available options exist in each given mode.
* Model names can be customised.
** English only.

4. Control Panel and LCD Operations

Setup Procedure

Step 1: Choose between GENERAL, SYSTEM, BATTERY and PRE-ALARM.

Step 2: Each item will show its current value and alternative settings.

Step 3: Choose -to confirm the change or to cancel any modifications.

GENERAL SYSTEM RATIPO PRE-ALARM PARALLEL SYSTEM ON Standby Mode Model Name SIRI200KX Language English Time 2015/10/22 15:30 Read Rate Port0:2400 Port1:2400 Audible Alarm Enable Factory Reset EEPROM Reset EPI Function Signal OPEN Action Password Save Setting Startup Screen Online OPs Screen Saving En…

Figure 4.12 Setting Procedure

4.2.5.1 Setup-General Screen

The Setup-General screen and setting list options are shown in Figure 4.13 and Table 4.6.

GENERAL SYSTEM BATTERY PRE-ALARM PARALLEL MODEL Name S3M200KX Language English Time 2015/10/22 15:30 Band Rate Port10:2400 Port1:2400 Audible Alarm Enable Factory Reset EEPROM Reset EPO Function Normal OPEN Action Password Save Setting Startup Screen Online UPS Screen Saving Enable SYSTEM ON Standby…

Figure 4.13 Setup-General Screen

4. Control Panel and LCD Operations

Table 4.6: Setup-General Setting List

Setting Item Sub Item Explanation
Model Name --Set UPS Name (xxxxxxxxx).The max. length is 10 characters.
Language -- English only
TIMEAdjust TimeSet current date and time.(yyyy / mm / dd hour : min : sec)MUST be set after UPS installation
System Installed DateSet system installed date(yyyy / mm / dd)2018/1/1 (Default)MUST be set after UPS installation
System Last Maintain DateSet system latest maintenance date(yyyy / mm / dd)MUST be set after UPS installationMaintainer/Administrator Only
Battery Installed DateSet battery installed date(yyyy / mm / dd)MUST be set after UPS installation
Battery Last Maintain DateSet battery latest maintenance date(yyyy / mm / dd)MUST be set after UPS installation
Baud Rate --Set SNMP Port (COM Port0) Baud Rate• 2400 (Default)• 4800• 9600Set RS-232 Port (COM Port1) Baud Rate• 2400 (Default)• 4800• 9600
Audible Alarm --Set Audible Alarm• Disable• Enable (Default)
Factory Reset --Restore to factory default settingRefer to Table 4.7
EEPROM Reset --Restore EEPROM to default settingRefer to Table 4.7
EPO Function --Set EPO active status• Normal Close Active (Default)• Normal Open Active
Password --Set New Password.0000 (Default)
Save Setting --Save all settings to EEPROM.Use this feature to save the changed setting(s). Must be performed when any changes are made to the settings.
Startup Screen --Set up initial screen. (xxxxxxxxx).The max. length is 12 characters.

4. Control Panel and LCD Operations

Table 4.7: EEPROM Reset Category List

Setting Item Factory Reset EEPROM Reset
GeneralModel Name
Language Y Y
Adjust Time
System Installed Date Y
System Last Maintain Date Y
Battery Installed Date Y
Battery Last Maintain Date Y
Change Password Y
Baud Rate Y
Audible Alarm Y Y
Factory Reset
EEPROM Reset
EPO Function Y
Save Setting
Startup Screen
SystemOutput Voltage Y
Bypass Voltage Range Y Y
Bypass Frequency RangeY Y
Converter ModeY Y
ECO ModeY Y
Bypass ModeY Y
Auto-RestartY Y
Cold StartY
Battery Mode Delay TimeY Y
System Shutdown TimeY Y
System Restore TimeY Y
Charger Test
BatteryBattery Capacity in Ah Y Y
Maximum Charging CurrentY Y
Battery Low/Shutdown SettingY Y
Periodic Battery TestY Y
Battery Test IntervalY Y
Stop by TimeY Y
Stop by Battery VoltageY Y
Stop by Battery CapacityY Y
Battery Age AlertY Y
Temperature CompensationY Y
Charging VoltageY Y
Auto-Restart Battery VoltageY Y
Pre-AlarmY

4. Control Panel and LCD Operations

The Setup-System Screen and setting options are shown in Figure 4.14 and Table 4.8. System Setting can only be accessed when the UPS is operated in a specific mode (refer to Table 4.5 for the details). If an option is not available under a specific mode, a warning screen will appear (Figure 4.15).

GENERAL SYSTEM BATTERY PRE-ALARM PARALLEL SYSTEM ON Standby Mode Output Voltage — 230.0V Bypass Setting — Voltage:-10% ~+10% Frequency:-Hz ~+Hz Converter Mode — Disable ECO Mode — Disable Bypass Mode — Disable Auto-Restart — Disable Cold Start — Disable Battery Mode Delay Time — 0(Sec) Shutdown/Rest…

Figure 4.14 Setup-System Screen Figure 4.15 Warning Screen

SYSTEM-ON This mode cannot be set up! This mode can LSC

Table 4.8: Setup-System Setting List

Setting Item Sub Item Explanation
Output Voltage(Line ->N)--Set output voltage• 220V AC (Default)• 230V AC• 240V ACMUST be reviewed after UPS installation
BYPASS SETTINGBypass Voltage RangeSet bypass voltage range:Upper limit• +10%• +15% (Default)• +20%Lower limit• -10%• -20% (Default)• -30%
Bypass Frequency RangeSet bypass Frequency range:Upper/ Lower limit• +/- 1 Hz• +/- 2 Hz• +/- 4 Hz (Default)
Converter Mode --Set Converter Mode• Disable (Default)• Enable
ECO Mode --Set ECO Mode• Disable (Default)• Enable
Bypass Mode --Set Bypass Mode• Disable• Enable (Default, MUST be in Bypass Mode to disable)MUST be reviewed after UPS installation.If you need the Bypass power when UPS is OFF, please enable it.
Auto-Restart --Set auto-restart• Disable• Enable (Default)When “Enable” is set and a UPS shutdown occurs due to low battery, the UPS will return to Line Mode once the utility power is restored.
Redundancy --Set redundancy• Redundancy: the QTY of unitMUST be set after UPS parallel enable

4. Control Panel and LCD Operations

Setting Item Sub Item Explanation
Cold Start --Set cold startDisableEnable (Default)After “Enable” is set, the UPS can be turned on without connecting to utility by pressing Battery Start Button. Refer to cold start operation for the details (refer to 7.2 Cold Startup).
Battery Mode Delay Time--Set system shutdown delay time in Battery Mode (0~9990 sec).0: Disable (Default)Not 0: EnableWhen this feature is enabled, UPS will shut off output after UPS operates in Battery Mode for the set number of seconds.
Shutdown/RestoreSystem Shutdown TimeSet system shutdown time (0.2~99 min.)0.2 min. (Default)This delay time will start counting when the CONTROL-Shutdown Restore command is executed.
System Restore TimeSet system restore time (0~9999 min.)1 min. (Default)This delay time will start counting after shutdown time is elapsed when the CONTROL-Shutdown Restore command is executed.
Charger Test --Set charger testDisable (Default)Enable

4.2.5.3 Setup-Battery Screen

The Setup-Battery Screen and Setting options are shown in Figure 4.16 and Table 4.9. Battery Setting can only be set when UPS is operated in Standby Mode.

graph TD A["GENERAL"] --> B["BATT Capacity in Ab"] C["SYSTEM"] --> D["MAX Charging Current"] E["BATTERY"] --> F["BATT Low/Shutdown"] G["PRE-ALARM"] --> H["Shutdown Voltage"] I["PARALLEL"] --> J["LOW Voltage"] K["0%"] --> L["0 (nV/C/c)"] M["10%"] --> N["Low Capacity"] O["30%"] --> P["Shutdown Voltage…

Figure 4.16 Setup-Battery Screen

4. Control Panel and LCD Operations

Table 4.9: Setup-Battery Setting List

Setting Item Sub Item Explanation
Battery Capacity in Ah--Set battery capacity. (up to 999)• 9Ah (Default)MUST be set after UPS installation or battery capacity is changed.
Maximum Charging CurrentRecommended to Use 10% Battery Amp-Hour RatingSet battery maximum charging current. (1~24A 100KVA/1~32A 120KVA/1~40A 160KVA/1~48A 200KVA)• 2A (Default), may be increased via the displayMUST be set after UPS installation or battery capacity is changed.
Battery Low/ Shutdown SettingLow VoltageSet battery low voltage. (10 ~11.5V) x (Battery Number)• 11V x Battery Number (Default)
Low CapacitySet battery low capacity. (20~50%)• 20% (Default)
Shutdown Voltage (LVC)Set battery voltage point for system shutdown in Battery Mode. (10.0V) x (Battery Number)• 10V x Battery Number (Default)
Battery Test PeriodicBattery TestSet periodic battery test disable or enable.• Disable (Default)• Enable
Battery Test IntervalSet battery test interval. (7~99 Days)• 30 Days (Default)
Stop by TimeSet testing time for battery test. (10~1000 Seconds)• 10 sec (Default)
Stop by Battery VoltageSet stop battery voltage in battery test. (11~12V) x (Battery Number)• 11V x Battery Number (Default)
Stop by Battery CapacitySet battery capacity to stop battery testing. (20~50%)• 20% (Default)
Battery Age Alert Battery Age Alert (Months)Set battery age for replacement. (Disable, 12~60 Months)• Disable (Default)If this feature is enabled and the battery has been installed over this period, there is a “Battery Age Alert” warning to indicate it.
Temperature Compensation--Set battery temperature compensation.• When Enabled, 3(mV/C/cell)
Charging Voltage --Set battery charging voltage. (2.30~2.35V)• 14.1V/Battery, 2.35V/Cell (Default)Set battery float voltage. (2.23~2.35V)• 13.65V/Battery, 2.27V/Cell (Default)
Auto-Restart Battery Voltage--Set auto-restart battery voltage. (0 or 12.0V~13.0V)• 0V (Default)

4. Control Panel and LCD Operations

4.2.5.4 Pre-Alarm Screen

The Pre-Alarm Screen Setup and Setting options are shown in Figure 4.17 and Table 4.10. The Pre-Alarm Setting can be accessed in any operation mode.

