USER MANUAL V160E75RS vänEE

USER AND INSTALLER MANUAL

vänEE V160E75RS - USER AND INSTALLER MANUAL - 1

vänEE V160E75RS - USER AND INSTALLER MANUAL - 2

A110H65RT
A130H65RT A130H65RS
A130E65RT
A150H75NT* A1150H75NS*
*A160H75RT**A160H75RS
A160H65RT A160H65RS
A160E65RT
A150E75NT* A1150E75NS*
*A160E75RT

*Recirculation mode is not offered on these models.

V110H65RT
V130H65RT V130H65RS
V130E65RT
V150H75NT* V150H75NS*
**V160H75RT *V160H75RS
V160H65RT V160H65RS
V160E65RT
V150E75NT* V150E75NS*
**V160E75RT

*Recirculation mode is not offered on these models.

REGISTER YOUR PRODUCT ONLINE AT:

www.venmar.ca/register-your-product.html or

www.vanee.ca/en/register-your-product.html

For additional information, visit www.venmar.ca or www.vanee.ca

INSTALLER: READ THESE INSTRUCTIONS SAVE THEM FOR USER

Please take note that this manual uses the following symbols to emphasize particular information:

WARNING

Identifies an instruction which, if not followed, might cause serious personal injuries including possibility of death.

CAUTION

Denotes an instruction which, if not followed, may severely damage the unit and/or its components.

NOTE: Indicates supplementary information needed to fully complete an instruction.

LIMITATION

For residential (domestic) installation only. Installation work and electrical wiring must be done by a qualified person in accordance with all applicable codes and standards, including fire-rated construction codes and standards.

WARNING

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:

  1. Use this unit only in the manner intended by the manufacturer.
  2. Before servicing or cleaning this unit, disconnect power cord from electrical outlet.
  3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
  4. When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities.
  5. Do not use this unit with any solid-state speed control device other than those specified in section 3.1.
  6. This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged into a mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances. Do not remove the ground prong. Do not use an extension cord.
  7. Do not install in a cooking area or connect directly to any appliances.
  8. Do not use to exhaust hazardous or explosive materials and vapors.
  9. When performing installation, servicing or cleaning this unit, it is recommended to wear safety glasses and gloves.
  10. When applicable local regulation comprises more restrictive installation and/or certification requirements, the aforementioned requirements prevail on those of this document and the installer agrees to conform to these at his own expense.

CAUTION

  1. To avoid prematurely clogged filters, turn the unit OFF during construction or renovation.
  2. Please read specification label on product for further information and requirements.
  3. Be sure to duct air outside - Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage. Do not attempt to recover the exhaust air from a dryer or a range hood.
  4. Intended for residential installation only in accordance with the requirements of NFPA 90B (for a unit installed in U.S.A.) or Part 9 of the National Building Code of Canada (for a unit installed in Canada).
  5. Do not run any air ducts directly above or within 2 ft (0.61 m) of a furnace or its supply plenum, boiler, or other heat producing appliance. If a duct has to be connected to the furnace return plenum, it must be connected 10^ (3.1 m) away from plenum's connection to the furnace.
  6. The ductwork is intended to be installed in compliance with all applicable local and national codes.
  7. When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit operates adequately.
  8. If the ductwork passes through an unconditioned space (e.g.: attic), the unit must operate continuously except when performing maintenance and/or repair. Also, the ambient temperature of the house should never drop below 18^ (65^) .
  9. At least once a year, the unit mechanical and electronic parts should be inspected by qualified service personnel.
  10. Do not use your unit during construction or renovation of your house or when sanding drywall. Certain types of dust and vapors may damage your system.
  11. Make sure at all times that the outside intake and exhaust hoods are free from any snow during the winter season. It is important to check your unit during a big snow storm, so it doesn't draw in any snow. If this is the case, please turn the unit OFF for a few hours.
  12. Since the electronic control system of the unit uses a microprocessor, it may not operate correctly because of external noise or very short power failure. If this happens, unplug the unit and wait approximately 10 seconds. Then, plug the unit in again.
  13. Do not make excessive use of fragrance appliances or chemicals since some may damage the unit components material.

TABLE OF CONTENT

1. TECHNICAL DATA 4

1.1 AIR DISTRIBUTION (NORMAL OPERATION) 4

2. INSTALLATION 4

2.1 LOCATING AND MOUNTING THE UNIT 4
2.2 INSTALLING THE DUCTWORK AND THE REGISTERS 6

2.2.1 FuLLy DUCTED SYSTEM (T-1) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.) 6
2.2.2 EXHAUST DUCTED SYSTEM (T-2) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.) 6
2.2.3 SIMPLIFIED INSTALLATION (T-4) (THIS CONFIGURATION DOES NOT ALLOW RECIRCULATION MODE TO OPERATE.) 7

2.3 CONNECTING THE DRAIN (HRV ONLY) 8
2.4 INSTALLING DUAL EXTERIOR HOOD USING TANDEM® TRANSITION KIT (OPTIONAL) 8
2.5 INSTALLING THE EXTERIOR HOODS 9
2.6 CONNECTING THE DUCTS TO THE UNIT 9
2.6.1 DUCTS CONNECTION 10

3. CONNECTIONS 11

3.1 ELECTRICAL CONNECTION TO OPTIONAL MAIN WALL CONTROL 11

3.1.1 ELECTRICAL CONNECTION TO DEHUMIDISTAT OR AUTOMATIC OPTIONAL MAIN WALL CONTROL 11
3.1.2 ELECTRICAL CONNECTION TO ADVANCED OPTIONAL MAIN WALL CONTROL 11

3.2 ELECTRICAL CONNECTION TO OPTIONAL AUXILIARY WALL CONTROL 12

3.2.1 ELECTRICAL CONNECTION TO 20-40-60 OPTIONAL AUXILIARY WALL CONTROL 12
3.2.2 ELECTRICAL CONNECTION TO DRY CONTACT OPTIONAL AUXILIARY WALL CONTROL (E.G. CRANK TIMER) 12

3.3 CONNECTION TO THE CENTRAL FORCED-AIR SYSTEM 13

3.3.1 UNIT OPERATION USING A DRY CONTACT CONNECTION 13
3.3.2 UNIT INTERCONNECTION WITH CENTRAL FORCED-AIR SYSTEM (R/C/G/GF) 13
3.3.3 SYNCHRONIZATION WITH CENTRAL FORCED-AIR SYSTEM FUNCTION 13

4.WIRING DIAGRAM 14

5. NAVIGATION ON LCD SCREEN 15

5.1 LCD SCREEN 16
5.2 UNIT FIRST BOOT 16
5.3 SETTINGS MODIFICATION 16

5.3.1 PROCEDURE TO MODIFY MIN CFM SETTING 16
5.3.2 PROCEDURE TO MODIFY MAX CFM SETTING 16
5.3.3 PROCEDURE TO MODIFY OPTIONS SETTING 16
5.3.4 PROCEDURE TO MODIFY INDEPENDENT AIRFLows SETTING 16

5.4 FACTORY SETTINGS RESET 17

6. USING THIS UNIT 17

6.1 YOUR VENTILATION SYSTEM 17
6.2 INTEGRATED CONTROL 17
6.3 AHU MODE DISPLAY 17

7. SERVICE PARTS 18

8. INSTALLER'S TROUBLESHOOTING 20

9. MAINTENANCE 23

9.1 QUARTERLY 23
9.2 ANNUAL (AT FALL) 24

10. USER'S TROUBLESHOOTING 24

11.WARRANTY 25

Consumer Information

A. To ensure quiet operation of the H/ERV, each product model must be installed using sound attenuation techniques appropriate for the installation.

