SI5007 - Detector IFM - Free user manual and instructions
Find the device manual for free SI5007 IFM in PDF.
User questions about SI5007 IFM
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Detector in PDF format for free! Find your manual SI5007 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. SI5007 by IFM.
USER MANUAL SI5007 IFM
Operating instructions
Flow monitor
SI5007
Contents
1 Preliminary note.... 3
1.1 Symbols used.... 3
1.2 Warnings.... 3
2 Safety instructions 4
2.1 Cybersecurity 4
3 Transport, handling and storage 5
4 Intended use 6
5 Function 7
5.1 Flow monitoring.... 7
5.2 Temperature monitoring 7
5.3 IO-Link 8
6 Installation.... 9
6.1 Installation position.... 9
6.1.1 Immersion depth 9
6.1.2 Recommended mounting position 9
6.1.3 Conditionally possible installation position.... 10
6.1.4 Impermissible installation position.... 10
6.1.5 Orientation.... 11
6.2 Interference.... 11
6.3 Process connection.... 11
7 Electrical connection 13
8 Operating and display elements.... 14
9 Set-up 15
10 Parameter setting 16
10.1 Parameter setting via the device keys.... 16
10.1.1 Switch point SP1 (flow rate) 16
10.1.2 Switch point SP2 (temperature).... 17
10.1.3 High-flow adjustment.... 18
10.1.4 Low-flow adjustment 18
10.1.5 Switch point logic 18
10.1.6 Reset the device 19
10.1.7 Lock/unlock 19
10.2 Parameter setting via IO-Link 19
11 Operation.... 21
12 Troubleshooting.... 22
13 Maintenance, repair and disposal 23
1 Preliminary note
You will find instructions, technical data, approvals, accessories and further information using the QR code on the device / packaging or at documentation.ifm.com.
1.1 Symbols used
√ Requirement
Instruction
Reaction, result
bold Designation of keys, buttons or indications
→ Cross-reference without link
→ Cross-reference with link

Important note
Non-compliance may result in malfunction or interference

Information
Supplementary note
1.2 Warnings
Warnings indicate the possibility of personal injury and damage to property. This enables safe product handling. Warnings are graded as follows:

WARNING
Warning of serious personal injury
▷ If the warning is not observed, fatal and serious injuries are possible.

CAUTION
Warning of minor to moderate personal injury
▷ If the warning is not observed, minor to moderate injuries are possible.

ATTENTION
Warning of damage to property
▷ If the warning is not observed, damage to property is possible.
2 Safety instructions
- The unit described is a subcomponent for integration into a system.
- The system architect is responsible for the safety of the system.
-
The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the architect of the system.
-
Read this document before setting up the product and keep it during the entire service life.
- The product must be suitable for the corresponding applications and environmental conditions without any restrictions.
- Only use the product for its intended purpose (→ Intended use).
- Only use the product for permissible media.
- If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur.
- The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator.
- Installation, electrical connection, set-up, operation and maintenance of the product must be carried out by qualified personnel authorised by the machine operator.
- Protect units and cables against damage.
2.1 Cybersecurity
Installation
The device is suitable for operation in a secure environment according to IEC 62443-1-1.
The device was designed for operation behind a firewall.
▶ Carry out a risk assessment of the system according to IEC 62443-1-1.
▶ Take measures to ensure physical security.
Operation
▶ Observe the security functions described in the product documentation and the recommendations for their use.
Maintenance
▶ Back up system configuration and system data in accordance with your company's change management processes.
Decommissioning
▶ Ensure that no sensitive information can fall into unauthorised hands.
▶ Always reset the system settings to the factory settings before decommissioning the device.
3 Transport, handling and storage
▶ Store the device in its original packaging.
▶ When the device is to be stored again, use the original packaging.
▶ Otherwise, provide unused connections with either a mating connector or a protective cap and pack the device in suitable packaging.
▶ Observe the permissible ambient conditions for the device during storage (→ Technical data).
4 Intended use
The device monitors the flow and temperature in liquid and gaseous media.
5 Function
- The unit detects flow based on the calorimetric measuring principle.
- As additional process value the unit detects the medium temperature.
The device generates two output signals:
• OUT1: switching signal for flow rate
• OUT2: switching signal for temperature
5.1 Flow monitoring
The device detects flow based on the calorimetric measuring principle and switches the output OUT1.
With the factory default setting, the switch point is at LED 7.
The device's output is set to a normally open contact by default and can be switched to a normally closed contact.
The switch point LED indicates the switching status:
• LED orange = output closed.
• LED red = output open.
Normal operation
With normal flow, the output has the following status:
• Output closed for normally open function.
• Output open for normally closed function.

