Product type Analog process indicator/transmitter
Brand Camille Bauer
Model SINEAX G536
Display 4-digit LED, height 20 mm
Input Standard signals 0/4-20 mA, 0-10 V, etc.
Output 2 relay outputs (thresholds) + 1 analog output 0/4-20 mA
Power supply 24 V AC/DC (option 115/230 V AC)
Dimensions (L x H x D) 96 x 48 x 120 mm
Weight Approximately 250 g
Mounting Panel mounting (cut-out 92 x 45 mm)
Protection rating IP65 (front face), IP20 (enclosure)
Operating temperature -10 °C to +55 °C
Main functions Measurement, display, threshold monitoring, conversion to analog output
Configuration Via front keys or USB software (option)
Maintenance and cleaning Clean with a soft, dry cloth. Do not use aggressive solvents.
Safety Double insulation, overvoltage category II, electromagnetic compatibility according to EN 61326
Spare parts and repairability Spare parts available on request. Repair by the manufacturer or authorized center.

Frequently Asked Questions - SINEAX G536 Camille Bauer

How to configure the threshold settings on the SINEAX G536?
Use the front keys SET and ▲/▼ to navigate the menu. Select THRESHOLD1 or THRESHOLD2, then set the desired value. Confirm with ENTER. Refer to the manual for full details.
What input range is accepted by the G536?
The G536 accepts standard signals 0/4-20 mA, 0-10 V, 0-5 V and other ranges programmable via configuration. The exact range depends on the internal setting.
Can I use a 230 V AC power supply?
Yes, the SINEAX G536 is available in 24 V AC/DC version or optionally 115/230 V AC. Check the nameplate for the version you have.
How to connect the sensor to the transmitter?
Connect the sensor to the input terminals according to the diagram in the manual (terminals 1-2 for current, 3-4 for voltage). Respect polarity and use shielded cables if necessary.
The display flashes or freezes, what should I do?
Check the power supply and wiring. Flashing may indicate an out-of-range value. Reset the device by turning off power for 10 seconds. If the problem persists, contact support.
How to calibrate the SINEAX G536?
Calibration is done via the configuration menu. Apply a precise input signal (e.g., 20 mA) and adjust the displayed value with the keys. Preferably use an external calibrator.
What is the measurement accuracy of the device?
Accuracy is typically ±0.2% of full scale, with high linearity and temperature stability.
Can I use the G536 with 0-10 V output?
Yes, the analog output can be configured as 0-10 V or 4-20 mA via the configuration menu. Ensure the load does not exceed 500 Ω for current output.
How to reset to factory settings?
Press and hold the SET and keys simultaneously when powering on. The display shows rES to confirm reset.
Where can I find the complete user manual?
The complete manual is available for free download on the website notice-facile.com in PDF format. Other languages are also available.

User questions about SINEAX G536 Camille Bauer

0 question about this device. Answer the ones you know or ask your own.

Ask a new question about this device

The email remains private: it is only used to notify you if someone responds to your question.

No questions yet. Be the first to ask one.

Download the instructions for your Electrical measuring instrument in PDF format for free! Find your manual SINEAX G536 - Camille Bauer and take your electronic device back in hand. On this page are published all the documents necessary for the use of your device. SINEAX G536 by Camille Bauer.

USER MANUAL SINEAX G536 Camille Bauer

Manual assistant
Powered by Anthropic
Waiting for your message
Product information

Brand : Camille Bauer

Model : SINEAX G536

Category : Electrical measuring instrument