TAA131 - Temperature transmitter IFM - Free user manual and instructions
Find the device manual for free TAA131 IFM in PDF.
User questions about TAA131 IFM
0 question about this device. Answer the ones you know or ask your own.
Ask a new question about this device
Download the instructions for your Temperature transmitter in PDF format for free! Find your manual TAA131 - IFM and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. TAA131 by IFM.
USER MANUAL TAA131 IFM
- It detects the current system temperature,
- converts it into digital coded analog values
- and transfers these values to the control level (master, controller or host). Analog value representation Signed 16-bit value as two's complement value. The analog value transmission protocol is specified in the slave profile 7.3. A master of AS-i version 2.11 detects the slave automatically. The ana- log value transmission to slave profile 7.3 is then supported. Masters of AS-i version 2.0 require a special driver (additional function block, available as an accessory).
- Temperature resistance
Maximum operation time depending on the medium temperatureInstallation Addressing You can address the sensor by using an addressing unit, the master or by means of the AS-i software of the host (the components must sup- port AS-i version 2.11). Assign an address between 1 and 31. At the factory the address is set to 0. Mechanical installation Mount the unit to G¼ process connection. Connection to the AS-i system Connect the sensor with the AS-i system by using the M12 connector. Voltage is supplied via the AS-i network. Wiring: Referring to UL: For use on a low voltage circuit with overcurrent protection in accordance with UL873 Tab. 28.1 or Imax = 100/Ub (Ub = voltage of the circuit).
ENGLISH Core colours of ifm sockets: 1 = BN (brown), 3 = BU (blue) ASI+ ASI
BUInstallation and set-up / Operation After mounting and wiring check whether the unit operates correctly. Indication at the sensor in the operating mode: Slave profile Representation of measured values by data bits D16 ... D1 Fault handling Automatic fault handling according to AS-i version 2.1.
- Power-up: During power-up the data is marked faulty until a valid data transfer is guaranteed.
- After interruption of the data communication the watchdog function starts communication again.
I/O Code [hex] 7 ID Code [hex]
Extended ID2 Code [hex] C ID1 Code code for temperature values [hex] 6 Slave address (factory setting) 0 Overflow (measured value outside the value range), overflow bit is set
Overrange (measured value is valid but outside the nominal range)
Nominal Range (measured value in the specified value range) -100 ... 1500 Underrange (measured value is valid but outside the nominal range) -150 ... -100 Underflow (measured value outside the value range), overflow bit is set -32768 Representation of measured values following ID1 °C × 0.1 Increments min. 0.1 LED green ON = unit is then ready for operation LED red ON = no communication FLASHING = internal fault is transferred to the master as periphery fault• Data triple in wrong order: If a fault occurs, the sensor sets its data triples to 0 (invalid) and waits for a new triple sequence. Data bits During one transmission cycle the following data is transferred in data triples.
Only 1 measuring channel is used. The bits E3, E2 and E1 are always 0. The analog values measured are transferred via the data bits D1 ... D16 according to slave profile 7.3. Overflow-Bit Valid-Bit
Overflow-Bit: O = 0: measured value is within the value range O = 1: measured value is outside the value range (above max. value for overload or below minimum value for overload) Valid-Bit: V = 0: measured value not valid V = 1: measured value validTechnical data
EasyManual