Fig. 1: Flow ≥ SP / normally open function

Fig. 2: Flow ≥ SP / normally closed function
Deviation from normal operation
If the flow velocity decreases, the switching status changes when the value falls below the switch point SP minus the hysteresis.

Fig. 3: Flow < SP / normally open function

Fig. 4: Flow < SP / normally closed function

The hysteresis changes with the flow velocity and it is essentially influenced by the set monitoring range. It is 2...5 cm/s for the setting 5...100 cm/s (= factory setting), it increases with higher flow velocities.
The typical response time of the device is 1 ... 10 s. It can be influenced by the setting of the switch point:
- Low switch point = quick reaction with rising flow.
• High switch point = quick reaction with falling flow.
5.2 Temperature monitoring
The device detects the current medium temperature and switches output OUT2.
The device's output is set to a normally open contact by default and can be switched to a normally closed contact.
In operating mode, the display indicates the flow rate. Press the ▶ button briefly to switch the device to the temperature display ➞ 14.
The switch point LED indicates the switching status:
• LED orange = output closed
• LED red = output open
The output OUT2 switches when the temperature exceeds the set switch point SP2. At factory setting (normally open function), the following applies:
• Output closed when medium temperature is ≥ SP2
• Output open when medium temperature is < SP2
5.3 IO-Link
IO-Link is a communication system for connecting intelligent sensors and actuators to automation systems. IO-Link is standardised in the IEC 61131-9 standard.

General information on IO-Link at io-link.ifm

Input Output Device Description (IODD) with all parameters, process data and detailed descriptions of the device at documentation.ifm.com
IO-Link offers the following advantages:
• Interference-free transmission of all data and process values
• Parameter setting in the running process or presetting outside the application
- Parameters for identifying the connected devices in the system
• Additional parameters and diagnostic functions
• Automatic backup and restore of parameter sets in case of device replacement (data storage)
- Logging of parameter sets, process values and events
• Device description file (IODD - Input Output Device Description) for easy project planning
• Standardised electrical connection
- Remote maintenance
6 Installation

CAUTION
During installation or in case of mechanical failure, high pressure or hot media can leak from the system.
▷ Risk of injury caused by pressure or burns.
▶ Ensure that the system is free of pressure during installation.
▶ Ensure that no media can leak at the mounting location during installation.
6.1 Installation position
6.1.1 Immersion depth


Fig. 5: Immersion depth
- The sensor tip must be completely surrounded by the medium.
- Recommended immersion depths: minimum 12 mm.
6.1.2 Recommended mounting position


Fig. 6: Recommended mounting position
- For horizontal pipes: mounting from the side.
- For vertical pipes: mounting in the rising pipe.
6.1.3 Conditionally possible installation position


Fig. 7: Conditionally possible installation position
- For horizontal pipes, if the pipe is free from build-up: mounting from below.
- For horizontal pipes, if the pipe is completely filled with medium: mounting from the top.
6.1.4 Impermissible installation position


Fig. 8: Impermissible installation position
- The sensor tip must not be in contact with the pipe wall.
- Do not mount in downpipes that are open at the bottom.
6.1.5 Orientation

Fig. 9: Flow direction (arrow)
▶ To ensure optimum measurement accuracy, install the sensor so that the connector is facing away from the direction of flow.

The side opposite the direction of flow is also marked by a hole above the wrench flat (1).
6.2 Interference
Structures in the pipe, bends, valves, reducing pieces and the like affect the function of the unit.
▶ Adhere to the distances between sensor and interference.


Fig. 10: Inlet and outlet pipe lengths
D: Outside diameter of the pipe
S: Interference
6.3 Process connection
Using process adapters the unit can be adapted to different process connections.
A correct fit of the unit and ingress resistance of the connection are only ensured using ifm adapters.
For small flow rates, ifm adapter blocks are available.

The device is supplied without accessories.
Information about available accessories at documentation.ifm.com.
The optimum function is not ensured when using components from other manufacturers.