GENERAL SYSTEM BATTERY PRE-ALARM PARALLEL LINE Voltage Range -20% -20% Line Frequency Range -1Hz +1Hz Loss Overload 100% Load Unbalance 100% SYSTEM ON Standby Mode L1 0% L2 0% L3 0% HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 15:30 2018/01/01

Figure 4.17 Setup-Pre-Alarm Screen

Table 4.10: Setup Pre-Alarm Setting List

Setting Item Sub Item Explanation
Line Voltage Range --Set line voltage range:Upper limit+5%+10%+15%+20% (Default)Lower limit-5%-10%-15%-20% (Default)
Line Frequency Range--Set line frequency range:Upper / Lower limit+/- 1 Hz+/- 2 Hz+/- 3 Hz+/- 4 Hz (Default)
Load --Set UPS overload percentage (40~100%)100% (Default)Set UPS load unbalance percentage (20~100%)100% (Default)

4. Control Panel and LCD Operations

4.2.5.5 Setup Parallel Screen

Touch the "PARALLEL" tab to access the parallel function page. Refer to Table 4.11 for Setup Parallel Setting List.

GENERAL SYSTEM BATTERY PRE-ALARM PARALLEL SYSTEM ON Standby Mode UPS Parallel —— Disable Independent Battery —— Disable L1 0% L2 0% L3 0% HOME CONTROL MEASUREMENT SETUP INFORMATION EVENT 15:30 2018/01/01

Figure 4.18 Setup Parallel Screen

Touch the "SYSTEM" tab to access the parallel or redundancy options.

(a) Paralleling two S3MX units for power. (b) Paralleling two S3MX units for redundancy, where each UPS is carrying 50% of the load. If one UPS goes down, the other will take over the full load.

GENERAL SYSTEM BATTERY PRE-RLAM PARALLEL SYSTEM ON Standby Mode Output Voltage Dynamos Setting Converter Mode ECF Mode Dynamos Mode Auto-Restars Cold Start Battery Mode Delay Time Shutdown/Restore Charger Test Redundancy Total UPS 2 0 Redundancy ESC HOME CONTROL REQUIREMENT SBUF INFORMATION EVENT 12…

Figure 4.19 Parallel Two Units Figure 4.20 Redundancy Across Two Units

GENERAL SYSTEM BATTERY PRE-ALARM PARALLEL SYSTEM ON Standby Mode Output Voltage Bypass Setting Converter Mode ECO Mode Bypass Mode Auto-Restart Cold Start Battery Mode Delay Time Shutdown/Restore Charger Test Refurbency Total UPS 2 1 Refrumbency ESC NONE CONTROL MEASUREMENT SUPPORT INFORMATION EVENT…

Table 4.11: Setup Parallel Setting List

Setting Item Sub Item Explanation
UPS Parallel --Set UPS ParallelDisable (Default)Enable
Independent Battery --Set Independent BatteryDisable (Default)Enable

4. Control Panel and LCD Operations

4.2.6 Information Screen

Touch 📋 to enter the submenu. In this screen, you can check the UPS configurations. There are three submenus: Identification, System and Battery.

graph TD A["INFORMATION"] --> B["Identification"] A --> C["System"] A --> D["Battery"]

Figure 4.21 Information Menu

4.2.6.1 INFORMATION - Identification Screen

When the Identification submenu is selected, the Model Name, Serial No. and Firmware Version will display. Use the UP and DOWN arrows to switch between pages.

IDENTIFICATION SYSTEM BATTERY Model Name XXXXXXXXXX Serial No. XXXXXXXXXXXXXXX Display#50 Firmware Version (XX) XX.XX STS#50 Firmware Version XX.XX STS#— Firmware Version XX.XX Module#00 DSP Firmware Version XX.XX Module#00 MCU Firmware Version XX.XX Module#00 Serial No. XXXXXXXXXXXXXXX SYSTEM ON St…

Figure 4.22 Identification Screen Page

4.2.6.2 INFORMATION - System Screen

When the System submenu is selected, information such as the system power, nominal voltage, nominal frequency, etc. will display. Use the UP and DOWN arrows to switch between pages.

IDENTIFICATION SYSTEM BATTERY Nominal Power (KVA) XXX Nominal AC Voltage (V) 230.0 Nominal Frequency (Hz) 50.0 Number of UPS 1 Number of UPS for Redundancy 0 System Installed Date 2018/01/01 System Last Maintain Date 2018/01/01 ECO Mode Disable Converter Mode Disable Battery Mode Shutdown Delay Disa…

IDENTIFICATION SYSTEM BATTERY Auto-Restart Enable Power by Bypass Disable Cold Start Disable Language English COM Port0 Baud Rate 2400 COM Port1 Baud Rate 2400 UPS Parallel Disable Independent Battery Disable Screen Saving Disable SYSTEM ON Standby Mode 0% 0% 0% PAGE» 2 HOME CONTROL MEASUREMENT SCUL…

Figure 4.23 INFORMATION System Screen Page 1 Figure 4.24 INFORMATION System Screen Page 2

4. Control Panel and LCD Operations

4.2.6.3. INFORMATION - Battery Screen

When the Battery submenu is selected, information such as battery, capacity, charging current, etc., will display.

IDENTIFACATION SYSTEM BATTERY Battery Capacity in Ah(Ah) 9 Maximum Charging Current(A) 2 Battery Low Voltage(V) 10.5 Battery Low Capacity(%) 30 Battery Shutdown Voltage(V) 11.0 Periodic Battery Test Disable Battery Installed Date 2015/01/01 Battery Last Maintain Date 2015/01/01 Charging Voltage(V) 2…

Figure 4.25 INFORMATION Battery Screen Page

4.2.7 Event Screen

When an event occurs, ⚠️ will flash on the main screen. You also can touch 📋 to check the latest events and history. Refer to Figure 4.27 for the menu tree.

System ON diagram showing standby mode with STS, AC/DC, and DC/AC components, including voltage levels and 85% battery connection.

Figure 4.26 Alarm Warning Screen

graph TD A["EVENTS"] --> B["Current Events"] A --> C["History Events"] A --> D["Reset All Events"]

Figure 4.27 Events Menu

4. Control Panel and LCD Operations

4.2.7.1 Current Events

When an event occurs, it will display the power stage ID* and alarm code on the Current Events screen. Up to 50 events can be saved, though only 10 events are listed per page. If more than 10 events are exceeded, touch PAGE>> to scroll to other events on the list.

Note: Refer to section 3.2 Open Front Panel to identify power stage ID.

CURRENT EVENT HISTORY EVENT RESET ALL EVENTS 1. Warning! EEPROM Fail #08 2. Warning! Communicate CAN Fail #00 3. Warning! Battery Open #00 4. Warning! Battery Open #01 5. Warning! Module Un-Lock #00 6. Warning! Module Un-Lock #01 7. 8. 9. 10. SYSTEM ON Standby Mode ! L1 0% L2 0% L3 0% PAGE>> 1 HOME…

Figure 4.28 Current Events Screen

4.2.7.2 History Events

Detailed event information is saved in HISTORY EVENT. Up to 500 events can be saved. When a warning occurs, it will display the alarm code, alarm time and power stage ID (refer to section 3.2 Open Front Panel to identify power stage ID). When a fault event occurs, it will display the alarm description, alarm time and power stage ID (refer to Table 4.12). In order to record more historical information about the UPS system, the important changes in setting (Table 4.13), UPS operation mode changes (Table 4.14) and control action execution (Table 4.15) will be saved in HISTORY EVENT. Refer to Figure 4.29 for details.

CURRENT EVENT HISTORY EVENT RESET ALL EVENTS 1. Warning! EEPROM Fail #08 2015/10/21 10:47:58 2. Warning! Communicate CAN Fail #00 2015/10/21 10:47:58 3. Warning! Battery Open #00 2015/10/21 10:47:50 4. Warning! Battery Open #01 2015/10/21 10:47:50 5. Warning! Module Un-Lock #00 2015/10/21 10:42:11 6…

Figure 4.29 History Events Screen

4. Control Panel and LCD Operations

4.3 Alarm List

Table 4.12 provides the complete list of UPS alarm messages.