B. The way your heat/energy-recovery ventilator is installed can make a significant difference to the electrical energy you use. To minimize the electricity use of the heat/energy-recovery ventilator, a stand-alone fully ducted installation is recommended. If you choose a simplified installation that operates your furnace air handler for room-to-room ventilation, an electrically efficient furnace that has an electronically commutated (EC) variable speed blower motor will minimize your electrical energy consumption and operating cost.

C. Installation of a user-accessible control with your product model will improve comfort and may significantly reduce the product model's energy use.

1. TECHNICAL DATA

1.1 AIR DISTRIBUTION (NORMAL OPERATION)

vänEE V160E75RS - AIR DISTRIBUTION (NORMAL OPERATION) - 1

vänEE V160E75RS - AIR DISTRIBUTION (NORMAL OPERATION) - 2
NOTE: The dimensions, performance charts, defrost cycle tables and specifications are listed on the specification sheets of the unit.
Visit our website at www.venmar.ca or www.vanee.ca.

2. INSTALLATION

WARNING

The wearing of safety glasses and gloves is recommended when installing, maintaining or cleaning the unit to reduce the risk of injury that could be caused by the presence of thin metal and/or high moving parts.

CAUTION

Make sure that no piece of mineral wool will enter in the unit during installation. Otherwise, this could reduce airflow and generate vibrations and noise in the unit.

2.1 LOCATING AND MOUNTING THE UNIT

Choose an appropriate location for the unit:

  • Within an area of the house where the ambient temperature is kept between 10^ C( 50^ F) and 65^ C( 149^ F) ;
  • Away from living areas (dining room, living room, bedroom), if possible;
    So as to provide easy access to the interior cabinet for maintenance, and to the control panel on the side of the unit;
  • Close to an exterior wall, so as to limit the length of the insulated flexible ducts to and from the unit;
  • HRV units only: close to a drain. If no drain is close by, use a pail to collect run-off;
  • Away from hot chimneys, electrical panel and other fire hazards;
  • Within 6 feet of a power source (standard outlet).

2.1 LOCATING AND MOUNTING THE UNIT (CONT'D)

Suspended to the joists or trusts:

  • Slightly bend the brackets on the unit to insert the provided chains.
  • Hang the unit to the joists using the provided chains. Springs are not required.
    Always make sure that the unit is no more than 1 / 4'' off level.

vänEE V160E75RS - Suspended to the joists or trusts: - 1

OR

Wall mounted:

  • Choose the appropriate location(s) for the mounting brackets (see illustration below) according to stud(s) position.
  • Insert the provided brackets under the unit frame (see illustration hereafter).
    Fix the bracket using the screw no. 8 × 3/8
  • Using the 4 no. 8 × 1 12 screws provided, secure the unit to the wall making sure that the 4 screws engage into a stud.
    Always make sure that the unit is no more than 1 / 4'' off level.

vänEE V160E75RS - Wall mounted: - 1

INSTALLATION WITH 2 BRACKETS INSTALLATION WITH 4 BRACKETS

vänEE V160E75RS - INSTALLATION WITH 2 BRACKETS INSTALLATION WITH 4 BRACKETS - 1

vänEE V160E75RS - INSTALLATION WITH 2 BRACKETS INSTALLATION WITH 4 BRACKETS - 2

2.2 INSTALLING THE DUCTWORK AND THE REGISTERS

WARNING

Never install a stale air exhaust register in a room where there is a combustion device, such as a furnace, gas water heater, fireplace or any appliance or equipment that can generate gaseous contaminants, or pollutants. The negative pressure this could create in the room may impair proper evacuation of the gas or pollutants, which may have severe health consequences.

CAUTION

If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts to prevent condensation formation inside and outside ducts, which could cause material damage and/or mold growth. Moreover, if fresh air to building duct and/or stale air from building duct goes/go through an unconditioned space, the unit must be set to operate continuously in cold conditions (below 10^ / 50^ ). Continuous air movement inside ducts will prevent condensation formation. The unit can be stopped temporarily for maintenance and/or repair purposes in such conditions.

2.2.1 FULLY DUCTED SYSTEM (T-1) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.)

STALE AIR FROM BUILDING:

  • Install registers in areas where contaminants and humidity are produced: kitchen, bathrooms, laundry room, etc.
  • Install registers on an interior wall, 6 to 12 inches away from the ceiling OR in the ceiling.
  • Install the kitchen register at least 4 feet away from the range.
  • Bathroom fans and range hoods can be used to better exhaust stale air.
    Homes with more than one level require at least one exhaust register at the highest level.

FRESH AIR TO BUILDING:

  • Install registers in bedrooms, dining room, living room and basement.
  • Install registers in the ceiling OR high on the walls with the airflow directed towards the ceiling.
    If a register must be installed in the floor, direct the airflow up the wall.

vänEE V160E75RS - FRESH AIR TO BUILDING: - 1

NOTE: For this type of configuration, the T-1 option must be selected on the LCD screen when auto-balancing the unit.

2.2.2 EXHAUST DUCTED SYSTEM (T-2) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.)

WARNING

Duct connection to the central forced-air system can be regulated by some codes and standards. It is your responsibility to consider and comply with your local requirements to avoid any non-compliance.

STALE AIR FROM BUILDING:

Same as for Fully Ducted System, described on point 2.2.1.

FRESH AIR TO BUILDING:

  • Connect the fresh air distribution duct of the unit to the central forced-air system return duct at least 10 feet away from the central forced-air system (A + B)^* .
  • This 10-ft. distance applies only in areas where the outside temperature falls below the freezing point 0^ C( 32^ F) .

NOTE: The central forced-air system blower operation can be synchronized with the unit (see Section 3.3). It is recommended, but not essential that the central forced-air system blower runs when the unit is in operation.

NOTE: For this type of configuration, the T-2 option must be selected on the LCD screen when auto-balancing the unit.

vänEE V160E75RS - FRESH AIR TO BUILDING: - 1

ALTERNATE INSTALLATION (T-3) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.)

Unit should be synchronized with central forced-air system operation to avoid condensation and mold growth in central forced-air system distribution ducting if cooling mode of central forced-air system is used.

CAUTION

This configuration is not recommended with high velocity central forced-air system. High pressures produced by these systems could affect unit proper operation and generate errors.

NOTE: For this type of configuration, the T-3 option must be selected on the LCD screen when auto-balancing the unit.

vänEE V160E75RS - CAUTION - 1

2.2.3 SIMPLIFIED INSTALLATION (T-4) (THIS CONFIGURATION DOES NOT ALLOW RECIRCULATION MODE TO OPERATE.)

CAUTION

The central forced-air system must be synchronized with the unit since fresh air evacuation and distribution come from the same section. The central forced-air system must operate to avoid fresh air to be directly drawn by the evacuation, which would reduce significantly fresh air supply to the building. See Section 3.3 for ducting.