Fig. 11: Connect the device to the process using the adapter
1: Process connection
2: Adapter
3: Sensor tip
4: Coupling nut
▶ Grease the threads of the process connection, adapter and sensor. Use a lubricating paste which is suitable and approved for the application.

Ensure no grease is applied to the sensor tip.
▶ Screw the suitable adapter into the process connection.
▶ Place the flow monitor onto the adapter and tighten the nut. Tightening torque 25 Nm. Ensure that the unit is correctly oriented.
7 Electrical connection

The unit must be connected by a qualified electrician.
Observe the national and international regulations for the installation of electrical equipment. Voltage supply according to SELV, PELV.
▶ Disconnect power.
▶ Connect the unit as follows:


Fig. 12: Wiring
1: L+ Voltage supply
2: OUT2 / • Digital output 2 (PNP): switching signal for temperature monitoring
IN • Programming wire for remote setting
3: L- Voltage supply
4: OUT1 • Digital output 1 (PNP): switching signal for flow monitoring
- IO-Link
8 Operating and display elements

The operating display indicates only the flow monitoring: LED 7 displays switch point SP1 at which the output OUT1 switches.

1: Operation indication
- The LEDs 0...9 represent the range between flow standstill and maximum flow.
- The green LEDs show the current flow.
- An illuminated LED shows the position of the switch point:
– Orange: output closed
- Red: output open
In the current example: normally open function (factory setting).
2: Setting buttons for adjustment and configuration
Change to the temperature display
▶ Briefly press the ▶ button.
▷ The device indicates the current temperature and the switch point for temperature in steps of 10\ °C for approx. 5 s.
①
| LED | 0 | 0...1 | 0...2 | 0...3 | 0...4 | 0...5 | ... | 0...9 |
| T | 0...9°C | 10...19°C | 20...29°C | 30...39°C | 40...49°C | 50...59°C | 90...99°C |

②
| LED | 0 | 1 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
| SP2 | 2...4°C | 5...14°C | 25...34°C | 35...44°C | 45...54°C | 55...64°C | 65...74°C | 75...80°C | --- |
Fig. 13: Temperature indication
1: The row of red LEDs indicates the current temperature.
In the example: T = 20...29 °C.
2: The green (orange) LED indicates the current switch point SP2 and the switching status of OUT2:
• LED green = output OUT2 open (OFF)
• LED orange = output OUT2 closed (ON)
In the example: SP2 = 45...54 °C, output open (at factory setting normally open).
9 Set-up
▶ Switch on the supply voltage.
▷ All LEDs light and go out again step by step. During this time, the output is closed if set to normally open and open if set to normally closed.
▷ The device is in the operating mode.

The operating display indicates only the flow monitoring: LED 7 displays switch point SP1 at which the output OUT1 switches.
▶ Let the normal flow circulate in the installation.
▶ Check the display and determine further actions:
| Display | Explanation | |
| 1 | ![]() | The factory set operating range is suited for the application.► ▶ If necessary, adjust the switch point to suit the application. |
| 2 | ![]() | The normal flow is below the display range.► ▶ Carry out high-flow adjustment.► ▶ Ajust the switch point to the application. |
| 3 | ![]() | Your normal flow exceeds the representation range of the display (LED 9 flashes).► ▶ Carry out high-flow adjustment. |
Tab. 1: Display settings at factory settings (→ Function)

The factory settings can be restored at any time (→ Reset Device).

For media other than water:
▶ Perform an additional calibration for minimum flow (→ Low-flow adjustment).
10 Parameter setting
Parameter setting can be carried out via the IO-Link interface or via the operating elements on the unit.
Parameters can be set before installation or during operation.

If you change parameters during operation, this will influence the function of the installation.
▶ Ensure that there will be no malfunctions in your installation.
During parameter setting the unit remains in the operating mode. It continues to monitor with the existing parameter until the parameter setting has been completed.