Messages in the LCD Explanation
Fault! Bus Over Voltage DC bus voltage is too high.
Fault! Bus Under Voltage DC bus voltage is too low.
Fault! Bus Voltage Unbalance DC bus voltage is not balanced.
Fault! Bus Short DC bus is short.
Fault! Bus Soft Start Time Out The rectifiers cannot start due to low DC bus voltage within specified duration.
Fault! Inverter Soft Start Time Out Inverter bus voltage cannot reach desired voltage within specified duration.
Fault! Inverter Voltage Over Inverter Voltage is over Peak Value.
Fault! Inverter Voltage High Inverter Voltage is too high.
Fault! Inverter Voltage Low Inverter Voltage is too low.
Fault! R Inverter Voltage Short R phase inverter Output is short-circuited.
Fault! S Inverter Voltage Short S phase inverter Output is short-circuited.
Fault! T Inverter Voltage Short T phase inverter Output is short-circuited.
Fault! RS Inverter Voltage Short R-S inverter Output is short-circuited.
Fault! ST Inverter Voltage Short S-T inverter Output is short-circuited.
Fault! TR Inverter Voltage Short T-R inverter Output is short-circuited.
Fault! Inverter R Negative Power R phase inverter Output Negative Power over range.
Fault! Inverter S Negative Power S phase inverter Output Negative Power over range.
Fault! Inverter T Negative PowerT phase inverter Output Negative Power over range.
Fault! Over Load FaultHeavy overload causes UPS fault.
Fault! Battery FaultBatteries reversed.
Fault! Over TemperatureMake sure adequate space is allowed for air ventilation and that the fan is working.
Fault! CAN FaultCAN communication fault.
Fault! TRIGO FaultSynchronised trigger signal fault.
Fault! Relay FaultInverter relay fault.
Fault! Line SCR FailLine SCR short circuit fault.
Fault! EEPROM FaultEEPROM operation error.
Fault! Parallel Cable Loose FaultAs stated.
Fault! DSP MCU Stop CommunicateAs stated.
Fault! Bypass Temperature FaultAs stated
Fault! Bypass SCR FaultAs stated.
Line FailUtility lost or abnormal.
Line RestoreUtility recovered to normal.
Warning! EPO ActiveCheck the EPO connector.
Warning! Over Load FailThe load devices are demanding more power than the UPS can supply. Line Mode will transfer to Bypass Mode.
Warning! Communicate CAN FailCAN communication error.
Warning! Over LoadWhen in Line Mode, the load devices are demanding more power than the UPS can supply.
Warning! Battery OpenBattery not connected.
Warning! Battery voltage HighBattery voltage is too high.
Warning! Turn On AbnormalAs stated.
Warning! Charge FailAs stated.
Warning! EEPROM FailEEPROM operation error.
Warning! Fan LockAs stated.
Warning! Line Phase ErrorAs stated.
Warning! Bypass Phase ErrorAs stated.
Warning! N Loss Neutral loss.
Warning! Internal Initial FailAs stated.
Warning! Comm Syn Signal FailCommunicate Synchronization Signal Fail.
Warning! Comm. TRIGO FailCommunicate Trigger signal fault.
Warning! Power Stage lossPower stage is not detected.
Warning! Parallel Sys Config. WrongParallel System Configure error.
Warning! Maintenance BypassEnter maintenance.
Warning! Battery Age AlertBattery Life expiration.
Warning! Parallel UPS Cable LooseAs stated.

4. Control Panel and LCD Operations

Messages in the LCD Explanation
Warning! Parallel UPS Config. WrongParallel UPS Configure error.
Warning! Battery Voltage Low Batteryvoltage is too low.
Warning! ID Conflict Power stage ID inconflict.
Warning! Redundancy Set Fail As stated.
Pre-Alarm! Line Voltage Fail Line voltage over range.
Pre-Alarm! Line Voltage Normal Line voltage recovered to normal.
Pre-Alarm! Line Frequency Unstable Line frequency over range.
Pre-Alarm! Line Frequency Normal Line frequency recovered to normal.
Pre-Alarm! Over Load Output Load over range.
Pre-Alarm! Load Normal Output Load recovered to normal.
Pre-Alarm! Load Unbalance Output Load unbalance.

4.4 History Record

Table 4.13: Warning List For Changing Important Settings

Item No.DescriptionItem No.Description
1Setup! Model Name2Setup! Turn On Password
3Setup! Language4Setup! Change Turn On Password
5Setup! Adjust Time6Setup! Nominal Power Display
7Setup! System Installed Date8Setup! Output Voltage
9Setup! System Last Maintain Date10Setup! Bypass Voltage Range
11Setup! Battery Installed Date12Setup! Bypass Frequency Range
13Setup! Battery Last Maintain Date14Setup! Converter Mode
15Setup! Change Password16Setup! ECO Mode
17Setup! Baud Rate18Setup! Bypass Mode
19Setup! Audible Alarm20Setup! Auto-Restart
21Setup! Factory Reset22Setup! Cold Start
23Setup! EEPROM Reset24Setup! Battery Mode Delay Time
25Setup! EPO Function26Setup! Shutdown Restore Time
27Setup! Save Setting28Setup! Redundancy
29Setup! Power Rating Setting30Setup! Charger Test
31Setup! Nominal Battery Voltage32Setup! Battery Capacity in Ah
33Setup! Maximum Charging Current34Setup! Battery Low Voltage
35Setup! Battery Low Capacity36Setup! Battery Shutdown Voltage
37Setup! Periodic Battery Test38Setup! Stop By Time
39Setup! BATTERY Age Alert40Setup! Temperature Compensation
41Setup! Charging Voltage42Setup! PRE-ALARM
43Setup! UPS Parallel44Setup! Independent Battery
45Setup! Auto-Restart Battery Voltage

Table 4.14: UPS Mode Changes

Item No.DescriptionItem No.Description
1UPS Mode! Power On Mode2UPS Mode! Standby Mode
3UPS Mode! Bypass Mode4UPS Mode! Line Mode
5UPS Mode! Battery Mode6UPS Mode! Battery Test Mode
7UPS Mode! Fault Mode8UPS Mode! Converter Mode
9UPS Mode! ECO Mode10UPS Mode! Shutdown Mode
11UPS Mode! Un-Connection

Table 4.15: Control Action Execution

Item No.DescriptionItem No.Description
1Control! System Turn On2Control! System Turn Off
3Control! Manual Battery Test4Control! Cancel Battery Test
5Control! Turn To Bypass6Control! Shutdown Restore
7Control! Cancel Shutdown8Control! Charger Turn On
9Control! Charger Turn Off

5. Interface and Communication

The front panel contains a Battery Temperature sensor port, two Emergency Power Off Ports, a communication port (RS-232/USB), SNMP card slot and an extra communication card slot.

X1 X2 SNMP Card Slot RS 232 Port USB Port

Figure 5.1 Dry Contact Ports and Communication Ports

Dry Contact No. Function
X1 Battery Temperature Detection Thermostat Port
X2 Remote EPO Input Port

5.1. X1 - Temperature Detection Port for External Battery Pack

The UPS is equipped with a battery temperature detection function. The UPS can receive a battery temperature signal through the temperature detection thermostat board. Communication between the UPS and battery temperature detection thermostat board is via I2C communication protocol. X1 is the battery temperature detection port. The port is shown in Figure 5.2 and described in Table 5.1.

SCL SDA +3V X1 X1.1 X1.2 X1.3 X1.4

Figure 5.2 Battery Temperature Detection Port

Table 5.1 Description of Battery Temperature Detection Port

Name Position Description
SCL X1.1 I2C communication SCL Signal
SDA X1.2 I2C communication SDA Signal
+3.0V X1.3 3V
Power GND X1.4 GND

5. Interface and Communication

5.2 X2 - Remote EPO Input Port

The UPS is equipped with Emergency Power Off (EPO) Function that can be operated by a remote contact assigned by the users. EPO is defaulted to Normally Closed (N.C.).

Note: The open contact activates EPO function.

Users may change the setting to Normally Open via the LCD display.

X2 is the remote EPO input port. This port is shown in Figure 5.3 and described in Table 5.2.

+12V X2 X2.1 X2.2

Figure 5.3 Remote EPO Input Port

Table 5.2 Description of Remote EPO Port

EPO Logic Setting Position Description
N.C X2.1 and X2.2 EPO activated when Opened X2.1 and X2.2
N.O X2.1 and X2.2 EPO activated when Shorted X2.1 and X2.2

If EPO Logic setting is Normally Closed (N.C), the EPO will be triggered when pins 1 and pin 2 of X1 are opened. Otherwise, EPO Logic setting is Normal Opened (N.O). The EPO will be triggered when pins 1 and pin 2 of X2 are closed.

Notes:

  1. EPO function shuts down the rectifiers, chargers, inverters and static transfer switch, but it does not internally disconnect the input power supply.
  2. The default setting of the EPO function logic is Normal Closed (N.C).
  3. A user-supplied REPO button must be latching type and in a normally closed position.

5.3 Other Communication Interfaces

5.3.1 RS-232 Port

The RS-232 port is located on the panel behind the front door. The RS-232 port provides service support when upgrading the UPS software to a different revision.

5.3.2 USB Port

This port is for service purposes only.

Note: The RS232 and USB ports WILL NOT work simultaneously.

5.3.3. SNMP Slot for Monitoring Using WEBCARDLX (Optional cards)

Install an optional WEBCARDLX card in this slot to remotely monitor and control the UPS via network. The RELAYCARDSV may also be inserted in this slot to provide dry contact I/P and O/P signals and temperature sensors communication functionality. Refer to the WEBCARDLX and RELAYCARDSV manuals for further details.

Note: Only one card may be used at a time.