WARNING

Duct connection to the central forced-air system can be regulated by some codes and standards. It is your responsibility to consider and comply with your local requirements to avoid any non-compliance.

Fresh air and exhaust air flow through the central forced-air system ducts, which simplifi es the installation. The use of bathroom fans and a range hood is suggested to exhaust stale air.

STALE AIR FROM BUILDING:

Connect the stale air intake port of the unit to the central forced-air system return duct at least 3 feet ahead of the fresh air distribution from the unit.

FRESH AIR TO BUILDING:

Connect the fresh air distribution duct of the unit to the central forced-air system return duct at least 10 feet away from the central forced-air system (A + B)^*

  • This 10-ft. distance applies only in areas where the outside temperature falls below the freezing point 0^ C( 32^ F) .

NOTE: For this type of configuration, the T-4 option must be selected on the LCD screen when auto-balancing the unit.

vänEE V160E75RS - FRESH AIR TO BUILDING: - 1

ALTERNATE INSTALLATION (T-5) (THIS CONFIGURATION DOES NOT ALLOW RECIRCULATION MODE TO OPERATE.)

Unit should be synchronized with central forced-air system operation to avoid condensation and mold growth in central forced-air system distribution ducting if cooling mode of central forced-air system is used.

CAUTION

This configuration is not recommended with high velocity central forced-air system. High pressures produced by these systems could affect unit proper operation and generate errors.

NOTE: For this type of configuration, the T-5 option must be selected on the LCD screen when auto-balancing the unit.

vänEE V160E75RS - CAUTION - 1

2.3 CONNECTING THE DRAIN (HRV ONLY)

CAUTION

Install the drain hose included and run it to a drain or a pail. This unit may generate a large amount of water in cooler weather. It is necessary to install the drain hose properly to prevent water damage and/or material damage.

  • Cut the appropriate length of drain tubing (see illustration at right).
  • Connect the tubing to the provided adaptor.
    Make a water trap loop in the tube to prevent the unit from drawing unpleasant odors from the drain source.
  • Add water in the loop to prevent noise or hiss.
  • Make sure there is a distance of at least 2^ between the unit and the tubing loop (see illustration at right).
  • Using tie wraps provided, attach the tubing as illustrated.
  • Run the tube to the floor drain or to an alternate drain pipe or pail.
  • IMPORTANT: If using a pail to collect water, place the tube end approximately 1" inside the pail in order to prevent water from being drawn back up into the unit.

vänEE V160E75RS - CAUTION - 1

2.4 INSTALLING DUAL EXTERIOR HOOD USING TANDEM TRANSITION KIT (OPTIONAL)

For units set at 110 CFM or less, a Tandem transition kit can be used instead of 2 exterior hoods; but take into account this device will generate approximately an additional 0.2 in w.g. static pressure depending on the installation.

The minimum joist opening needed to install the Tandem transition is 9 12 . The maximum height of the Tandem transition is 8 12 .

To connect the insulated flexible ducts to the Tandem transition (Exhaust air to outdoors and Fresh air from outdoors), follow the instructions included with the Tandem transition kit (part no.14690).

vänEE V160E75RS - INSTALLING DUAL EXTERIOR HOOD USING TANDEM TRANSITION KIT (OPTIONAL) - 1

2.5 INSTALLING THE EXTERIOR HOODS

To avoid cross-contamination:

  • Keep at least 6 feet between both hoods OR use approved combined hoods model 14690.
  • Install hood(s) at least at 18 inches away from the ground OR depth of expected snow accumulation, whichever is greater.

WARNING

Make sure intake hood is at least 6 feet (1.8 m) away from any of the following:

  • Dryer exhaust, high efficiency central forced-air system vent central vacuum vent
    Gas meter exhaust, gas barbecue-grill
  • Any exhaust from a combustion source
  • Garbage bin and any other source of contamination.

Ignoring these recommendations could significantly degrade the quality of the incoming air which, in some cases, could result in health consequences.

In the event of a conflict between our conditions and local requirements, the latter will have priority.

vänEE V160E75RS - WARNING - 1

vänEE V160E75RS - WARNING - 2

Refer to illustration above for proper connection method of the insulated ducts to the hoods. "Anti-Gust Hoods" should be installed in regions where a lot of snow is expected to fall.

2.6 CONNECTING THE DUCTS TO THE UNIT

CAUTION

  • If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts to prevent condensation formation inside and outside ducts, which could cause material damage and/or mold growth.
  • Do not use screws to connect the ducts or transitions to the ports so as not to interfere with ports inner dampers operation. A non-functioning damper could freeze the unit, which could cause damages.

INSULATED FLEXIBLE DUCTS

Use the following procedure to connect the insulated flexible ducts to the ports of the unit (exhaust to outside and fresh air from outside).

  1. Expose the flexible duct by pulling back the insulation, and place it over the inner port ring.
  2. Attach the fl exible duct to the port using a tie wrap.
  3. Seal the joint using duct tape.
  4. Pull the insulation and vapor barrier over the joint, tuck them between the inner and outer rings of the double collar and fasten them in place using duct tape.

CAUTION

The vapor barrier should remain intact and free of cracks or openings. An opening could produce condensation inside or outside duct, which could cause material damage and/or mold growth in the long run.

vänEE V160E75RS - CAUTION - 1

vänEE V160E75RS - CAUTION - 2

vänEE V160E75RS - CAUTION - 3

vänEE V160E75RS - CAUTION - 4

vänEE V160E75RS - CAUTION - 5
VJ0157

TRANSITIONING TO 6-IN. DUCTS (FOR 110, 130 AND 150 CFM UNITS ONLY)

If using 6-in. ducts, install 5-in. to 6-in. transitions on the ports, and secure using duct tape only. If rigid ducting is used, install a 12-in. section of flexible duct between the transition and the rigid ducting (see above). Rigid ducts

To prevent potential water leakage in cold side rigid ducting insulation, seal all rigid ducting joints with duct tape. To avoid transmission of vibrations, always use a 12-inch section of flexible duct to connect rigid ducts to the unit. To connect insulated rigid ducts to the unit (cold side) using insulated flexible ducts, follow instructions in section 2.5. To connect regular rigid ducts (warm side) to the unit using non-insulated flexible ducts, use a tie wrap.

NOTE: It is recommended to use 6" ducting instead of 5" ducting for 150H75NT, 150H75NS, 150E75NT and 150E75NS units if required airflow is over 130 CFM. It will prevent having too high static pressure in the ducting.

2.6.1 DUCTS CONNECTION

IMPORTANT: Make sure to connect ducting as illustrated below to get airflows reading accuracy. Correct installation will also allow proper drainage of water that may accumulate in ducting.

vänEE V160E75RS - DUCTS CONNECTION - 1
CORRECT INSTALLATION

VD0489

CAUTION

Ducting must not be too crushed. Otherwise, airflows reading accuracy will be affected.

