IFM O1D121 - Rangefinder

O1D121 - Rangefinder IFM - Free user manual and instructions

Find the device manual for free O1D121 IFM in PDF.

📄 23 pages English EN Download 💬 AI Question
Notice IFM O1D121 - page 1
View the manual : Français FR Deutsch DE English EN
Pick your language and provide your email: we'll send you a specifically translated version.

User questions about O1D121 IFM

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Rangefinder in PDF format for free! Find your manual O1D121 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. O1D121 by IFM.

USER MANUAL O1D121 IFM

Operating instructions

Photoelectric distance sensor

01D

Contents

1 Preliminary note 3

1.1 Symbols used 3
1.2 Warnings.... 3

2 Safety instructions.... 4

3 Intended use.... 6

3.1 Applications 6

4 Functions 7

4.1 Output function hysteresis.... 7
4.2 Output function window.... 7
4.3 Analogue function mode 7
4.4 Switch off the laser 7

5 Installation.... 8

5.1 Installation conditions 8
5.2 Mounting accessories 8

6 Electrical connection.... 9
7 Operating and display elements 10
8 Menu.... 11

8.1 Menu structure 11
8.2 Explanation of the menu 11

9 Operating modes 13

9.1 Run mode 13
9.2 Display mode 13
9.3 Object reflectivity.... 13
9.4 Programming mode.... 13

10 Parameter setting 14

10.1 General parameter setting.... 14

10.1.1 Setting a parameter value.... 14
10.1.2 Change from menu level 1 to menu level 2.... 14
10.1.3 Electronic lock.... 14

10.2 Configuration of the basic settings 15

10.2.1 Selection of the display unit.... 15
10.2.2 Set the display 15
10.2.3 Configure OUT1 15
10.2.4 Hysteresis function 15
10.2.5 Setting of the switch point for hysteresis function OUT1 16
10.2.6 Window function 16
10.2.7 Setting of the switch points for window function OUT1 17
10.2.8 Configure OUT2 17
10.2.9 Setting of the switch point for hysteresis function OUT2 18
10.2.10 Setting of the switch points for window function OUT2 18
10.2.11 Scaling of the measuring range (analogue output) 18

10.3 Teach mode 19

10.3.1 Setting of the sampling rate.... 19
10.3.2 Setting of the repeatability.... 20

10.4 Extended functions 20

10.4.1 Set the delay time for switching outputs 20
10.4.2 Setting of the fault suppression time for switching output / analogue output ..... 20
10.4.3 Reset all parameters to factory setting 20
10.4.4 Display of the software version number.... 21

11 Operation 22

11.1 Error indications 22
Maintenance, repair and disposal 23

1 Preliminary note

You will find instructions, technical data, approvals and further information using the QR code on the unit / packaging or at documentation.ifm.com.

1.1 Symbols used

√ Requirement
Instructions
Reaction, result

[...] Designation of keys, buttons or indications

→ Cross-reference

IFM O1D121 - Symbols used - 1

Important note

Non-compliance may result in malfunction or interference.

IFM O1D121 - Symbols used - 2

Information

Supplementary note

1.2 Warnings

Warnings indicate the possibility of personal injury and damage to property. This enables safe product handling. Warnings are graded as follows:

IFM O1D121 - Warnings - 1

WARNING

Warning of serious personal injury

▷ If the warning is not observed, fatal and serious injuries are possible.

IFM O1D121 - Warnings - 2

CAUTION

Warning of minor to moderate personal injury

▷ If the warning is not observed, minor to moderate injuries are possible.

ATTENTION

Warning of damage to property

▷ If the warning is not observed, damage to property is possible.

2 Safety instructions

- The unit described is a subcomponent for integration into a system.

  • The system architect is responsible for the safety of the system.
  • The system architect undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system. This documentation must contain all necessary information and safety instructions for the operator, the user and, if applicable, for any service personnel authorised by the architect of the system.

  • Read this document before setting up the product and keep it during the entire service life.

  • The product must be suitable for the corresponding applications and environmental conditions without any restrictions.
  • Only use the product for its intended purpose ( → → Intended use).
  • If the operating instructions or the technical data are not adhered to, personal injury and/or damage to property may occur.
  • The manufacturer assumes no liability or warranty for any consequences caused by tampering with the product or incorrect use by the operator.
  • Installation, electrical connection, set-up, operation and maintenance of the product must be carried out by qualified personnel authorised by the machine operator.
  • Protect units and cables against damage.