6. Operation Principles

6.1 UPS Block Diagram
graph TD A["Input Breaker"] --> B["Static Switch"] B --> C["UPS Module"] C --> D["Output Breaker"] D --> E["Maintenance Breaker"] E --> F["Rect Inv"] F --> G["Charger"] G --> C C --> H["UPS Module"] H --> I["Charge"] I --> J["Bat Module"] J --> K["Input 1/2 Input 2"] style A fill:#99ccff,stroke:#333…

Figure 6.1 Wiring Diagram for a Standard Single Input UPS
graph TD subgraph_Input_Input2["Input 1input2"] L1["L1"] --> Input_Breaker["Input Breaker"] L2["L2"] --> Input_Breaker L3["L3"] --> Input_Breaker N["N"] --> Input_Breaker end Input_Breaker --> Rect_inv["RECT Inv"] Input_Breaker --> Charger["Charger"] Input_Breaker --> UPS_Module["UPS Module"] Input_…

Figure 6.2 Wiring Diagram for Dual Inputs (Offered on a Different S3MX UPS Model)

6. Operation Principles

6.2 Operation Modes

This UPS is a 3-phase, four wire on-line, double-conversion and reverse-transfer UPS that permits operation in the following modes:

- Standby Mode

- Line Mode

- Battery Mode

- Bypass Mode

- Converter Mode

- ECO Mode

- Shutdown Mode

- Maintenance Bypass Mode (Manual Bypass)

6.2.1 Standby Mode

The UPS will enter Standby Mode (if BYPASS is disabled) until the UPS is turned on. When the UPS is powered on in Standby Mode, the charger function will be active when the battery is connected. The load is not powered under this mode.

graph TD subgraph Single Input A["Main"] --> B["Q1 Input Breaker"] B --> C["Rectifier"] C --> D["Inverter"] D --> E["Inverter Relay"] E --> F["Q3 Output Breaker"] F --> G["Load ~"] H["Battery Breaker"] --> I["Ground"] end subgraph Dual Inputs J["Bypass"] --> K["Q2 Bypass Breaker"] K --> L["Rectifier…

Standby Mode Diagrams

6. Operation Principles

6.2.2 Line Mode

In Line Mode, the rectifier delivers power from the mains and supplies DC power to the inverter and the charger charges the battery. The inverter filters the DC power and converts it into pure, stable AC power to power the load.

graph TD subgraph Single Input A["Main"] --> B["Input Breaker"] B --> C["Rectifier"] C --> D["Inverter"] D --> E["Inverter Relay"] E --> F["Output Breaker"] F --> G["Load"] end subgraph Dual Inputs H["Bypass"] --> I["Input Breaker"] I --> J["Rectifier"] J --> K["Inverter"] K --> L["Inverter Relay"]…

Line Mode Diagrams

6. Operation Principles

6.2.3 Battery Mode

The UPS automatically transfers to Battery Mode if the Utility fails. There is no interruption to the load upon failure. In Battery Mode, the rectifier delivers power from the battery and supplies DC power to the inverter. The inverter filters the DC power and converts it into pure and stable AC power to power the load.

graph TD subgraph Single Input A["Main"] --> B["Input Breaker"] B --> C["Rectifier"] C --> D["Inverter"] D --> E["Output Breaker"] E --> F["Load"] G["Battery Breaker"] --> C end subgraph Dual Inputs H["Bypass"] --> I["Input Breaker"] I --> J["Rectifier"] J --> K["Inverter"] K --> L["Output Breaker"]…

Battery Mode Diagrams

6. Operation Principles

6.2.4 Frequency Conversion Mode

When the UPS is manually set in Converter Mode, the output frequency can be set as 50 Hz or 60 Hz. After the output frequency is set up, the system will automatically disable the bypass function. Once the inverter shuts down, there is no bypass output. During Converter Mode, the NORMAL LED indicator (NORMAL) illuminates (green).

graph LR MAINS["MAINS"] --> Rectifier["Rectifier"] Rectifier --> Inverter["Inverter"] Inverter --> LOAD["LOAD"] Batteries["Batteries"] --> Rectifier Rectifier --> Inverter Inverter --> LOAD

Frequency Conversion Mode Diagram

6. Operation Principles

6.2.5 Bypass Mode

Upon connecting to utility input power, the UPS is in Bypass Mode before the UPS is turned on (if BYPASS setting is enabled), and charger function will be active when battery is connected.

If the UPS has been turned on and encounters abnormal situations (over-temperature, overload, etc.), the static transfer switch will transfer the load from the inverter to the bypass source with no interruption. If the transference was caused by a recoverable reason, the UPS will return to Line Mode once the situation has been resolved.

graph TD subgraph Dual Inputs A["Main"] --> B["Input Breaker"] B --> C["Rectifier"] C --> D["Inverter"] D --> E["Output Breaker"] E --> F["Load"] G["Bypass"] --> H["Input Breaker"] H --> I["Rectifier"] I --> J["Inverter"] J --> K["Output Breaker"] L["Main"] --> M["Input Breaker"] M --> N["Rectifier"…

Bypass Mode Diagrams

6. Operation Principles

6.2.6 ECO Mode

ECO Mode can be enabled through the LCD control panel. In ECO Mode, the load is diverted to bypass when the bypass voltage and frequency are within their acceptable range. If the bypass voltage is out of range, the UPS will transfer the power source from bypass to inverter. In order to shorten the transfer time, the rectifier and inverter will be operating when the UPS is in ECO Mode.

graph TD subgraph Dual Inputs A["Main"] --> B["Bypass"] B --> C["Q1 Input Breaker"] C --> D["Rectifier"] D --> E["Inverter"] E --> F["Inverter Relay"] F --> G["Q3 Output Breaker"] G --> H["Load"] I["Q4 Maintenance Breaker"] --> J["STS"] J --> K["Rectifier"] K --> L["Inverter"] L --> M["Inverter Rela…

ECO Mode Diagrams

6. Operation Principles

6.2.7 Shutdown Mode

When the UPS is in the off state and utility power source is absent, the UPS will enter Shutdown Mode. When the utility power source is absent and the UPS has discharged the batteries to the cut-off voltage level of 10V/battery at 25C, the UPS will also enter into a Shutdown Mode. When the UPS enters this mode, it will shut off the control power of the UPS and rectifier, and shut down the charger and inverter.

graph TD subgraph Single Input A["Main"] --> B["Input Breaker"] B --> C["Rectifier"] C --> D["Inverter"] D --> E["Inverter Relay"] E --> F["Output Breaker"] F --> G["Load"] H["Battery Breaker"] --> I["-+"] end subgraph Dual Inputs J["Bypass"] --> K["Input Breaker"] K --> L["Rectifier"] L --> M["Inve…

Shutdown Mode Diagrams

6. Operation Principles

6.2.8 Maintenance Bypass Mode

A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS becomes unavailable (e.g. during a maintenance procedure). Before entering the Maintenance Bypass Mode, make sure the bypass power source is available.

graph TD subgraph Single Input A["Main"] --> B["Input Breaker"] B --> C["Rectifier"] C --> D["Inverter"] D --> E["Inverter Relay"] E --> F["Output Breaker"] F --> G["Load"] H["Battery Breaker"] --> I["Ground"] end subgraph Dual Inputs J["Bypass"] --> K["Input Breaker"] K --> L["Rectifier"] L --> M["…

Maintenance Bypass Mode Diagrams

7. UPS Operation

Tripp Lite S3M160KXD - UPS Operation - 1

WARNING

  • Do not start the UPS until the installation is completed.
  • Make sure the wiring is connected correctly and power cables are firmly fixed.
  • Make sure the Power Stages' addresses have been configured correctly. Refer to section 3.3 and Table 3.1 for details.
    • Make sure all breakers are switched OFF.

7.1 AC Startup

Use the following procedures when turning on the UPS from a fully "powered-down" state.

Step 1: Apply utility power to the UPS.

Step 2: Turn ON the battery breaker (external battery cabinet).

Step 3: Turn ON the Input breaker (Q1).

For Dual Input models: Turn ON both the Input breaker (Q1) and Bypass breaker (Q2).

graph TD A["STS"] --> B["AC/DC"] B --> C["DC/AC"] C --> D["LOAD"] E["STS"] --> F["0.0V L2 230.0V L3 230.0V"] G["AC/DC"] --> H["+ -"] I["DC/AC"] --> J["0.0V L2 230.0V L3 230.0V"] K["85%"] --> L["Ground"]

Step 4: Wait one minute. The LCD panel is displayed as shown below. The UPS will enter Bypass Mode if the setting of Bypass Mode is enabled (default setting). If Bypass Mode is disabled, the UPS will remain in Standby Mode.

graph TD A["STS"] --> B["AC/DC"] B --> C["DC/AC"] C --> D["LOAD"] D --> E["85%"] F["Ground"] --> G["+"] H["Ground"] --> I["-"] J["Ground"] --> K["Ground"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333 style E fill:#ffc,stroke:…

7. UPS Operation

Step 5: Make sure there are no warning or fault events recorded. However, if there is a warning or fault event, please refer to 8. Troubleshooting to resolve the issue.