CAUTION

Insulated ducts must have the same diameter as the ports to ensure proper drainage of water that may accumulate in ducts.

vänEE V160E75RS - CAUTION - 1

NOTE: Route ducts as straight as possible, minimize the number of elbows and design and install ducts in accordance with HRAI best practices.

3. CONNECTIONS

3.1 ELECTRICAL CONNECTION TO OPTIONAL MAIN WALL CONTROL

WARNING

Always disconnect the unit before making any connections. Failure to cut power could result in electrical shock or damage to the wall control or electronic module inside the unit.

CAUTION

Never install more than one optional main wall control per unit. Make sure that the wires do not short-circuit between themselves or by touching any other components on the wall control. Avoid poor wiring connections. To reduce the risk of electrical interference (noise), do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or lighting wiring or power distribution panel.

vänEE V160E75RS - CAUTION - 1
HD0491

Use the terminal connector included to perform the electrical connection for optional main wall control. Check if all wires are correctly inserted in their corresponding holes in the terminal connector. Use screws to fix wires in the terminal connector. Once the wall control connections have been made, insert the terminal connector in the electrical compartment.

NOTE: For information about the operation of the wall control, refer to the corresponding Installation and User Guide, available at www.vanee.ca or www.venmar.ca.

3.1.1 ELECTRICAL CONNECTION TO DEHUMIDISTAT OR AUTOMATIC OPTIONAL MAIN WALL CONTROL

vänEE V160E75RS - CAUTION - 2
VC0241

3.1.2 ELECTRICAL CONNECTION TO ADVANCED OPTIONAL MAIN WALL CONTROL

vänEE V160E75RS - CAUTION - 3

3. CONNECTIONS (CONT'D)

3.2 ELECTRICAL CONNECTION TO OPTIONAL AUXILIARY WALL CONTROL
3.2.1 ELECTRICAL CONNECTION TO 20-40-60 OPTIONAL AUXILIARY WALL CONTROL

vänEE V160E75RS - CONNECTIONS (CONT'D) - 1

When configuring OVR option on the LCD screen, choose among these 3 configurations: BAL (the unit remains balanced while providing maximum airflow), PER (the unit is slightly unbalanced since the distribution motor is in MAX speed while allowing maximum exhaust ventilation) and DIS (the unit is unbalanced since air distribution is constant despite a higher need in exhaust ventilation).

NOTE : The auxiliary wall control can be used with a 3-wire connection by removing the LED signals. This optional wiring will not allow an installation with more than 1 auxiliary wall control to properly synchronize their LEDs on an event requested from a peer. Only the auxiliary wall control having requested the timer event will have the LEDs updated accordingly.

3.2.2 ELECTRICAL CONNECTION TO DRY CONTACT OPTIONAL AUXILIARY WALL CONTROL (E.G. CRANK TIMER)

vänEE V160E75RS - CONNECTIONS (CONT'D) - 2

WARNING

A miswiring that sends a 24 VAC signal to the 6-position terminal block (OVR, LED, 12V, D-, D+, GND) could permanently damage the control circuit. Verify carefully wire connections before powering-up the unit.

3.3 CONNECTION TO THE CENTRAL FORCED-AIR SYSTEM

WARNING

Never connect a 120-volt AC circuit to the terminals of the central forced-air system interlock (standard wiring). Only use the low voltage class 2 circuit of the central forced-air system blower control. The unit is designed for low voltages only. Connecting the unit on 120-volt circuit would damage it instantly.

3.3.1 UNIT OPERATION USING A DRY CONTACT CONNECTION

This unit can be controlled by any dry contact connection such as the thermostat equipped with an optional ventilation output.

Once wired, unit will toggle between the Standby mode when contact is opened and the selected mode when contact is closed. Choose among these 4 configurations: minimum (unit operating in MIN speed), intermittent (unit operating in MIN speed 20 min/hr then as per INT configuration selection for 40 min), auto* (unit operating according to outdoor temperature) and maximum (unit operating in MAX speed) in DRY option on the LCD screen when the VENT contact is activated. Refer to section 5 for more details.

  • In auto mode, the unit will operate as follows:

Less than -25^ = 10min / hr
- 25^ to -7^ = 20 /hr
- 7^ to 10^ = 40min / hr
10^ to 25^ = MIN speed
- 25^ C to 28^ C = 30 min/hr
- 28^ C to 33^ C = 20 min/hr
Above 33^ = 10min / hr

3.3.2 UNIT INTERCONNECTION WITH CENTRAL FORCED-AIR SYSTEM (R/C/G/GF)

vänEE V160E75RS - UNIT OPERATION USING A DRY CONTACT CONNECTION - 1

vänEE V160E75RS - UNIT OPERATION USING A DRY CONTACT CONNECTION - 2

NOTE : This dry contact option will override the main wall control so we do not recommend the use of a wall control with this type of connection.

NOTE : Following ducting installation configuration and temperature conditions, it may be necessary for the unit to operate continuously. Refer to section 2.2 for more details.

AL FORCED-AIR SYSTEM (R/C/G/GF)

vänEE V160E75RS - UNIT OPERATION USING A DRY CONTACT CONNECTION - 3

These connections must be done if you want the unit to force the central forced-air system blower operation when ventilating (refer to solid lines in above diagram).

NOTE: These connections are required for installation configuration T-4. Refer to section 2.2 for more details.

3.3.3 SYNCHRONIZATION WITH CENTRAL FORCED-AIR SYSTEM FUNCTION

The Virtuo technology allows synchronizing the unit operation with the central forced-air system operating time. It prevents unnecessary central forced-air system operating time while providing a better air distribution. To use this function, W and Y connections must be added to R and C connections to inform the unit that the central forced-air system is running (refer to dotted lines in above diagram).

4. WIRING DIAGRAM

WARNING

  • Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
  • This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation. If the fuse blows, unplug the product from the outlet. Discontinue using the unit and contact technical support.

vänEE V160E75RS - WARNING - 1

VE0452A

vänEE V160E75RS - WARNING - 2

vänEE V160E75RS - WARNING - 3

OK button To confirmm a selection.
+ buttonTo increase a value.
To scroll up in a selection.
- buttonTo decrease a value.
To scroll down in a selection.

PRESS ON OK BUTTON TO CHANGE THE OPERATING MODE. PRESS ON + BUTTON OR - BUTTON TO MODIFY MAX CFM, MIN CFM OR OPTIONS CONFIGURATION.

USE BUTTON OR - BUTTON TO SELECT THE DESIRED OPERATING MODE.

vänEE V160E75RS - WARNING - 4

vänEE V160E75RS - WARNING - 5

vänEE V160E75RS - WARNING - 6

vänEE V160E75RS - WARNING - 7

vänEE V160E75RS - WARNING - 8

vänEE V160E75RS - WARNING - 9

PRESS ON OK BUTTON DURING 4 SECONDS TO MODIFY OPTIONS CONFIGURATION.
FOR EACH

USE + BUTTON TO INCREASE VALUE OR - BUTTON TO
VALUE OF BUDGET TO DECREASE VALUE.
PRESSEONOKDUT
PRESS ON OR BUTTON TO CONFIRM VALUE.