IFM O1D121 - Safety instructions - 1

WARNING

Visible laser light; laser protection class 2.

▷ Use of controls or adjustments other than those specified herein may result in hazardous radiation exposure. Damage to the retina is possible.
▶ Do not stare into the laser beam!
▶ Apply the enclosed labels (laser warning) in the immediate vicinity of the unit.
▶ Adhere to the caution and warning notes on the product label.
▶ Use the enclosed label for the power supply cable.
▶ EN/IEC 60825-1 : 2007 and EN/IEC 60825-1 : 2014 Complies with 21 CFR 1040.10 except for conformance with IEC 60825-1 Ed. 3., as described in Laser Notice No. 56, dated May 8, 2019.

Label for supply cable
IFM O1D121 - Safety instructions - 2

Product label
IFM O1D121 - Safety instructions - 3

3 Intended use

The unit is used as a photoelectric distance sensor.

3.1 Applications

The optical distance sensor measures distances between 0.2...10 m.

• It has a background suppression at >10...19 m.
- The measured value is shown in a 10-segment display.
• 2 output signals (according to the set output function).
• Certification 21 CFR PART 1040.10

The distance between the sensor and the background must be limited to max. 19 m. Otherwise measured values can be ambiguous ( → Installation conditions ☐ 8)

4 Functions

4.1 Output function hysteresis

The hysteresis keeps the switching state of the output stable if the measured value varies about the sensing range. Both outputs [OUT1] and [OUT2] can be set as hysteresis function. Hysteresis function ( → 15)

4.2 Output function window

The window function enables the monitoring of a defined acceptable range. Both outputs [OUT1] and [OUT2] can be set as window function. Window function ( → ☐ 16)

4.3 Analogue function mode

An analogue signal that is proportional to the distance can be output at [OUT2]. Scaling of the measuring range (analogue output)

4.4 Switch off the laser

For safety and maintenance purposes the laser of the unit can be temporarily switched off via the input on pin 5.

Input signal at pin 5Laser
Low / not usedon
HighOff

5 Installation

5.1 Installation conditions

▶ Install the unit so that the object to be detected is within a measuring range of 0.2...10 m.

The unambiguity range of the sensor is fixed to 19.2 m. Objects within a range >10...19.2 m are suppressed.

Reflecting objects in the direct beam path of the sensor - also in the range >19.2 m – are to be avoided by the customer. Otherwise the measured values can be ambiguous.

5.2 Mounting accessories

The unit is supplied without mounting accessories.

Examples of mounting accessoriesArt. no.
Protective cover O1DE21133
Mounting set E2D101 + E20938 + E20951E21079
Mounting set O1D (for rod mounting ∅ 12 mm)E2D101
Mounting rod straight ∅ 12 mm / M10E20938
Mounting set O1D (for rod mounting ∅ 14 mm)E2D111
Mounting rod straight ∅ 14 mm / M12E20939
Mounting and fine adjustment unit for O1D laser devices (rod or free-standing; depending on the clamp)E1D100

IFM O1D121 - Mounting accessories - 1

Fig. 1: Installation example

1: Mounting set for rod ∅ 12 mm

Art. no. E2D101

2: Mounting rod straight ∅ 12 mm / M10

Art. no. E20938

6 Electrical connection

The device must be connected by a qualified electrician.

▶ Observe the national and international regulations for the installation of electrical equipment.
▶ Voltage supply according to SELV, PELV.

▶ Disconnect power.

▶ Connect the device as follows:

IFM O1D121 - Electrical connection - 1

Fig. 2: Wiring diagram (colours to DIN EN 60947-5-2)

1 =BN (brown)2 =WH (white)
3 =BU (blue)4 =BK (black)
5 =GY (grey)

7 Operating and display elements

IFM O1D121 - Operating and display elements - 1

1:4x green LEDLighting LED = power and set display unit (mm, m, inch)
2:4x yellow LEDIndication of the switching state; is on if the corresponding output is switched.
3:4-digit alphanumeric displayIndication of the measured distance, the parameters and parameter values.
4:Programming button [SET]Setting of the parameter values (scrolling by holding pressed, incrementally by pressing once).
5:Programming button [MODE/ENTER]Selection of the parameters and acknowledgement of the parameter values.