Step 6: Turn ON the Output breaker (Q3).

graph TD A["Power Supply"] --> B["STS"] C["AC/DC"] --> D["DC/AC"] B --> E["LOAD"] D --> E E --> F["0.0V"] E --> G["0.0V"] E --> H["0.0V"] style A fill:#f9f,stroke:#333 style C fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style D fill:#ccf,stroke:#333 style E fill:#cfc,stroke:#333 style F fill…

graph TD A["BYPASS"] --> B["INV"] B --> C["LOAD"] D["LINE"] --> B E["BATT"] --> B F["FAULT"] --> G["ALARM"] H["POWER"] --> I["Power"]

Power On/Off button

Step 7: Press the Power ON/OFF button for two seconds until a beep is heard, then release to start the inverter.

graph TD A["AC DC"] --> B["DC AC"] B --> C["LOAD"] D["STS"] --> C E["85%"] --> F["Ground"] G["1 230.0V L2 230.0V L3 230.0V"] --> H["Control"] I["1 230.0V L2 230.0V L3 230.0V"] --> J["Measurement"] K["1 230.0V L2 230.0V L3 230.0V"] --> L["SETUP"] M["1 230.0V L2 230.0V L3 230.0V"] --> N["Information"]…

Step 8: The UPS is now in Line Mode. AC startup is now complete.

7. UPS Operation

7.2. Cold Start Startup

Step 1: Switch ON the battery breaker (external battery cabinet).

Step 2: Press the "Battery Start" button on any one of power stages to start up the control power.

Battery Start Button

Step 3: After pressing the "Battery Start" button, the UPS will display the initialization screen.

Online UPS BYPASS INV LINE LOAD BATT FAULT ALARM POWER

Step 4: While the UPS is displaying the Online screen, immediately press the "Power On/Off" button for 2 seconds until a beep is heard, then release to start the inverter.

Online UPS BYPASS INV LINE LOAD BATT FAULT ALARM POWER Power On/Off button

7. UPS Operation

Step 5: The UPS will enter Battery Mode.

graph TD A["STS"] --> B["AC/DC"] B --> C["DC/AC"] C --> D["LOAD"] D --> E["BYPASS INV LINE BATT LOAD ALARM POWER"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333

Step 6: Switch ON the output breaker (Q3). The cold start startup procedure is complete.

Step 7: Turn on the Input Breaker (Q1) when utility power is restored and verified OK.

For Dual Input models: Turn ON the Input breaker (Q1) and Bypass breaker (Q2) when utility power is restored and verified OK.

7. UPS Operation

7.3 Maintenance Bypass Operation

Follow the below steps to transfer to maintenance bypass for power stage maintenance and UPS protection.

7.3.1 Transfer Critical Load from Line Mode to Maintenance Bypass

Tripp Lite S3M160KXD - Transfer Critical Load from Line Mode to Maintenance Bypass - 1

Confirm Bypass Mode is enabled via the LCD display menu prior to performing the Maintenance Bypass procedure.

Step 1Remove the mechanical locking plate securing the Q4 Maintenance Bypass breaker (all models).
Tripp Lite S3M160KXD - Transfer Critical Load from Line Mode to Maintenance Bypass - 2Tripp Lite S3M160KXD - Transfer Critical Load from Line Mode to Maintenance Bypass - 3
S3M100KX/S3M100KXD S3M120KX/S3M120KXD (100 kVA/120 kVA) ModelsS3M160KX/S3M160KXD S3M200KX/S3M200KXD (160 kVA/200 kVA) Models
Step 2Confirm the UPS is operating in Bypass Mode.
Tripp Lite S3M160KXD - Transfer Critical Load from Line Mode to Maintenance Bypass - 4
Step 3Turn ON the Q4 Maintenance Bypass breaker (all models).
Tripp Lite S3M160KXD - Transfer Critical Load from Line Mode to Maintenance Bypass - 5Tripp Lite S3M160KXD - Transfer Critical Load from Line Mode to Maintenance Bypass - 6
S3M100KX/S3M100KXD S3M120KX/S3M120KXD (100 kVA/120 kVA) ModelsS3M160KX/S3M160KXD S3M200KX/S3M200KXD (160 kVA/200 kVA) Models

7. UPS Operation

Step 4Turn OFF the Q3 Output breaker.Tripp Lite S3M160KXD - UPS Operation - 1S3M100KX/S3M100KXDS3M120KX/S3M120KXD(100 kVA/200 kVA) ModelsTurn OFF the Q3 Output breaker.Tripp Lite S3M160KXD - UPS Operation - 2S3M160KX/S3M160KXDS3M200KX/S3M200KXD(160 kVA/200 kVA) Models
Step 5 Single input model:Turn OFF the Q1 Input 1 breaker.Tripp Lite S3M160KXD - UPS Operation - 3S3M100KXS3M120KX(100 kVA/200 kVA) ModelsSingle input model:Turn OFF the Q1 Output breaker.Tripp Lite S3M160KXD - UPS Operation - 4S3M160KXS3M200KX(160 kVA/200 kVA) Models
Step 6The UPS will enter Shutdown Mode and will slowly de-energise. After the UPS powers off, turn OFF the battery breaker (external battery cabinet).
Step 7The critical load is now supported in Maintenance Bypass Mode.

7. UPS Operation

7.3.2 Transfer Critical Load from Maintenance Bypass to Line Mode

Step 1Turn ON the battery breaker (external battery cabinet).
Step 2 Single input model:Turn ON the Q1 Input 1 breaker.Tripp Lite S3M160KXD - UPS Operation - 1S3M100KXS3M120KX(100 kVA/200 kVA) ModelsSingle input model:Turn ON the Q1 Input 1 breaker.Tripp Lite S3M160KXD - UPS Operation - 2S3M160KXS3M200KX(160 kVA/200 kVA) Models
Dual input model (Option):Turn ON the Q1 Input breaker and Q2 Input breaker.Tripp Lite S3M160KXD - UPS Operation - 3 Tripp Lite S3M160KXD - UPS Operation - 4S3M100KXD S3M120KXD (100 kVA/200 kVA) ModelsDual input model (Option):Turn ON the Q1 Input breaker and Q2 Input breakerTripp Lite S3M160KXD - UPS Operation - 5 Tripp Lite S3M160KXD - UPS Operation - 6S3M160KXD S3M200KXD (160 kVA/200 kVA) Models
Step 3Go to the LCD INFORMATION Menu. Choose “SYSTEM” to ensure that Bypass Mode is enabled (“Power By Bypass”). If Bypass Mode is disabled, set it to “enabled” through the SETUP menu and confirm the UPS is operating in Bypass Mode before proceeding.Tripp Lite S3M160KXD - UPS Operation - 7
Step 4Turn ON the Q3 Output breaker.Tripp Lite S3M160KXD - UPS Operation - 8S3M100KX/S3M100KXDS3M120KX/S3M120KXD(100kVA/120kVA) ModelsTurn ON the Q3 Output breaker.Tripp Lite S3M160KXD - UPS Operation - 9S3M160KX/S3M160KXDS3M200KX/S3M200KXD(160 kVA/200 kVA) Models

7. UPS Operation

Step 5Turn OFF the Q4 Maintenance Bypass breaker (all models).
Tripp Lite S3M160KXD - UPS Operation - 1Tripp Lite S3M160KXD - UPS Operation - 2
S3M100KX/S3M100KXD S3M120KX/S3M120KXD (100 kVA/200 kVA) ModelsS3M160KX/S3M160KXD S3M200KX/S3M200KXD (160 kVA/200 kVA) Models
Step 6Secure the mechanical locking plate to the Q4 Maintenance Bypass breaker (all models).
Tripp Lite S3M160KXD - UPS Operation - 3Tripp Lite S3M160KXD - UPS Operation - 4
S3M100KX/S3M100KXD S3M120KX/S3M120KXD (100 kVA/200 kVA) ModelsS3M160KX/S3M160KXD S3M200KX/S3M200KXD (160 kVA/200 kVA) Models
Step 7Press Power ON/OFF button for 2 seconds until a beep is heard, then release to start the inverter.
Step 8The critical load is now supported in Line Mode.

7. UPS Operation

7.4 Turn Off Operation

7.4.1 Turn Off Operation in Line Mode

Tripp Lite S3M160KXD - Turn Off Operation in Line Mode - 1

WARNING: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm all power loads are turned off.

The LCD diagrams shown below are when the UPS is operating in Line Mode.

graph TD A["AC/DC"] --> B["85%"] C["DC/AC"] --> D["LOAD"] E["STS"] --> F["1 0%"] E --> G["2 0%"] E --> H["3 0%"] I["+"] --> J["Ground"] K["STS"] --> L["1 230.0V"] K --> M["2 230.0V"] K --> N["3 230.0V"] O["LOAD"] --> P["1 230.0V"] O --> Q["2 230.0V"] O --> R["3 230.0V"]

Step 1: Stop the inverter. Press the "Power On/Off" button for 2 seconds until a beep is heard to turn off the UPS, or use the Menu-Control-System. The UPS will transfer to Bypass Mode – or Standby Mode if the Bypass Mode setting is disabled.

graph TD A["Power On/Off button"] --> B["BYPASS"] B --> C["INV"] C --> D["LINE"] D --> E["BATT"] E --> F["LOAD"] F --> G["FAULT ALARM"] G --> H["POWER"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333 style E fill:#cff,stroke:#3…

7. UPS Operation

The LCD diagram below is showing Bypass Mode (Bypass Mode is enabled).

graph TD A["Start"] --> B["StS"] B --> C["LOAD"] C --> D["+ -"] D --> E["A-10C"] E --> F["DC-SAG"] F --> G["0.0V"] F --> H["0.0V"] F --> I["0.0V"] B --> J["STS 230.0V 230.0V 230.0V"] C --> K["LOAD 230.0V 230.0V 230.0V"]

Step 2: Turn off the Output Breaker (Q3).

Step 3: Turn off the Input Breaker (Q1).

For Dual Input models: Turn off the Input Breaker (Q1) and Bypass Breaker (Q2).