PRESS ON OK BUTTON TO
CONFIRM THE OPE MODE SELECTION.

5.1 LCD SCREEN

DISPLAY DEFINITION
STB Standby mode
MED MED speed
INT Intermittent mode
REC Recirculation mode(Min, Med or Max speed)
AUT AUTO modc
SMT SMART mode
OVR 20 Override 20 min
OVR 40 Override 40 min
DISPLAY DEFINITION
OVR 60Override 60 min
OVR CNT Override by dry contact
AHURefer to section 6.3 for explanation
HUMHumidistat or Dehumidistat override
TURTurbo mode
OTHAway mode or Scheduling mode
DEFDefrost mode
EXX or WXX (XX referring to error or warning number)Refer to section 8 for each error/warning explanation

5.2 UNIT FIRST BOOT

PREPARATION

Follow these steps to ensure accurate measurements:

  • Seal all the ductwork with tape. Close all windows and doors.
  • Turn off all exhaust devices such as range hood, dryer and bathroom fans.
    If the installation is in any way connected to a ductwork of a central forced-air system, make sure that the central forced-air system blower is ON. If not, leave central forced-air system blower OFF.

AUTO-BALANCING PROCEDURE

Plug the unit and wait for the maximum CFM to display on the LCD screen. If unit is colder than ambient temperature, it is normal to experience a 60 s longer boot-up since motors have to preheat.
The maximum CFM will display on the LCD screen. Use (+ / - ) to adjust the CFM and OK to confirm.
The minimum CFM will display on the LCD screen. Use (+ / - ) to adjust the CFM and OK to confirm.
The house that flashes on the LCD screen indicates which side currently limits the airflow (supply or exhaust). If the airflow reached is not sufficient, the installer can improve the installation to increase airflow.

INSTALLATION CONFIGURATION SELECTION

INS will display on the LCD screen. Choose among T-1, T-2, T-3, T-4 or T-5 following the installation configuration (Refer to section 2.2 for more details).
- Auto-balancing is completed.

5.3 SETTINGS MODIFICATION

5.3.1 PROCEDURE TO MODIFY MIN CFM SETTING

  • Go to MIN using (+/-) then press on the OK button for 4 seconds.

  • Use (+/-) to increase/decrease CFM and OK to confirm.

5.3.2 PROCEDURE TO MODIFY MAX CFM SETTING

  • Go to MAX using (+ / - ) then press on the OK button for 4 seconds.
  • Use (+/-) to increase/decrease CFM and OK to confirm.

5.3.3 PROCEDURE TO MODIFY OPTIONS SETTING

  • Go to CFG OPT using (+/-) then press on the OK button for 4 seconds.

5.3.4 PROCEDURE TO MODIFY INDEPENDENT AIRFLOWS SETTING

  • Press simultaneously (+/-) buttons for 4 seconds.

vänEE V160E75RS - PROCEDURE TO MODIFY INDEPENDENT AIRFLOWS SETTING - 1

vänEE V160E75RS - PROCEDURE TO MODIFY INDEPENDENT AIRFLOWS SETTING - 2

SUPPLY AIRFLOW VALUE WILL FLASH.
PRESS ON + BUTTON OR - BUTTON TO
INCREASE/DECREASE VALUE.
PRESS OK BUTTON.
EXHAUST AIRFLOW VALUE WILL FLASH.
PRESS ON + BUTTON OR - BUTTON TO
INCREASE/DECREASE VALUE.
PRESS OK BUTTON.

WHEN MAX DISPLAYS, PRESS ON + BUTTON TO EXIT INDEPENDENT AIRFLOWS SETTING.

Options Confi guralations available
DEF (Defrost)DIS* (Discretion - defrost without speed variation for more comfort), PLU (Plus - extended defrost for colder areas)
INS (Installation)T-1, T-2, T-3, T-4*, T-5 (Refer to section 2.2)
DRY (Dry contact)MIN* (Minimum), INT (Intermittent), AUT (AUTO), MAX (Maximum) (Refer to section 3.3.1)
OVR (Override)BAL* (Balanced), PER (Performance), DIS (Discretion) (Refer to section 3.2.1)
INT (Intermittent)STB* (Standby - 20 min in MIN speed and 40 min in standby mode), REC** (Recirculation - 20 min in MIN speed and 40 min in recirculation mode) **REC (Recirculation) configuration is not available for T-2 to T-5 installation configurations nor for 150H75NT, 150H75NS, 150E75NT and 150E75NS units. NOTE: Following ducting installation configuration and temperature conditions, it may be necessary for the unit to operate continuously. Refer to section 2.2 for more details.
  • Factory setting
    NOTE: If no selection is confirmed within 10 minutes, the unit will exit the menu without saving any changes.
    5.4 FACTORY SETTINGS RESET
    If any change is made to the ducting, reset settings to restart the airflow test.
    PROCEDURE TO RESET SETTINGS
    Press on the OK and (-) buttons simultaneously for 4 seconds. Use (+/-) to select Yes or No and OK to confirm.
    Then perform the auto-balancing procedure.

6. USING THIS UNIT

6.1 YOUR VENTILATION SYSTEM

This balanced ventilation unit is designed to provide fresh air to your home while exhausting stale, humid air. Thanks to its energy/heat recovery module, the unit recovers a large proportion of heat or energy that is part of indoor or outdoor air according to the seasons to improve comfort and energy efficiency during the heating and the cooling periods. With the Virtuo Air Technology™, this unit responds to the variations in its environment in an autonomous way, ensuring to provide a proper level of ventilation and air quality. This unit also features automatic modes (AUTO or SMART) that manage autonomously the required ventilation level as per indoor and/or outdoor conditions. In colder areas, the unit will perform, at intervals, recovery module discreet defrost to maintain performance and comfort.

6.2 INTEGRATED CONTROL

All units are equipped with an integrated control, located in front of the electrical compartment. For more convenience, these units can be controlled using an optional wall control or the central forced-air system thermostat equipped with external fan activation.

MODE SELECTION

  1. To change the mode, use (+ / -) to access the Mode screen. Press OK to edit the mode and use (+ / -) to change the mode (Standby, Min, Max).
  2. Press OK to confirm selection. The airflows will be displayed for both MIN and MAX modes.

NOTE: If an optional auxiliary wall control or the central forced-air system thermostat equipped with external fan activation is used, it overrides the integrated control.

vänEE V160E75RS - MODE SELECTION - 1

6.3 AHU MODE DISPLAY

Depending on unit configuration and/or installation, the unit could not be able to reach desired set minimum CFM. This situation could happen with installed configurations T-2 to T-5 due to AHU static pressure and a set minimum CFM below 60. In such a case, AHUXX (XX referring to desired minimum CFM value) will display on LCD screen. In AHU mode, the unit operates in intermittent mode to reach desired minimum CFM value. Intermittent mode duration varies as per desired minimum CFM value.