8 Menu

8.1 Menu structure

IFM O1D121 - Menu structure - 1

8.2 Explanation of the menu

ParameterExplanation
[OU1]Configuration for output 14 switching functions can be selected:[Hno], [Hnc], [Fno], [Fnc]
Configure OUT1 (→ □ 15)
[SP1]Switch point for hysteresis function OUT1
Limit value at which the output with selected hysteresis function changes its switching state (object near-er/farther than distance set). [SP1] is only active if [OU1] = [Hno] or [Hnc]. Setting of the switch point for hysteresis function OUT1 (→ □ 16)
[nSP1][FSP1]Switch points for window function OUT1
Limit values at which the output with selected window function changes its switching state (object pres-ent/not present between the distance "near" and the distance "far"). [nSP1] = switch point "near" / [FSP1] = switch point "far". [nSP1] / [FSP1] are only active if [OU1] = [Fno] or [Fnc]. Setting of the switch points for window function OUT1 (→ □ 17)
[OU2]Configuration for output 24 switching functions and 2 analogue signals can be selected:[Hno], [Hnc], [Fno], [Fnc], [I], [U]
Configure OUT2 (→ □ 17)
[SP2]Switch point for hysteresis function OUT2
Limit value at which the output with selected hysteresis function changes its switching state (object near-er/farther than distance set). [SP2] is only active if [OU2] = [Hno] or [Hnc]. Setting of the switch point for hysteresis function OUT2
[nSP2][FSP2]Switch points for window function OUT2
Limit values at which the output with selected window function changes its switching state (object pres-ent/not present between the distance "near" and the distance "far"). [nSP2] = switch point "near" / [FSP2] = switch point "far". [nSP2] / [FSP2] are only active if [OU2] = [Fno] or [Fnc]. Setting of the switch points for window function OUT2
[ASP]Analogue start point
Measured value at which 4 mA / 0 V are provided. [ASP] is only active if [OU2] = [I] or [U]. Scaling of the measuring range (analogue output)
[AEP]Analogue end point
Measured value at which 20 mA / 10 V are provided. [AEP] is only active if [OU2] = [I] or [U]. Scaling of the measuring range (analogue output)
[TEAC]Teach mode
Selection "sampling rate" or "repeatability".--- FEHLENDER LINK ---
[EF]Extended functions
Press [SET] to open the submenu "Extended functions". Extended functions
[dS1][dr1][dS2][dr2]Delay for the switching outputs▶ [dSx] = switch-on delay; [drx] = switch-off delay. The output does not immediately change its switching state when the switching condition is met but only after the delay has elapsed. If the switching condition is no longer met after the delay has elapsed, the switching state of the output does not change. [dS2] and [dr2] are not effective if [OU2] = [I] or [U].--- FEHLENDER LINK ---
[dFo]Setting of the fault suppression time for switching outputs/analogue output
This function suppresses brief saturation of the measuring element (such saturation may result from di-rect reflection or strong fluctuations in brightness). During the set delay time, the latest valid value meas-ured is displayed, the output signals remain unchanged. Setting of the fault suppression time for switch-ing output / analogue output
[diS]Setting of the display7 settings can be selected:[d1], [d2], [d3], [rd1], [rd2], [rd3], [OFF]--- FEHLENDER LINK ---
[Uni]Setting of the display unit
Selection of the unit of measurement for [SP1], [SP2], [ASP], [AEP]
Options: [mm], [m], [inch]--- FEHLENDER LINK ---
[rES]Restore Factory Settings--- FEHLENDER LINK ---
[SW]Display of the software version number--- FEHLENDER LINK ---

9 Operating modes

9.1 Run mode

The run mode is the normal operating mode.

After power on the unit is in the Run mode. It carries out its monitoring function and generates output signals according to the set parameters.

The display indicates the current distance, the yellow LEDs signal the switching state of the outputs.

9.2 Display mode

Indication of the parameters and the set parameter values.

▶ Briefly press [MODE/ENTER].
▷ The unit goes to the display mode. Internally it remains in the operating mode. The set parameter values can be read:
▶ To scroll through the parameters, briefly press[MODE/ENTER].
▶ To display the corresponding parameter value, briefly press [SET].
▷ After another 15 s the unit returns to the Run mode.

9.3 Object reflectivity

Indication of the object reflectivity.

▶ Press [SET] in the Run mode.
▷ The unit displays an orientation value for the object reflectivity (e.g. +100 corresponds to a white object, +020 corresponds to a grey object).