Step 4: The UPS will enter Shutdown Mode and slowly de-energise. Wait until the LCD is OFF.

Step 5: After the UPS powers off, switch OFF the external power switch to disconnect the AC power to the UPS.

Step 6: If the UPS will remain disconnected from the AC power for an extended period, switch OFF the battery breaker (external battery cabinet).

7.4.2 Turn Off Operation in Battery Mode

Tripp Lite S3M160KXD - Turn Off Operation in Battery Mode - 1

WARNING: The UPS system shutdown procedure will eliminate the AC power output for all loads. Before shutdown, confirm all power loads are turned off.

The LCD diagrams shown below are when the UPS is operating in Battery Mode.

graph TD A["STS"] --> B["AC/DC"] B --> C["DC/AC"] C --> D["LOAD"] E["Ground"] --> F["Control"] G["Measurement"] --> H["Setup"] I["Information"] --> J["Launch"] K["Device"] --> L["12:00 2018/01/01"] M["Power Supply"] --> N["0.0V 0.0V 0.0V"] O["Current Power Supply"] --> P["25% 25% 25%"] Q["Ground Pow…

7. UPS Operation

Step 1: Press the "Power On/Off" button for 2 seconds to turn off the UPS, or use the Menu-Control-System. The UPS will first transfer to Standby Mode, then Shutdown Mode after a few seconds.

graph TD A["Power On/Off button"] --> B["I/O Bus"] B --> C["12:00"] C --> D["Output"] style A fill:#f9f,stroke:#333 style B fill:#ccf,stroke:#333 style C fill:#cfc,stroke:#333 style D fill:#fcc,stroke:#333

Step 2: Turn off the Output Breaker (Q3).

Step 3: Turn off the Input Breaker (Q1).

For Dual Input models: Turn off the Input Breaker (Q1) and Bypass Breaker (Q2).

Step 4: While in Shutdown Mode the UPS will slowly de-energise. Wait until the LCD is OFF.

graph TD A["230.0V"] --> B["STS"] C["230.0V"] --> B D["230.0V"] --> B E["0.0V"] --> F["+"] G["0.0V"] --> F H["0.0V"] --> F I["0.0V"] --> F J["85%"] --> F K["0.0V"] --> L["LOAD"] M["0.0V"] --> L N["0.0V"] --> L O["0.0V"] --> L P["0.0V"] --> L Q["0.0V"] --> L R["0.0V"] --> L

Step 5: After the UPS powers off, switch OFF the external power switch to disconnect the AC power to the UPS.

Step 6: If the UPS will remain disconnected from the AC power for an extended period, switch OFF the battery breaker (external battery cabinet).

8. Troubleshooting

Fault and Warning events should be reviewed by authorised service personnel.

LCD Message Explanation Solution
Fault! Bus Over Voltage DC bus voltage is too high. Contact service personnel.
Fault! Bus Under Voltage DC bus voltage is too low. Contact service personnel.
Fault! Bus Voltage Unbalance DC bus voltage is not balanced. Contact service personnel.
Fault! Bus Short DC bus is short. Contact service personnel.
Fault! Bus Soft Start Time Out The rectifiers could not start due to low DC bus voltage within specified duration.Turn off UPS and then restart the UPS. If it fails again, contact service personnel.
Fault! Inverter Soft Start Time Out Inverter voltage cannot reach desired voltage within specified duration.Turn off UPS and then restart the UPS. If it fails again, contact service personnel.
Fault! Inverter Voltage Over Inverter Voltage over (Peak Value). Contact service personnel.
Fault! Inverter Voltage High Inverter Voltage is too high. Contact service personnel.
Fault! Inverter Voltage LowInverter Voltage is too Low. Contact service personnel.
Fault! R Inverter Voltage ShortR phase inverter Output is shorted.Contact service personnel.
Fault! S Inverter Voltage ShortS phase inverter Output is shorted.Contact service personnel.
Fault! T Inverter Voltage ShortT phase inverter Output is shorted.Contact service personnel.
Fault! RS Inverter Voltage ShortR-S inverter Output is shorted.Contact service personnel.
Fault! ST Inverter Voltage ShortS-T inverter Output is shorted. Contact service personnel.
Fault! TR Inverter Voltage ShortT-R inverter Output is shorted. Contact service personnel.
Fault! Inverter R Negative PowerR phase inverter Output Negative Power over range.Contact service personnel.
Fault! Inverter S Negative PowerS phase inverter Output Negative Power over range.Contact service personnel.
Fault! Inverter T Negative PowerT phase inverter Output Negative Power over range.Contact service personnel.
Fault! Over Load FaultHeavy overload causes UPS fault.Reduce some load.
Fault! Battery FaultBattery reverse.Check the polarity of battery connection and contact service personnel.
Fault! Over TemperatureMake sure adequate space is allowed for air vents and the fan is working.Check if the ambient temperature is over specification or contact service personnel.
Fault! CAN Fault CAN communication fault. Contact service personnel.
Fault! TRIGO FaultSynchronised trigger signal fault.Contact service personnel.
Fault! Relay FaultInverter relay fault.Contact service personnel.
Fault! Line SCR FailLine SCR short circuit fault.Contact service personnel.
Fault! EEPROM FaultEEPROM operation error.Contact service personnel.
Fault! Parallel Cable Loosen FaultAs stated.Check if the parallel cable is loose and contact service personnel.
Fault! DSP MCU Stop CommunicateAs stated.Contact service personnel.
Fault! Bypass Temperature FaultAs stated.Check if the ambient temperature is over specification or contact service personnel.
Fault! Bypass SCR FaultAs stated.Contact service personnel.
Warning! EPO ActiveCheck the EPO connector.Check if the connector is loose when EPO acts abnormally.
Warning! Over Load FailThe load devices are demanding more power than the UPS can supply. Line Mode will transfer to Bypass Mode.Reduce some load and check output Load-Capacity and specification.
Warning! Communicate CAN FailCAN communication error.Contact service personnel.
Warning! Over LoadWhen in Line Mode, the load devices are demanding more power than the UPS can supply.Reduce some load and check output Load-Capacity and specification.
Warning! Battery OpenBattery not connected.1. Check battery breaker.2. Check if the battery connection is well connected.3. Check the setting of Nominal Battery voltage.4. Contact service personnel if necessary.
Warning! Battery voltage HighBattery voltage is too High.Check the setting of Nominal Battery voltage and contact service personnel.
Warning! Turn On AbnormalAs stated.Check if the input voltage or frequency is out of range.
Warning! Charge FailAs stated.Contact service personnel.
Warning! EEPROM FailEEPROM operation error.Contact service personnel.
Warning! Fan LockAs stated.Check if the fan is blocked or contact service personnel.

8. Troubleshooting

LCD Message Explanation Solution
Warning! Line Phase Error As stated.Check if the Mains phase sequence iscorrect and contact service personnel.
Warning! Bypass Phase Error As stated.Check if the Bypass phase sequence iscorrect and contact service personnel.
Warning! N Loss Neutral loss. Check ifthe Neutral connection is correctand contact service personnel.
Warning! Internal Initial Fail As stated.Contact service personnel.
Warning! Comm. Syn. Signal Fail Communicate Synchronization Signal Fail. Contact servicepersonnel.
Warning! Comm. TRIGO Fail Communicate Trigger signal fault. Contact service personnel.
Warning! Power Stage Loss As stated.Check if the number of power stagesinstalled in the system is correct
Warning! Parallel Sys Config. Wrong Parparallel System Configure error. Contact service personnel.
Warning! Maintenance Bypass Enter maintenance. Check if the connector is loose when it acts abnormally.
Warning! Battery Age AlertBattery Life expiration.Check if the battery has been used over its service age or contact service personnel.
Warning! Parallel UPS Cable LoosenAs stated. Check if the Parallel UPS Cable is loose andcontact service personnel.
Warning! Parallel UPS Config. WrongParallel UPS Configure error.Check that the Parallel UPS Setting is correct and contact service personnel.
Warning! Parallel Firmware ErrorPower Stage parallel firmware error.The firmware version does not support UPS Parallel feature. Contact service personnel.
Warning! ID ConflictPower Stage ID conflict.There are two Power Stages with the same ID numbers. Change the repeated ID to release it or contact service personnel.
Warning! Redundancy Set FailAs stated. Check if the UPS is set from parallel tosingle. The Redundancy setting needs to be set to 0.

9. Storage and Service

9.1 Storage

The UPS system must be stored in a clean, secure environment with a temperature less than 40° C and a relative humidity less than 90% (non-condensing). Store the UPS system in its original shipping container, if possible. If installation occurs more than 6 months after you receive the UPS system, recharge the batteries for at least 24 hours prior to use. Do not rely on the UPS system to provide backup power to connected equipment until the batteries are fully charged.

Note: If the UPS system remains off for an extended period of time, it should be turned on periodically to allow the batteries to recharge. The UPS system should be turned on and the batteries should be recharged at least one uninterrupted 24-hour period every 3 months. Failure to recharge the batteries periodically may cause irreversible battery damage.