7. SERVICE PARTS

vänEE V160E75RS - SERVICE PARTS - 1

VL0086

ITEMDESCRIPTIONPART NUMBERA110H65RT/RSV110H65RT/RSA130H65RT/RSV130H65RT/RSA130E65RT/RSV130E65RT/RSA160H65RT/RSV160H65RT/RSA160E65RTV160E65RTA160H75RT/RSV160H75RT/RSA150H75NT/NSV150H75NT/NS
2222
16" port warm side SV66139 2 2 222222
5" port warm side SV66140 2 2 222222222222222222222222222222222222222222222222222
26" metal port motorized damper SV66135 1 1 111111111111111111111111111111111111111111111111111
5" metal port motorized damper SV66136 1 1 11111111111111111111111111111111111111111111111I
3 Electronic assembly SV66144** 1 1 1Electrical block SV66145 1 1 1 11 1 1 11111111111111111111111111111111111111111111111J
4 Terminal blocks SV66145 1 1 1 1Exhaust port assembly SV66137 11 1 1 111111111111111111111111111111111111111111111J
56" exhaust port assembly SV66138 11 1 1 11111111111111111111111111111111111111111111J
5" exhaust port assembly SV66138 11 1 1 1111111111111111111111111111111111111111J
6 Door latches and keepers for door SV612Door latches and keepers for door SV61218 1 1 11111111111111111111111111111111111111111J
7 Thermistor SV66134 1111111111111111Recirculation damper with thermistor SV66148 1 1 11111111111111111111111111111111111111111J
8 Recirculation damper with thermistor SV66148 1 1 1Exhaust blower with damper SV66142 1 1 11 1 1 111111111111111111111111111111111111111J
9 Exhaust blower with damper SV66142 1 1 1Exhaust blower assembly SV66142 1 1 11 1 1 1111111111111111111111111111111111111J
10 Supply blower assembly SV66144 1Supply blower assembly SV66144 1 1 1 11 1 1 1111111111111111111111111111111111111J
11 Core ERV 65 %Core ERV 65 % SV66113
  • Not shown.
    ** See next page to get the part number that corresponds to the ventilation unit model.
VENTILATION UNIT MODEL
ELECTRONIC ASSEMBLY PART NUMBERA/V110H65RSA/V110H65RTA/V130H65RSA/V130H65RTA/V160H65RSA/V160H65RTA/V150H75NSA/V150H75NTA/V160H75RSA/V160H75RTA/V130E65RSA/V130E65RTA/V160E65RTA/V150E75NSA/V150E75NTA/V160E75RT
SV66144-01X
SV66144-02X
SV66144-03X
SV66144-04X
SV66144-05X
SV66144-06X
SV66144-07X
SV66144-08X
SV66144-09X
SV66144-10X
SV66144-11X
SV66144-12X
SV66144-14X
SV66144-19X
SV66144-20X
SV66144-18X

REPLACEMENT PARTS AND REPAIRS

In order to ensure your ventilation unit remains in good working condition, you must use the manufacturer's genuine replacement parts only. The manufacturer's genuine replacement parts are specially designed for each unit and are manufactured to comply with all the applicable certification standards and maintain a high standard of safety. Any third party replacement part used may cause serious damage and drastically reduce the performance level of your unit, which will result in premature failing. The manufacturer recommends to contact a certified service depot for all replacement parts and repairs.

8. INSTALLER'S TROUBLESHOOTING

WARNING

The wearing of safety glasses and gloves is recommended since a few diagnosis procedures may require the unit to be in operation while proceeding. Be careful with moving and live parts to prevent any risk of injury.