9.4 Programming mode

Setting a parameter value

10 Parameter setting

During parameter setting the unit remains internally in the operating mode. It continues its monitoring function with the existing parameters until the change has been completed.

10.1 General parameter setting

10.1.1 Setting a parameter value

Set the display unit [ Uni ] before the values for the parameters are defined. In case of subsequent changes of the display unit, rounding errors during internal conversion to other units may falsify the set values. Selection of the display unit (→ 15)

1Select Parameter▶ Press [MODE/ENTER] until the required parameter is displayed.
2Set parameter value▶ Press [SET] and keep it pressed. ▷ The current parameter value flashes for 5 s. ▶ Increase the setting value step by step by pressing the button once or continuously by holding it down.
Decrease the value: let the display move to the maximum setting value. Then the cycle starts again at the minimum setting value.
3Confirmation of the parameter value▶ Briefly press [MODE/ENTER]. ▷ The parameter is displayed again; the new parameter value is effective.
4Set other parameters▶ Start again with step 1.
5Finish parameter setting▶ Wait for 15 s or press [MODE/ENTER]. ▷ The current measured value is displayed.

10.1.2 Change from menu level 1 to menu level 2

▶ Repeatedly press [MODE/ENTER] until [EF] is displayed.
▶ Briefly press [SET].
▷ The first parameter of the submenu is displayed.

10.1.3 Electronic lock

The unit can be locked electronically to prevent unauthorised setting. On delivery the unit is not locked.

Locking

▶ Make sure that the unit is in the normal operating mode.
▶ Keep [MODE/ENTER] + [SET] pressed until [Loc] is displayed.
▷ The unit is locked.

[Loc] is displayed briefly if you try to change parameter values on the locked unit during operation.

Unlocking

▶ Keep [MODE/ENTER] + [SET] pressed until [uLoc] is displayed.
▷ The unit is unlocked.

IFM O1D121 - Electronic lock - 1

If no button is pressed for 15 s during the setting procedure, the unit returns to the Run mode with unchanged values.

10.2 Configuration of the basic settings

10.2.1 Selection of the display unit

Set [Uni] before the values for the parameters [SPx], [nSPx], [FSPx], [ASP], [AEP] are defined. In case of subsequent changes of the display unit rounding errors during internal conversion to other units may falsify the set values.

▶ Change to [EF].
▶ Select [Uni] and set the unit of measurement. Selection of the unit of measurement: [mm], [m], [inch]
▶ Confirm with [MODE/ENTER].
▷ The selected unit is indicated by a green LED on the display.

10.2.2 Set the display

▶ Change to [EF].
▶ Select [diS] and make settings.

7 settings can be selected:

• [d1] = update of the measured values every 50 ms.
• [d2] = update of the measured values every 200 ms.
• [d3] = update of the measured values every 600 ms.
- [rd1], [rd2], [rd3] = display as for [d1], [d2], [d3] rotated by 180°. The update of the measured value only refers to the display. It has no effect on the outputs.
- [OFF] = the measured value display is deactivated in the Run mode. When one button is pressed, the current measured value is displayed for 15 s.
▶ Confirm with [MODE/ENTER].

The LEDs remain active even if the display is deactivated.

10.2.3 Configure OUT1

▶ Select [OU1] and set the switching functions.

Switching functions:

• [Hno] = hysteresis function / normally open
• [Hnc] = hysteresis function / normally closed
• [Fno] = window function / normally open
• [Fnc] = window function / normally closed

▶ Confirm with [MODE/ENTER].

10.2.4 Hysteresis function

The hysteresis keeps the switching state of the output stable if the measured value varies about the sensing range. In both cases the set and reset points are symmetrically arranged about the selected switch point [SPx]. The hysteresis is the distance between set and reset points; it is calculated on the basis of the repeatability with a safety factor of 1.5. The calculation is based on the repeatability for max. 40 klx.

Example Hno

  1. For the output function [Hno] the output switches when the object approaches and when the set point (A) is reached.

IFM O1D121 - Hysteresis function - 1

[SPx]: Switch point
A: Switch-on point
B: Reset point

  1. When the object is removed again, the output does not switch back before the reset point (B) is exceeded. The reset point (B) is above the set point (A).

IFM O1D121 - Hysteresis function - 2

[SPx]: Switch point
A: Switch-on point
B: Reset point

If the output function [Hnc] has been selected, the set and reset points are reversed. The output switches off when the object approaches. When the object is removed again, the output switches.