9.2 Service

  • The UPS system operates with hazardous voltages. Repairs should only be performed by qualified service personnel.
  • Even after the unit is disconnected from the mains, potentially dangerous components inside the UPS system are still connected to the battery packs.
  • Before carrying out any service and/or maintenance, disconnect the batteries and verify that no current is present and no hazardous voltage exists.
  • Only qualified technicians taking the required precautionary measures may replace batteries and supervise operations. Unauthorised persons should not perform battery maintenance.
  • Verify that no voltage between the battery terminals and the ground is present before maintenance or repair. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground.
  • Batteries may cause electric shock and have a high short-circuit current. Remove all wristwatches, rings and other metal personal objects before maintenance or repair, and only use tools with insulated grips and handles for maintenance or repair.
  • When replacing the batteries, install the same number and same type of batteries.
  • Do not attempt to dispose of batteries by burning them. This could cause a battery explosion. The batteries must be appropriately disposed according to local regulations.
  • Do not open or destroy batteries. Escaping electrolytes may be toxic and can cause injury to the skin and eyes.
  • To avoid fire hazards replace fuses only with the same type and amperage and do not disassemble the UPS.

9.3 Batteries (External Only – Refer to the Battery Cabinet Manual for More Information)

Tripp Lite's S3MKX-Series UPS systems use sealed lead-acid batteries. Battery life depends on operating temperature, usage, and charging/discharging frequency. High-temperature environments and high charging/discharging frequency will quickly shorten battery life. Please follow the suggestions below to ensure a normal battery lifecycle.

  1. Keep operating temperature between 0° C\~ 40° C.
  2. For optimum battery performance and life cycle, operate at a regulated 25° C.
  3. When the UPS needs to be stored for an extended period, the batteries must be recharged once every three months and the charging time must be at least 24 hours each time.

9.4 Fans

Higher temperatures shorten fan life. When the UPS is running, check to see all fans work normally and make sure air can move freely around and through the UPS. If not, replace the fans.

Note: Contact Tripp Lite Technical Support for more maintenance information. Do not perform maintenance if you are not qualified to do so.

10. Specifications

Model S3M100KX/KXD* S3M120KX/KXD*S3M160KX/KXD* S3M200KX/KXD*
Capacity (VA) 100 kVA 120 kVA 160 kVA 200 kVA
Capacity (Watts) 90 kW 108 kW 144 kW 180 kW
INPUT
Nominal Voltage Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
Voltage RangePh-Ph 208-478V at < 50% Load; Ph-Ph 208-478V to 305-478V at 50% to 80% Load(Voltage Range Varies with Load); > 80% Load: Ph-Ph 305-478V
Voltage Comeback Low-Loss Voltage +10V;High-Loss Voltage -10V
Nominal Frequency 50/60 Hz (Auto-Selectable)
Frequency Range 40-70 Hz
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Power Factor (100% Load) > 0,99
Harmonic Distortion (THDi; 100% Load) < 3%
OUTPUT
Phase 3-Phase with Neutral (3-Phase, Neutral** + Ground)
Nominal VoltagePh-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
AC Voltage Regulation(Double-Conversion Mode)±1% (Balanced Load)
AC Voltage Regulation(Converter Mode or Battery Mode)±1%
Power Factor0,9
AC Voltage Regulation (ECO Mode)± 15V of Nominal
FrequencySelectable ± 1 Hz, ± 2 Hz, ± 4 Hz of Input (Default: ± 4 Hz)
Frequency Regulation(Converter Mode or Battery Mode)± 0,1 Hz
Frequency Range (Battery Mode) 50 Hz ± 0,1 Hz or 60 Hz ± 0,1 Hz
Overload (AC Mode)Up to 110% = 1 hr; Up to 125% = 10 min;Up to 150% = 1 min; > 150% = 200 ms
Overload (Battery Mode)Up to 110% = 1 hr; Up to 125% = 10 min;Up to 150% = 1 min; > 150% = 200 ms
Current Crest Ratio3:1 Maximum
Harmonic Distortion (100% Load)≤ 2% THD (Linear Load); ≤ 4% THD (Non-Linear Load)
Transfer Time (Line ←→ Battery)0 ms
Transfer Time (Inverter ←→ Bypass)Synchronous = 0 ms; Asynchronous < 1 cycle
Transfer Time (Inverter ←→ ECO)< 20 ms
BYPASS INPUT
Nominal VoltagePh-Ph 380V/400V/415V
Phase 3-Phase with Neutral (3-Phase, Neutral + Ground)
Voltage RangeUpper Limit: +10%, +15% or +20% (Default: +15%)Lower Limit: -10%, -20% or -30% (Default: -20%)
Nominal Frequency 50/60 Hz (Auto-Selectable)
Frequency RangeSelectable: ± 1 Hz, ± 2 Hz, ± 4 Hz (Default: ± 4 Hz)
Overload (Bypass Mode)105-110% = 1 hr; 111-125% = 10 min;126-150% = 1 min; > 150% = 200 ms
EFFICIENCY
AC Line Mode94% at 100% Resistive Load; 93.5% at 50% Resistive Load
ECO Mode98% at 100% Resistive Load; 97% at 50% Resistive Load
Battery Mode93% at 100% Resistive Load; 92.5% at 50% Resistive Load
PARALLEL
Parallel for CapacityUp to 2 Units
Parallel for RedundancyRequires externalN+1 bypass panelUp to 2 units
EXTERNAL BATTERIES(S3M100KX/KXD*, S3M120KX/KXD*, S3M160KX/KXD* and S3M200KX/KXD* require external batteries to operate.)
Type12V Non-Spillable VRLA AGM/GEL
DC Nominal Acceptance Voltage± 240 VDC
Quantity40N (N ≥ 1 x Strings of 20 + 20)
Maximum Charging CurrentAdjustable up to 24A± 1%Adjustable up to 32A± 1%Adjustable up to 40A± 1%Adjustable up to 48A± 1%

*KXD models are dual-AC input capable. **The UPS output Neutral must be connected to the Load Neutral at all times.

10. Specifications

Model S3M100KX/KXD* S3M120KX/KXD*S3M160KX/KXD* S3M200KX/KXD*
EXTERNAL BATTERIES(S3M100KX/KXD*, S3M120KX/KXD*, S3M160KX/KXD* and S3M200KX/KXD* require external batteries to operate.)
Float Voltage 13,65V/Battery; 2,27V/Cell
Boost Charging 14,1V/Battery; 2,35V/Cell
End of Discharge 10V/Battery; 1,67V/Cell
Charger Temperature Compensation -3 mV/Cell/°C (Requires optional TEMPC100200 thermostat kit.)
PHYSICAL
Dimensions (H x W x D)1015 x 567 x 945 mm1455 x 567 x 995 mm
Unit Weight (With Internal Batteries)N/A N/AN/A N/A
Unit Weight (Without Internal Batteries)197 kg 232 kg309 kg 343 kg
ENVIRONMENT
Operating Temperature 0 to 40°C (< 25°C for optimal battery lifespan.)
Storage Temperature 0 to 35°C (UPS with Batteries), -15 to 60°C (UPS without Batteries)
Operating Humidity 0 to 95% (Non-Condensing)
Operating Altitude< 1000 m (Derate output power by 1% per 100 m above 1000 m.)
Audible Noise< 70 dBA at 1 m< 73 dBA at 1 m
Heat Dissipation (100% Load)19600 BTU/hr23507 BTU/hr31343 BTU/hr39179 BTU/hr
Heat Dissipation (50% Load)9974 BTU/hr11048 BTU/hr14731 BTU/hr18414 BTU/hr
MANAGEMENT
Network Management InterfaceRequires optional WEBCARDLX. (Monitor, control and reboot the UPS using embedded HTML5 web, SSH/telnet and SNMP interfaces. Supports centralised management through integration with a wide range of Network Management Systems and DCIM platforms.)
Control PanelLarge 254 mm / 10 in. colour LCD touchscreen with supplemental LEDs.(Monitor, control, configure and diagnose the UPS from the display.)
Contact Closure InterfaceRequires Optional RELAYCARDSV Programmable Relay I/O Card
Remote Emergency Power Off (REPO)Feature Included (Default: Normally Closed)
RS-232Included (Service Only)
STANDARDS
SafetyIEC 62040-1:2008+A1:2013 (TUV Approval)
EMC/EMIEN 62040-2:2006 (Category C3) (TUV Approval)
Ingress Protection RatingIP20
CE MarkingYes
RoHS CompliantYes
Quality Management SystemISO 9001
OTHER INFORMATION
ColourRAL 9005 Jet Black
MobilityCasters
ACCESSORIES (Sold Separately)
Scalable Battery CabinetsSupport 5 min. to 3 h runtime at 100% load. Available models include BP480V100-NIB, BP480V100, BP480V65-NIB, BP480V65, BP480V40-NIB, BP480V40.(NIB=No internal batteries.)
Network Management CardWEBCARDLX(Monitor, control and reboot the UPS using embedded HTML5 web platform, SSH/telnet or SNMP. Supports centralised management via third-party NMS or DCIM platform.)
Remote Environmental Sensors(Require WEBCARDLX.)E2MT (Temperature Sensor); E2MTDO (Temperature Sensor with Digital Outputs);E2MTDI (Temperature Sensor with Digital Inputs);E2MTHDI (Temperature/Humidity Sensor with Digital Inputs)
Contact Closure CardRELAYCARDSV
External Bypass PanelContact your local sales representative or distributor for more information.
Scalable Charger Board KitsCBKIT30-40(Adds 4A; Max 2)CBKIT30-80(Adds 8A; Max 2)N/A
Battery Temperature Compensation Thermostat KitTEMPC100200

*KXD models are dual-AC input capable.