ERRORDESCRIPTION SOLUTION
E01Supply damper rangeSTEP 1: Unplug unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the damper system). Plug unit.
E02Supply damper timeoutIf STEP 1 did not fix the problem, perform STEP 2: Open electrical compartment, check if connector J5 (white) is well inserted, check for any loose wires. If STEP 2 did not fix the problem, perform STEP 3: If the damper is not moving at all, unplug J7 (red) from the electronic assembly, connect the white damper system connector into J7. If the damper moves (but the system still shows an error), the electronic assembly must be replaced. Otherwise, replace the damper system.
E03Supply damper
E05Exhaust damper rangeSTEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the damper system). Plug the unit.
E06Exhaust damper timeoutIf STEP 1 did not fix the problem, perform STEP 2: Open electrical compartment, check if connector J7 (red) is well inserted, check for any loose wires. If STEP 2 did not fix the problem, perform STEP 3: If the damper is not moving at all, unplug J5 (white) from the electronic assembly, connect the white damper system connector into J5. If the damper moves (but the system still shows an error), the electronic assembly must be replaced. Otherwise, replace the damper system.
E07Exhaust damper
E09Recirculation damper rangeSTEP 1: Unplug the unit, inspect the damper system, remove any undesirable obstacle or dirt (filters and core may have to be removed to access the damper system). Plug the unit.
E10Recirculation damper timeoutIf STEP 1 did not fix the problem, perform STEP 2: Open electrical compartment, check if connector J6 (blue) is well inserted, check for any loose wires. If STEP 2 did not fix the problem, perform STEP 3: If the damper is not moving at all, unplug J5 (white) from the electronic assembly, connect the blue damper system connector into J5. If the damper moves (but the system still shows an error), the electronic assembly must be replaced. Otherwise, replace the damper system.
E11Recirculation damper
E22Supply airfl owSTEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean filters, distribution registers and outside supply hood. Inspect ducting to ensure it is not squeezed or bent. Plug the unit. If STEP 1 did not fix the problem, perform STEP 2: Remove ducting of the supply path. On the LCD screen, select MAX to check if the unit is able to reach the selected flow. If so, review the ducting path. If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select the MIN and MAX flow setting values then reset the unit. MAX flow value will display on the LCD screen. If MAX flow is above desired MAX flow, set MAX and MIN flows. If STEP 3 did not fix the problem, perform STEP 4: Replace the supply blower and repeat STEP 3. If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic assembly.
E23Supply motor (drive over current)STEP 1: Unplug/plug unit.
E27Supply motor (drive foc duration)If STEP 1 did not fix the problem, perform STEP 2: Remove core and clear the ventilation wheel from any dirt or obstacles.
E28Supply motor (drive speed feedback)If STEP 2 did not fix the problem, perform STEP 3: Disconnect J2 (white) and connect a spare blower system. If it works, replace supply blower.
E29Supply motor (startup)If STEP 3 did not fix the problem, perform STEP 4: Replace the electronic assembly.
E24Supply motor (drive over voltage)STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply fluctuation and stop the motor for protection.
E25Supply motor (drive under voltage)If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
  1. INSTALLER'S TROUBLESHOOTING (CONT'D)
ERROR DESCRIPTION SOLUTION
E26Supply motor (drive over temp)STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
E32Exhaust airflowSTEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean filters, distribution registers and outside exhaust hood. Make sure no non-return damper is installed in exhaust hood since it can freeze in winter. Inspect ducting to ensure it is not squeezed or bent. Plug the unit. If STEP 1 did not fix the problem, perform STEP 2: Remove ducting of the supply path. On the LCD screen, select MAX to check if the unit is able to reach the selected flow. If so, review the ducting path.If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select the MIN and MAX flow setting values then reset the unit. MAX flow value will display on the LCD screen. If MAX flow is above desired MAX flow, set MAX and MIN flows.If STEP 3 did not fix the problem, perform STEP 4: Replace the exhaust blower and repeat STEP 3.If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic assembly.
E33Exhaust motor (drive over current)STEP 1: Unplug/plug unit.If STEP 1 did not fix the problem, perform STEP 2: Remove core and clear the ventilation wheel from any dirt or obstacles.If STEP 2 did not fix the problem, perform STEP 3: Disconnect J3 (red) and connect a spare blower system. If it works, replace exhaust blower.If STEP 3 did not fix the problem, perform STEP 4: Replace the electronic assembly.
E37Exhaust motor (drive foc duration)
E38Exhaust motor (drive speed feedback)
E39Exhaust motor (startup)
E34Exhaust motor (drive over voltage)STEP 1: Unplug/plug unit. Under and over voltage may be detected with severe in-house power supply fluctuation and stop the motor for protection.If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
E35Exhaust motor (drive under voltage)
E36Exhaust motor (drive over temp)STEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
E40Outside air thermistorSTEP 1: Check if thermistor is well connected in connector J7A.If STEP 1 did not fix the problem, perform STEP 2: Disconnect connector J7A and check if the measured resistance (thermistor connector) is within 5 Kohms to 120 Kohms. If outside the range, replace the thermistor.If STEP 2 did not fix the problem, perform STEP 3: Replace the electronic assembly.
E41Distribution air thermistorSTEP 1: Check if thermistor is well connected in connector J7B.If STEP 1 did not fix the problem, perform STEP 2: Disconnect connector J7B and check if the measured resistance (thermistor connector) is within 5 Kohms to 120 Kohms. If outside the range, replace the thermistor.If STEP 2 did not fix the problem, perform STEP 3: Replace the electronic assembly.
E42PCBA thermistor faultSTEP 1: Replace the electronic assembly.
E43PCBA temperature over limitSTEP 1: Validate if the air exchanger is exposed to ambient temperatures within the operating limits (see p. 4)If STEP 1 did not fix the problem, perform STEP 2: Replace the electronic assembly.
E50Wall control communication lostSTEP 1: Unplug unit, inspect wires, plug unit.If STEP 1 did not fix the problem, perform STEP 2: Remove wall control from the wall installation and test with a short cable. If it works, bring a new cable to the wall installation location.If STEP 2 did not fix the problem, perform STEP 3: Test the air exchanger with a spare wall control. If it works, replace the wall control.If STEP 3 did not fix the problem, perform STEP 4: Replace the electronic assembly.
E51Wall control sensorSTEP 1: Unplug unit, inspect wires, plug unit.If STEP 1 did not fix the problem, perform STEP 2: Replace the wall control.
E60Protection modeSTEP 1: Perform general inspection of the unit (dampers, core, filters).
  1. INSTALLER'S TROUBLESHOOTING (CONT'D)
WARNING DESCRIPTION SOLUTION
W22Supply airfl owSTEP 1: Unplug the unit. Perform a visual inspection of the supply damper system. Clean filters, distribution registers and outside supply hood. Inspect ducting to ensure it is not squeezed or bent. Plug the unit.If STEP 1 did not fix the problem, perform STEP 2: Remove ducting of the supply path. On the LCD screen, select MAX to check if the unit is able to reach the selected flow. If so, review the ducting path.If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select the MIN and MAX flow setting values then reset the unit. MAX flow value will display on the LCD screen. If MAX flow is above desired MAX flow, set MAX and MIN flows.If STEP 3 did not fix the problem, perform STEP 4: Replace the supply blower and repeat STEP 3.If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic assembly.
W32Exhaust airfl owSTEP 1: Unplug the unit. Perform a visual inspection of the exhaust damper system. Clean filters, distribution registers and outside exhaust hood. Make sure no non-return damper is installed in exhaust hood since it can freeze in winter. Inspect ducting to ensure it is not squeezed or bent. Plug the unit.If STEP 1 did not fix the problem, perform STEP 2: Remove ducting of the supply path. On the LCD screen, select MAX to check if the unit is able to reach the selected flow. If so, review the ducting path.If STEP 2 did not fix the problem, perform STEP 3: On the LCD screen, select the MIN and MAX flow setting values then reset theunit. MAX flow value will display on the LCD screen. If MAX flow is above desired MAX flow, set MAX and MIN flows.If STEP 3 did not fix the problem, perform STEP 4: Replace the exhaust blower and repeat STEP 3.If STEP 4 did not fix the problem, perform STEP 5: Replace the electronic assembly.
W52Initial setting incompleteSTEP 1: Press + or - to access the selection menu.STEP 2: Complete configuration. (Refer to section 5 for more details).
W61Protection mode electronics overheatingThe unit is currently in protection mode. The power transmitted to the motor is deliberately reduced to decrease electronics temperature. The unit will exit this mode by itself once conditions are back to normal. It is normal to observe reduction in airflows during this period. This condition should appear only when the unit is set in high speed and located in a warmer environment, for example over 30°C (86°F).

CAUTION

Make sure that no piece of mineral wool will enter in the unit during installation. Otherwise, this could reduce airflow and generate vibrations and noise in the unit.

9. MAINTENANCE

WARNING

High voltage risk. During maintenance or repairs, always stop the unit then unplug it to prevent any risk of electric shock. The wearing of safety glasses and gloves is recommended when handling unit components to prevent any risk of injury that could be caused by the presence of thin metal.

9.1 QUARTERLY

  1. Disconnect power cord.
  2. The door of this unit is hinged and maintained closed by 2 latches. Open them and set aside.
  3. Clean the inside of the door with a damp cloth.
  4. Clean fi Iters:

  5. Remove filters.
    Vacuum to remove most of the dust.

  6. Wash with a mixture of warm water and mild soap. You may add bleach if you wish to disinfect (one tablespoon per gallon). Rinse thoroughly. Shake filters to remove excess water and let dry.

Note: The optional MERV13 filter is a disposable filter. It should be replaced when it is too dirty. Vacuum the MERV13 membrane filter quarterly using the dusting brush attachment to extend its service life.

vänEE V160E75RS - QUARTERLY - 1

  1. Remove the core.
  2. Clean the condensing tray with a damp cloth.
  3. Check the exterior air intake hood:

CAUTION

A blocked air vent or filter, even partially, could cause the unit to malfunction. The comfort provided by the unit could be reduced and the risk of unit frost could increase. This could cause unit breakdown and/or damage to property.

Make sure there are no leaves, twigs, ice or snow that could be drawn into the vent.
Clean if necessary.

  1. Rotate the blower wheels by hand. If one of the wheels does not rotate easily, contact your installer.
  2. Reassemble the components. Pay special attention to the filters by making sure that they are engaged in their slots.
  3. Close the unit door and reconnect power supply.
  4. Reset filters, if required. If using an optional main wall control (DEHUMIDISTAT OR AUTOMATIC), press on the INT/AUTO button for 5 seconds to reset the filters. If using the ADVANCED optional main wall control, follow the instructions on the touch screen.

MERV8 FILTER INCLUDED

EXHAUST FILTER INCLUDED

vänEE V160E75RS - CAUTION - 1
OPTIONAL MERV13 FILTER OR HEPA MEMBRANE FILTER (EXHAUST FILTER NOT INCLUDED)

vänEE V160E75RS - CAUTION - 2

Pull the core 3^ to 4^ out.