Switching state of the outputs

Output functionObject distance (D)switching status
[Hno]D < [SPx]Closed
D > [SPx]Open
[Hnc]D < [SPx]Open
D > [SPx]Closed

10.2.5 Setting of the switch point for hysteresis function OUT1

▶ Under [OU1], select the output function [Hno] or [Hnc].
▶ Confirm with [MODE/ENTER].
▶ Select [SP1] and set the switch point.
▶ Confirm with [MODE/ENTER].

10.2.6 Window function

It is possible to define a window for the object recognition for each of the two outputs (OUT1 / OUT2).

Switches off when the object is detected

IFM O1D121 - Window function - 1

[nSPx]: switch point "near"
[FSPx]: switch point "far"
FE: window

If the measured value is between the switch point “near” [nSPx] and the switch point “far” [FSPx], the output is opent (if [OUx] = [Fnc]).

Switches when the object is detected

IFM O1D121 - Window function - 2

[nSPx]: switch point "near"
[FSPx]: switch point "far"
FE: window

If the measured value is between the switch point "near" [nSPx] and the switch point "far" [FSPx], the output is closed (if [OUx] = [Fno]).

Switching state of the outputs

Output functionObject distance (D)switching status
[Fno]D < [nSPx]Open
D > [FSPx]
[nSPx] < D < [FSPx]Closed
[Fnc]D < [nSPx]Closed
D > [FSPx]
[nSPx] < D < [FSPx]Open

IFM O1D121 - Window function - 3

Both window limits([nSPx] and [FSPx]) work with a switching hysteresis.

10.2.7 Setting of the switch points for window function OUT1

▶ Under [OU1], select the output function [Fno] or [Fnc].
▶ Confirm with [MODE/ENTER].
▶ Select [nSP1] and set the switch point “near”.
▶ Confirm with [MODE/ENTER].
▶ Select [FSP1] nd set the switch point "far".
▶ Confirm with [MODE/ENTER].

10.2.8 Configure OUT2

▶ Select [OU2].
▶ Set switching functions or analogue signals:

• [Hno] = hysteresis function / normally open
• [Hnc] = hysteresis function / normally closed
• [Fno] = window function / normally open
• [Fnc] = window function / normally closed
• [I] = current output analogue 4...20 mA:
• [U] = voltage output analogue 0...10 V
▶ Confirm with [MODE/ENTER].

10.2.9 Setting of the switch point for hysteresis function OUT2

▶ Select [OU2], [Hno] or [Hnc].
▶ Confirm with [MODE/ENTER].
▶ Select [SP2] and set the switch point.
▶ Confirm with [MODE/ENTER].

Hysteresis function ( → 15)

10.2.10 Setting of the switch points for window function OUT2

▶ Select [OU2], [Fno] or [Fnc].
▶ Confirm with [MODE/ENTER].
▶ Select [nSP2] and set the switch point “near”.
▶ Confirm with [MODE/ENTER].
▶ Select [FSP2] nd set the switch point "far".
▶ Confirm with [MODE/ENTER].

Window function ( → 16)

10.2.11 Scaling of the measuring range (analogue output)

▶ Select [OU2], [I] or [U].
▶ Confirm with [MODE/ENTER].
▶ Select [ASP] and set the "Analogue start point". With [ASP]], you define at which measured value the output signal is 4 mA / 0 V.
▶ Confirm with [MODE/ENTER].
▶ Select [AEP] and set the "Analogue end point". With [AEP]], you define at which measured value the output signal is 20 mA/10 V. It can also be selected so that it is located before [ASP]. This implements a falling edge.
▶ Confirm with [MODE/ENTER].

Minimum distance between [ASP] and [AEP]: 100 mm When the minimum distance is not reached, the error message [SIZE] will be displayed.

Current output 4...20 mA

Factory settingMeasuring range scaled
IFM O1D121 - Scaling of the measuring range (analogue output) - 1

MEW: Final value of the measuring range

In the set measuring range the output signal is between 4 and 20 mA.

Faults are also displayed:

Too much light or object too near: 3.5 mA for a rising edge ([ASP] < [AEP]), 20.5 mA for a falling edge ([ASP] > [AEP]).

Object too far or no object present:

20.5 mA for rising edge. 3.5 mA for falling edge.

Voltage output 0...10 V

Factory settingMeasuring range scaled
IFM O1D121 - Scaling of the measuring range (analogue output) - 2

MEW: Final value of the measuring range

In the set measuring range the output signal is between 0 and 10 V.