10. Specifications

m=2m 1501 mm

Interior view of a perforated metal panel with 1221 mm height dimension (no text or symbols on the panel itself)

12V 65/100Ah x 40pcs 12V 40Ah x 40pcs

Battery Cabinet Models Breaker IncludedDimensions (H x W x D) mm Description
BP480V100400A, 3-Pole1501 x 826 x 1136Battery Cabinet with 40 x 100Ah batteries
BP480V100-NIBBattery Cabinet without batteries, but designed for 40 x 100Ah batteries (includes battery cabling and breaker)
BP480V65300A, 3-PoleBattery Cabinet with 40 x 65Ah batteries
BP480V65-NIBBattery Cabinet without batteries, but designed for 40 x 65Ah batteries (includes battery cabling and breaker)
BP480V40200A, 3-Pole 1220 x 626 x 900Battery Cabinet with 40 x 40Ah batteries
BP480V40-NIBBattery Cabinet without batteries, but designed for 40 x 40Ah batteries (includes battery cabling and breaker)

11. Warranty

Your SmartOnline 3-Phase UPS System is covered by the limited warranty described below. Extended warranties (3- and 4-year) and start-up service programs are available. For more information, call Tripp Lite Customer Service at +1.773.869.1234 or visit tripplite.com/support.

3-Phase UPS System Limited Warranty

Seller warrants this product, if used in accordance with all applicable instructions as verified by Tripp Lite's "Start-up" service, to be free from original defects in material and workmanship for a period of two (2) years from the date of start-up. If the product should prove defective in material or workmanship within that period, Seller will repair or replace the defective parts without charge for labor or parts. If the product was not started- up by authorised Tripp Lite service, replacement parts will be provided but labour charges will apply based on published Tripp Lite Time and Material Rates. Tripp Lite will assign to you any warranties provided by the manufacturers of components of the Tripp Lite product. Tripp Lite makes no representations as to the extent of these warranties and assumes no responsibility for warranties of these components. Service under this Warranty can only be obtained by contacting: Tripp Lite Customer Service; 1111 W. 35th Street; Chicago IL 60609; +1.773.869.1234; intlservice@tripplite.com.

THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, IMPROPER INSTALLATION, MISUSE, ABUSE OR NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN. EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights, and you may have other rights which vary from jurisdiction to jurisdiction).

Regulatory Compliance Identification Numbers

For the purpose of regulatory compliance certifications and identification, your Tripp Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with all required approval markings and information. When requesting compliance information for this product, always refer to the series number. The series number should not be confused with the marketing name or model number of the product.

WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union)

Tripp Lite S3M160KXD - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 1

Under the Waste Electrical and Electronic Equipment (WEEE) Directive and implementing regulations, when customers buy new electrical and electronic equipment from Tripp Lite they are entitled to:

  • Send old equipment for recycling on a one-for-one, like-for-like basis (this varies depending on the country)
  • Send the new equipment back for recycling when this ultimately becomes waste

Tripp Lite has a policy of continuous improvement. Specifications are subject to change without notice. Photos and illustrations may differ slightly from actual products.

TRIPP·LITE

Tripp Lite S3M160KXD - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 3
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

Modelos: S3M100KX, S3M100KXD, S3M120KX, S3M120KXD, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

Entrada: 220V / 230V / 240V (Fase - Neutro) 380V / 400V / 415V (Fase - Fase), 3∅ 4 Hilos + Tierra Física

Two black TPXUTE air conditioners with control panel displays, no visible text or symbols on the main body.

TRIPP·LITE

Tripp Lite S3M160KXD - WEEE Compliance Information for Tripp Lite Customers and Recyclers (European Union) - 6

1111 W. 35th Street, Chicago, IL 60609 EE. UU. • tripplite.com/support

1175 mm 1125 mm

705 mm

Figura 3.4A Figura 3.5A

Figura 3.1B

Technical diagram of a mechanical assembly with numbered components for identification

Figura 3.2B Figura 3.3B
Technical diagram of a server rack with numbered components labeled 1 to 4

Simple line drawing of a mechanical component with a downward arrow indicating force or direction (no text or symbols)

1610 mm 1125 mm

705 mm

Figura 3.4B Figura 3.5B

Figura 4.2 Pantalla Inicial

4.2.2 Pantalla Principal

Figura 4.6 Menú de Control

SYSTEM ON Standby Mode POSTIVE NEFATIVE CAPACITY 0% VOLTAGE 216.0V VOLTAGE 216.0V REWATS TIME 1Min CURRENT 10.0A CURRENT 10.0A TEST RESULT Passed TEMPERATURE 01 35.0C TEMPERATURE 02 37.0C CHARGING STATUS Float TEMPERATURE 03 34.0C TEMPERATURE 04 38.0C TEMPERATURE 05 34.0C INPUT OUTPUT BYPASS LOAD BA…

Figura 5.3 Puerto de Entrada de EPO Remoto

12V 65 / 100Ah x 40 pzas 12V 40Ah x 40 pzas

TRIPP·LITE

Tripp Lite S3M160KXD - Pantalla Principal - 3

1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

Simple line drawing of a mechanical component with a downward arrow indicating force or direction (no text or symbols)

1 125 mm 1 175 mm

705 mm

Figure 3.4A Figure 3.5A

3. Installation et configuration

1610 mm 1 125 mm

705 mm

Figure 3.4B Figure 3.5B

3. Installation et configuration

Figure 4.2 Écran initial

SYSTEM ON Standby Mode POSTIVE NEFATIVE CAPACITY 0% VOLTAGE 216.0V VOLTAGE 216.0V REWATS TIME 1Min CURRENT 10.0A CURRENT 10.0A TEST RESULT Passed TEMPERATURE 01 35.0C TEMPERATURE 02 37.0C CHARGING STATUS Float TEMPERATURE 03 34.0C TEMPERATURE 04 38.0C TEMPERATURE 05 34.0C INPUT OUTPUT BYPASS LOAD BA…

Figure 4.9 Écrans Mesure : INPUT (ENTRÉE), OUTPUT (SORTIE), BYPASS (DÉRIVATION), LOAD (CHARGE) et BATTERY (BATTERIES)

Figure 4.21 Menu Information

4.2.6.1 INFORMATION - Écran Identification

Tripp Lite S3M160KXD - INFORMATION - Écran Identification - 1
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

Модели: S3M100KX, S3M100KXD, S3M120KX, S3M120KXD, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

TRIPP·LITE

Tripp Lite S3M160KXD - INFORMATION - Écran Identification - 3

1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

Модели S3M100KX, S3M100KXD и S3M120KX, S3M120KXD
Prc. 3.1A Prc. 3.2A Prc. 3.3A

Simple line drawing of a mechanical component with a downward arrow indicating force or direction (no text or symbols)

Рис. 3.4А Рис. 3.5А

1175 MM 1125 MM

705 MM

Рис. 3.1В

Technical diagram of a mechanical assembly with numbered components for identification

Рис. 3.2В Рис. 3.3В

Technical diagram of a server rack with numbered components for identification

Simple line drawing of a mechanical component with a downward arrow indicating force or direction (no text or symbols)

Рис. 3.4В Рис. 3.5В
1610 mm 1125 mm

705 mm

SW1 SW2 CN10 CN9 CN7 CN8

POSTIVE NEFATIVE CAPACITY SYSTEM ON Standby Mode 0% VOLTAGE 216.0V VOLTAGE 216.0V REPAINT TIME 1Min CURRENT 10.0A CURRENT 10.0A TEST RESULT Passed TEMPERATURE 01 35.0C TEMPERATURE 02 37.0C CHARGING STATUS Float TEMPERATURE 03 34.0C TEMPERATURE 04 38.0C TEMPERATURE 05 34.0C INPUT OUTPUT BYPASS LOAD B…

Рис. 4.9 Экраны измерений: INPUT/BXOD, OUTPUT/BYXOD, BYPASS/OБХОДНАЯ ЦЕПЬ, LOAD/НАГРУЗКА и BATTERY/БАТАРЕЯ

7. Эксплуатация ИБП

Моделях S3M100KX/S3M100KXD
S3M120KX/S3M120KXD
(100 kBA/120kVA)

Q4 Powertrain finans

Моделях S3M160KX/S3M160KXD
S3M200KX/S3M200KXD
(160 kBA/200kVA)

Tripp Lite S3M160KXD - Эксплуатация ИБП - 2
1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

Bedienungsanleitung

Modelle: S3M100KX, S3M100KXD, S3M120KX, S3M120KXD, S3M160KX, S3M160KXD, S3M200KX, S3M200KXD

TRIPP·LITE

Tripp Lite S3M160KXD - Bedienungsanleitung - 2

1111 W. 35th Street, Chicago, IL 60609 USA • tripplite.com/support

1175 mm 1125 mm

705 mm

SW1 SW2 CN10 CN9 CN7 CN8

POSTIVE NEFATIVE CAPACITY SYSTEM ON Standby Mode 0% VOLTAGE 216.0V VOLTAGE 216.0V REMAIN TIME 1Min CURRENT 10.0A CURRENT 10.0A TEST RESULT Passed TEMPERATURE 01 35.0C TEMPERATURE 02 37.0C CHARGING STATUS Float TEMPERATURE 03 34.0C TEMPERATURE 04 38.0C TEMPERATURE 05 34.0C INPUT OUTPUT BYPASS LOAD BA…

Abbildung 4.9 Messungsbildschirme: INPUT (EINGANG), OUTPUT (AUSGANG), BYPASS (BYPASS), LOAD (LAST) y BATTERY (BATTERIE)

7. USV-Betrieb

Table of contents Click a title to access it
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Tripp Lite

Model : S3M160KXD

Category : Inverter