Depending on the parameter setting, the parameters available in the menu may change.
10.1 Parameter setting via the device keys
10.1.1 Switch point SP1 (flow rate)
For the factory setting the switch point is at LED 7. A change makes sense in the following cases:
-
The normal flow falls below the representation range of the display, see ➞ 15.
• The flow fluctuates strongly or pulsates.
• A faster response time of the device is required. -
Low switch point = quick reaction with rising flow.
– High switch point = quick reaction with falling flow.
▶ Briefly press the Ⓓ button.
▷ The switch point LED (SP1) is flashing.
▶ Press Ⓐ or ▶ as often as required.
▷ Each press of the pushbutton shifts the LED by one position in the indicated direction.
▶ When the required switch point is reached, do not press the button for more than 2 seconds.
▷ The device goes into operating mode with the newly set value.
10.1.2 Switch point SP2 (temperature)
▶ Briefly press the ▶ button.
▷ The device indicates the current temperature and the switch point for temperature in steps of 10\ °C for approx. 5 s:

Fig. 14: Display mode
1: Row of red LEDs: current temperature → 14.
2: LED green: current switch point SP2 ➞ 14 (range display; exact value ➞ Fig. setting mode) If the current temperature is above the switch point, the LED is orange.
3: Setting ranges for the switch point LED.
▶ Briefly press the button ▶ again within 5 s.
▷ The setting mode for SP2 is activated.
▶ Press < or ▶ as often as required.
▷ Each press of the pushbutton shifts the switch point in the indicated direction.
▷ The switch point is indicated by 2 green LEDs: LED on = tens digit, LED flashing = units digit. The switch point can be changed in 1 °C increments.
▶ When the required switch point is reached, do not press the button for more than 5 seconds.
▷ The device returns to display mode (→ Figure above).
▷ After another 5 seconds the device returns to the operating mode with the newly set value.



Fig. 15: Setting mode
A: Current switch point when the setting mode is activated. Example: SP2 = 51.
• LED green flashing: units digit of SP2
• LED green on: tens digit of SP2.
B: Shifting the units digit. Example: Setting SP2 = 53 by pressing the ▶ button twice.
C: Shifting the tens digit. Example: Setting SP2 = 60 by pressing the ▶ button until it goes beyond LED 9. The cycle starts again at LED 0, and the tens digit moves one position to the right.
10.1.3 High-flow adjustment
The device defines the current flow as the normal flow and adapts the display accordingly.
▶ Let the normal flow circulate in the installation.
▶ Press the ⬤ button and keep it pressed..
▷ LED 9 is on, after approx. 5 seconds it flashes.
▶ Release the ⬤ button.
▷ The device is adapted to the flow conditions. It goes into operating mode.
▷ The display should now show an LED indication similar to example 1 ➞ 15.

If all LEDs are flashing red, the adjustment has failed. Possible causes ➕ Chapter “Troubleshooting”. The device switches to operating mode with unchanged values.

The adjustment affects the switch point: It is increased proportionally (maximum up to LED 7).
10.1.4 Low-flow adjustment
If the device is used in media other than water, the device should additionally be adapted to the minimum flow.

The low-flow adjustment may only be carried out after the high-flow adjustment.
▶ Let the minimum flow circulate in the installation or ensure flow standstill.
▶ Press the Ⓐ button and keep it pressed.
▷ LED 0 is on, after approx. 5 seconds it flashes.
▶ Release the Ⓓ button.
▷ The device adopts the new value and enters operating mode.
10.1.5 Switch point logic
Upon delivery, the device is set to normally open. If necessary, the outputs can be changed to normally closed function. The setting applies to both outputs.
Changeover to normally closed function:
▶ Press the Ⓐ button for at least 15 seconds.
▷ LED 0 is on, after approx. 5 seconds it flashes.
▷ After 10 seconds the current setting is displayed: LEDs 5...9 are on in orange (= outputs in normally open function).
▷ After approx. 15 seconds the LEDs 0...4 flash orange.
▶ Release the Ⓓ button.
▷ The outputs are changed to normally closed function.
▶ For a new changeover repeat the operation.