10.3 Teach mode

10.3.1 Setting of the sampling rate

The sampling rate indicates the maximum time after which a new result of measurement is provided and the outputs are updated. The switching frequency is typ. approx. 1/3 of the sampling rate.

▶ Select [TEAC] and keep [SET] pressed until [WAIT] is displayed.
▷ [rATE] and [rEPr] are displayed alternately.
▶ If [rATE] is displayed: Press [SET] until the preset sampling rate value flashes.
▶ Enter a value incrementally by pressing [SET] repeatedly.
▶ Confirm with [MODE/ENTER].

▷ [WAIT] is displayed while the repeatability [rEPr] is calculated.
▷ The sampling rate [rATE] and repeatability [rEPr] are displayed alternately.

10.3.2 Setting of the repeatability

▶ Select [TEAC] and keep [SET] pressed until [WAIT] is displayed.
▷ [rATE] and [rEPr] are displayed alternately.
▶ If [rEPr] is displayed: Press [SET] until the preset repeatability value flashes.
▶ Enter a value incrementally by pressing [SET] repeatedly.
▶ Confirm with [MODE/ENTER].
▷ [WAIT] is displayed while the sampling rate [RATE] is calculated.
▷ The sampling rate [rATE] and repeatability [rEPr] are displayed alternately.

10.4 Extended functions

10.4.1 Set the delay time for switching outputs

▶ Select [EF].
▶ Press [SET] to change to the menu [EF].
▶ Select parameter with [MODE/ENTER]:
▶ [dSx] = switch-on delay; [drx] = switch-off delay
▶ Set the parameter value with [SET]:
▶ Setting range [s]: 0 / 0.1...5 s in steps of 0.1 s (0 = delay time is not active)
▶ Confirm with [MODE/ENTER].

10.4.2 Setting of the fault suppression time for switching output / analogue output

▶ Select [EF].
▶ Press [SET] to change to the menu [EF].
▶ Select[dFo] (old designation: [dAP]).
▶ Set the parameter value with [SET]: Setting range [s]: 0.0...0.1...0.2...0.5...1...2...5.
▶ Confirm with [MODE/ENTER].

With [dFo], the error types "too much light" and "not enough light" are suppressed.

10.4.3 Reset all parameters to factory setting

▶ Select [EF].
▶ Press [SET] to change to the menu [EF].
▶ Select [rES] and keep [SET] pressed until [----] is displayed.
▶ Confirm with [MODE/ENTER].
▷ The unit changes to the Run mode.

10.4.4 Display of the software version number

▶ Select [EF].
▶ Press [SET] to change to the menu [EF].
▶ Select[SW], then press [SET].
▷ The software version number is displayed.
▶ Press [MODE/ENTER] to return to the menu [EF].

11 Operation

▶ After installation, electrical connection and programming, check whether the unit operates correctly.
▷ If the unit has been correctly set up, the distance to the object is indicated.

IFM O1D121 - Operation - 1

Lifetime of a laser diode: 50000 hours.

11.1 Error indications

IndicationPossible causeSwitching outputCurrent output / voltage output
[Hno][Hnc][Fno][Fnc][ASP] < [AEP][ASP] > [AEP]
[++]Too much light, e.g. reflective surfaceONOFFOFFON3.5 mA/0 V20.5 mA/10 V
[--]Not enough light, no objectOFFONOFFON20.5 mA/10 V3.5 mA/0 V
[nEAr]Object to be measured outside the measuring range < 0.2 mONOFFOFFON3.5 mA/0 V20.5 mA/10 V
[FAr]Object to be measured outside the measuring range > 10 mOFFONOFFON20.5 mA/10 V3.5 mA/0 V
[Errp]Plausibility (e.g. object too fast) X1) X1) X1) X1) X1) X1)
[LoFF]Laser switched offOFFONOFFON20.5 mA/10 V3.5 mA/0 V
[SC1]Short circuit in switching output 12)2)
[SC2]Short circuit in switching output 22)2)
[SC]Short circuit in all switching outputs2)2)

1) unchanged

2) [SC1] or [SC] only active if output 2 is configured as switching output.

3) see IODD of the device

12 Maintenance, repair and disposal

▶ Keep the lenses of the sensor free from soiling.
▶ For cleaning do not use any solvents or cleaning agents which could damage the plastic parts.
▶ After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations.

Faulty sensors must only be repaired by the manufacturer.