Bend the two MERV13 flaps to form a 45-degree angle, as illustrated below.

Install the MERV13 fi iter over the core as illustrated hereafter.

Push the core and the MERV13 fi iter to the bottom of the unit.

vänEE V160E75RS - CAUTION - 3

NOTES: 1. The optional MERV13 filter replaces the MERV8 filter.

  1. MERV13 filter and HEPA membrane filter have the same installation instructions.

9. MAINTENANCE (CONT'D)

9.2 ANNUAL (AT FALL)

  1. Repeat steps 1 to 6 from the previous section and continue with the following steps:

CAUTION

  • Handle the recovery core with care.

  • Clean the recovery core:

vänEE V160E75RS - CAUTION - 1

HRV MODELS ERV MODELS
·Remove the core. ·Let it soak in a mixture of cold or lukewarm water and mild soap (dishwashing liquid). ·Rinse thoroughly. ·Shake the core to remove excess water and let it dry.Remove the dust on the core using a vacuum cleaner and a soft brush attachment. CAUTION: DO NOT SOAK THE ENERGY RECOVERY CORE IN WATER
  1. Clean the blower assemblies. Do not disassemble the blower assemblies.
  2. Remove the dust using a vacuum cleaner with a soft brush attachment.
  3. Reassemble the components.
  4. Reconnect power supply.

10. USER'S TROUBLESHOOTING

If the unit does not work properly, reset the unit by unplugging it for one minute then replug it.

Contact customer service at 1-800-567-3855 for any unresolved issue.

PROBLEM TRY THIS
1. Nothing works. · See if the unit is plugged in. · See if the unit is receiving power from the house circuit breaker or fuse.Clean the unit (see Section 9). If the problem is not solved, contact your installer.
2. Noisy unit.
3. Condensation inside windows under cold weather conditions.Operate the unit at MAX speed during activities generating excess humidity (family gatherings, extra cooking, etc.). ·Leave curtains half-open to allow air circulation. ·Store all firewood in a closed room with a dehumidifier or in a well ventilated room, or store the wood outdoors. ·Keep the temperature in your house above 18 °C(64°F).
4. Humidity inside under hot/humid weather conditions.Operate the unit in MIN speed. ·Temporarily switch to INT mode (if available). ·Use a dehumidifi er.
5. Air too dry.Operate the unit at MIN speed. ·Temporarily switch to INT mode (if available). ·Temporarily use a humidifi er.
6. Air too cold at the air supply register.Make sure the outdoor hoods are not blocked. ·Operate the unit at MIN speed. ·Install a duct heater (contact your installer).

11. WARRANTY

This ventilation unit is a high quality product, built and packaged with care. The manufacturer warrants to the original purchaser of its product, that such products will be free from defects for the period stated below, from date of original purchase. For all units, the warranty covers parts only against any operational defect. This 5-year warranty is subject to performance of the core maintenance according recommendations in this manual. The heat recovery core (HRV) has a limited lifetime warranty, and the energy recovery core (ERV) has a 5-year warranty. If any defect should occur, we urge you to read the user guide carefully. If the problem persists, observe the following rules:

RULES TO FOLLOW

If the unit is defective, contact your ventilation contractor (see address on your manual's cover page). The contractor will determine with you the reason for the defect, and if needed, do the replacement or repair. If ever it is impossible to reach your ventilation contractor, call 1-800-567-3855 (in North America); the personnel will be pleased to give you the phone number of a distributor or a service center near you.

REPLACEMENT PARTS AND REPAIR

In order to ensure your ventilation unit remains in good working condition, you must use the manufacturer's genuine replacement parts only. The manufacturer's genuine replacement parts are specially designed for each unit and are manufactured to comply with all the applicable certification standards and maintain a high standard of safety. Any third party replacement part used may cause serious damage and drastically reduce the performance level of your unit, which will result in premature failing. The manufacturer also recommends that you contact a service depot certified by the manufacturer for all replacement parts and repair.

BILL OF PURCHASE

No replacement or repair covered by the warranty will be carried out unless the unit is accompanied by a copy of the original bill of purchase. Please retain your original.

MISCELLANEOUS COSTS

In each case, the labor and shipping costs for the removal of a defective part and/or installation of a compliant part will not be covered by the manufacturer.

CONDITIONS AND LIMITATIONS

These units are created for residential use only and must be used in a building as defined below:

Building: All structures zoned and/or erected for the act, process or art of human or animal habitation and/or the storage or warehousing of goods.

Residential use: Dwelling, lodging, suite; Building, or part of a building, intended to act as either the domicile to one or several people which can include general sanitary, food consumption and rest facilities. Buildings of only one room or a group of rooms including those occupied by a tenant or owner; comprise the lodgings, the individual rooms of the motels, hotels, rooming/lodging houses, boarding/half-way/foster homes, dormitories, and suites, as well as the stores and the business establishments constituted by only one room in a dwelling.

Commercial use: Agricultural establishment, commercial establishment for assembly, care, or detention: Building or part of a building that does not contain a dwelling, situated on land dedicated to agriculture or farming and used primarily to shelter animals, or for the production, the storage or the treatment of agricultural or horticultural products or animal food. Building or part of a building, used for the display or retail of goods, professional or personal services, or commodities. Building, or part of a building used by persons gathering for civic activities, religious or political assembly, tourism, educational/vocational training, recreation or the consumption of food or drink. Building, or part of a building used to shelter persons of impaired physical or psychological states, persons requiring palliative care or medical treatments, or persons for reasons out of their control, cannot escape harm or threat of danger autonomously.

Industrial use: Building, or part of a building, used for the assembly, the manufacture, the creation, the treatment, the repair or the storage of products and combustible materials and that contain fuels that when ignited or exploded in sufficient quantity may constitute a risk of fire.

The above warranty applies to all cases where the damage is not a result of poor installation, improper use, mistreatment or negligence, acts of God, or any other circumstances beyond the control of the manufacturer. Furthermore, the manufacturer will not be held responsible for any bodily injury or damage to personal property or real estate, whether caused directly or indirectly by the unit. This warranty supersedes all prior warranties.

Venmar Ventilation ULC, 550 Lemire Blvd., Drummondville, Quebec, Canada J2C 7W9 venmar.ca / vanee.ca 800-567-3855

GUIDE D'INSTALLATION ET D'UTILISATION

vänEE V160E75RS - GUIDE D'INSTALLATION ET D'UTILISATION - 1

vänEE V160E75RS - GUIDE D'INSTALLATION ET D'UTILISATION - 2

A110H65RT
A130H65RT A130H65RS
A130E65RT
A150H75NT* A150H75NS*
*A160H75RT**A160H75RS
A160H65RT A160H65RS
A160E65RT
A150E75NT* A150E75NS*
*A160E75RT

vänEE V160E75RS - GUIDE D'INSTALLATION ET D'UTILISATION - 3
INSTALLATION CORRECTE

VD0489

ATTENTION

Table of contents Cliquez un titre pour y accéder
Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : vänEE

Model : V160E75RS

Category : Air Conditioning