Using an IO-Link capable parameter setting tool, the outputs can be separately set as normally closed or normally open.
10.1.6 Reset the device
▶ Press the ⬤ button for at least 15 seconds.
▷ LED 9 is on, after approx. 5 seconds it flashes.
▷ After approx. 15 seconds LEDs 0...9 flash orange.
▶ Release the ⬤ button.
▷ All settings are reset to the factory setting:
• Operating range: 5 ...100 cm/s for water
- Switch point SP1 (flow rate) = LED 7
- Switch point SP2 (temperature) = LED 0 (4 °C)
• Output function: normally open
- Not locked
10.1.7 Lock / unlock
The unit can be locked electronically to prevent unauthorised setting.
Factory setting: not locked.
▶ Press both setting keys for 10 seconds.
▷ The display goes off.
▷ The unit is locked.
▶ For unlocking repeat the process.
10.2 Parameter setting via IO-Link
The device parameters can be set via the IO-Link interface in the following ways, for example:
- Parameter setting via a suitable parameter setting software, e.g. ifm moneo|configure
• Parameter setting via a PLC
• Parameter setting via an IIoT application
Requirements for parameter setting via the IO-Link interface:
√ The Input Output Device Description (IODD) for the device in case of parameter setting via a parameter setting software, see documentation.ifm.com
√ The IO-Link interface description (PDF) for the device in case of parameter setting via a PLC or IIoT application, see documentation.ifm.com
√ An IO-Link master
▶ Connect the IO-Link master to the parameter setting software, the PLC or the IIoT application.
▶ Connect the device to a suitable free port of the IO-Link master.
▶ Set the port of the IO-Link master to the IO-Link operating mode.
▷ The device changes to the IO-Link mode.
▶ Change the parameter settings in the software.
▶ Write the parameter settings to the device.

Support for system integration and parameter setting via IO-Link:
→ Manual of the parameter setting software (e.g. moneo)
Explanations and startup packages at ifm.com/cnt/io-link-system-integration.
Via IO-Link, all parameters can be set that are also accessible via the keys on the device. In addition, the functions described below are available.
Device information
Unalterable device information is stored on the device. In addition, an application-specific tag can be assigned to the device.
Switch-on and switch-off delay
For both outputs a delay time can be set for the respective output to switch and to be reset. The switch-on and switch-off delay is in the range from 0 to 60 seconds.
Switch point logic
A different switch point logic (normally closed or normally open) can be set for each of the two outputs. When parameter setting via the device keys, both outputs have the same switch point logic.
11 Operation
The device detects the flow and switches the outputs according to the parameter setting.
The device displays the current flow and the switching status.

In case of power failure or interruption of the operating voltage, all settings remain.
| Display | Explanation | |
| 1 | ![]() | Green LED bar: current flow within the display range. Indication of the switch point:LED orange: output closed. LED red: output open. |
| 2 | ![]() | LED 9 flashes: current flow above the display range. |
| 3 | ![]() | LED 0 flashes: current flow far below the display range. |
Tab. 2: Display settings at factory settings (NO; SP1 = LED 7)

Pressing the ▶ button during operation will switch the display to the temperature indication for a few seconds ➞ 14.
12 Troubleshooting
The device displays the following faults via the LEDs:
| Display | Description | Corrective measures |
| The LED display goes out briefly (0.6 s) when a button is pressed. | The device is permanently locked. An IO-Link communication is active. | ▸ Unlock device.▸ Terminate the IO-Link communication. |
LEDs are permanently off. | Operating voltage too low (< 19 V) or failed. | ▸ Ensure correct voltage supply. |
The operating indicator and 5 red LEDs on the left are on alternately. | Short circuit at switching output OUT1. | ▸ Remove short circuit.▸ The device immediately returns to the normal operating status and the current operating indication appears in the display. |
The operating indicator and 5 red LEDs on the right are on alternately. | Short circuit at switching output OUT2. | ▸ Remove short circuit.▸ The device immediately returns to the normal operating status and the current operating indication appears in the display. |
LEDs flash red after flow adjustment. The device then returns to the operating mode with unchanged values. | High-flow adjustment or low-flow adjustment not successful. | ▸ Check whether all installation requirements have been met.▸ Increase the distance between maximum flow and minimum flow and carry out the adjustment again.▸ ▶ Carry out the two adjustment operations again in the right sequence. |
13 Maintenance, repair and disposal
Only the manufacturer is allowed to repair the unit.
▶ Ensure that the sensor tip is free from build-up:
- Check the sensor tip regularly for deposits. Determine check intervals based on the application.
- In case of soiling clean the sensor tip with a soft cloth. Stubborn build-up, such as lime, can be removed using a common vinegar cleaning agent.
▶ After use, dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations.






LEDs are permanently off.
The operating indicator and 5 red LEDs on the left are on alternately.
The operating indicator and 5 red LEDs on the right are on alternately.
LEDs flash red after flow adjustment. The device then returns to the operating mode with unchanged values.